Worldwidewww.tyco-fire.comContactsSeries DS-2 Dry-Type Sprinklers11.2K PendentExtended Coverage, Light and Ordinary HazardGeneralDescriptionSeries DS-2 Dry-Type Sprinklers mustonly be installed in fittings that meetthe requirements of the Design Criteria section.TYCO Series DS-2 Dry-Type Sprinklers,11.2K Pendent, Extended Coverage,Light and Ordinary Hazard (ECLH/ECOH) are decorative glass bulb automatic sprinklers typically used where:SprinklerIdentificationNumber (SIN) pendent sprinklers are required ondry pipe systems that are exposedto freezing temperatures (e.g.,sprinkler drops from unheatedportions of buildings) sprinklers and/or a portion of theconnecting piping may be exposedto freezing temperatures (e.g.,sprinkler drops from wet systemsinto freezers)NOTICESeries DS-2 Dry-Type Sprinklersdescribed herein must be installedand maintained in compliance with thisdocument, as well as with the applicable standards of the NATIONAL FIREPROTECTION ASSOCIATION (NFPA),in addition to the standards of any otherauthorities having jurisdiction. Failureto do so may impair the performanceof these devices.The owner is responsible for maintaining their fire protection systemand devices in proper operating condition. Contact the installing contractor or product manufacturer with anyquestions.IMPORTANTRefer to Technical Data SheetTFP2300 for warnings pertaining toregulatory and health information.Always refer to Technical DataSheet TFP700 for the “INSTALLERWARNING” that provides cautionswith respect to handling and installation of sprinkler systems and components. Improper handling andinstallation can permanently damagea sprinkler system or its components and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.Page 1 of 8TY5238TechnicalDataApprovalsUL and C-UL ListedNYC Approved under MEA 173-02-ERefer to Table A.(These Approvals apply to the servicecondition indicated in the Design Criteria section.)Maximum Working Pressure175 psi (12,1 bar)Inlet Thread Connections1 inch NPT orISO 7-R 1Discharge CoefficientRefer to Table DTemperature RatingsRefer to Table AFinishesSprinkler: Refer to Table EEscutcheon: Refer to Table EPhysical CharacteristicsInlet CopperYoke. . . . . . . . . . . . . . . . . . . . . . . . Stainless SteelCasing. . . . . . . . . . . . . . Galvanized Carbon SteelInsert BronzeBulb Seat BronzeBulb GlassCompression Screw BronzeDeflector BronzeFrame BronzeGuide Tube Stainless SteelWater Tube Stainless SteelSpring. . . . . . . . . . . . . . . . . . . . . . Stainless SteelPlug. . . . . . . . . . . . . . . . Copper Gasketed SpringPlate Seal . . . . . . . . Beryllium Nickel w/TEFLONPin. . . . . . . . . . . . . . . . . . . . . . . . . Stainless SteelButton Spring Stainless SteelEscutcheon Carbon SteelAUGUST 2018OperationWhen TYCO Series DS-2 Dry-TypeSprinklers, 11.2K Pendent, ExtendedCoverage, Light and Ordinary Hazardare in service, water is prevented fromentering the assembly by the Plugwith Gasketed Spring Plate Seal (Ref.Figure 1) in the Inlet of the sprinkler.The glass bulb contains a fluid thatexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatterthe glass bulb, and the Bulb Seat isreleased.The compressed Spring is then ableto expand and push the Water Tube aswell as the Guide Tube outward. Thisaction simultaneously pulls inward onthe Yoke, withdrawing the Plug withGasketed Spring Plate Seal from theInlet allowing the sprinkler to activateand flow water.TFP540

TFP540Page 2 of 8TY5238with Flush Escutcheon(Figure 2)TemperatureRatingTY5238with Recessed Escutcheon(Figure 3)with Extended Escutcheon(Figure 4)BulbColor Codewithout Escutcheon(Figure 5)SPRINKLER FINISHNaturalBrass135 F (57 C)Orange155 F (68 C)Red175 F (79 C)Yellow200 F (93 C)Green286 F (141 C)*BlueChromedPlatedPolyester**NaturalBrass1, 2, 3ChromePlatedPolyester**1, 2, 3Notes:1. UL Listed (maximum order length of 48 inches)2. C-UL Listed (maximum order length of 48 inches)3. Approved by the City of New York under MEA 173-02-E* 286 F (141 C) temperature rating applies to installations in Ordniary Hazard Occupancies only.** Frame and deflector onlyTABLE ASERIES DS-2 ECLH/ECOH DRY-TYPE PENDENT SPRINKLERSLABORATORY LISTINGS AND APPROVALSPLUG WITHGASKETED SPRINGPLATE SEALSPRINGINLET BANDWATER T RE 1SERIES DS-2 ECLH/ECOH DRY-TYPE PENDENT SPRINKLERASSEMBLYDesignCriteriaUL and C-UL ListingRequirementsTYCO Series DS-2 Dry-Type Sprinklers, 11.2K Pendent, Extended Coverage, Light and Ordinary Hazardare intended for use in fire sprinklersystems designed in accordancewith the extended coverage installation rules recognized by the applicable Listing agency (e.g., UL Listing isbased on NFPA 13 requirements). Referto Table C for coverage and flow ratecriteria.

TFP540Page 3 of 8ResponseRatingArea(4),Coverageft x ft(m x m)Minimum Flow(1)Light Hazard(2),(0.10 gpm/ft 2)gpm(lpm)Minimum Flow(1)Ordinary HazardGroup I(3),(0.15 gpm/ft 2)gpm(lpm)Minimum Flow(1)Ordinary HazardGroup II(3),(0.20 gpm/ft 2)gpm(lpm)EscutcheonTypeQuick16 x 16(4,9 x 4,9)30(114)——Flush, Recessed,ExtendedQuick18 x 18(5,5 x 5,5)33(125)——Flush, ExtendedStandard520 x 20(6,1 x 6,1)40(151)——Flush, Recessed,ExtendedQuick14 x 14(4,3 x 4,3)—30(148)39(148)Flush, Recessed,ExtendedStandard16 x 16(4,9 x 4,9)—39(148)51(193)Flush, Recessed,ExtendedNotes:1. Requirement is based on minimum flow in gpm from each sprinkler. The required residual pressure is to based on the use of a K-factor derived from Table D.2. Light Hazard Occupancies are limited to a type of unobstructed construction consisting of flat, smooth ceilings.3. Ordinary Hazard Occupancies may have either “combustible or non-combustible, unobstructed ceiling construction” or “noncombustible obstructed ceiling construction.”4. Minimum spacing between sprinklers is 12.5 feet (3,8 m).5. For retrofit applications of projects installed prior to the NFPA Quick Response / Light Hazard requirementTABLE BUL AND C-UL LISTINGCOVERAGE AND FLOW RATE CRITERIAUL and C-UL Specific ApplicationListing Requirements forInstallation Under Concrete TeesTYCO Series DS-2 Dry-Type PendentSprinklers (TY5238) have a UL andC-UL Specific Application Listing foruse under concrete tees when installedas follows: Stems of the concrete tee construction must be spaced at less than7.5 feet (2,3 m) on center but morethan 3 feet (0,9 m) on center. Thedepth of the concrete tees must notexceed 30 inches (762 mm). Themaximum permitted concrete teelength is 32 feet (9,8 m). However,where the concrete tee lengthexceeds 32 feet (9,8 m), noncombustible baffles, equal in heightto the depth of the tees, can beinstalled to ensure that the spacebetween the tees does not exceed32 feet (9,8 m) in length. Sprinkler deflectors are to belocated in a horizontal plane at orabove 1 inch (25,4 mm) below thebottom of the concrete tee stems. When sprinkler deflectors arelocated higher than a horizontalplane 1 inch (25,4 mm) beneath thebottom of the concrete tee stems,obstruction to sprinkler dischargecriteria requirements of NFPA 13 forextended coverage upright sprinklers applies.Temperatures for Heated Area(1)Ambient TemperatureExposed toDischarge End of Sprinkler40 F(4 C)50 F(10 C)60 F(16 C)40 F(4 C)00030 F(-1 C)00020 F(-7 C)4(100)0010 F(-12 C)8(200)1(25)00 F(-18 C)12(305)3(75)0-10 F(-23 C)14(355)4(100)1(25)-20 F(-29 C)14(355)6(150)3(75)-30 F(-34 C)16(405)8(200)4(100)-40 F(-40 C)18(455)8(200)4(100)-50 F(-46 C)20(510)10(255)6(150)-60 F(-51 C)20(510)10(255)6(150)Minimum Exposed Barrel Length(2),Inches(mm)Notes:1. For protected area temperatures that occur between values listed above, use the next cooler temperature2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).TABLE CEXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMSMINIMUM RECOMMENDED LENGTHS

TFP540Page 4 of 8SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)FACE OFSPRINKLERFITTING3-5/8" DIA.(92,1 mm)ORDER LENGTHS:3" to 48"(76,2 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTS2-3/4" DIA.(69,9 mm)FACE OFCEILING2-1/4 1/8" *(57,2 3,2 mm)* ESCUTCHEONWILL PERMIT 1/4" (6,4 mm)ADJUSTMENTFIGURE 2SERIES DS-2 DRY-TYPE PENDENT SPRINKLER (ECLH/ECOH)WITH FLUSH ESCUTCHEON (TY5238)SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)FACE OFSPRINKLERFITTING3-5/8" DIA.(92,1 mm)ORDER LENGTHS:3-1/2" to 48"(88,9 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTSK-factor,gpm/psi1/2(lpm/bar1/2)2-1/2 to 6-1/4(63 mm to 159 mm)11.2(161,3)6-1/2 to 10-1/2(165 mm to 267 mm)11.1(159,8)10-3/4 to 14-3/4(273 mm to 375 mm)11.0(158,4)15 to 18-3/4(381 mm to 476 mm)10.9(157,0)19 to 23(483 mm to 584 mm)10.8(155,5)23-1/4 to 26-3/4(591 mm to 679 mm)10.7(154,1)27-1/4 to 31-1/4(692 mm to 794 mm)10.6(152,6)31-1/2 to 35-1/4(800 mm to 895 mm)10.5(151,2)35-1/2 to 39-1/2(902 mm to 1003 mm)10.4(149,8)39-3/4 to 43-1/2(1010 mm to 1105 mm)10.3(148,3)43-3/4 to 48(1111 mm to 1219 mm)10.2(146,9)Notes:K-factor Length is determined as follows: Flush: Order Length from Figure 2 plus 1/2 inch(12,7 mm) Recessed: Order Length from Figure 3 plus 1/4inch (6,3 mm) Extended: Order Length from Figure 4 plus 3-1/4inch (82,6 mm) Without Escutcheon: Order Length from Figure 5minus 2-1/4 inches (57,2 mm)TABLE DDISCHARGE COEFFICIENTS2-3/4" DIA.(69,9 mm)FACE OFCEILING1-5/8 1/8" *(41,3 3,2 mm)K-factorLENGTH,Inches(mm)* ESCUTCHEONWILL PERMIT 3/8" (9,5 mm)ADJUSTMENTFIGURE 3SERIES DS-2 DRY-TYPE PENDENT SPRINKLER (ECLH/ECOH)WITH RECESSED ESCUTCHEON (TY5238)

TFP540Page 5 of 8FACE OFORDER LENGTHS: SPRINKLERFITTING1" to 45-1/4"(25,4 to 1149,4 mm)IN 1/4" (6,4 mm)INCREMENTSFACE OFCEILINGFOR ORDER LENGTHS 3-1/4" (82,6 mm):4-7/8 1/8" (123,8 3,2 mm) *-orFOR ORDER LENGTHS 3-1/4" (82,6 mm):5-5/8 1/8" (142,9 3,2 mm) **3-5/8" DIA.(92,1 mm)SPRINKLERWRENCHINGAREASPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)WRENCHRECESS2-3/4" DIA.(69,9 mm)* ESCUTCHEONWILL PERMIT 5/8" (15,9 mm)ADJUSTMENT** ESCUTCHEONPUSH WRENCHIN TO ENSUREENGAGEMENTWITH SPRINKLERWRENCHING AREAFIGURE 6W-TYPE 17SPRINKLER WRENCHWILL PERMIT 1-3/8" (34,9 mm)ADJUSTMENTFIGURE 4SERIES DS-2 DRY-TYPE PENDENT SPRINKLER (ECLH/ECOH)WITH EXTENDED ESCUTCHEON (TY5238)FACE OFSPRINKLERFITTINGSPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)DO NOTFIGURE 7DO NOT GRASP DEFLECTORORDER LENGTHS:5" to 48"(127,0 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTSMINIMUM2-1/4" (57,2 mm)DEFLECTORTO CEILINGFIGURE 5SERIES DS-2 DRY-TYPE PENDENT SPRINKLER (ECLH/ECOH)WITHOUT ESCUTCHEON (TY5238)

TFP540Page 6 of 8TO E 8SPRINKLER FITTINGHEATED AREARUNOUTLETPLUGGEDTO DRYSYSTEMAREASUBJECTTOFREEZINGFACE OFSPRINKLERFITTINGHEATEDAREASPRINKLERFITTING(SEE DESIGNCRITERIASECTION)SPRINKLERFITTING(SEE DESIGNCRITERIASECTION)DSB-2BOOTFor wet pipe system installations of 1inch NPT Series DS-2 Dry-Type Sprinklers connected to CPVC piping, useonly the following TYCO CPVC fittings:DSB-2BOOTEXPOSURELENGTH(SEE DESIGNCRITERIASECTION)FIGURE 9EXPOSURE LENGTHSTRAP TIES(ENDS ONOPPOSINGSIDES OFBOOT)DSB-2 BOOTADHESIVE2-3/4" DIA.(69,9 WITH FLUSHESCUTCHEONFIGURE 10SPRINKLER FITTINGUNHEATED AREASprinkler FittingsInstall 1 inch NPT Series DS-2 Dry-TypeSprinklers in the 1 inch NPT outlet orrun of the following fittings: malleable or ductile iron threadedtee fittings that meet the dimensional requirements of ANSI B16.3(Class 150) cast iron threaded tee fittings thatmeet the dimensional requirementsof ANSI B16.4 (Class 125)Do not install Series DS-2 Dry-TypeSprinklers into elbow fittings. The Inletof the sprinkler can contact the interiorof the elbow.The unused outlet of the threaded tee isplugged as shown in Figure 10.FIGURE 11MODEL DSB-2 DRY SPRINKLERBOOT WITH SERIES DS-2DRY-TYPE PENDENT SPRINKLERYou can also install Series DS-2 DryType Sprinklers in the 1 inch NPT outletof a GRINNELL Figure 730 MechanicalTee. However, the use of the Figure 730Tee for this arrangement is limited towet pipe systems.The configuration shown in Figure 8 isonly applicable for wet pipe systemswhere the sprinkler fitting and waterfilled pipe above the sprinkler fitting arenot subject to freezing and where thelength of the Dry-Type Sprinkler has theminimum exposure length depicted inFigure 9. Refer to the Exposure Lengthsection. 1 in. x 1 in. NPT Female Adapter(P/N 80145) 1 in. x 1 in. x 1 in. NPT SprinklerHead Adapter Tee (P/N 80249)For dry pipe system installations,use only the side outlet of maximum2-1/2 inch reducing tee when locating Series DS-2 Dry-Type Sprinklersdirectly below the branch line. Otherwise, use the configuration shownin Figure 9 to assure complete waterdrainage from above Series DS-2 DryType Sprinklers and the branchline.Failure to do so may result in pipefreezing and water damage.NOTICEDo not install Series DS-2 Dry-TypeSprinklers into any other type fittingwithout first consulting the TechnicalServices Department. Failure to use theappropriate fitting may result in one ofthe following: failure of the sprinkler to operateproperly due to formation of iceover the Inlet Plug or binding of theInlet Plug insufficient engagement of theInlet pipe-threads with consequentleakageDrainageIn accordance with the minimumrequirements of the NATIONAL FIREPROTECTION ASSOCIATION for drypipe sprinkler systems, branch, cross,and feed-main piping connected to DrySprinklers and subject to freezing temperatures must be pitched for properdrainage.Exposure LengthWhen using dry sprinklers in wet pipesprinkler systems to protect areassubject to freezing temperatures, useTable C to determine a sprinkler’sappropriate exposed barrel length toprevent water from freezing in the connecting pipes due to conduction. Theexposed barrel length measurementmust be taken from the face of thesprinkler fitting to the surface of thestructure or insulation that is exposedto the heated area. Refer to Figure 9 foran example.For protected area temperaturesbetween those given above, theminimum recommended length fromthe face of the fitting to the outside ofthe protected area may be determinedby interpolating between the indicatedvalues.

TFP540Page 7 of 8Clearance SpaceIn accordance with NFPA 13, whenconnecting an area subject to freezing and an area containing a wet pipesprinkler system, the clearance spacearound the sprinkler barrel of Dry-TypeSprinklers must be sealed. Due totemperature differences between twoareas, the potential for the formation ofcondensation in the sprinkler and subsequent ice build-up is increased. Ifthis condensation is not controlled, icebuild-up can occur that might damagethe dry-type sprinkler and/or preventproper operation in a fire situation.Step 1. With a non-hardening pipethread sealant such as TEFLON appliedto the Inlet threads, hand-tighten thesprinkler into the sprinkler fitting. Donot grasp the sprinkler by the deflector(Ref. Figure 7).Use of the Model DSB-2 Dry Sprinkler Boot, described in Technical DataSheet TFP591 and shown in Figure 11,can provide the recommended seal.Note: If sprinkler removal becomesnecessary, remove the sprinkler usingthe same wrenching method notedabove. Sprinkler removal is easier whena non-hardening sealant was usedand torque guidelines were followed.After removal, inspect the sprinkler fordamage.InstallationTYCO Series DS-2 Dry-Type Sprinklers, 11.2K Pendent, Extended Coverage, Light and Ordinary Hazard mustbe installed in accordance with thissection.General InstructionsSeries DS-2 Dry-Type Sprinklers mustonly be installed in fittings that meetthe requirements of the Design Criteria section. Refer to the Design Criteriasection for other important requirements regarding piping design andsealing of the clearance space aroundthe Sprinkler Casing. With referenceto Figure 7, do not grasp the sprinklerby the deflector. Failure to follow thisinstruction may impair performance ofthe device.Do not install any bulb-type sprinklerif the bulb is cracked or there is a lossof liquid from the bulb. With the sprinkler held horizontally, a small air bubbleshould be present. The diameter of theair bubble is approximately 1/16 inch(1,6 mm) for the 135 F (57 C) rating to1/8 inch (3,2 mm) for the 360 F (182 C)rating.A leak-tight 1 inch NPT sprinkler jointshould be obtained by applying a minimum-to-maximum torque of 20 to30 lb-ft (26,8 to 40,2 N·m). Higher levelsof torque may distort the sprinkler Inletwith consequent leakage or impairmentof the sprinkler.Do not attempt to compensate forinsufficient adjustment in an Escutcheon Plate by under or over-tighteningthe Sprinkler. Re-adjust the position ofthe sprinkler fitting to suit.Note: Install pendent sprinklers only inthe pendent position. The deflector ofa pendent sprinkler must be parallel tothe ceiling.Step 2. Wrench-tighten the sprinklerusing either: a pipe wrench on the Inlet Band orthe Casing (Ref. Figure 1) a W-Type 17 Sprinkler Wrench onthe wrench flat (Ref. Figure 6); applythe wrench recess of the W-Type 17Sprinkler Wrench to the wrench flatStep 3. After installing the ceiling andapplying a ceiling finish, slide on theouter piece of the Escutcheon untilit comes in contact with the ceiling.Do not lift the ceiling panel out of itsnormal position.When using the Deep Escutcheon,hold the outer piece in contact with themounting surface (ceiling or wall). Thenrotate the inner piece approximately 1/4turn with respect to the outer piece,to hold the Deep Escutcheon firmlytogether.Care andMaintenanceTYCO Series DS-2 Dry-Type Sprinklers,11.2K Pendent, Extended Coverage,Light and Ordinary Hazard must bemaintained and serviced in accordancewith this section.Before closing a fire protection systemmain control valve for maintenancework on the fire protection systemthat it controls, obtain permission toshut down the affected fire protectionsystems from the proper authoritiesand notify all personnel who may beaffected by this action.Absence of the outer piece of anescutcheon, which is used to cover aclearance hole, may delay the time tosprinkler operation in a fire situation.A Vent Hole is provided in the BulbSeat (Ref. Figure 1) to indicate if the DrySprinkler is remaining dry. Evidence ofleakage from the Vent Hole indicatespotential leakage past the Inlet sealand the need to remove the sprinklerto determine the cause of leakage, e.g.,an improper installation or an ice plug.Close the fire protection system controlvalve and drain the system beforeremoving the sprinkler.Sprinklers which are found to beleaking or exhibiting visible signs ofcorrosion must be replaced.Automatic sprinklers must never bepainted, plated, coated, or otherwise altered after leaving the factory.Modified sprinklers must be replaced.Sprinklers that have been exposed tocorrosive products of combustion, buthave not operated, should be replacedif they cannot be completely cleanedby wiping the sprinkler with a cloth orby brushing it with a soft bristle brush.Care must be exercised to avoiddamage to the sprinklers before,during, and after installation. Sprinklers damaged by dropping, striking,wrench twist/slippage, or the like, mustbe replaced. Also, replace any sprinklerthat has a cracked bulb or that has lostliquid from its bulb. (Refer to Installation Section.)The owner is responsible for the inspection, testing, and maintenance of theirfire protection system and devices incompliance with this document, as wellas with the applicable standards of theNATIONAL FIRE PROTECTION ASSOCIATION (e.g., NFPA 25), in addition tothe standards of any other authoritieshaving jurisdiction. Contact the installing contractor or product manufacturerwith any questions.Automatic sprinkler systems are recommended to be inspected, tested,and maintained by a qualified Inspection Service in accordance with localrequirements and/or national codes.

TFP540Page 8 of 8P/N* 61 – XXX – X – XXXSIN40Pendent withFlush EscutcheonTY5238(Figure 2)41Pendent withRecessed EscutcheonTY5238(Figure 3)42Pendent withExtended EscutcheonTY5238(Figure 4)43Pendent withoutEscutcheonTY5238(Figure 5)Notes:1. Escutcheon Finish applies to sprinklers with escutcheons.2. 286 F (141 C) temperature rating applies to non-recessed sprinkler assemblies.3. Dry-Type Sprinklers are furnished based upon “Order Length” asmeasured per Figures 2 through 5, as applicable, and for eachindividual sprinkler where it is to be installed. After the measurement is taken, round it to the nearest 1/4 inch increment.* Use Prefix “I” for ISO 7-R 1 Connection (e.g., 0CHROMEPLATEDSIGNAL WHITE(RAL9003)POLYESTER1NATURALBRASSSIGNAL WHITE(RAL9003)POLYESTER4SIGNAL WHITE(RAL9003)POLYESTERSIGNAL GTH(3)0135 F (57 C)0555.50 in.1155 F (68 C)0828.25 in.2175 F (79 C)18018.00 in.3200 F (93 C)18718.75 in.4286 F (141 C)37237.25 in.48048.00 in.TABLE ESERIES DS-2 EXTENDED COVERAGE DRY-TYPE SPRINKLERSPART NUMBER SELECTIONLimitedWarrantyFor warranty terms and conditions, visitwww.tyco-fire.com.OrderingProcedureContact your local distributor for availability. When placing an order, indicate the full product name, includingdescription and Part Number (P/N).Dry-Type SprinklerWhen ordering Series DS-2 Dry-TypeSprinklers, 11.2K Pendent, ExtendedCoverage, Light and Ordinary Hazard,specify the following information: SIN TY5238 Order Length:Dry-Type Sprinklers are furnishedbased upon Order Length asmeasured from the face of theceiling to the face of the sprinklerfitting (Ref. Figures 2 through 5).After the measurement is taken,round it to the nearest 1/4 inchincrement. Inlet Connections:1 Inch NPT(Standard)ISO 7-R 1(For information on ISO Inlet ThreadConnections, contact your JohnsonControls Sales Representative.)Sprinkler WrenchSpecify W-Type 17 Sprinkler Wrench,P/N 56-010-4-118Sprinkler BootSpecify Model DSB-2 Dry SprinklerBoot, P/N 63-000-0-002This P/N includes one (1) Boot, two (2)Strap Ties, and 1/3 oz of Adhesive (asufficient quantity for installing oneboot). Temperature Rating Sprinkler Finish Escutcheon Type and Finish, asapplicable Part Number from Table E1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone 1-215-362-0700 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;TEFLON is a registered trademark of DuPont

with sprinkler wrenching area sprinkler wrenching area order lengths: 5" to 48" (127,0 to 1219,2 mm) in 1/4" (6,4 mm) increments minimum 2-1/4" (57,2 mm) deflector to ceiling face of sprinkler fitting sprinkler fitting (refer to design criteria section) escutcheon will permit 1-3/8" (34,9 mm) adjustment escutcheon will permit 5/8" (15,9 mm .

Related Documents:

AIR CONTROL REQUIREMENTS FOR DRY CLEANERS WITH EXISTING MACHINES ARE BASED ON PERC PURCHASES Small Area Dry Cleaners Large Area Dry Cleaners Major Dry Cleaner Dry-to-Dry Machines ONLY: Less than 140 gal/yr OR Transfer Machines ONLY: Less Than 200 gal/yr OR Transfer AND Dry-to-Dry Machines: Less Than 140 gal/yr* Dry-to-Dry Machines ONLY:

Taking Advantage on In-Network Cost-Share Accessing Out-of-Network Cost-Share Member sees a Kelsey-Seybold Clinic PCP 0 Member sees an out-of-network PCP 10 Member sees a Kelsey-Seybold Clinic specialist 25 Member sees an out-of-network specialist 35 Member sees an affiliate provider contracted with Kelsey 25 Member sees an MD Anderson .

(MMA)** Ennis - Flint 04/ Richmond, VA 4161 Piedmont Pkwy Greensboro, NC 27410 www.ennisflint americas.com 800-331-8118 336-475-7900 fax Paint Paint Paint High Build Paint (HB) High Build Paint (HB) Thermoplastic Thermoplastic Dry Dry Dry Dry Dry Dry Dry N/A N/A N/A N/A N/A N/A N/A Y W B W Y W Y TRAF87052 TRAF87051 TRAF87041 TRAF87061 TRAF87062 .File Size: 218KB

Independent Personal Pronouns Personal Pronouns in Hebrew Person, Gender, Number Singular Person, Gender, Number Plural 3ms (he, it) א ִוה 3mp (they) Sֵה ,הַָּ֫ ֵה 3fs (she, it) א O ה 3fp (they) Uֵה , הַָּ֫ ֵה 2ms (you) הָּ תַא2mp (you all) Sֶּ תַא 2fs (you) ְ תַא 2fp (you

This research aims to develop an innovative electrical discharge machining (EDM) process, i.e., dry and near-dry EDM milling, as the finishing technology for rapid and precision die, mold and tool fabrication. Applied as the post-process of direct metal deposition (DMD), the dry and near-dry EDM milling processes are targeted to finish the

HOOVER H-Wash & Dry 500 [pdf] Instruction Manual H-Wash Dry 500 HOOVER H-Wash & Dry 500 [pdf] User Guide HOOVER, H-Wash, Dry, 500, Wash Dry Related Posts Join the Conversation 1. 2. 2 Comments 1. ISABEL RODRIGUEZ says: June 25, 2021 at 5:35 pm I just bought a Hoover washer-dryer and unfortunately in the manuals it brings and on the website I .

Dry eye is problem of tear quantity, quality or stability, and a process of inflammation is often associated with dry eye. Factors associated with dry eye Diabetes mellitus, autoimmune disease, hepatitis C, HIV infection, radiation therapy and bone marrow transplantation have all been associated with dry eye disease. Medications and dry eye .

engine or high performance street engine supplier. To learn . BMW 44DF: 92-94MM DRY TYPE FLANGED SLEEVE: DOUBLE FLATS 1994-05 M62 740I V-8 BMW V10SF: . 1988-96 M70/S70 V-12 FL3336DF : 92MM DRY TYPE FLANGED SLEEVE: S-65 4.0L DOUBLE FLATS FL3336SF: 92MM DRY TYPE FLANGED SLEEVE: S-65 4.0L SINGLE FLAT BMWS62DF/SF : 94MM DRY TYPE FLANGED