MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130)

MANDATORY LIGHTING CONTROLS 1. Area Controls: Manual controls that control lighting in each area separately 2. Multi-level Controls: Allow occupants to choose the appropriate light level for each area 3. Shut-off Controls: Automatically shuts off lighting or reduces light levels when illumination is not needed 4. Automatic Daylighting Controls: Adjust electric lighting in response to the presence of daylight 5. Demand responsive controls: Receive and automatically respond to demand response (DR) signals Section 130.1 (a) 10/7/2013 SLIDE 126 SECTION 6 MANDATORY MEASURES

MANUAL ON/OFF CONTROLS An “area” is a space enclosed by ceiling-height partitions. All lighting in each area must be controlled separately from luminaires in other areas by manual on/off lighting controls that are: 1. Readily accessible 2. Located in the same room or area as the lighting they control and with the lighting in view 3. Able to provide any required dimming or multi-level controls steps in addition to on/off Section 100.1 10/7/2013 SLIDE 127 SECTION 6 MANDATORY MEASURES

EGRESS LIGHTING Up to 0.2 watts per square foot of lighting may remain on during occupied hours only for emergency egress. This lighting must be designated for emergency egress on building plans. When controls are required to shut off all lighting in a building, this includes emergency egress lighting. Draft Measure Information Template – Egress Lighting Controls, 2013 California Building Energy Efficiency Standards, California Utilities Statewide Codes & Standards Team, March 2011 Section 130.1 (a) 10/7/2013 SLIDE 128 SECTION 6 MANDATORY MEASURES

SEPARATELY CONTROLLED LIGHTING SYSTEMS General lighting must be controlled separately from all other lighting systems in an area. Display lighting must each be separately controlled on circuits of 20 amps or less. For example, window displays must be controlled separately from wall displays, which must also be controlled separately from case displays. When using track lighting: General, display, ornamental, and special effects lighting must be separately controlled. Section 130.1 (a) 10/7/2013 SLIDE 129 SECTION 6 MANDATORY MEASURES

PUBLIC RESTROOMS Any public restroom with two or more stalls may use a manual switch that is not accessible to unauthorized personnel. All other lighting controls are still required. Section 130.1 (a)2 10/7/2013 SLIDE 130 SECTION 6 MANDATORY MEASURES

MIXED-USE BUILDINGS For some mixed-use buildings, (e.g. high-rise residential, hotels, and motels) the common areas must comply with the Nonresidential Lighting Standards, while dwelling units must comply with the Residential Lighting Standards. Photo: UC Davis 10/7/2013 SLIDE 131 SECTION 6 MANDATORY MEASURES

MULTI-LEVEL LIGHTING CONTROLS Title 24 sets a minimum number of control steps and illuminance uniformity requirement for most major luminaire types in TABLE 130.1-A. These requirements are required in addition to any manual, daylight, shut-off or demand response controls. These criteria apply only to general lighting for enclosed areas that: Are at least 100 square feet in size Have a connected lighting load over 0.5 watts per square foot Has more than one luminaire or more than two lamps Section 130.1 (b) 10/7/2013 SLIDE 132 SECTION 6 MANDATORY MEASURES

MULTI-LEVEL LIGHTING CONTROLS Each luminaire must meet every step of the multi-level control requirement. Controlling alternating luminaires or rows of luminaires does not meet this requirement. 50% Section 130.1 (b) 100% 10/7/2013 SLIDE 133 SECTION 6 MANDATORY MEASURES

TABLE 130.1-A Section 130.1, page 138 10/7/2013 SLIDE 134 SECTION 6 MANDATORY MEASURES

AUTOMATIC SHUT-OFF CONTROLS Automatic shut-off controls turn off the lights when a space is unoccupied. All lighting must be controlled by one or more of the following: 1. Occupant sensing control 2. Automatic time-switch 3. Building Energy Management System 4. Other control capable of automatically shutting off all lights for vacant periods Photo: Lutron Section 130.1 (c) 10/7/2013 SLIDE 135 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Space parameters Each room needs to be separately controlled. A single control may not monitor more than 5,000 square feet of floor area (20,000 square feet in malls and single-tenant retail spaces). Applications The following types of lighting must be separately controlled: 1. General 2. Display 3. Ornamental 4. Display case Section 130.1 (c) 10/7/2013 SLIDE 136 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Countdown timer switches are usable only in: 1. Single-stall bathrooms smaller than 70 square feet 2. Closets smaller than 70 square feet 3. Lighting in sever rooms smaller than 500 square feet If time-based controls are used, occupants there after hours must be able to activate lighting as needed: Manual switch Temporary override Occupancy-based control Section 130.1 (c) 10/7/2013 SLIDE 137 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Adaptive controls in secondary spaces Controls for lighting in the following spaces must be capable of partially reducing lighting power during hours of operation in addition to providing full shut-off functionality when the building is vacant. Section 130.1 (c) 10/7/2013 SLIDE 138 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Warehouse aisles and open areas 1. Each aisle must be independently controlled 2. Minimum automatic 50% reduction in lighting power when vacant Section 130.1 (c) 10/7/2013 SLIDE 139 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Corridors and stairwells 1. Sensors/controls should be activated from all potential entrances 2. Minimum automatic 50% reduction in lighting power when vacant Section 130.1 (c) 10/7/2013 SLIDE 140 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC SHUT-OFF CONTROLS Spaces that are exempt from automatic shut-off controls requirements: 1. Buildings with lighting in continuous use 24 hours per day, 365 days per year 2. Areas where partial on/off controls are required instead of shut-off controls (ex: stairwells and corridors) 3. Electrical equipment rooms 4. Emergency egress lighting Section 130.1 (c) 10/7/2013 SLIDE 141 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC DAYLIGHTING CONTROLS Automatic daylight controls adjust electric lighting power when daylight is available. Automatic daylighting controls are required for luminaires that: 1. Provide general lighting 2. Are at least half in a skylit or sidelit area 3. Are in an area where the total installed general lighting power exceeds 120 watts Photo: Lutron 4. Are located in an area which has more than 24 square feet of glazing Photo: Lutron Section 130.1 (d) 10/7/2013 SLIDE 142 SECTION 6 INDOOR LIGHTING CONTROLS

AUTOMATIC DAYLIGHTING CONTROLS Automatic daylighting controls requirements: 1. If the controlled lighting has a lighting power density greater than 0.3 watts per square foot, controls must provide multi-level lighting in accordance with Table 130.1-A. 2. The combined illuminance from the controlled lighting and daylight must be at least as much as would be provided by the controlled lighting when no daylight is present. 3. When the light received from daylight is more than 150% of the design illuminance of the general lighting system at full power, the general lighting power in that space must be reduced by at least 65%. Section 130.1 (d) 10/7/2013 SLIDE 143 SECTION 6 INDOOR LIGHTING CONTROLS

DEMAND RESPONSE When the demand for electricity threatens to exceed supply, the power grid becomes less stable and the risk of outages increases. Demand response (DR) programs allow end users to temporarily reduce their electricity use in response to a notice or automated signal sent from a utility, independent system operator (ISOs) or other power provider. This flexibility in what time power is consumed helps reduce peak demand and maintain grid stability. Currently, participating customers also receive financial incentives. Section 130.1 (e) 10/7/2013 SLIDE 144 SECTION 6 INDOOR LIGHTING CONTROLS

DEMAND RESPONSE How DR Works In traditional, non-automated DR programs, a local service provider sends notification of a pending DR event to facility managers, via e-mail, phone call or text message, requesting a reduction in electricity consumption for a limited period of time. Automated demand response (ADR) programs make use of energy management technologies and controls to respond to DR events quickly. The provider issues an automated DR signal to energy management control systems enrolled in ADR programs. The systems then automatically respond by reducing electricity use according to pre-programmed load shed strategies. Section 130.1 (e) 10/7/2013 SLIDE 145 SECTION 6 INDOOR LIGHTING CONTROLS

DEMAND RESPONSE Lighting is extremely well-suited to DR 1. Peak demand periods typically coincide with daylight hours (noon to 5 p.m., particularly during summer months) 2. Research indicates illuminance levels can be reduced by as much as 20% without impacting end-user comfort. 3. Light levels can be immediately restored when DR events end Buildings larger than 10,000 square feet must be capable of responding to a DR signal by reducing building lighting power at least 15% while maintaining the uniformity requirements of Table 130.1-A. Spaces that use less than 0.5 watts per square foot and non-habitable spaces, such as storage closets, are exempt from demand response requirements and cannot be counted towards compliance. Section 130.1 (e) 10/7/2013 SLIDE 146 SECTION 6 INDOOR LIGHTING CONTROLS

SUMMARY OF MANDATORY LIGHTING CONTROLS DISCUSSION: What types of controls will retail spaces typically require? 1. Manual switches (what needs to be switched separately?) 2. Automatic shut-off controls (where are they required?) 3. Automatic daylighting controls (which lighting systems must comply?) 4. Demand responsive controls (how large does a building need to be?) 10/7/2013 SLIDE 147 SECTION 6 INDOOR LIGHTING CONTROLS

CHECK YOUR UNDERSTANDING: DEMAND RESPONSE An 18,000 square foot building is being constructed that will contain ten retail tenant spaces that are 1,000 square feet each. Do these tenant spaces need to comply with demand response signals? 10/7/2013 SLIDE 148 SECTION 6 INDOOR LIGHTING CONTROLS

1. Area Controls: Manual controls that control lighting in each area separately 2. Multi-level Controls: Allow occupants to choose the appropriate light level for each area 3. Shut-off Controls: Automatically shuts off lighting or reduces light levels when illumination is not needed 4. Automatic Daylighting Controls: Adjust electric lighting in

Related Documents:

Small Lighting controls 20 80/22 21 Small Lighting-only 20 80/22 18 Large Lighting controls 10 80/31 10 Large Lighting-only 10 80/31 7 2013-2014 Small Lighting controls 40 80/16 42 Small Lighting-only 20 80/22 21 Large Lighting controls 30 80/18 33 Large Lighting-only 10 80/31 10 Total 160 80/15 162

Dec 06, 2016 · COMMERCIAL LIGHTING 01-13 14-29 industrial lighting hazardous area lighting cleanroom lighting INDUSTRIAL LIGHTING street lighting area lighting induction lighting landscape lighting CITYSCAPE LIGHTING 30-51 ballast light sources HID lamps spares price list A

LIGHTING ( DEFINED ) OPEN AREA (ANTI-PANIC) LIGHTING ( UNDEFINED ) HIGH RISK TASK LIGHTING Emergency lighting standards tree. Escape route lighting. 1.Escape Route Lighting The emergency lighting on a route forming part of the means of escape from a point in a building to final exit. 2.Open Area (Anti-panic) Lighting The part of emergency .

Jeff Davis County - Jeff Davis Pre-K, Jeff Davis Learning Center, Mt. Zion Learning Center, Head Start, Jeff Davis Primary, Jeff Davis Elementary, Jeff Davis Middle, Jeff Davis High 3 Literacy Assessments. The JDCSS student assessment system is arranged in three tiers consisting of state-mandated, district-level, and building-level assessments.

LitePak 2 from Douglas Lighting Controls is a standardized digital lighting control system that provides automated and manual control over indoor and outdoor lighting. Contractors find standard off-the-shelf lighting control panels valuable for smaller projects due to their low cost and ease of installation.

7.11.2 Indoor Air Sample Locations 7.11.3 Indoor Air Sample Duration 7.11.4 Indoor Air Sample Frequency 7.11.5 Indoor Air Sample Containers And Analytical Methods 7.11.6 Indoor-Outdoor Air Sample Logs 7.12 Passive Soil Vapor and Indoor Air Sample Collection Procedures 7.12.1 Passive Sampling of Soil Vapor

2 15 ' 1 2 15 ' 2 15 ' notes: mainline 1 typ. lighting limits interchange 215' lighting limits interchange lighting limits interchange lighting limits interchange lighting limits interchange 3. 2. 1. interchange lighting limits n.t.s. reports indicates. of what that the lighting justification the mainline will be illuminated regardless

Given a power point presentation on . Ramcharitmanas: The Journey of a Text . in India International Centre, New Delhi on 7/3/2003. 7. Participated as a resource person in a refresher course for lecturers on “Hindi Public Sphere” organized by Mahatma Gandhi International University at Nainital on 13. th &14. th. June’2003. 8. Participated in the International Seminar on Fyodor J.Tyutchev .