Transcription

Cable Support and Fixing Systems

INTRODUCTIONLinking the futureAs the worldwide leader in the cable industry, Prysmian Groupbelieves in the effective, efficient and sustainable supply ofenergy and information as a primary driver in the developmentof communities.With this in mind, we provide major global organisationsin many industries with best-in-class cable and accessorysolutions, based on state-of-the-art technology. Through tworenowned commercial brands - Prysmian and Draka – based inalmost 50 countries, we’re constantly close to our customers,enabling them to further develop the world’s energy andtelecoms infrastructures, and achieve sustainable,profitable growth.In our energy business, we design, produce, distribute andinstall cables and systems for the transmission and distributionof power at low, medium, high and extra high voltage.In telecoms, the Group is a leading manufacturer of all typesof copper and fibre cables, systems and accessories - coveringvoice, video and data transmission.Drawing on over 130 years’ experience and continuouslyinvesting in R&D, we apply excellence, understanding andintegrity to everything we do, meeting and exceeding theprecise needs of our customers across all continents, at thesame time shaping the evolution of our industry.UTILITIESCable solutions to support the developersof the world’s utility infrastructure?Cable solutions to support the development of smarter andgreener power grids.From Asia-Pacific to the Americas, and from Europe to theMiddle East to Africa, Prysmian cable solutions sit at theheart of the development of power grids worldwide, helpingmajor utilities in transmitting and distributing power totheir customers.Unmatched in our manufacturing capabilities and with anunwavering commitment to R&D, we design, produce2and install low, medium, high and extra-high voltageunderground and submarine cables and systems, along withnetwork components and value-added engineering services.Always aware of the need to minimize our impact on theplanet, we’re constantly driving innovation in our industry,aiming to optimise supply chain processes, reduce totalcost of ownership for our customers and help them achievesustainable, profitable growth.

engineering building on the pedigree of our previous companynames - going back to BICC. Of course Prysmian Group’sComponents products are the perfect installation accessoryfor the Company’s vast range of quality, approved cables.Prysmian Group’s comprehensive component productrange includes:From its UK base, Prysmian Group’s Components business is able toefficiently service the needs of its UK and overseas customers andoffers a high level of pre-sales and post-sales customer service.For further information please contact:0845 767 8345International Sales Office: 44 2380 295481Sales Hotline:INTRODUCTIONPrysmian Group’s dedicated Components facility based inWrexham, Wales manufactures and supplies the market withproducts which are widely used in industrial, commercial anddomestic power distribution systems. In addition it offersproducts for more specialist applications such as Utilities,Railways, Oil, Gas and Petrochemical, Hazardous Areas, Windand Solar Energy. Today’s BICON product ranges representover 100 years of cable accessory development and quality BICON Cable Glands BICON Cable Cleats BICAST Joints & Terminations BICON Connectors and Tooling Flexo Modular Power Systems Flexo Rail products JEM Resin Connecta System www.biconcomponents.co.ukIntroduction to cable support and fixing systemsPrysmian Group’s Components business unit, based inWrexham, is the UK’s leading manufacturer of CableSupport and Fixings Systems and offers a range that is bothcomprehensive and diverse. Through many years of industryexperience and working closely with our customers, PrysmianGroup is able to offer cleats to support and fix all cable typeson the market.Our accessory range has been designed and tested with ThePrysmian Group cable products and are recommended as thepreferred method of installation.The ever popular two-bolt, hook, telcleat and claw cleats areavailable in a range of materials to suit a variety of applications,including heavy duty variants. Our patented Multicleat/Multistrap system and the Trefoil families offer installersseveral viable options for Trefoil installations.When installing fire resistant and Low Smoke Zero Halogencables it is important that the accessories used meet the sameperformance requirements as the cable so as not to impacton the system performance in case of fire. As the UK’s marketleader in both of these types of cables it is no surprise that thePrysmian Group is able to offer specific fixing solutions. Lookout for the FP, Afumex, FT and Saffire logos in the cataloguewhich highlight these.A thermoset epoxy coating is available on all our ranges ofaluminium cleats and bases, and can be specified whereconsideration as to the nature of the environment is oneof prime concern. It offers outstanding protection in areascontaining a combination of one or more of the following:saline, chemical attack, pollution, high humidity and/or highambient temperatures.Our cleats have been used on a vast number of major electricalengineering projects including: the Channel Tunnel, Gorgon LNG,PEARL, London Heathrow T5, Helwyn Windfarm and theWoodhead Tunnel.3

Cleat selectionCables can be mounted on supports in many ways, however if cable cleats are correctly used to do this they will satisfy therequirements of the IET 17th Edition Wiring Regulations.522.8.4 “Where the conductors or cables are not supported continuously due to the method of installation, they shallbe supported by suitable means at appropriate intervals in such a manner that the conductors or cables do not sufferdamage by their own weight.” (1)522.8.5 ”Every cable and conductor shall be supported in such a way that it is not exposed to undue mechanical strainand so that there is no appreciable mechanical strain on the terminations of the conductors, account being taken ofthe mechanical strain imposed by the supported weight of the cable or conductor itself.” (1)(1)522.8.4 , 522.8.5 extracts from BS 7671 – IET 17th edition wiring regulationsCable cleats also offer the following additional advantages:- They facilitate a neat and orderly installation allowing cables to be used at their optimum ratings whilst maximisingthe use of available space.- They maintain cables in position making reworking easier and potentially safer.- They provide restraint against short circuit forces.This catalogue is designed to direct you to the most suitable Prysmian Components cleat for your application.The logic tree below shows the decisions that need to be made in order to specify the correct cleat for a specific installation.The 1st decision is whether or not the arrangement is a single cable or a trefoil grouping: When fixing a single cable the cleats should be installed in line with the IET 17th Edition – guide to use table. When fixing trefoil groups the controlling factor becomes the system short circuit rating and cleats should be selected andspaced according to their short circuit performance.4

INTRODUCTIONContentsIntroductionLinking the FutureIntroduction to cable support and fixing systemsCleat selectionCorrect spacingApprovals and Standards2346-77Single Way CleatsTelcleatAfumex Telcleat (LSOH)Ranger CleatHeavy Duty Hook CleatPlastic Two Bolt CleatAfumex Two Bolt Cleat (LSOH)Hook Cleat (Aluminium)Claw Cleat (Aluminium)Two Bolt Cleat (Aluminium)Shoe CleatLinear Short Circuit StrapsHeavy Duty Two Bolt Cleat (Aluminium)Orbit Cleat8910111213141516 - 1718192021Fire Resistant CleatsFirefix Single ClipFirefix Double ClipAP ClipsClaw Cleat (Cast Iron)Two Bolt Cleat (Cast Iron)2223242526Trefoil CleatsMulticleat / Multistrap SystemSirius CleatOrion CleatOrion Cleat - ShapedLibra Cleat27 - 2930 - 31323334Bespoke SolutionsInstallation EquipmentRigid Tunnel Clamping ArrangementSystem Repair CleatAuxiliary Stand Off35353636AccessoriesCable TiesAdaptor Plate and Packing Piece37385

INTRODUCTIONCorrect SpacingSingle CablesSpacings of supports for cables in accessible positionsMaximum spacings of cable fixingsOverall diameter of cable*Non‑armoured thermosetting,thermoplastic or lead sheathed cablesand non-armoured fire resisting cables.Single wire armoured cablesincluding fire resistingarmoured cableMineral insulated coppersheathed or aluminiumsheathed t exceeding 9250400--600800Exceeding 9 and not exceeding 153004003504509001200Exceeding 15 and not exceeding 2035045040055015002000Exceeding 20 and not exceeding 40400550450600--Exceeding 40 and not exceeding 506008009001100--Exceeding 50 and not exceeding 6075010009501100--Exceeding 60 and not exceeding 70900120010001200--Exceeding and above1000140012001400--Note:Fire resistant fixings should be used for fire resistant cables.* For flat cables taken as the dimension of the major axis.The spacings shown above apply to multi-core cables.The spacing of fixings on single core cables in a.c. installations must take account of the magnitude of forces generated under fault conditions.† The spacings stated for horizontal runs may be applied also to runs at an angle of more than 30 from the vertical.For runs at an angle of 30 or less from the vertical, the vertical spacing’s are applicable.Cleating Cables in TrefoilWhen a short circuit fault occurs in a three phase system, there is at first a period of extreme asymmetry which is then followedby a steadier more symmetrical state.The degree of asymmetry depends on when in the cycle the fault is initiated and also the nature of the fault, e.g. three phase toearth. By convention, the “Peak” is the maximum current value achieved in the early asymmetrical period and it is at this pointthat the highest instantaneous force between the cables occurs.6

INTRODUCTIONBS EN 61914:2009 ( IEC 61914 ) provides aformulae which enables us to calculate themaximum force on a cable conductor.Three phase short circuit plotis the maximum force on the cableconductor in a trefoil configuration for athree phase short circuit [N/m]is the peak short-circuit current [kA]is the centre to centre distance between twoneighbouring conductors [m](for Trefoil arrangements S Cable Diameter)Short circuit tests in accordance with BS EN 61914:2009 are performed on the most critical cleat size within its range; the Formula(B.4) can then be used to calculate the maximum force generated during the test. This maximum force figure can then be usedwhen specifying alternative configurations of cable size and fault current – calculating the theoretical Ft for the alternativeconfiguration and ensuring that it is less than or equal to the as tested value.Trefoil Cleat SpacingTrefoil cleats that are required to withstand the high forces generated by high short circuit currents will often be spaced at veryregular intervals – typically matching the commonly available cable ladder (i.e. 300mm / 225mm).The maximum short circuit current values will be quoted with the test information for each design of trefoil cleat - if a system useslarger cables or has a lower fault current it may be possible to broaden these spacings - (contact the Prysmian technical team).As a general rule in order to create and maintain a satisfactory trefoil installation a maximum strap/cleat spacing of900mm is preferred.Approvals, Testing and StandardsFor many years there were no British or International standards for cable cleats; Prysmian Components were actively involved inthe creation of the European Standard and in progressing the standard through to it being published as the current internationalstandard BS EN 61914:2009 (IEC 61914).Our cleats have been tested by independent testing authorities including:BSTS (ASTA)ERDA (ASTA)CPRI (ASTA)IPH CESI (ASTA)ZKUWe also hold third party test reports for our LSOH cleats detailing compliance with LUL requirements.7

Single Way CleatsTelcleat 385 series uitable for use with cable diameters 10 to 51mm.S Manufactured from Low Density Polythene. Overlapping self-adjusting ranges. Sunlight (UV) and weather resistant. One piece, single fixing design. Can be double stacked on a single fixing. Operating temperature -40 C to 60 C. Tested in accordance with BS EN 50368.Technical DataDesign 5AA07385AA08Cable and Cleat SelectionCable DiameterStandard PackA 110Cleat DetailsScrew BoltDimensions (mm)Roundhead woodscrewWeight (g) masonry, concrete or wood for Cable TrayBCDins x NommMinMax Max2.315M4 x 301832121 1/4 x 8173.42236141 1/2 x 8M4 x 355.5211 3/4 x 8M4 x 402643162x8M4 x 45258.63151183012.43757202 1/4 x 12M6 x 503516.44365222 1/2 x 12M6 x 6042245278252 3/4 x 12M6 x 7050629126353 1/4 x 12M6 x 80Method of FixingThe cleat is opened up and placed around the cable so that the end of the cleat containing the slot will be in contact with the mountingsurface, except for the 385AA01, which should be reversed to put the slot uppermost. In this case an M5 washer should be used toprevent the nut entering the slot of the cleat.When mounting directly on channel section an adaptor plate should be used (please see page 38).Performance DataTest StandardEN 50368:2003Type6.1.2 Non-MetallicImpact Resistance6.2.4 Heavy - 6.2.5 V. HeavyLateral Load0.188 - 0.775 kNAxial Load0.046 - 1.118 kNNeedle Flame 60 secs* Technical Information subject to change without notice8

Single Way CleatsAfumex Telcleat (LSOH) 385 series uitable for use with cable diameters 10 to 51mm.S Manufactured from LSOH polymer. Designed for use with Afumex LSOH and Saffire OHLS cables. Overlapping self-adjusting ranges. Sunlight (UV) and weather resistant. One piece, single fixing design. Can be double stacked on a single fixing. Operating temperature -40ºC to 40ºC. Tested in accordance with BS EN 50368. LUL APR Product ID 1259.Technical DataCable and Cleat SelectionDesign NumberCable DiameterStandard PackA 9.351.1385LSF0810Cleat DetailsScrew BoltDimensions (mm)Roundhead woodscrewWeight (g) masonry, concrete or wood for Cable TrayBCDins x NommMinMax Max3.3151832121 1/4 x 8M4 x 30175.62236141 1/2 x 8M4 x 359.5211 3/4 x 8M4 x 402643162x8M4 x 452514.73151183020.43757202 1/4 x 12M6 x 503529.24365222 1/2 x 12M6 x 604236.75278252 3/4 x 12M6 x 705062912658.13 1/4 x 12M6 x 80Method of FixingThe cleat is opened up and placed around the cable so that the end of the cleat containing the slot will be in contact with the mountingsurface, except for the 385LSF01, which should be reversed to put the slot uppermost. In this case an M5 washer should be used toprevent the nut entering the slot of the cleat.When mounting directly on channel section an adaptor plate should be used (please see page 38).Performance DataTest StandardEN 50368:2003Type6.1.2 Non-MetallicImpact Resistance6.2.4 Heavy - 6.2.5 V. HeavyLateral Load0.136 - 0.781 kNAxial Load0.119 - 1.024 kNNeedle Flame 120 secs* Technical Information subject to change without notice9

Single Way CleatsRanger Cleat382 series uitable for use with cable diameters 13 to 76mm.S Overlapping, self-adjusting ranges. Sunlight (UV) and weather resistant. Made from ABS which provides good oil and chemical resistance. Two piece, single bolt fixing. Double stacking facility. Operating temperature -20 C to 90 C. ‘C’ Section channel location aids fixing and stacking. Not designed for long vertical runs.Technical DataCable and Cleat SelectionDesign NumberCable diameterA 04273651382AA0550382AA0676Dimensions 236111529247Method of FixingIn all applications the cleat should be mounted on suitable M10 fixings. There is no need for any channeladaptor when mounting directly on to ‘C’ section channel.SWL data based upon the use of commercial grade 4.6 mild steel.SWL Safe working load.FOS 2 Values include a factor of safety of 2.10Cleat DetailsSWL FOS2 (kgfl)Weight (g)3002602951671581105152.56376121193

Technical DataCable and Cleat SelectionDesign NumberCable DiameterNylonA ble for use with cables diameters 25 to 80mm.Manufactured from glass-filled nylon.Two-piece, single fixing design.Can be double stacked on a single fixing.Can be installed in temporary open position to aidsingle person working.All sizes secured with 10mm fixings.Operating temperature -25 C to 85 C.For normal industrial use Indoor and Outdoor.Fits most ladder and tray systems.Not designed to secure cables in long vertical routes.Tested in accordance with BS EN 50368.Cleat DetailsDimensions (mm)CDBSingle Way CleatsHeavy Duty HookCleat 384 44Weight (g)E1818181820206374105129175221Method of FixingIn all applications the cleat should be mounted on suitable M10 fixings. There is no need for any channeladaptor when mounting directly on to ‘C’ section channel.Performance DataTest StandardEN 50368:2003Type6.1.2 Non-MetallicImpact Resistance6.2.4 Heavy - 6.2.5 V. HeavyLateral Load1.320 - 1.5 kNAxial Load82 - 109 NNeedle Flame 120 secs* Technical Information subject to change without notice11

Single Way CleatsPlastic Two BoltCleat 374 series S uitable for use with cable diameters 50 to 94mm. Manufactured from black high-density nylon 66. Unaffected by corrosive environments such as oilsand many chemicals. Sunlight (UV) and weather resistant. Two-piece, two fixing design. Can be double stacked on common fixings. Operating temperature -25 C to 85 C. Tested in accordance with BS EN 50368.Technical DataCable and Cleat SelectionCable diameterDesign NumberA 110118121Method of FixingIn all applications the cleat should be mounted on suitable M10 fixings.There is no need for any channel adaptor when mounting directly on to ‘C’ section channel.Performance DataTest StandardEN 50368:2003Type6.1.2 Non-MetallicImpact Resistance6.2.4 Heavy - 6.2.5 V. HeavyLateral Load10.9 - 14.8 kNAxial Load198 - 494 NNeedle Flame 120 secs* Technical Information subject to change without notice12Cleat DetailsDimensions (mm)DC10210211411412612613645454550505060Weight (g)E808092921041041149798106132154160204

Single Way CleatsAfumex Two BoltCleat (LSOH) 374 series Suitable for use with cable diameters 50 to 94mm. Manufactured from LSOH Polymer. Designed for use with Afumex LSOH and Saffire OHLS cables. Low Smoke and Zero Halogen. Sunlight (UV) and weather resistant. Two-piece, two fixing design. Can be double stacked on common fixings. Operating temperature -40 C to 60 C. Tested in accordance with BS EN 50368. LUL APR Product ID 1958.Technical DataCable and Cleat SelectionDesign NumberCable DiameterA 9398104110118121Cleat DetailsDimensions (mm)CD10210211411412612613645454550505060Weight (g)E80809292104104114174158174210254264326Method of FixingIn all applications the cleat should be mounted on suitable M10 fixings.There is no need for any channel adaptor when mounting directly on to ‘C’ section channel.Performance DataTest StandardEN 50368:2003Type6.1.2 Non-MetallicImpact Resistance6.2.5 V. HeavyLateral Load1.22 - 3.485 kNAxial Load82 - 110 NNeedle Flame 120 secs* Technical Information subject to change without notice13

Single Way CleatsHook Cleat(Aluminium) 371 series Technical DataCable and Cleat SelectionDesign NumberCable diameterA 70371AA117076371AA12Cleat DetailsDimensions (mm)CDEBMin29343744505564728091 Suitable for use with cable diameters 19 to 76mm. Manufactured from aluminium alloy. Self-adjusting ranges. Two-piece, single fixing design. Can be double stacked on a single fixing. Can be installed in temporary open position to aidsingle person working. Suitable for indoor dry normal industrial use oroutdoor unpolluted areas. Operating temperature -60 C to 105 C. Not designed to secure cables in long vertical routes. LUL APR Product ID 1323838454545454545454524262932353843485357Method of FixingIn all applications the cleat should be mounted on suitable M10 fixings.When mounting directly on “Unistrut” or “Leprack” type channel, adaptor plate 380AG02 should be used (please see page 38).Performance DataTest StandardEN 50368:2003Type6.1.1 MetallicImpact Resistance6.2.5 V. HeavyLateral Load1.32 - 1.5 kNAxial Load82 - 109 NNeedle Flame 120 secs* Technical Information subject to change without notice14Weight 26

Claw CleatSingle Way Cleats(Aluminium) 370 series uitable for use with cable diameters 10 to 51mm.S Manufactured from aluminium alloy. Two-piece, single fixing design. Can be stacked to a maximum of three on one fixing. Operating temperature -60 C to 105 C. Can be used for all types of cable routes. Plain finish - for normal industrial areas or outdoorunpolluted areas. Epoxy coated versions available for harsher environments. Packing pieces to be used where required. LUL APR Product ID 1959.Technical DataCable and Cleat SelectionDesign NumberStandardEpoxy BB05370BB06370BB07370BB08370BB09Cable diameterA nsions 464646464646161618192124273034Cleat DetailsWeight (g)605060708090110120150Stud SizeM10M10M10M10M10M10M10M10M10Method of FixingIn all applications the cleats should be mounted on suitable M10 fixings. When mounting directly on channel,adaptor plate 380AG02 should be used. When stacking claw cleats use packing piece 389AC03 between cleats.(Please see page 38 for selecting both of these items.)Performance DataTest StandardEN 50368:2003Type6.1.1 MetallicImpact Resistance6.2.5 V. HeavyLateral Load3.7 - 8.2 kNAxial Load1.332 - 5.855 kNNeedle Flame 120 secs* Technical Information subject to change without notice15

Single Way CleatsTwo Bolt Cleat(Aluminium) 370 seriesTechnical Data Suitable for use with cable diameters 51 to 159mm.Manufactured from aluminium alloy.Two-piece, two fixing design.Can be double stacked on common fixings.Operating temperature -60 C to 105 C.Suitable for LV & HV cables.Can be used for all types of cable routes.Plain finish - for normal industrial areas or outdoor unpolluted areas.Epoxy coated versions available for harsh environments.Optional rubber liners available.Tested in accordance with BS EN 50368.LUL APR Product ID 1963.Cable and Cleat SelectionDesign NumberCable DiameterEpoxy CoatedB (mm)StandardA BB35370BA35370BA36152159172370BB3616Dimensions t DetailsStud 12M12Weight 31325

Design Numbers with the Suffix “L” are fitted with a 5mm rubber liningCleat DetailsB (max)133139145152158164172Dimensions ud SizeWeight 5Single Way CleatsCable and Cleat SelectionDesign NumberCable DiameterStandardEpoxy CoatedA 36L149370BA36LE150150175175175185190* 370BA/BB & BA*L cleats are supplied without fixing bolts which should be selected by using dimension ‘B’together with the thickness of the cable support arrangementPerformance DataTest StandardEN 50368:2003Type6.1.1 MetallicImpact Resistance6.2.5 V. HeavyLateral Load18.1 kNAxial Load11.4 - 13.8kNNeedle Flame 120 secs* Technical Information subject to change without notice17

Single Way CleatsShoe Cleat370 seriesIn order to allow for the linear expansion of larger cables the supportpositions are often broadly spaced. Such broad spacing would put veryhigh point loading on the cables which could lead to long term failure.The shoe cleats are designed to allow this potentially damaging loadto be spread over a significantly longer length thus avoiding anypotential cable damage. Based on the 370 series of aluminium 2 boltcleats with the shoes made from 316L stainless steel with rubberlining. The shoes are designed and formed with the correct bendradius to match the cable’s expansion curve.Contact the Prysmian Components technical team who will be ableto match the correct cleat and spacing to the size of cable andinstallation design.Technical DataCable and Cleat SelectionDesign NumberCable 123130136142Max85111117123130136142149Stud SizeM12M12M12M12M12M12M12M12Cleat DetailsBolt 0500600700700800800Expansion Radius(mm)30003000300030003000300030003000

Single Way CleatsLinear ShortCircuit StrapsThe linear short circuit straps can be used in horizontal or verticalinstallations. They can be designed and manufactured to userspecified interaxial spacings. Options are available for them to besupplied with or without rubber liners to meet the cable systemdesign requirements.Contact the Prysmian Components technical team who will be ableto match the correct cleat and spacing to the size of cable andinstallation design.Technical DataCable and Cleat SelectionAluminium Alloy3 way2 way370SA66-xxx370SA16-xxxEpoxy Coated Aluminium Alloy3 way2 -xxx370SB86-xxxCleat DetailsCable 117130123136130142136149142Replace ‘xxx’ with 300, 400, 500, 600, 700 for required cable separation.19

Heavy DutyTwo Bolt CleatSingle Way Cleats(Aluminium)370 series I deally suitable for larger cables with diameters 100 to 159 mm. Manufactured from aluminium alloy. Two-piece, two fixing design. Operating temperature -60 C to 105 C. Designed to protect the cable sheaths during installation. Plain finish - for normal industrial areas or outdoorunpolluted areas. Epoxy coated versions available for harsher environments. Supplied with rubber liners. Tested in accordance with BS EN 61914.Contact the Prysmian Components technical team who will beable to match the correct cleat and spacing to the size of cableand installation design.Performance DataTest StandardEN 50368:2003Type6.1.1 MetallicImpact Resistance6.3.3 MediumLateral Load50 kNAxial Load8kNNeedle Flame 120 secs* Technical Information subject to change without notice20

Orbit Cleat379 series Suitable for use with cable diameters 33 to 150mm.Single bolt fixing.Operating temperatures -40 C to 120 C.Ergonomic design allows easy installation, withsingle tool tightening from the top side.Manufactured from non-magnetic, corrosion resistant 316L stainless steel.Liners are made from LSOH materials.Suitable for use with single and multicore cables withhigh fault current requirements.Suitable for standard and LSOH cable sheaths.Can be used in harsh environments.Can be used with all standard ladder and tray systems.Complies with IEC 61914:2009.Single Way Cleats Technical DataCleat SelectionDesign NumberCable 046536067748292103113123132141150Cleat DetailsDimensions (mm)ABCWeight l cleats have a single central fixing hole for a 12mm diameter fixing bolt.Performance g Temperature6.2-40 C to 120 CImpact Resistance6.3V. Heavy10.1 120secsNeedle FlameResistance toShort CircuitClauseClassification6.4.3 (1 short circuit)Depends on cable spacing - refer tomanufacturerDepends on cable spacing - refer tomanufacturer6.4.4 (2 short circuits)Corrosion6.5.2High, Outdoor - wet conditions* Technical Information subject to change without notice21

Firefix Single ClipFire Resistant Cleats L UL APR Product ID 1960. Nail fixed fire resistant clip. The Firefix system is fast easy and meets the cable support requirements ofBritish standards: BS5839-1: 2002, BS5266-1:2011 and BS5839-8: 2006. Designed to be used with the Spit Pulsa

Prysmian Group’s Components business unit, based in Wrexham, is the UK’s leading manufacturer of Cable Support and Fixings Systems and offers a range that is both comprehensive and diverse. Through many years of industry experience and working closely with our customers, Prysmian Group is able to offer cleats to support and fix all cable types

Related Documents:

requirements as the cable so as not to impact on the system performance in case of fire. As the UK’s market leader in both of these types of cables it is no surprise that the Prysmian Group is able to offer specific fixing solutions. Look out for the FP, Afumex, FT and Saffire logos in the catalogue which highlight these.

Supplement to Prysmian Group General Catalogue (CEE Region) As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient . and sustainable supply of energy and information as a primary driver in the development of communities.

Draka, the Prysmian Group is now the world’s largest producer of power and telecommunication cables with 97 manufacturing plants, 17 Research & Development Centres, and around 22,000 employees. A global solutions provider, Prysmian offers a wide range of integrated solutions, such as cable systems, system design and engineering,

Airfield Cable & Accessory Catalogue NORTH EUROPE 1. As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy and information as a primary driver in the development of communities. With

Welcome to the new edition of the Prysmian Components’ Shortform Catalogue, containing our extensive range of power cable accessories. As you may be aware Prysmian is the new name for the Pirelli Cables Businesses worldwide. This is the first Shortform

Automobile Cable Catalogue GENERAL 5. Als Weltmarktführer in der Kabelindustrie, glaubt die Prysmian Group an eine effektive, effiziente und nachhaltige Versorgung mit Energie und Informationen als Hauptwachs-tumstreiber bei der Entwicklung von Gemein-den. In diesem Sinne statten wir große globale

As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy and information as a primary driver in the . These products are highlighted in the catalogue. Please note the relevant LUL APR Product ID numbers on the relevant pages.

5National Institute of Basic Biology, Okazaki, Aichi, 444-8585 Japan 6Present address: The University of Tokyo, Nikko, Tochigi, . 26 bryophyte (Smith and Read 2008). The AM fungi provide host plants with phosphate taken up from the 27 soil, and in return receive carbon from the host plants. This symbiosis was already thought to be 28 present more than 400 million years ago when the .