Defrost Time Controls / HVAC/RGrässlin Defrost Timers were designed specifically for OEMor contractor integration control of various loads withincommercial refrigeration systems which require systematicoverriding of these loads to defrost evaporator coils inmedium (cooler) or low-temperature (freezer) applications.Whether voltage specific mechanical, autovoltageelectromechanical, or electronic, Grässlin Defrost Timers offerconsolidated value solutions to meet the commercialrefrigeration contractor or OEM’s needs. Grässlin DefrostTimers are used in electric or hot gas defrost applicationswhere the defrost is terminated when the coil is frost-free, assensed by a temperature or pressure switch, even though thedefrost programmed termination time has not been reached.The time termination functions as a fail-safe and will terminatethe defrost if the temperature or pressure switch fails to do so.The temperature or pressure switch on the refrigeration coil hascontacts which close on a temperature or pressure rise abovefreezing, indicating that frost and ice have melted from theevaporator coil.Defrost Time Controls / HVAC/RDefrost Timer Controls / HVAC/RContentsGrässlin 24-Hour Electromechanical Defrost Timer 96-97Grässlin 24-Hour and/or 7-Day Electronic Defrost Timer 98DTAV Series Common Wiring Diagrams & Enclosure/Mounting Dimensions 9924-Hour Mechanical Defrost Timer 100-10195

Defrost Time Controls / HVAC/RDefrost Time Controls / HVAC/RGrässlin 24-Hour Electromechanical Defrost TimerDTAV40 SeriesTime Initiated and Temperature, Pressure or TimeTerminated 40 A Autovoltage ElectromechanicalDefrost TimerDTAV40DTAV40 InsideCompliant#E106942002/95/ECRatingsInput VoltageAll ModelsQ ModelSwitch TypeResistiveMotorOperating TemperatureQuartzOperating HumidityWiring ConnectionsEnclosure/MountingMIN ON/OFFMAX ON/OFFElectrical LifeShipping WeightWarranty120-240 VAC, 60 Hz120-240 VAC, 50/60 Hz1 SPDT, 1 NC SPST40 A, 120-240 VAC1 HP, 16 FLA, 96 LRA @ 120 VAC2 HP, 12 FLA, 72 LRA @ 240 VAC-40º F to 104º F (-40º C to 40º C)-4º F to 104º F (-20º C to 40º C)0-95% RH, non-condensingScrew box lug terminals.Up to one #8 AWG WireUL Type 1, UL Type 3R, or Bracket15 minutes23 hours, 45 minutes50,000 operations at full load3 lbs.1-year limitedFor electric heat, hot gas or compressor shutdown defrost. The GrässlinDTAV40 Series Auto Voltage Defrost Timer is applicable to air defrost(compressor shutdown) and electric or hot gas defrost systems wherethe defrost cycle is terminated by the timer. If the coil is frost-free, thetimer can also be terminated by temperature or pressure switches beforethe programmed defrost termination time has been reached. The timetermination functions as a fail-safe and terminates the defrost cycle if thetemperature or pressure switch fails to do so.Applications Medium and low-temperature commercial refrigeration systemsFeatures DTAV40 Series replaces over 40 competitive models 40 A, 2 HP Rating Autovoltage automatically adjusts between 120 and 240 VAC Q model features self-recharging battery backup with 7-day carry-over Can mount in an existing enclosure – no tools required for installation Moisture resistant conformal-coated board LED indicators for defrost and refrigeration cycles Defrost cycles are programmed independently "Real-time" clock face for quick, easy and accurate setting Defrost times programmable in 15-minute intervals Captive trippers won’t get lost Finger-safe box lug terminalsModel #EnclosureBattery BackupDTAV40UL Type 3R Outdoor PlasticNoDTAV40QUL Type 3R Outdoor PlasticYes (7 Days)DTAV40IMUL Type 1 Metallic (Not Raintight)NoDTAV40MMechanism OnlyNoNotes: For mounting & enclosure dimensions see page 99.For wiring examples see page 99.Accessories/ReplacementsBracket Mount (material electrically isolated)mounting screws includedDT-BSpecificationFurnish and install a Grässlin Defrost Control, which will automaticallyadjust between 120 VAC and 240 VAC operation and shall have defrost initiationtimes settable in 15-minute intervals with captive trippers. The defrost timer shallbe housed in a UL Type 3R indoor/outdoor plastic enclosure or UL Type 1 metallicenclosure. The relay output will be rated for 40A Resistive, 2 HP @ 240 VAC.Defrost termination to be by time (or by a remote temperature or pressure switch).For carry-over, the time controls shall have quartz a drive with (DTAV40Q) 7-Dayreserve carry-over from a self-recharging battery.Setting Defrost TimesConfigure defrost times easily!Just scan the QR code with yoursmartphone or tablet for detailson how to choose a defroststarting time.96

Defrost Time Controls / HVAC/RGrässlin 24-Hour Electromechanical Defrost Timer40 A Autovoltage Electromechanical Defrost Timerwith Voltage Monitoring and Short Cycle ProtectionThe Grässlin DTAV40VM Auto Voltage Defrost Timer with VoltageMonitoring and Short Cycle Protection offers all of the same featuresas the DTAV40 Series, plus it also includes built-in voltage monitoringand short cycle delay options to help protect the compressor andincrease system life.The low-voltage monitor circuit measures theinput voltage across several line cycles. A brownout condition existsif an average input voltage falls below 95 VAC ( /-2 VAC) for 120 VACoperation or 190 VAC ( /-2 VAC) for 240 VAC operation. A brownoutcondition triggers short cycle protection and disables normalcompressor operation until normal operating voltage is restored.DTAV40VMDTAV40VM InsideApplications Medium and low-temperature commercial refrigeration systemsFeaturesSame features as DTAV40 series on pg 96, plus: Voltage monitoring protects against low-voltage conditions(brownouts) Adjustable short cycle delay helps extend compressor life DTAV40VM replaces over 40 competitive models,including the DTMV40Defrost Time Controls / HVAC/RDTAV40VMCompliant#E10694Model #DTAV40VM2002/95/ECEnclosureRatingsUL Type 3R Raintight PlasticInput VoltageSwitch TypeResistiveMotorNotes: For mounting & enclosure dimensions see page 99.For wiring examples see page 99.Accessories/ReplacementsBracket Mount (material electrically isolated)mounting screws includedDT-BSpecificationFurnish and install a Grässlin Defrost Control, which will automaticallyadjust between 120 VAC and 240 VAC operation. The defrost timer shall havedefrost initiation times settable in 15-minute intervals with captive trippers. Thedefrost timer shall incorporate voltage monitoring to protect against low-voltageconditions. The defrost timer shall also incorporate a short cycle delayadjustable from 0 sec. (off), 6 sec. minimum to 10 min. max to prevent rapidcompressor cycling. The defrost timer shall be housed in a UL Type 3R indoor/outdoor plastic enclosure. The relay output shall be rated for 40 A Resistive, 2 HP @240 VAC. Defrost termination to be by time (or by a remote temperature or pressureswitch).120-240 VAC, 60 Hz1 SPDT, 1 NC SPST (NC in powered state)40 A, 120-240 VAC1 HP, 16 FLA, 96 LRA @ 120 VAC2 HP, 12 FLA, 72 LRA @ 240 VACVoltage Protection 95 VAC for 120 VAC 190 VAC for 240 VAC ( /- 2 VAC)Short Cycle Delay 0 (disabled), 6-second, 30-second, 1, 2, 4, 6, 8,10-minuteOperating Temperature -40º F to 104º F (-40º C to 40º C)Operating Humidity0-95% RH, non-condensingWiring ConnectionsScrew box lug terminals. Up to one #8AWG WireEnclosure/MountingUL Type 3RMIN ON/OFF15 minutesMAX ON/OFF23 hours, 45 minutesElectrical Life50,000 Operations at full loadShipping Weight3 lbs.Warranty1-year limitedAdjusting Short Cycle TimeAdjust the short cycle delaytime easily! For step-by-stepinstructions, scan the QR codewith your smartphone or tablet.97

Defrost Time Controls / HVAC/RDefrost Time Controls / HVAC/RGrässlin 24-Hour and/or 7-Day Electronic DefrostDTAV40E2 SeriesTime Initiated and Temperature, Pressureor Time Terminated 40 A AutovoltageElectronic Defrost TimerDTAV40E2DTAV40E2 Inside#E10694RatingsInput VoltageSwitch TypeResistiveMotorOperating TemperatureOperating HumidityWiring ConnectionsEnclosure/MountingMIN ON/OFFMAX ON/OFFElectrical LifeShipping WeightWarranty120-240 VAC, 50/60 Hz1 SPDT, 1 NC SPST40 A, 120-240 VAC1 HP, 16 FLA, 96 LRA @ 120 VAC2 HP, 12 FLA, 72 LRA @ 240 VAC-13º F to 104º F (-25 ºC to 40 ºC)0-95% RH, non-condensing#8 AWGUL Type 3R1 minute23 hours, 45 minutes50,000 operations at full load3 lbs.1-year limitedThe Grässlin DTAV40E2 Electronic Autovoltage Defrost Timer has flexible 7-dayscheduling and to-the-minute defrost duration control to increase systemefficiency (decrease defrost scheduling during low demand periods). It isapplicable to air defrost (compressor shutdown) and electric or hot gas defrostsystems where the defrost cycle is terminated by the timer. If the coil is frost-free,the timer can also be terminated by temperature or pressure switches before theprogrammed defrost termination time has been reached. The time terminationfunctions as a fail-safe and cancels the defrost cycle if the temperature orpressure switch fails to do so.Applications Medium and low-temperature commercial refrigeration systemsFeatures 24-Hour/7-Day flexible scheduling increases system efficiency 40 A, 2 HP rating DTAV40 Series replaces over 40 competitive models Autovoltage automatically adjusts between120 and 240 VAC, 50/60 Hz Self-recharging battery backup with 2500-hour carry-over Can mount in an existing enclosure – no tools required for installation LED indicators for defrost and refrigeration cycles Finger-safe box lug terminals Simple to programModel #DTAV40E2EnclosureBattery BackupUL Type 3R Raintight Plastic Yes (2500-Hour)Notes: For mounting & enclosure dimensions see page 99.For wiring examples see page 99.SpecificationFurnish and install a Grässlin Defrost Control, which will automatically adjustbetween 120 VAC and 240 VAC operation and shall have defrost initiation times settablein 1-minute intervals with an integrated electronic timer interface. This control shall have24-Hour/7-Day programming, 7 ON and 7 OFF setpoint programs, and 5 preset blockprograms to allow a selection of any combination of days for different weekday schedules.The LCD shall display time of day in AM/PM format. A daylight Saving Time adjustmentbutton shall also be provided. The timer shall provide a manual override button to initiate amanual defrost. The defrost timer shall be housed in a UL Type 3R indoor/outdoor plasticenclosure. The relay output will be rated for 40 A Resistive, 2 HP @ 240 VAC. Defrostterminations to be by time (or by a remote temperature or pressure switch). For carry-over,the time controls shall have 2500-Hour reserve carry-over from a self-recharging battery.Set up system schedulingThe electronic face and programmingbuttons make scheduling straightforwardand easy. Just scan the QR code withyour smartphone or tablet for details.98

Defrost Time Controls / HVAC/RDTAV Series Common Wiring Diagrams & Enclosure/Mounting DimensionsDimensionsWiring diagrams in powered refrigeration mode.Type 1 Enclosure Dimensions2 1/2"3/8"8145 Replacement (Retrofit)DTAV40 Default Out of Box3F12L14NDEFROSTHEATER(2) KNOCKOUT1/2" & 3/4"(1 THIS SIDE &1 OPP. SIDE)X6 11/16"1/8"1 3/16"5 1/8"1 3/16"3"(2) KNOCKOUT1/2" & 3/4"3 7/16"TERMINATIONTHERMOSTATW/FAN DELAY3/16"1 1/4"1 3/8"2 1/2"2 11/16"3 7/16"FANMOTORCOMPRESSORORSOLENOID VALVEORCONTACTOR COIL4 1/16"7 1/4"TERMINATEINPUTTHERMOSTATLINE3 7/16"7 7/8"CONTROLPOWER5X 5 11/16"(3 KNOCKOUTS)R1/16"R1/8"(1) KNOCKOUT1/2" & 3/4"3/16"1 3/16"15/16"1 7/8"Type 3R Enclosure DimensionsL26.61"[16.79 cm]5.73"[14.55 cm]8041 Replacement t Time Controls / HVAC/RWiring Diagrams8041LABELTHERMOSTATFANLINE8.88"[22.56 cm]COMPRESSORORSOLENOID VALVEORCONTACTOR COILDEFROSTHEATERL28045 Replacement (Retrofit)CONTROLPOWERTERMINATEINPUT3"[7.62 cm]DT-B Bracket 5LABELFANMOTORCOMPRESSORORSOLENOID VALVEORCONTACTOR COILL28141 Replacement OID VALVEORCONTACTOR COILTERMINATIONTHERMOSTATW/FAN DELAY High Impact Polystyrene Material Electrically Isolated Mounting Screws included UL94HB Flame Class RatingUniversal Replacement (See wiring diagrams for examples)GrässlinParagonL2DTAV40 47-208141-206141-20Note: Equivalent in function, terminal identification, and wiring allows for quickand easy installation.99

Defrost Time Controls / HVAC/RDefrost Time Controls / HVAC/R24-Hour Mechanical Defrost TimerG8000 SeriesTime Initiated and Temperature,Pressure or Time Terminated40 A Mechanical Defrost TimerG8045-00SA33993151753UL873,UL917,CSA24,CSA117 Refrigeration ControllerRatingsInput VoltageG8045-00, G8145-00G8045-20, G8145-20Switch TypeResistivePilot DutyMotorOperating TemperatureOperating HumidityWiring ConnectionsLargeSmallMIN ON/OFFMAX ON/OFFElectrical LifeShipping WeightWarranty120 or 208-240 VAC, 60Hz120 VAC, 60 Hz208-240 VAC, 60 Hz1 NO, 1 NC40 A, 120-240 VAC1000 V2 HP, 120-240 VAC-40º F to 104º F (-40ºC to 40ºC)0-95% RH, non-condensing#14-8 AWG#18-12 AWG4 minutes110 minutes30,000 operations at full load2.75 lbs.2-year limitedThe Grässlin G8000 Series Mechanical Defrost Timer is applicableto air defrost (compressor shutdown) and electric or hot gas defrostsystems where the defrost cycle is terminated by the timer. If thecoil is frost-free, the timer can also be terminated by temperature orpressure switches before the programmed defrost termination timehas been reached. The time termination functions as a fail-safe andterminates the defrost cycle if the temperature or pressure switch failsto do so. The encapsulated design prevents dust and dirt build-upto ensure reliable and lasting performance. The G8000 easily snapsinto competitive enclosures and is equivalent in function, terminalidentification and wiring, allowing a quick and easy installation.Applications Medium and low-temperature commercial refrigeration systemsFeatures Exceeds UL873 Refrigeration standard for 30,000 cycleswitch design Heavy-duty welded and silver-plated 40 A contacts Mounts in existing enclosures, no tools required Encapsulated timer module design prevents dust and dirt build-up Heavy-duty synchronous motor for accurate timekeeping Defrost durations programmable in 2-minute increments Up to 6 defrost cycles per day Works with external temperature or pressure switches Includes 4 trippers and spare tripper holder is built-in MIN defrost time: 4 minutes MAX defrost time: 110 minutesModel #DescriptionG8045-00Time Initiated, Time Terminated, 120 VAC,Type 1 EnclosureG8045-20Time Initiated, Time Terminated, 208-240 VAC,Type 1 EnclosureG8145-00Time Initiated. Temperature, Pressure, orTime Terminated, 120 VAC, Type 1 EnclosureG8145-20Time Initiated. Temperature, Pressure, orTime Terminated, 208-240 VAC, Type 1 EnclosureOptional bracket-mount, "mechanism only" model available in bulk packs of 20;To order, add a "B" suffix to model number (i.e. G8045-00B).SpecificationFurnish and install a Grässlin Defrost Control, which shall have upto 6 defrost cycles per day with initiation times settable in 2 minute incrementsfrom 4 to 110 minutes. The defrost timer shall be housed in a UL Type 1 indoormetallic enclosure or be supplied with a suitable bracket mount. The contactsshall be 1 NO, 1 NC and rated for 40 A Resistive, 2 HP @ 240 VAC. Defrosttermination to be by time (or by a remote temperature or pressure switch).Defrost Time Switch shall comply with UL Refrigeration standard UL873.100

Defrost Time Controls / HVAC/R24-Hour Mechanical Defrost TimerG8000 Series DimensionsType 1 Enclosure DimensionsG8045-002 1/2" 2 1/2"3/8"3/8"7 7/8" 7 7/8"7 1/4" 7 1/4"(2) KNOCKOUT(2) KNOCKOUT1/2" & 1/2"3/4" & 3/4"(1 THIS(1SIDETHIS&SIDE &1 OPP.1SIDE)OPP. SIDE)1 3/16"1 3/16"3"3 7/16"3 7/16"G8045-205 1/8" 5 1/8"3"2 1/2"3 7/16"3 7/16"3/8"15/16"15/16"Defrost Time Controls / HVAC/RG8000 Series Wiring Diagrams1 3/16"1 3/16"1 1/4" 1 1/4"R1/1R1 3/8" 1 3/8"(2) KNOCKOUT(2) KNOCKOUT2 1/2" 2 1/2"1/2" & 1/2"3/4" & 3/4"5X511/16"2 11/16"2 11/16"R1/16"(3 KNOCKOUTS)R1/8"1 3/16"1 3/16"7 7/8"1 7/8" 1 7/8"3 7/16"4 1/16"6 11/16"7 1/4"(2) KNOCKOUT1/2" & 3/4"(1 THIS SIDE &1 OPP. SIDE)1/8"1 3/16"G8145-001 3/16"5 1/8"3"1 1/4"(2) KNOCKOUT1/2" & 3/4"3 7/16"1 3/8"(1) KNOCKOUT1/2" & 3/4"3/16"2 1/2"2 11/16"3 7/16"15/16"3/16"1 3/16"1 7/8"2 1/2"7 7/8"R13/8"(2) KNOCKOUT1/2" & 3/4"(1 THIS SIDE &1 OPP. SIDE)7 7/8"7 1/4"5 1/8"1 3/16"G8145-203"(2) KNOCKOUT1/2" & 3/4"(1 THIS SIDE &1 OPP. SIDE)(2) KNOC1/2" & 3/3 7/16"3 7/16"1 3/16"5 1/8"1 3/16"3"15/16"(2) KNOCKOUT1/2" & 3/4"3 7/16"1 1/4"1 3/8"1 3/16"2 1/2"1 7/8"2 11/16"3 7/16"15/16"1 3/16"1 3/16"1 7/8"101

Defrost Time Controls / HVAC/R Defrost Time Controls / HVAC/R 98 Grässlin 24-Hour and/or 7-Day Electronic Defrost Ratings Input Voltage 120-240 VAC, 50/60 Hz Switch Type 1 SPDT, 1 NC SPST Resistive 40 A, 120-240 VAC Motor 1 HP, 16 FLA, 96 LRA @ 120 VAC 2 HP, 12 FLA, 72 LRA @ 240 VAC Operating Temperature-13º F to 104º F (-25 ºC to 40 ºC)

Related Documents:

Refrigerator- off cycle defrost, defrost Icon will light up Time initiated once every 2 hours Terminates when defrost thermistor reaches 40 F (4.4 C) Defrost minimum time is 20 minutes, maximum 1 hour Freezer- heated defrost, defrost Icon will light up and "def" will be displayed

4 1. technical data 1.1 air distribution (normal operation) 1.3 defrost cycles table 1.2 air distribution (defrost mode) vf0054 vf0055 outside temperature defrost cycles (minutes)extended defrost cycles (minutes) celcius ( c) fahrenheit ( f) defrosting operation time between each defrost cycles defrosting operation time between each defrost cycles-5 23 9 60 10 30-15 5 9 32 10 20

Running a Manual Defrost Cycle This unit is pre-programmed to run automatic defrost cycles at preset intervals. However, if you would like to run a manual defrost cycle at any time, please follow the steps below: Freezers: Press the defrost button (“def” and down arrow) for approximately 5 seconds. Repeat to stop the defrost cycle.File Size: 467KB

The chiller will beep for 20 seconds and a defrost cycle will begin if needed (even with product inside). 3. Food remaining in the chiller WILL remain safe during defrost because: a) The inside air temperature is approx. 10-14 F, and. b) Defrost time is generally less than 40-minutes. 4. Chill cycle data WILL be available after defrost.

attach to the control box as illustrated in Figure 1. b. If installing into a heat pump unit, remove the three (3) screws holding the defrost board, place low ambient kit assembly behind the defrost board and reattach the defrost board and low ambient control with the three (3) screws provided in the original defrost board mounting location .File Size: 441KB

The defrost frequency varies according to the outdoor temperature. Defrost lasts 7 minutes for HRV Constructo 1.5ES, 6 minutes for HRV Constructo 2.0ES and 10 minutes for ERV Constructo 2.0ES models (or 10 minutes for all models if set on "Extented Defrost"). During the defrost cycle, the unit shifts to maximum speed and the dampers close.

hvac piping abbreviations hvac piping symbols hvac symbols hvac electrical symbols sheet metal general notes hvac piping general notes project general notes all starters, disconnect switches, motor control centers, and variable frequency drives, for equipment provided under division 23, shall be furnished under