MANUAL – INSTALLATION Dual Duct Terminal Unit - Direct Digital Controls DDS5 Series v200 – Issue Date: 01/06/21 2021 Price Industries Limited. All rights reserved.

DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES TABLE OF CONTENTS Product Overview General. 1 Receiving Inspection. 1 Wiring. 1 Installation Instructions Installing the DDS5 Terminal Unit. 2 Air Volume Ranges. 2 SP300 Calibration Curves. 3 Maintenance Replacement Parts. 5 II DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES - Manual priceindustries.com

DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES PRODUCT OVERVIEW General Receiving Inspection The DDS5 assembly is designed to accept Direct Digital Controls (DDC) for VAV pressure independent operation. After unpacking the assembly, check it for shipping damage. If any shipping damage is found, report it immediately to the delivering carrier. During unpacking and installation do not handle by the inlet velocity sensor, damper shaft, or tubing. Damage may result. The terminal unit controls are supplied by the controls contractor and either factory or field mounted and wired. For information concerning controls, components, sequence of operation, etc., please refer to the documentation provided by the controls contractor. Wiring If controls have been factory mounted, a wiring diagram will be included with the unit indicating the factory mounted components. For field wiring of room sensors and other accessories, refer to the controls contractor’s documentation. If the controls have been field mounted, refer to the controls contractor’s documentation for all wiring information. Damper rotation is always clockwise to the open position. An identification mark on the end of the shaft indicates the damper position. The factory supplied sensing lines are color coded. Red indicates the total pressure or “HI” line which should be located on the upstream side. Green indicates the static pressure or “LO” line which should be located on the downstream side. An optional protective enclosure may be provided to house the terminal unit control components. The enclosure cover is removable with two sheet metal screws. The velocity sensor is normally supplied as standard with the terminal unit. However, in some cases a flow sensing device supplied by the controls contractor may be factory or field mounted. Refer to the submittal drawing for illustration. The air volume ranges listed are recommended for optimum performance. A minimum value of zero is also acceptable for either the hot deck or the cold deck. Selection of air flow limits below the listed values is not recommended. Stability and Product Key accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied. DXX X000 DDS5 Controller Type P -- Pneumatic STANDARD E -- Electronic D -- Digital ½” (13) Configuration Primary Air Control S -- Standard 5 -- DDC Controls supplied by others CONFIGURATION SIDE MOUNTED) Q -- Quiet (CONTROLS - c/w 36" 8 -- Pressure Independent Controls Sound Attenuator by Price UQ -- Ultra Quiet with discharge DAMPER SHAFT ½” (13) DAMPER SHAFT silencer included V -- Variable SENSOR Volume MULTI-POINT no mixing M -- High mixing Flow Sensor Orientation DxS, DxQ, DxUQ and DxM Series DxS, DxQ, DxUQ and DxM Series are supplied with SP300 flow sensors on both inlet ducts and one downstream total sensor at the discharge. SLOTflow INDICATES DAMPER POSITIONsequences the cold deck For pneumatic and electronic inlet sensor and downstream total flow sensors are utilized for all standard constant and variable volume configurations. The hot deck inlet sensor is not used. AIR FLOW UP Where DDC controls are supplied by the controls contractor for factory or field mounting, the appropriate sensors required will depend on the model of controls and application. To accommodate all variations and allow future field modification, both inlet and downstream sensors are supplied as standard. DxV Series DxV series is not meant for constant volume applications so air flow sensors are only supplied at both inlets and priceindustries.com DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES - Manual none on the discharge end. 1

DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES INSTALLATION INSTRUCTIONS Installing the DDS5 Terminal Unit Where accessory modules, such as attenuators or silencers are included, the assembly should be supported directly. Use the support method prescribed for the rectangular duct in the job specifications. NOTE: For optimum performance there should be a minimum of three duct diameters of straight inlet duct, same size as the inlet, between the inlet and any transition, take off or fitting. To control radiated noise in critical applications it is recommended that the inlet ducts be fabricated of a minimum gauge of 24 in place of flexible duct. The assembly should be mounted right side up. It should be level within 10 degrees of horizontal, both parallel to the air flow and at right angles to the air flow. The side of the assembly is labelled with an arrow indicating UP. Do not mount the control side of the assembly tight to a wall, pipe or other obstruction. Allow sufficient room for access to the controls. To prevent excess air leakage, all joints should be sealed with an approved duct sealer. This would apply to all accessory module connections as well as the basic assembly. NOTE: Factory calibrated controls must be selected within the above flow range limits. A minimum value of zero is also available. When an auxiliary flow setting is specified, the value must be greater than the minimum setting and within the range limits. 2 Air Volume Chart Inlet Size Adjustment Range CFM Adjustment Range L/s Max. Min. Max. Min. 4 75-225 45-225 35-106 21-106 5 115-350 63-350 54-165 30-165 6 135-400 66-400 64-189 31-189 7 185-550 99-550 87-260 47-260 8 245-750 132-750 116-354 62-354 9 320-1000 167-1000 151-472 79-472 10 425-1300 221-1300 201-613 104-613 12 605-1900 304-1900 285-897 143-897 14 930-2900 439-2900 439-1369 205-1369 16 1190-3500 568-3500 562-1652 268-1652 On controls mounted by Price but supplied by others, the air volume ranges are guidelines only. Selection of air flow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied. DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES - Manual priceindustries.com

DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES INSTALLATION INSTRUCTIONS Inlet Airflow Sensor SP300 Inlet Calibration Curves Airflow Sensor SP300 Calibration Curves Differential Pressure at Sensor (Amplified Velocity Pressure, In. W.G.) 2 4 10 8 7 5 0.2 0.02 6 9 100 14 10 24 x 26 12 16 1000 10000 Air Flow: CFM at Standard Density Calibration Equation VP (KQ) 2 VP - differential pressure at sensor, inches w.g. Q - air flow rate, cfm at standard density. K - calibration constant Inlet Sensor Downstream Sensor Unit Size K Unit Size K 4 340 4 215 5 426 5 340 6 468 6 442 7 673 7 588 8 890 8 769 9 1155 9 1004 10 1487 10 1300 12 2141 12 1890 14 3050 14 2980 16 4074 16 3679 1. Setting flow limits for a differential pressure of less than 0.02 inches is NOT recommended. Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal. Performance will vary depending on the terminal unit controls provided. 2. For field calibration of air flow limits refer to the control contractor’s documentation. priceindustries.com DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES - Manual 3

DUAL DUCT DUAL DUCTVARIABLE VARIABLE VOLUME VOLUME CONTROL CONTROLASSEMBLIES ASSEMBLIES INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Downstream r Calibration Downstream Calibration Curves Curves 4 DUAL DUCT SINGLE DUCT VARIABLE VARIABLE VOLUME VOLUME CONTROL CONTROL ASSEMBLIES ASSEMBLIES - Manual - Manual priceindustries.com priceindustries.com

DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES MAINTENANCE Replacement Parts Component Removable SP300 Sensor Part# Description 041688-001 041688-002 041688-003 041688-004 041688-005 041688-006 041688-007 041688-008 203132-999 203136-999 041510-001 041683-001 Sensor SP300, Sizes 4,5 & 6 Sensor SP300, Size 7 Sensor SP300, Size 8, Size 24x16 (qty. 4 required) Sensor SP300, Size 9 Sensor SP300, Size 10 Sensor SP300, Size 12 Sensor SP300, Size 14 Sensor SP300, Size 16 .250” Green Tubing, Low Signal .250” Red Tubing, High Signal Rubber Grommet RB-215 Tee, Brass, .250” x .250” x .250” priceindustries.com DUAL DUCT VARIABLE VOLUME CONTROL ASSEMBLIES - Manual 5

This document contains the most current product information as of this printing. For the most up-to-date product information, please go to priceindustries.com 2021 Price Industries Limited. All rights reserved.

accept Direct Digital Controls (DDC) for VAV pressure independent operation. The terminal unit controls are supplied by the controls contractor and either factory or field mounted and wired. For information concerning controls, components, sequence of operation, etc., please refer to the documentation provided by the controls contractor.

Related Documents:

installed as described in the TDC or TDF addendum to the SMACNA Duct Construction Standards except the corners may not be bolted. Standard 5" metal clips may be used with spacing as shown in diagram. SLEEVE DUCT TYPICAL TDC/TDF JOINT DUCT 60" Duct 3 REQ'D. 48" Duct 3 REQ'D. 36" Duct 3 REQ'D. 24" Duct 2 REQ'D. 18" DUCT and .

Duct Sizing Tools OR Duct Sizing Chart Ductulator (Manual/Digital) AIRAH DA3 Duct Design Manual Manufacturers/Programs . Duct Sizing Methods . More available in the ASHRAE Handbook or SMACNA Obtain other duct fittings pressure losses from manufacturers such as duct heaters, dampers, filters, grilles, coils, etc

Air Duct Design & Sizing Duct sizing methods Static regain method Normally used with a computer package for high velocity systems (e.g. in main duct) Size air duct so that static pressure nearly offset the pressure loss of succeeding duct section along main duct T me

Under Floor Duct 1.5 OFFSET FOR #6 DUCT PU6-OFS15 Duct / Under Floor Duct. L 4 International Drive Rye Brook, NY 10573 Toll Free: 1 888.764.7681 Phone: 914.934.2075 Fax: 914.934.2190 MonoSystems.com 03/2016 DOCUMENT REF. NO. PU6FFL45-PU6WE Manufactured by MonoSystems, Inc. Under Floor Duct

lsc bus duct system 1. introduction 3 1.1 general specifications 1.2 outstanding feature of lsc bus duct 1.3 cataloging 2. high power distribution (600a 6000a) 9 2.1 general specifications 2.1.1 i-series bus duct 2.1.2 8-series bus duct 2.1.3 f-series bus duct 2.1.4 y-series bus duct 2.2 grounding & ip degree 2.2.1 grounding 2.2.2 ip degree 2.3 .

IMPERIAL MANUFACTURING GROUP INC. / GALVANIZED DUCT, PIPE & FITTINGS PAGE 5 Galvanized Duct, Pipe & Fittings IMG DIMENSION / UNIT STD . STD . RACK UPC SKUDESCRIPTION MSRPKG QTYQTYCODE Stack Duct - 30 Gauge GV1306 2-1/4" x 10" x 24" Stack Duct 30ga /ft . 12' Ctn - 063467112839 GV1318 2-1/4" x 12" x 24" Stack Duct 30ga /ft .

Capacity Correction Factor for Height Difference 8. Noise Data 9. Electrical Characteristics 10. Static Pressure . Corresponding relation between Rectangular duct and Round duct 5. Method for duct calculation 6. Unit conversion 7. Recommended outlet velocity for different occasions . Indoor air flow (Hi/Med/Lo) (No duct) CFM 353/283/177 353 .

Duct Width Spiral Seam Duct Gauge Fitting Gauge to 24" 24 20 25 to 36" 22 20 37 to 48" 22 18 49 to 60" 20 18 61 to 70" 20 16 71" and up 18 16 DUAL WALL OVAL DUCT AND FITTINGS CONSTRUCTION STANDARDS Outer Shell Positive Pressure Gauge selection for galvanized (ASTM A653). Fittings are manufactured with standing seam, welded seam .