ONSETUPOFFThe power behind competitivenessDelta UPS - Amplon FamilyN Series, Single Phase6/ 10 kVAUser Manualwww.deltapowersolutions.com

Save This ManualThis manual contains important instructions and warnings that you shouldfollow during the installation, operation, storage and maintenance of thisproduct. Failure to heed these instructions and warnings will void the warranty.Copyright 2016 by Delta Electronics Inc. All Rights Reserved. All rights of thisUser Manual (“Manual”), including but not limited to the contents, information,and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”).The Manual can only be applied to the operation or the use of this product. Anydisposition, duplication, dissemination, reproduction, modification, translation,extraction, or usage of this Manual in whole or in part is prohibited without the priorwritten permission of Delta. Given that Delta will continuously improve and developthe product, changes may be made to the information in this Manual at any timewithout obligation to notify any person of such revision or changes. Delta will makeall possible efforts to secure the accuracy and the integrity of this Manual. Deltadisclaims any kinds or forms of warranty, guarantee, or undertaking, either expresslyor implicitly, including but not limited to the completeness, faultlessness, accuracy,QRQ LQIULQJHPHQW PHUFKDQWDELOLW\ RU ¿WQHVV IRU D SDUWLFXODU SXUSRVH RI WKH 0DQXDO Amplon N SeriesII

Table of ContentsTable of ContentsChapter 1 : Important Safety Instructions --------------------------- 11.1Safety Instructions ---------------------------------------------- 11.2Standard Compliance ------------------------------------------ 41.3Storage ----------- 4Chapter 2 : Introduction - 52.1General Overview ----------------------------------------------- 52.2Exterior & Dimensions ----------------------------------------- 52.3Package List ---- 6Chapter 3 : Operation Panel ---------------------------------------------- 93.1LED Indicators - 93.2Multi-function Buttons -----------------------------------------103.3LCD Display ---133.47-Segment Display 16-Segment Display ror Code -183.7LCD Display Flow Chart --------------------------------------19Chapter 4 : Rear Panel --21Chapter 5 : Wiring --------275.1Pre-wiring Warnings put/ Output Wiring ternal Battery Pack Connection -------------------------30Chapter 6 : Operation Modes andby Mode -346.2On-line Mode --346.3Bypass Mode --346.4Battery Mode --35III

6.5ECO Mode -----356.6Setup Mode ----35Chapter 7 : Turn-on & Turn-off Procedures ------------------------397.1Turn-on ----397.2Turn-off ----40Chapter 8 : Alarm ---------41Chapter 9 : Optional Accessories -------------------------------------42Chapter 10 : Troubleshooting r 11 : Maintenance 11.1 UPS --------------4711.2 Batteries --------4711.3 Fans -------------48 SSHQGL[ 7HFKQLFDO endix 2 : Warranty --51Amplon N SeriesIV

Chapter 1Important Safety InstructionsChapter 1 : Important Safety Instructions1.1 Safety InstructionsInstallation Warningsz Before installation and usage, please read this User Manual thoroughly. Thishelps you to use the product correctly and safely.z Install the UPS in a well-ventilated area, away from excess moisture, heat, dust,ÀDPPDEOH JDV RU H[SORVLYHV z R DYRLG ¿UH DFFLGHQWV DQG HOHFWULF VKRFN SOHDVH LQVWDOO WKH 836 LQ D WHPSHUDWH 7and humidity well-controlled indoor area that is free of conductive contaminants.For the temperature and humidity specifications, please refer to Appendix 1:7HFKQLFDO 6SHFL¿FDWLRQV.z Leave adequate space (at least 50cm) around all sides of the UPS for properventilation.Connection Warningsz The UPS must be well grounded due to a possible risk of current leakage.z The installation of upstream and downstream protective devices is highly recommended when the UPS is connected to the mains and the loads.z The protective devices connecting to the UPS must be installed near the UPSand must be easily accessible for operation.z If you need to move the UPS or perform re-wiring, please turn off the AC inputpower and ensure that the UPS has been safely shutdown and the connectedexternal battery pack has been disconnected. Otherwise, the output end mightstill be energized, which might cause electric shock.Usage Warningsz This is a class-A product. In a domestic environment, this product may cause radio interference, in which case, the user is required to take adequate measures.z The UPS can be used to power computers and associated peripheral devices,such as monitors, modems, cartridge tape drives, external hard drives, etc.1

z It is strictly forbidden to connect the UPS with:1. any regenerative-type loads. DQ\ DV\PPHWULFDO ORDGV H[ KDOI ZDYH UHFWL¿HU z To ensure reliable operation of the UPS and to protect the UPS from overheating, the slits and openings in the UPS must not be blocked or covered.z Before usage, you must allow the UPS to adjust to room temperature for at leastone hour to avoid moisture condensing inside the UPS.z Do not pour and splash any liquid on the UPS. Do not insert any object intothe UPS’s slits and openings. Do not put beverage containers on or around theUPS.z When an emergency occurs, press the OFF button and release the button afteryou hear one beep to turn off the UPS. Cut off the input power to completelyshut down the UPS.z Do not use any cleaning liquid or spray to clean the UPS. Before cleaning,please make sure that the UPS has been completely shut down, and the connection between the UPS and the input power and the connection between theUPS and the external battery pack have been entirely cut off.z OO PDLQWHQDQFH VHUYLFHV PXVW EH SHUIRUPHG E\ TXDOL¿HG VHUYLFH SHUVRQQHO )RU bid opening or removing the cover of the UPS by yourself to avoid high voltageelectric shock.z RX PXVW FRQWDFW TXDOL¿HG VHUYLFH SHUVRQQHO LI HLWKHU RI WKH IROORZLQJ HYHQWV RFcur:1. Liquid is poured or splashed on the UPS.2. The UPS does not run normally after this 8VHU 0DQXDO is carefully observed.NOTE :If you use the UPS in an area that generates or incurs dust, you shouldLQVWDOO D GXVW ¿OWHU LQ WKH 836 WR HQVXUH QRUPDO SURGXFW OLIH DQG IXQFWLRQ Battery Warningsz Servicing of batteries or battery packs must be performed or supervised byqualified service personnel knowledgeable in batteries, battery packs and therequired precautions. Keep unauthorized personnel away from batteries andbattery packs.Amplon N Series2

Chapter 1Important Safety Instructionsz The risk of electric shock and short-circuit current is possible when the batteriesand battery packs are connected to the UPS. Before maintenance, disconnectall batteries and battery packs to cut off the battery power.z For battery replacement, only use the same number and type of batteries.z Observe the following before replacing the batteries:1. Remove watches, rings, or other metal objects.2. Use tools with insulated handles.3. Wear rubber gloves and boots.4. Do not lay tools or metal parts on the top of batteries.5. Before battery removal, replacement or installation, disconnect any circuitconnected to the batteries.z R QRW FRQQHFW WKH EDWWHULHV LQ UHYHUVH RWKHUZLVH D ULVN RI HOHFWULF VKRFN RU ¿UH 'accidents might occur.z A loss of battery charge capacity may occur during shipping and storage. Before1st use of the UPS, please fully charge the batteries until the Battery Level BarGraphz shown on the UPS’s LCD is fully on.If the UPS needs to be stored for an extended period of time, idle batteriesmust be fully charged every three months. When every time you charge the idlebatteries, please charge them until the Battery Level Bar Graph shown on theUPS’s LCD is fully on.WARNING :1. The risk of electric shock and short-circuit current is possible whenthe batteries are still connected to the UPS even though the UPSis disconnected from the mains. Do not forget to cut off the batterysource before maintenance.2. When connecting the external battery pack with the UPS, you mustinstall an appropriate non-fuse DC breaker or the fast-acting fuse thatPHHWV WKH VDIHW\ FHUWL¿FDWLRQ 'R QRW XVH DQ & EUHDNHU 3. The breaker must be a 2-pole non-fuse DC breaker with characteristicsof 1-pole 250Vdc, 2-pole 500Vdc and 35kA (or above) DC breakingcapacity.3

1.2 Standard Compliancez CEz EN 62040-1z EN 62040-2 Category C21.3 Storagez Prior to installationIf the UPS needs to be stored prior to installation, it should be placed in a dryarea. The allowable storage temperature is between -15 C and 50 C.z After usagePress the OFF button for 3 seconds and release it after you hear a beep, makesure that the UPS has been completely shut down, disconnect the UPS fromthe utility power, remove all loads from the UPS, and store the UPS in a dry andwell-ventilated area at a temperature between -15 C and 50 C. Idle batteriesmust be recharged fully every three months if the UPS needs to be stored foran extended period of time. When every time you charge the batteries, pleasecharge them until the Battery Level Bar Graphfully on.shown on the UPS’s LCD isNOTE :After storage and before start-up of the UPS, you must allow the UPS toadjust to room temperature (20 C 25 C) for at least one hour to avoidmoisture condensing inside the UPS.Amplon N Series4

Chapter 2IntroductionChapter 2 : Introduction2.1 General OverviewThe N series UPS is a single-phase on-line UPS providing reliable and consistentsine-wave quality power to your electronic equipment. It adopts the latest technology and the highest quality components providing output power factor up to unity,DQG LWV HI¿FLHQF\ LQ RQ OLQH PRGH FDQ UHDFK DW PD[LPXP 7KH 836 QRW RQO\ provides safe, reliable and uninterrupted power to your sensitive electronic equipPHQW DW DOO WLPHV EXW DOVR SURGXFHV JUHDWHU HOHFWURQLF SRZHU HI¿FLHQF\ DW OHVV FRVW Its compact design does not occupy much space and is easy to use. There are twodifferent ratings, 6kVA and 10kVA, for your selection.2.2 Exterior & Dimensions325mmONSETOFF390mmUP190mm)LJXUH N9 N9 ([WHULRU 'LPHQVLRQV5

2.3 Package Listz For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA )14256x3ONx4OFFSETUP937ONSETUPOFF10The power behind competitivenessDelta UPS - Amplon Family8N Series, Single Phase6/ 10 kVAUser 1UPS1 PC2Parallel Cable1 PC3User Manual1 PC4Battery Cable1 PC5CU Terminal Type A3 PCS6CU Terminal Type B4 PCS7Battery Cable Holder1 PC8Screw for Battery Cable Holder9USB Cable10Cable TieAmplon N Series2 PCS1 PC6 PCS6

Chapter 2z IntroductionFor models UPS602N2004N0B0 (6 kVA ) & UPS103N2004N0B0 (10 kVA )14256x2ONx4x3OFFSETUP71038ONSETUPOFF11The power behind competitivenessx69Delta UPS - Amplon FamilyN Series, Single Phase6/ 10 kVAUser PS1 PC2Parallel Cable1 PC3User Manual1 PC4CU Terminal Type A2 PCS5CU Terminal Type B4 PCS6CU Terminal Type C3 PCS7Battery Terminal Box1 PC8Battery Terminal Box Cover1 PC9Screw for Battery Terminal Box Cover10USB Cable11Cable Tie2 PCS1 PC6 PCS7

z For models UPS602N2004N0BA (6 kVA ) & UPS103N2004N0BA (10 kVA )14256x2ONx4x3OFFSETUP71038ONSETUPOFF11The power behind competitivenessx69Delta UPS - Amplon FamilyN Series, Single Phase6/ 10 kVAUser PS1 PC2Parallel Cable1 PC3User Manual1 PC4CU Terminal Type A2 PCS5CU Terminal Type B4 PCS6CU Terminal Type C3 PCS7Battery Terminal Box1 PC8Battery Terminal Box Cover1 PC9Screw for Battery Terminal Box Cover10USB Cable11Cable Tie2 PCS1 PC6 PCSNOTE :1. If there is any damage or anything missing, please immediatelycontact the dealer from whom you purchased the unit.2. If the UPS needs to be returned, carefully repack the UPS and all ofthe accessories using the original packing material that came with theunit.Amplon N Series8

Chapter 3Operation PanelChapter 3 : Operation Panel3.1 LED IndicatorsIN RUN TIMEV MINECOSET IN OUT BATT LOAD TEST3.3 LCD Display (including3.4 7-Segment Display &3.5 16-Segment Display)AHV%HzKVAKWMIN CONOFF3.2 Multi-function ButtonsSETUP)LJXUH 2SHUDWLRQ 3DQHO3.1 LED IndicatorsNo.1LEDDescriptionIndicates the output status.1. On (green): There is output.2. Off: There is no output.2Indicates the warning status.1. On (red): The UPS is in failure mode.2. Flash (red): The UPS’s working conditions are abnormal.9

3.2 Multi-function ButtonsNo.MultifunctionButtonDescriptionThe button has two functions. Please refer to the following fordetailed information.11. Buzzer On/ Off:When the buzzer is on, press the button for 0.1 second toturn off the buzzer. When the buzzer is off, press the buttonfor 0.1 second to turn on the buzzer. &RQ¿UPDWLRQIn setup mode, press the button for 0.1 second to enter intoWKH LWHP WKDW \RX ZDQW WR VHW XS RU FRQ¿UP \RXU SDUDPHWHU setup.2ONThe button has three functions. Please refer to the following fordetailed information.1. Turn-on:z Inbypass mode, press and hold the button for 3 seconds,release it after you hear one beep and the UPS will run inon-line mode.z Coldstart: When there is no AC input, press and hold thebutton for 3 seconds, release it after you hear one beepand the UPS will start up in battery mode.2. Battery Test:z A batterytest can only be executed in on-line mode.z Formanual battery test, please press and hold the buttonfor 3 seconds, release it after you hear one beep, and theUPS will transfer to run in battery mode and perform a10-second battery test. If the test result is ok, the 7-segment display will show ‘PAS’ and the UPS will return toon-line mode. If the test result is abnormal, the 7-segmentdisplay will show ‘FAL’, the no-battery/ battery replacement icon () will illuminate and the UPS will return toon-line mode. For 7-segment display information, pleaserefer to 6HJPHQW 'LVSOD\.Amplon N Series10

Chapter 3No.2MultifunctionButtonONOperation PanelDescriptionNOTE :z Formodels UPS602N2004N035 (6 kVA ) &UPS103N2004N035 (10 kVA ) &UPS602N2004N0BA (6kVA) &UPS103N2004N0BA (10kVA):For automatic regular battery test, you must install theUPSentry 2012 software (please download from wareFHQWHU SKS RU FRQ¿JXUH WKH 6103 FDUG RSWLRQDO RU ModBus card (optional).z Formodels UPS602N2004N0B0 (6 kVA ) &UPS103N2004N0B0 (10 kVA ):For automatic regular battery test, you must install theUPSentry 2012 software (please download from wareFHQWHU SKS RU FRQ¿JXUH WKH PLQL 6103 FDUG RSWLRQDO or mini ModBus card (optional).3. Scrolling Up/ Increasing Number:z Pressthe button for 0.1 second to go to the previous display or increase number.3OFFThe button has three functions. Please refer to the following fordetailed information.1. Turn-off:z Inon-line mode, press and hold the button for 3 seconds,release it after you hear one beep and the inverter will beoff and the UPS will transfer to run in bypass mode.The UPS will keep charging the batteries when the UPSis in bypass mode. To fully turn off the UPS, pleasecompletely disconnect the UPS from the input power.z Inbattery mode, press and hold the button for 3 seconds,release it after you hear one beep and the UPS will turnoff its output.11

No.MultifunctionButton3OFFDescription2. Scrolling Down/ Decreasing Number:Press the button for 0.1 second to go to the next display orto decrease number.3. Fault Clear:When the UPS has a fault condition, press and hold thebutton for 3 seconds, release it after you hear one beep andthe UPS will clear the fault condition and return to standbymode.NOTE :When the UPS clears the fault condition, it doesn’t meanthat the fault has been automatically eliminated butmeans that the buzzer has been turned off. For moreinformation, please refer to (UURU &RGH ,QIRUPDWLRQand &KDSWHU 7URXEOHVKRRWLQJ.4ONSETUPz Enteringinto the Setup Modeand ON these two buttonsSimultaneously press thefor 3 seconds to enter into the setup mode.z Exitingfrom the Setup ModeIn setup mode, press these two buttons simultaneously for 3seconds to exit from the setup mode.NOTE :For more information about the setup mode, pleaserefer to 6HWXS 0RGH 3OHDVH QRWH WKDW RQO\ TXDOL¿HG service personnel can perform setup action.NOTE :The backlight of the LCD automatically turns off after 3 minutes of inactivity.You can press any button to wake up the display and enable each buttonfunction. The duration of backlight (3 minutes) cannot be changed.Amplon N Series12

Chapter 3Operation Panel3.3 LCD DisplayIN RUN TIMEV MINECOSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CNo.1IconNamingACIconDescriptionIndicates the input source status.1. ON: The AC input is within the acceptablebypass range.2. Flashing: The AC input is out of the acceptable bypass range but is able to let the unitoperate in on-line mode.3. OFF: The AC input is out of the acceptablebypass range and is not able to let the unitoperate in on-line mode.2OutputIconIndicates the output status.1. ON: There is output.2. OFF: There is no output.3BatteryPowerIconIndicates the battery power status.1. ON: The UPS runs in battery mode or thebatteries are charging.2. OFF: It is not the batteries to supply power tothe connected loads or the batteries are notcharging.4PFCIconIndicates the PFC status.1. ON: The PFC is running.2. OFF: The PFC is not running.13

No.Icon5NamingInverterIconDescriptionIndicates the inverter status.1. ON: The inverter is running.2. OFF: The inverter is not running.6StandbyModeGraphIlluminates when the UPS is operating in standby mode.7OnlineModeGraphIlluminates when the UPS is operating in online mode.8BatteryModeGraphIlluminates when the UPS is operating in battery mode.9BypassModeGraphIlluminates when the UPS is operating in bypass mode.10ECOModeGraphIlluminates when the UPS is operating in ECOmode.ECOModeIlluminates when the UPS is operating in ECOmode. It is bypass to supply power to the connected loads in ECO mode.11ECO12BuzzerOffIconIlluminates when the buzzer is disabled.13ParallelIcon1. ON: The UPS is in parallel mode.2. OFF: The UPS is in single mode.NOTE :1. You can parallel at maximum four UPSunits. To enhance parallel reliability,please adopt the Daisy Chain methodto execute parallel configuration.Please note that parallel UPSs cannotshare common batteries.Amplon N Series14

Chapter 3No.IconNamingOperation PanelDescription2. Only when the parallel iconilluminates can you perform turn on procedures for parallel units.1415LoadLevelBarGraph1. ON: 7RWDO FDSDFLW\ RI WKH FRQQHFWHG loads*1.BatteryLevelBarGraph1. ON: 7KH UHPDLQLQJ EDWWHU\ FDSDFLW\ *1.2. Flashing: Overload.2. Flashing: Low battery.NOTE :*1 means that: WKH st segment will illuminate. WKH ¿UVW WZR VHJPHQWV ZLOO LOOXPLQDWH WKH ¿UVW WKUHH VHJPHQWV ZLOO LOOXPLQDWH DOO VHJPHQWV ZLOO LOOXPLQDWH 3.4 7-Segment DisplayIN RUN TIMEV MINECOSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN C15

No.DisplayMeaning7-segmentdisplay1NumberSetup mode.Please refer to 6HWXS 0RGH 2SET3IN4OUTOutput5BATTBattery status6LOADLoad 12HzFrequency13KVAkVA14KWkW15MINMinute16 CAmplon N SeriesCategoryInputStatusThe combination of the threecategories (left-hand side)presents relevant informationsuch as input voltage, outputvoltage, output frequency,load capacity etc.Ampere hourUnitThe UPS’s internal temperature.16

Chapter 3Operation Panel3.5 16-Segment DisplayIN RUN TIMEV MINECOSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CNo.DisplayMeaning16-segmentdisplay12INInput3RUN yNumber/ Error code (Forerror code information,please refer to (UURU The combination&RGH ,QIRUPDWLRQ.)of the three categories (left-handside) presentsrelevant inforStatusmation such asinput voltage andremaining batterytime (minutes).Unit17

No.DisplayMeaningDescriptionwill illuminate when anyThe warning iconof the following situations occurs.6Warning1. When the fault LEDilluminates.2. When an abnormality such as overload orbattery missing is detected.3. When the 16-segment displayan error code.shows3.6 Error Code Information1. The error code only appears on the 16-segment display.2. The error code is composed of an alphabet and four numbers such as E2303,E0301, E2002, E2702, etc. The display of the error code shown on theis presented by two alternate screens and each16-segment displayscreen appears for 0.5 second. Please see )LJXUH as the example of thealternate screens for error cord E2302.IN RUN TIMEIN RUN TIMEV MINV MIN)LJXUH OWHUQDWH 6FUHHQV IRU (UURU &RGH ( 3. For each error code’s meaning, please refer to &KDSWHU 7URXEOHVKRRWLQJ.4. In battery mode, the 16-segment displaytime. Please see )LJXUH .will display the remaining battery5. In any mode (except battery mode), the 16-segment displaythe input voltage. Please see )LJXUH .Amplon N Series18will display

Chapter 3In battery mode, here displaysthe remaining battery time.In any mode (except battery mode),here displays the input voltage.IN RUN TIMEV MINOperation PanelIN RUN TIMEECOV MINSET IN OUT BATT LOAD TESTECOSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CAHV%HzKVAKWMIN C)LJXUH VHJPHQW 'LVSOD\ LQ %DWWHU\ 0RGH LQ Q\ 2WKHU 0RGH3.7 LCD Display Flow Chart7KH IROORZLQJ ÀRZ FKDUW KHOSV \RX WR XQGHUVWDQG KRZ WR JR WKURXJK HDFK GLVSOD\ screen. Here, we take ‘Bypass Mode’ as an example. Press thesecond to view the previous screen and press thethe next screen.OFFONbutton for 0.1button for 0.1 second to viewAny No., diagram, icon, text, etc. shown in the LCD diagrams presented below arefor reference only. Actual display depends on the operation of the UPS.19

Bypass ModeIN RUN TIMEIN RUN TIMEOFFV MINInputVoltageECOV MINSET IN OUT BATT LOAD TESTSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CT 0.1SOFFV MINONT 0.1SONV MINT 0.1SSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CONT 0.1SONIN RUN TIMEV MINV MINT 0.1SSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CONT 0.1SONIN RUN TIMEV MINV MINSET IN OUT BATT LOAD TESTT 0.1SAHV%HzKVAKWMIN CONT 0.1SONIN RUN TIMEBattery %OFFIN RUN TIMEECOV MINSET IN OUT BATT LOAD TESTECOSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN CAHV%HzKVAKWMIN CLoad kVAIN RUN TIMEONONV MINT 0.1SECOSET IN OUT BATT LOAD TESTAHV%HzKVAKWMIN COFFAmplon N SeriesOFFECOAHV%HzKVAKWMIN CV MINBatteryVoltageIN RUN TIMEECOSET IN OUT BATT LOAD TESTOFFOFFECOAHV%HzKVAKWMIN COutputFrquencyBatteryRemainingTimeIN RUN TIMEECOSET IN OUT BATT LOAD TESTOFFOFFECOAHV%HzKVAKWMIN COutputVoltageInternalTemperatureIN RUN TIMEECOSET IN OUT BATT LOAD TESTOFFLoadPercentageAHV%HzKVAKWMIN CONIN RUN TIMEInputFrequencyECO20T 0.1SOFFLoad KW

Chapter 4Rear PanelChapter 4 : Rear Panelz For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA )1EX TE R N A L B A TT . C O N N E C TO R240Vdc.48APARALLELPARALLELRS-232EX TE R N A L B A TT . C O N N E C TO R240Vdc.48A4SMART SLOT32PARALLELREPO9SMART SLOTPARALLELRS-232REPO10115AC IN P U TIN P U TBR E A KE RL6UPS O U T PU TNNL7OFF(Before Removal of Wiring Panel)LUPS O U T PU TNN12L138ONNo.AC IN P U TIN P U TBR E A KE RONOFF(After Removal of Wiring Panel)ItemFunctionsFor external battery pack’s grounding.12External BatteryConnectorConnects to the external battery pack.3Smart SlotAccepts an SNMP, Relay I/O, USB and ModBuscard (optional).4Parallel PortsFor UPS parallel communication. You can parallelat maximum four UPS units. To enhance parallelreliability, please adopt the Daisy Chain methodWR H[HFXWH SDUDOOHO FRQ¿JXUDWLRQ 3OHDVH QRWH WKDW parallel UPSs cannot share common batteries.5FansCool and ventilate the UPS.6AC InputTerminals (L & N)Connect the UPS to the mains.7For UPS grounding.21

No.ItemFunctions8Input BreakerIt is the input power’s protective device and is forsafety protection.9RS-232 PortConnects to your computer. You can monitor theUPS’s status via your computer by installing theUPSentry 2012 software (please download tware-center.php).NOTE : Do not use the USB port andthe RS-232 port at the same time. If youconnect the USB cable to the USB port, theRS-232 port will disable right away.10REPO PortRemotely shuts down the UPS when anemergency occurs.NOTE : Please connect a user-suppliednormally-open switch to the REPO port.When the user-supplied switch is closed,the UPS will immediately shut down theinverter and output (the UPS won’t transferinto bypass mode).11USB PortConnects to your computer. You can monitor theUPS’s status via your computer by installing theUPSentry 2012 software (please download tware-center.php).NOTE : Do not use the USB port andthe RS-232 port at the same time. If youconnect the USB cable to the USB port, theRS-232 port will disable right away.12UPS OutputTerminals (L & N)13Amplon N SeriesConnect to your loads.NOTE : To avoid output from over currentprotection, please follow the load capacity(from the largest to the smallest) to connectthe loads to the UPS.For connected loads’ grounding.22

Chapter 4z Rear PanelFor models UPS602N2004N0B0 (6 kVA ) & UPS103N2004N0B0 (10 kVA )1MINI SLOT3EXTERNAL BATT. CONNECTOR 240Vdc.48APARALLELPARALLELRS-23228MINI SLOTEXTERNAL BATT. CONNECTOR 240Vdc.48APARALLELREPOPARALLELRS-2329REPO104AC IN P U TIN P U TBR E A KE RL5UPS O U T PU TNNL6OFF(Before Removal of Wiring Panel)LUPS O U T PU TNN11L127ONNo.AC IN P U TIN P U TBR E A KE RONOFF(After Removal of Wiring Panel)ItemFunctions1External BatteryConnectorConnects to the external battery pack.2Mini SlotAccepts an mini SNMP, mini Relay I/O, mini USBand mini ModBus card (optional).3Parallel PortsFor UPS parallel communication. You can parallelat maximum four UPS units. To enhance parallelreliability, please adopt the Daisy Chain methodWR H[HFXWH SDUDOOHO FRQ¿JXUDWLRQ 3OHDVH QRWH WKDW parallel UPSs cannot share common batteries.4FansCool and ventilate the UPS.5AC InputTerminals (L & N)Connect the UPS to the mains.For UPS grounding.67Input BreakerIt is the input power’s protective device and is forsafety protection.23

No.8ItemRS-232 PortFunctionsConnects to your computer. You can monitor theUPS’s status via your computer by installing theUPSentry 2012 software (please download tware-center.php).NOTE : Do not use the USB port andthe RS-232 port at the same time. If youconnect the USB cable to the USB port, theRS-232 port will disable right away.9REPO PortRemotely shuts down the UPS when anemergency occurs.NOTE : Please connect a user-suppliednormally-open switch to the REPO port.When the user-supplied switch is closed,the UPS will immediately shut down theinverter and output (the UPS won’t transferinto bypass mode).10USB PortConnects to your computer. You can monitor theUPS’s status via your computer by installing theUPSentry 2012 software (please download tware-center.php).NOTE : Do not use the USB port andthe RS-232 port at the same time. If youconnect the USB cable to the USB port, theRS-232 port will disable right away.11UPS OutputTerminals (L & N)12Amplon N SeriesConnect to your loads.NOTE : To avoid output from over currentprotection, please follow the load capacity(from the largest to the smallest) to connectthe loads to the UPS.For connected loads’ grounding.24

Chapter 4z Rear PanelFor models UPS602N2004N0BA (6 kVA ) & UPS103N2004N0BA (10 kVA )13SMART SLOTEXTERNAL BATT. CONNECTOR 192Vdc.58APARALLELPARALLELRS-23228SMART SLOTEXTERNAL BATT. CONNECTOR 192Vdc.58APARALLELREPOPARALLELRS-2329REPO104AC IN P U TIN P U TBR E A KE RL5UPS O U T PU TNNL6OFF(Before Removal of Wiring Panel)LUPS O U T PU TNN11L127ONNo.AC IN P U TIN P U TBR E A KE RONOFF(After Removal of Wiring Panel)ItemFunctions1External BatteryConnectorConnects to the external battery pack.2Smart SlotAccepts an SNMP, Relay I/O, USB and ModBuscard (optional).3Parallel PortsFor UPS parallel communication. You can parallelat maximum four UPS units. To enhance parallelreliability, please adopt the Daisy Chain methodWR H[HFXWH SDUDOOHO FRQ¿JXUDWLRQ 3OHDVH QRWH WKDW parallel UPSs cannot share common batteries.4FansCool and ventilate the UPS.5AC InputTerminals (L & N)Connect the UPS to the mains.For UPS grounding.67Input BreakerIt is the input power’s protective device and is forsafety protection.25

No.8ItemRS-232 PortFunctionsConnects to your computer. You can monitor theUPS’s status via your computer by installing theUPSentry 2012 software (please download fromhttp://www.deltapowersolutions.com/en/mci

mended when the UPS is connected to the mains and the loads. z The protective devices connecting to the UPS must be installed near the UPS and must be easily accessible for operation. z If you need to move the UPS or perform re-wiring, please turn off the AC input power and ensure that the UPS has been safely shutdown and the connected

Related Documents:

May 02, 2018 · D. Program Evaluation ͟The organization has provided a description of the framework for how each program will be evaluated. The framework should include all the elements below: ͟The evaluation methods are cost-effective for the organization ͟Quantitative and qualitative data is being collected (at Basics tier, data collection must have begun)

Silat is a combative art of self-defense and survival rooted from Matay archipelago. It was traced at thé early of Langkasuka Kingdom (2nd century CE) till thé reign of Melaka (Malaysia) Sultanate era (13th century). Silat has now evolved to become part of social culture and tradition with thé appearance of a fine physical and spiritual .

On an exceptional basis, Member States may request UNESCO to provide thé candidates with access to thé platform so they can complète thé form by themselves. Thèse requests must be addressed to esd rize unesco. or by 15 A ril 2021 UNESCO will provide thé nomineewith accessto thé platform via their émail address.

̶The leading indicator of employee engagement is based on the quality of the relationship between employee and supervisor Empower your managers! ̶Help them understand the impact on the organization ̶Share important changes, plan options, tasks, and deadlines ̶Provide key messages and talking points ̶Prepare them to answer employee questions

Dr. Sunita Bharatwal** Dr. Pawan Garga*** Abstract Customer satisfaction is derived from thè functionalities and values, a product or Service can provide. The current study aims to segregate thè dimensions of ordine Service quality and gather insights on its impact on web shopping. The trends of purchases have

Delta UPS - Modulon Family DPH Series, 50-300/500/600kVA The power behind competitiveness Delta Modulon DPH series UPS 500kVA The highest power density with uncompromised power performance and reliability www.deltapowersolutions.com Largest power density per module in the world at 55.6kVA Industry-leading AC-AC efficiency up to 96.5%

Chính Văn.- Còn đức Thế tôn thì tuệ giác cực kỳ trong sạch 8: hiện hành bất nhị 9, đạt đến vô tướng 10, đứng vào chỗ đứng của các đức Thế tôn 11, thể hiện tính bình đẳng của các Ngài, đến chỗ không còn chướng ngại 12, giáo pháp không thể khuynh đảo, tâm thức không bị cản trở, cái được

Alpha Phi X Alpha Omicron Pi X Alpha Xi Delta Chi Omega X Delta Delta Delta X Delta Gamma X Delta Zeta X . Kappa Delta X Kappa Kappa Gamma X Phi Mu X Pi Beta Phi X Sigma Kappa Sigma Delta Tau X Zeta Tau Alpha X Total # Packets 18 1 set of digital documents 1. 5 Sample Resume Caitlin Cowboy 123 Main St. . Quill & Scroll National Honor .