IF16C User Manual Compact High-Density Analog Input

2y ago
18 Views
3 Downloads
2.29 MB
84 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Luis Wallis
Transcription

Compact High-density Analog InputModulesUser Manual(Catalog Numbers1769-IF16C, 1769-IF16V)

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. SafetyGuidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 availablefrom your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describessome important differences between solid state equipment and hard-wired electromechanical devices. Because ofthis difference, and also because of the wide variety of uses for solid state equipment, all persons responsible forapplying this equipment must satisfy themselves that each intended application of this equipment is acceptable.In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resultingfrom the use or application of this equipment.The examples and diagrams in this manual are included solely for illustrative purposes. Because of the manyvariables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assumeresponsibility or liability for actual use based on the examples and diagrams.No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment,or software described in this manual.Reproduction of the contents of this manual, in whole or in part, without written permission of RockwellAutomation, Inc., is prohibited.Throughout this manual, when necessary, we use notes to make you aware of safety considerations.WARNINGIMPORTANTATTENTIONIdentifies information about practices or circumstances that can cause an explosion in ahazardous environment, which may lead to personal injury or death, property damage, oreconomic loss.Identifies information that is critical for successful application and understanding of the product.Identifies information about practices or circumstances that can lead to personal injury or death,property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, andrecognize the consequenceSHOCK HAZARDLabels may be on or inside the equipment, for example, a drive or motor, to alert people thatdangerous voltage may be present.BURN HAZARDLabels may be on or inside the equipment, for example, a drive or motor, to alert people thatsurfaces may reach dangerous temperatures.Rockwell Automation, Allen-Bradley, TechConnect, CompactLogix, Compact I/O, ControlLogix, MicroLogix 1500, RSLogix 5000, RSLogix 500, RSNetWorx, RSNetWorx for DeviceNet, and RSLinx aretrademarks of Rockwell Automation, Inc.Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of ContentsPrefaceIntroduction . . . . . . . . . . . . . . . .About this Publication . . . . . . . . .Who Should Use This PublicationAdditional Resources. . . . . . . . . .Conventions . . . . . . . . . . . . . . . .77788. 9. 91111Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .General Considerations . . . . . . . . . . . . . . . . . . . . . .Hazardous Location Considerations . . . . . . . . . .Prevent Electrostatic Discharge . . . . . . . . . . . . . .Remove Power . . . . . . . . . . . . . . . . . . . . . . . . .Reduce Noise . . . . . . . . . . . . . . . . . . . . . . . . . .Protecting the Circuit Board from Contamination.Assemble the Compact I/O System . . . . . . . . . . . . .Mounting the Module . . . . . . . . . . . . . . . . . . . . . . .Minimum Spacing . . . . . . . . . . . . . . . . . . . . . . .Mount to a Panel . . . . . . . . . . . . . . . . . . . . . . . .Mount to a DIN Rail. . . . . . . . . . . . . . . . . . . . . .Replace a Single Module Within a System . . . . . . . .Grounding the Module . . . . . . . . . . . . . . . . . . . . . .System Wiring Guidelines . . . . . . . . . . . . . . . . . . . .Effect of Transducer/Sensor and Cable LengthImpedance on Voltage Input Accuracy . . . . . . . .Label the Terminals. . . . . . . . . . . . . . . . . . . . . . . . .Remove the Finger-safe Terminal Block . . . . . . . . . .Wire the Finger-safe Terminal Block . . . . . . . . . . . .Wire Size and Terminal Screw Torque . . . . . . . .Wire the Modules . . . . . . . . . . . . . . . . . . . . . . . . . r 1OverviewIntroduction . . . . . .Module Description.System Overview . .Module Operation. .Chapter 2Installation and WiringChapter 3Module Data, Status, and Channel Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29ConfigurationInput Image. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Output Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303Publication 1769-UM018A-EN-P - October 20083

Table of ContentsInput Data File . . . . . . . . . . . . . . . . .Time Stamp Value (Word 16) . . . .General Status Bits (S0 S15) . . . .Low Alarm Flag Bits (L0 L15) . .High Alarm Flag Bits (H0 H15). .Over-Range Flag Bits (O0 O15) .Under-Range Flag Bits (U0 U15).Output Data File . . . . . . . . . . . . . . . .Configuration Data File . . . . . . . . . . .Channel Configuration . . . . . . . . .Enable/Disable Channel (EC) . . . .Input Filter Selection . . . . . . . . . .Input Type/Range Selection . . . . .Input Data Selection Formats . . . .Real Time Sampling . . . . . . . . . . .Time Stamping. . . . . . . . . . . . . . .Process Alarms . . . . . . . . . . . . . .Alarm Deadband . . . . . . . . . . . . .313232323233333334383939414143434445Introduction . . . . . . . . . . . . . . . . . . . . . . . .Safety Considerations . . . . . . . . . . . . . . . . .Status Indicators. . . . . . . . . . . . . . . . . . .Activate Devices When Troubleshooting .Stand Clear of the Machine. . . . . . . . . . .Program Alteration. . . . . . . . . . . . . . . . .Safety Circuits . . . . . . . . . . . . . . . . . . . .Power Cycle Diagnostics . . . . . . . . . . . . . . .Channel Diagnostics . . . . . . . . . . . . . . . . . .Out-of-range Detection . . . . . . . . . . . . .Process Alarm Detection . . . . . . . . . . . .Open-circuit Detection . . . . . . . . . . . . . .Non-critical vs. Critical Module Errors . . . . .Module Error Definition Table . . . . . . . . . . .Module Error Field. . . . . . . . . . . . . . . . .Extended Error Information Field . . . . . .Error Codes . . . . . . . . . . . . . . . . . . . . . . . .Invalid Input Range Selected . . . . . . . . .Invalid Input Filter Selected . . . . . . . . . .Invalid Input Format Selected. . . . . . . . .Alarm Not Enabled. . . . . . . . . . . . . . . . .Invalid Alarm Data. . . . . . . . . . . . . . . . .Invalid Real Time Sample Value . . . . . . .Module Inhibit Function . . . . . . . . . . . . . . .Contacting Rockwell Automation . . . . . . . . 7Chapter 4Module Diagnostics andTroubleshooting4Publication 1769-UM018A-EN-P - October 2008

Table of ContentsAppendix ASpecificationsIntroduction . . . . . . . .General Specifications .Input Specifications. . .Certifications. . . . . . . .Replacement Parts. . . .5959606161Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Module Input Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Module Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . .Configure Analog I/O Modules in a MicroLogix 1500 System63636464Appendix BModule Addressing andConfiguration with MicroLogix1500 ControllerAppendix CConfiguration Using the RSLogix5000 Generic Profile forCompactLogix ControllersIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Add the Module to Your Project . . . . . . . . . . . . . . . . . . . . . 69Configure Each I/O Module. . . . . . . . . . . . . . . . . . . . . . . . . 72Appendix DTwo’s Complement BinaryNumbersPositive Decimal Values . . . . . . . . . . . . . . . . . . . . . . . . . . . 73Negative Decimal Values . . . . . . . . . . . . . . . . . . . . . . . . . . . 74GlossaryIndexPublication 1769-UM018A-EN-P - October 20085

Table of Contents6Publication 1769-UM018A-EN-P - October 2008

PrefaceIntroductionRead this preface to familiarize yourself with the rest of the manual.TopicAbout this PublicationPageAbout this Publication7Who Should Use This Publication7Additional Resources8Conventions8This manual is a guide for using Compact High Density Analog InputModules, catalog numbers 1769-IF16C and 1769-IF16V. It describes theprocedures you use to configure, operate, and troubleshoot yourmodule.For detailed information on related topics like programming yourCompactLogix or MicroLogix controller, or DeviceNet adapter, or forinformation on CompactLogix components, see the list of AdditionalResources on page 8.Who Should Use ThisPublication7Publication 1769-UM018A-EN-P - October 2008Use this manual if you are responsible for designing, installing,programming, or troubleshooting control systems that use CompactI/O modules.7

PrefaceAdditional ResourcesThese documents contain additional information about controlsystems that use Compact I/O modules.ResourceDescriptionMicroLogix 1500 User Manual, publication 1764-UM001A user manual containing information on how to install, use andprogram your MicroLogix 1500 controller.DeviceNet Adapter User Manual, publication 1769-UM001A user manual containing information on how to install, and use your1769-ADN DeviceNet adapter.CompactLogix User Manual, publication 1769-UM007A user manual containing information on how to install, use andprogram your 1769-L20 and -L30 CompactLogix controllers.CompactLogix System User Manual, publication 1769-UM011A user manual containing information on how to install, use andprogram your 1769-L31, -L32C, -L32E, -L35CR and -L35E CompactLogixcontrollers.Compact I/O Selection Guide, publication 1769-SG002An overview of 1769 Compact I/O modules.MicroLogix Programmable Controllers Selection Guide,publication 1761-SG001An overview of the MicroLogix 1500 System, including the 1769Compact I/O system.Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1In-depth information on grounding and wiring Allen-Bradleyprogrammable controllers.You can view or download publications athttp://literature.rockwellautomation.com. To order paper copies oftechnical documentation, contact your local Rockwell Automationdistributor or sales representative.ConventionsThese conventions are used throughout this manual: Bulleted lists, such as this one, provide information, notprocedural steps. Numbered lists provide sequential steps or hierarchicalinformation. Bold type is used for emphasis.8Publication 1769-UM018A-EN-P - October 2008

Chapter1OverviewIntroductionTopicModule DescriptionPageModule Description9System Overview11Module Operation11The modules convert and digitally store analog data for retrieval bycontrollers, such as the CompactLogix or MicroLogix 1500 controllers.The modules provide the following input types and ranges.Normal and Full RangesCat. No.Normal Operating Input RangeFull Module Range1769-IF16V 10V DC 10.5V DC1 5V DC0.5 5.25V DC0 5V DC-0.5 5.25V DC0 10V DC-0.5 10.5V DC0 20 mA0 21 mA4 20 mA3.2 21 mA1769-IF16CThe data can be configured as: engineering Units.scaled-for-PID.percent range.raw/proportional data.Module configuration is normally done via the controller’sprogramming software. In addition, some controllers supportconfiguration via the user program. In either case, the moduleconfiguration is stored in the memory of the controller. Refer to yourcontroller’s user manual for more information.9Publication 1769-UM018A-EN-P - October 20089

Chapter 1OverviewHardware Features12a12a3OK3OKAnalogAnalogDANGERDANGERDo Not Remove RTB Under PowerUnless Area is Non-Hazardous10aDo Not Remove RTB Under PowerUnless Area is Non-Hazardous10aIN0 IN1 IN2 IN0 IN1 IN2 IN3 IN3 IN4 IN4 IN5 IN5 IN6 IN6 IN7 10IN7 10COMCOMIN8 COMCOMIN8 IN9 IN9 IN10 IN10 IN11 IN11 IN12 IN12 IN13 10bIN14 IN15 Ensure AdjacentBus Lever is Unlatched/LatchedBefore/AfterRemoving/Inserting ModuleIN13 10b4IN14 IN15 Ensure AdjacentBus Lever is Unlatched/LatchedBefore/AfterRemoving/Inserting 5a5b95b967b1041769-IF16V8b7b67bItemDescription1Bus lever (with locking function)2aUpper-panel mounting tab2bLower-panel mounting tab8b3Module status LEDs4Module door with terminal identification label5aMovable bus connector with female pins5bStationary bus connector with male pins7b6Nameplate label7aUpper tongue-and-groove slots7bLower tongue-and-groove slots8aUpper DIN-rail latch8bLower DIN-rail latch9Write-on label for user identification tags10Removable terminal block (RTB) with finger-safe cover10aRTB upper retaining screw10bRTB lower retaining screwPublication 1769-UM018A-EN-P - October 2008

OverviewSystem OverviewChapter 1The modules communicate to the controller through the bus interface.The modules also receive 5 and 24V DC power through the businterface.You can install as many analog modules as your power supply cansupport. However, the modules may not be located more than eightmodules away from the system power supply.123End Cap1Compact I/O2Compact I/O3Compact I/OCompact I/OSystem Power SupplyCompact I/O4Compact I/OCompactLogix Controlleror I/O CommunicationAdapterDetermine Power Supply DistancePower Supply DistanceModule OperationCompact I/OCompact I/OCompact I/OEnd CapMicroLogix 1500 Controllerwith Integrated SystemPower SupplyCompact I/Oor1234Power Supply DistanceWhen you cycle power, the modules perform a check of their internalcircuits, memory, and basic functions. During this time, the modulestatus OK indicator remains off. If no faults are found duringpower-cycle diagnostics, the module status OK indicator is turned on.After power-cycle checks are complete, the modules wait for validchannel configuration data. If an invalid configuration is detected, themodules generate a configuration error. Once a channel is properlyconfigured and enabled, it begins the analog-to-digital conversionprocess.Each time a channel is read, the converted analog data value is testedfor an over-range or under-range condition. In addition, the modulessupport user-configured high and low alarm condition tests for eachchannel. If any of these conditions are detected, unique bits are set inthe channel status words.Publication 1769-UM018A-EN-P - October 200811

Chapter 1OverviewThe channel status words are described in the Input Data File onpage 31.The controller reads the two’s complement binary converted analogdata from the modules. This typically occurs at the end of the programscan or when commanded by the control program. If the controllerand the modules determine that the bus data transfer was madewithout error, the data is used in your control program.No field calibration is required.12Publication 1769-UM018A-EN-P - October 2008

Chapter2Installation and WiringIntroductionTopicGeneral ConsiderationsPageGeneral Considerations13Assemble the Compact I/O System16Mounting the Module17Replace a Single Module Within a System19Grounding the Module20System Wiring Guidelines21Label the Terminals23Remove the Finger-safe Terminal Block23Wire the Finger-safe Terminal Block23Wire the Modules25The Compact I/O system is suitable for use in an industrialenvironment when installed in accordance with these instructions.Specifically, this equipment is intended for use in clean, dryenvironments (Pollution degree 2(1)) and to circuits not exceedingOver Voltage Category II(2) (IEC 60664-1).(3)(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except thatoccasionally a temporary conductivity caused by condensation shall be expected.(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transientvoltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)designations.13Publication 1769-UM018A-EN-P - October 200813

Chapter 2Installation and WiringHazardous Location ConsiderationsThis equipment is suitable for use in Class I, Division 2, Groups A, B,C, D or non-hazardous locations only. The following attentionstatement applies to use in hazardous locations.ATTENTIONEXPLOSION HAZARD Substitution of components may impair suitability for Class I,Division 2. Do not replace components or disconnect equipment unlesspower has been switched off or the area is known to benon-hazardous. Do not connect or disconnect components unless power hasbeen switched off or the area is known to be non-hazardous. This product must be installed in an enclosure. All wiring must comply with N.E.C. article 501-4(b).Prevent Electrostatic DischargeATTENTIONElectrostatic discharge can damage integrated circuits orsemiconductors if you touch analog I/O module bus connector pinsor the terminal block on the input module. Follow these guidelineswhen you handle the module: 14Touch a grounded object to discharge static potential.Wear an approved wrist-strap grounding device.Do not touch the bus connector or connector pins.Do not touch circuit components inside the module.Use a static-safe work station, if available.When it is not in use, keep the module in its static-shield box.Publication 1769-UM018A-EN-P - October 2008

Installation and WiringChapter 2Remove PowerATTENTIONRemove power before removing or inserting this module. Whenyou remove or insert a module with power applied, an electricalarc may occur. An electrical arc can cause personal injury orproperty damage by: sending an erroneous signal to your system’s field devices,causing unintended machine motion. causing an explosion in a hazardous environment.Electrical arcing causes excessive wear to contacts on both themodule and its mating connector and may lead to prematurefailure.Reduce NoiseMost applications require installation in an industrial enclosure toreduce the effects of electrical interference. Analog inputs are highlysusceptible to electrical noise. Electrical noise coupled to the analoginputs will reduce the performance (accuracy) of the module.Group your modules to minimize adverse effects from radiatedelectrical noise and heat. Consider the following conditions whenselecting a location for the analog module. Position the module: away from sources of electrical noise such as hard-contactswitches, relays, and ac motor drives. away from modules which generate significant radiated heat,such as the 1769-IA16 module. Refer to the module’s heatdissipation specification.In addition, route shielded, twisted-pair analog input wiring awayfrom any high-voltage I/O wiring.Protecting the Circuit Board from ContaminationThe printed circuit boards of the analog modules must be protectedfrom dirt, oil, moisture, and other airborne contaminants. To protectthese boards, the system must be installed in an enclosure suitable forthe environment. The interior of the enclosure should be kept cleanand the enclosure door should be kept closed whenever possible.Publication 1769-UM018A-EN-P - October 200815

Chapter 2Installation and WiringAssemble the Compact I/OSystemThe module can be attached to the controller or an adjacent I/Omodule before or after mounting.For mounting instructions, see Panel Mounting Using the DimensionalTemplate on page 18, or Mount to a DIN Rail on page 19. To workwith a system that is already mounted, see Replace a Single ModuleWithin a System on page 19.34216151. Disconnect power.2. Check that the bus lever of the module to be installed is in theunlocked (fully right) position.3. Use the upper and lower tongue-and-groove slots (1) to securethe modules together (or to a controller).4. Move the module back along the tongue-and-groove slots untilthe bus connectors (2) line up with each other.5. Use your fingers or a small screwdriver to push the bus leverback slightly to clear the positioning tab (3).16Publication 1769-UM018A-EN-P - October 2008

Installation and WiringChapter 26. To allow communication between the controller and module,move the bus lever fully to the left (4) until it clicks.Make sure it is locked firmly in place.ATTENTIONWhen attaching I/O modules, it is very important thatthe bus connectors are securely locked together to besure of proper electrical connection.7. Attach an end cap terminator (5) to the last module in thesystem by using the tongue-and-groove slots as before.8. Lock the end cap bus terminator (6).IMPORTANTA 1769-ECR or 1769-ECL right or left end cap must be used toterminate the end of the bus.Mounting the ModuleATTENTIONDuring panel or DIN rail mounting of all devices, be sure that alldebris (that is, metal chips or wire strands) is kept from fallinginto the module. Debris that falls into the module could causedamage when you cycle power.Minimum SpacingMaintain spacing from enclosure walls, wireways, or adjacentequipment. Allow 50 mm (2 in.) of space on all sides for adequateventilation.Space RequirementsEnd CapCompact I/OCompact I/OCompact I/OHost ControllerCompact I/OSideCompact I/OTopSideBottomPublication 1769-UM018A-EN-P - October 200817

Chapter 2Installation and WiringMount to a PanelMount the module to a panel using two screws per module. Use M4or #8 panhead screws. Mounting screws are required on everymodule.Panel Mounting Using the Dimensional TemplateLocate holes every 17.5 mm (0.689 in.) to allow for a mix ofsingle-wide and one-and-a-half-wide modules (for example, the1769-OA16 module).Overall hole spacing tolerance: 0.4 mm (0.016 in.).Host ControllerSpacing for single-wide modules 35 mm (1.378 in.).l MountingSpacing for one-and-a-half-widemodules 52.5 mm (2.067 in.).Refer to host controller documentation for this dimension.Panel Mounting Using the Modules as a TemplateThis procedure lets you to use the assembled modules as a templatefor drilling holes in the panel. If you have sophisticatedpanel-mounting equipment, you can use the dimensional templateprovided. Due to module mounting hole tolerance, it is important tofollow these procedures.1. On a clean work surface, assemble no more than three modules.2. Using the assembled modules as a template, carefully mark thecenter of all module-mounting holes on the panel.3. Return the assembled modules to the clean work surface,including any previously mounted modules.4. Drill and tap the mounting holes for the recommended M4 or #8screw.5. Place the modules back on the panel, and check for proper holealignment.18Publication 1769-UM018A-EN-P - October 2008

Installation and WiringChapter 26. Attach the modules to the panel using the mounting screws.TIPIf mounting more modules, mount only the last one of this groupand put the others aside. This reduces remounting time duringdrilling and tapping of the next group.7. Repeat steps 1 6 for any remaining modules.Mount to a DIN RailThe module can be mounted using the following DIN rails:35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x15).Before mounting the module on a DIN rail, close the DIN rail latches.Press the DIN rail mounting area of the module against the DIN rail.The latches will momentarily open and lock into place.Replace a Single ModuleWithin a SystemThe module can be replaced while the system is mounted to a panel(or DIN rail). Follow these steps in order.1. Remove power.ATTENTIONRemove power before removing or inserting this module. Whenyou remove or insert a module with power applied, an electricalarc may occur. An electrical arc can cause personal injury orproperty damage by: sending an erroneous signal to your system’s field devices,causing unintended machine motion. causing an explosion in a hazardous environment.Electrical arcing causes excessive wear to contacts on both themodule and its mating connector and may lead to prematurefailure.2. On the module to be removed, remove the upper and lowermounting screws from the module or open the DIN latchesusing a flat-blade or Phillips screwdriver.3. Move the bus lever to the right to disconnect (unlock) the bus.4. On the right-side adjacent module, move its bus lever to theright (unlock) to disconnect it from the module to be removed.Publication 1769-UM018A-EN-P - October 200819

Chapter 2Installation and Wiring5. Gently slide the disconnected module forward.If you feel excessive resistance, check that the module has beendisconnected from the bus, and that both mounting screws havebeen removed or DIN latches opened.TIPIt may be necessary to rock the module slightlyfrom front to back to remove it, or, in apanel-mounted system, to loosen the screws ofadjacent modules.6. Before installing the replacement module, be sure that the buslever on the module to be installed and on the right-sideadjacent module are in the unlocked (fully right) position.7. Slide the replacement module into the open slot.8. Connect the modules together by locking (fully left) the buslevers on the replacement module and the right-side adjacentmodule.9. Replace the mounting screws or snap the module onto the DINrail.Grounding the Module20This product is intended to be mounted to a well-grounded mountingsurface such as a metal panel. Additional grounding connections fromthe module’s mounting tabs or DIN rail (if used) are not requiredunless the mounting surface cannot be grounded. Refer to IndustrialAutomation Wiring and Grounding Guidelines, Allen-Bradleypublication 1770-4.1, for additional information.Publication 1769-UM018A-EN-P - October 2008

Installation and WiringSystem Wiring GuidelinesChapter 2Consider the following when wiring your system: All module commons (COM) are connected in the analogmodule. The analog common (COM) is not connected to earth groundinside the module. Channels are not isolated from each other. To ensure optimum accuracy, limit overall cable impedance bykeeping your cable as short as possible. Locate the I/O systemas close to your sensors or actuators as your application willpermit. Use Belden 8761, or equivalent, shielded wire. Under normal conditions, the drain wire and shield junctionmust be connected to earth ground via a panel or DIN railmounting screw at the analog I/O module end.(1) Keep shieldconnection to ground as short as possible. If multiple power supplies are used with analog inputs, thepower supply commons must be connected. The modules do not provide loop power for analog inputs. Usea Class 2 power supply that matches the input transmitterspecifications. Voltages on IN terminals of the modules must be within 10V DC of module common (COM).Effect of Transducer/Sensor and Cable Length Impedance onVoltage Input AccuracyFor voltage inputs, the length of the cable used between thetransducer/sensor and the module can affect the accuracy of the dataprovided by the module.(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cableshields to earth at the module end and via a 0.1µF capacitor at the sensor end.Publication 1769-UM018A-EN-P - October 200821

Chapter 2Installation and WiringVoltage Input AccuracyRsRc VsV inRi-RcWhere:Rc DC resistance of the cable (each conductor) depending oncable lengthRs Source impedance of analog transducer/sensor inputRi Impedance of the voltage input (1 MΩ for 1769-IF16V module)Vs Voltage source (voltage at the transducer/sensor input device)Vin Measured potential at the module input%Ai Percent added inaccuracy in a voltage-based system dueto source and cable impedance.[ Ri Vs]Vin -----[ Rs ( 2 Rc ) Ri ]For example, for Belden 8761 two conductor, shielded cable:Rc 16 Ω/1000 ftVin% Ai 1 – --------- 100Rs 0 (ideal source) Vs Table 2.1 Effect of Cable Length on Input AccuracyLength of Cable,m (ft)DC Resistance of the Cable,Rc (Ω)Accuracy Impact at theInput Module50 (164)2.6250.000525%100 (328)5.250.00105%200 (656)10.500.0021%300 (984)15.750.00315%As input source impedance (Rs) and/or resistance (DC) of the cable(Rc) get larger, system accuracy decreases. If you determine that theinaccuracy error is significant, implementing the following equation inthe control program can compensate for the added inaccuracy errordue to the impedance of the source and cable.[ Rs ( 2 Rc ) Ri ]Vs Vin -----RiTIP22For the 1769-IF16C module, source and cable impedance do notimpact system accuracy.Publication 1769-UM018A-EN-P - October 2008

Installation and WiringChapter 2Label the TerminalsA removable, write-on la

MicroLogix 1500 User Manual, publication 1764-UM001 A user manual containing information on how to install, use and program your MicroLogix 1500 controller. DeviceNet Adapter User Manual, publication 1769-UM001 A user manual containing information on

Related Documents:

Morphy Richards Fastbake Breadmaker 48280 User Manual Honda GCV160 User Manual Canon Powershot A95 User Manual HP Pocket PC IPAQ 3650 User Manual Navman FISH 4200 User Manual - Instruction Guide Jensen VM9021TS Multimedia Receiver User Manual Sanyo SCP-3100 User Manual Honda GC160 User Manual Canon AE-1 Camera User Manual Spektrum DX7 User Manual

Equipment, Gunn JCB Compact Equipment, Holt JCB Compact Equipment, Scot JCB Compact, TC Harrison JCB Compact and Watling JCB Compact - will also create separate compact equipment showrooms at selected depots covering England, Scotland and Wales. The dealers' expansion follows a decision earlier this year by JCB to set up its own Compact

Ademco Passpoint Plus User Manual Morphy Richards Fastbake Breadmaker 48280 User Manual Honda GCV160 User Manual Canon Powershot A95 User Manual HP Pocket PC IPAQ 3650 User Manual Navman FISH 4200 User Manual - Instruction Guide Jensen VM9021TS Multimedia Receiver User Manual Sanyo SCP-3100 User Manual Honda GC160 User Manual Canon AE-1 Camera .

E-816 DLL Manual, PZ120E E-621.CR User Manual, PZ160E E-816 LabVIEW Software Manual, PZ121E E-621.SR, .LR User Manual, PZ115E Analog GCS LabVIEW Software Manual, PZ181E E-625.CR User Manual, PZ166E PIMikromove User Manual, SM148E E-625.SR, .LR User Manual, PZ167E E-665 User Manual, PZ127E E-801 User Manual

VAST RANGE OF BACKHOE LOADER ATTACHMENTS. WITH THE ADDITION OF THE 3CX COMPACT PLUS AND 3CX COMPACT PRO, IT ALSO HAS THE ABILITY TO PICK UP A WIDER RANGE OF HIGH POWERED SKID STEER LOADER ATTACHMENTS. A 3-in-1 machine, the 3CX Compact can be a compact excavator and wheel load

Delta Electronics (Netherlands) B.V. Eindhoven Ofice De Witbogt 20, 5652 AG Eindhoven, The Netherlands TEL: 31 (0)40-8003800 / FAX: 31 (0)40-8003898 *We reserve the right to change the information in this user manual without prior notice. Delta Standard Compact Drive MS300 Series User Manual (High Speed Models) Delta Standard Compact Drive .

Horizon Compact Release 1.01.01 Wireless Ethernet Product User Manual – Volume 1 2.0 Introduction to Horizon Compact DragonWave’s Horizon Compact is a next-generation, high capacity, native Ethernet, microwave syst

Studi Pendidikan Akuntansi secara keseluruhan adalah sebesar Rp4.381.147.409,46. Biaya satuan pendidikan (unit cost) pada Program Studi Akuntansi adalah sebesar Rp8.675.539,42 per mahasiswa per tahun. 2.4 Kerangka Berfikir . Banyaknya aktivitas-aktivitas yang dilakukan Fakultas dalam penyelenggaraan pendidikan, memicu biaya-biaya dalam penyelenggaraan pendidikan. Biaya dalam pendidikan .