Three Phase Transformers Theory and Calculations Copyright 1999-2019 Dan Dudley

DELTA Transformer Copyright 1999-2019 Dan Dudley

WYE Transformer Copyright 1999-2019 Dan Dudley

Voltage and Current in a Delta Transformer Copyright 1999-2019 Dan Dudley

Voltage and Current in a WYE Transformer Copyright 1999-2019 Dan Dudley

Delta – Volts are Equal ü Delta Configuration Transformer Voltage is EQUAL Phase and Line Ø The Phase Voltage Line Voltage Current is NOT EQUAL Ø Phase Ø Line Current Line Current / 1.732 Current Phase Current X 1.732 D V W I , Phase Divide, Line Multiply, by 1.732 Copyright 1999-2019 Dan Dudley

Wye – Current is Equal ü Wye Configuration Transformer Current is EQUAL Phase and Line Ø The Phase Voltage Line Voltage Voltage is NOT EQUAL Ø Phase Voltage Line Voltage / 1.732 Ø Line Voltage Phase Voltage X 1.732 n D V W I , Phase Divide, Line Multiply, by 1.732 Copyright 1999-2019 Dan Dudley

DELTA Configuration WYE (“Y”) Configuration Copyright 1999-2019 Dan Dudley

Ratio of Transformation Copyright 1999-2019 Dan Dudley

(4) (1) (2) (3) 1. Primary Line 2. Primary Phase 3. Secondary Phase 4. Secondary Line Core Copyright 1999-2019 Dan Dudley

230 V 6.25 amps 6.25 amps X 25 amps What is the Primary Line voltage of a Delta-Wye connected transformer with a secondary line voltage of 230 volts, secondary line current of 25 amps, and primary line current of 6.25 amps Answer 1. Ratio Primary amps / Secondary amps 25/6.25 4 2. Secondary Line to Secondary Phase 230 / 1.732 132.8v 3. Primary Phase volts using ratio 132.8 X 4 531.2 volts 4. Delta Phase Volts Line Volts 531.2 volts Primary Line Copyright 1999-2019 Dan Dudley

1920 V 125 amps 15.6 amps What is the Secondary Line voltage of a Delta-Wye connected transformer with a Primary line voltage of 1920 volts, secondary line current of 125 amps, and primary line current of 15.6 amps Answer 1. Ratio Primary amps / Secondary amps 125/15.6 8 2. Primary Line to Primary Phase 1920v 1920v Primary Phase 3. Secondary phase using ratio 1920 / 8 240 volts 4. Wye Line Volts Phase Volts X 1.732 415.68 volts Sec Line Copyright 1999-2019 Dan Dudley

7200v 480v 26 a X What is the Secondary Line Current of a Delta-Wye connected transformer with a Primary line voltage of 7200 volts, secondary line voltage of 480, and primary line current of 26 amps Answer 1. Ratio Primary volts / Secondary volts 7200/480 15 2. Pri Line amps to Pri Phase amps 26 / 1.732 15.01 amps 3. Sec phase amps using ratio 15 X 15.01 225.17 amps 4. Wye Line amps Phase amps 225 amps Sec Line Current Copyright 1999-2019 Dan Dudley

120 V 1440 V 140 amps What is the Primary Line current of a Delta-Wye connected transformer with a secondary line voltage of 120 volts, secondary line current of 140 amps, and primary line voltage of 1440 volts. Answer §1. Ratio Primary volts / Secondary volts 1440/120 12 §2. Secondary Line to Secondary Phase 140 140a (Wye ) §3. Primary Phase current using ratio 140 / 12 11.66 amps §4. Delta Line Current 11.66a X 1.732 20.20 amps Pri Line Delta Copyright 1999-2019 Dan Dudley

Three Phase example #2 Phase volts for a 3 phase transformer are 208 v, what is the line voltage connected Wye ? Line Volts Phase Volts X 1.732 208 X 1.732 360.256 Volts Copyright 1999-2019 Dan Dudley

Three Phase example #3 Phase Current for a Delta connected transformer, 480 v, 45 kva, with 20 amps on the line are ? Phase Amps Line amps / 1.732 20 / 1.732 11.547 amps Copyright 1999-2019 Dan Dudley

Three Phase Fault Current Calculation Transformer: 3phase, 265 kva, 208/120 volt with 2.5% impedance I W / E (no Power Factor W VA 3 Phase use 1.732 I - 3 phase VA / E X 1.732 Whatever your Impedance simply Divide it into 100 Convert K (Kilo) by dividing by 1000 265,000 / 208 X 1.732 Do this calc first 265,000 / 360.256 735.58802 Multiplier 100 / 2.5 40 736 amps X 40 29,440 amps fault current Copyright 1999-2019 Dan Dudley

Service Entrance Raceway & Conductors NESC HIGH LEG PHASE “C” Meter Base NEC 230.56 & 215.8 HIGH LEG – PHASE “B” Service Equipment Feeder CB HIGH LEG Phase “B” 408.3(E) 215.8 Feeder Circuit The HIGH LEG IS ALWAYS Grounding Electrode Conductor Electrical Equipment ORANGE Copyright 1999-2019 Dan Dudley

NEC – Phase Arrangement 408.3(E) A–B–C Front to Back Top to Bottom Left to Right Higher Voltage to Ground B Phase – Center Phase Copyright 1999-2019 Dan Dudley

Open Delta System 1. Requires 3 transformers 2. Advantage: 3 phase power 3. Disadvantage: Reduced capacity Approx: 58% of total Copyright 1999-2019 Dan Dudley

You can derive two (2) Different voltages from this Transformer 120 volts and 208 volts Copyright 1999-2019 Dan Dudley

You can derive three (3) Different voltages from this Transformer 120, 208 and 240 volts This transformer configuration Is also called a “Center Tapped Delta” Copyright 1999-2019 Dan Dudley

Copyright 1999-2019 Dan Dudley

Copyright 1999-2019 Dan Dudley

Transformer Connection Identification Copyright 1999-2019 Dan Dudley

Transformer Connection Identification Copyright 1999-2019 Dan Dudley

Transformer Connection Identification Copyright 1999-2019 Dan Dudley

Three Phase Transformer Questions 30 Minutes Copyright 1999-2019 Dan Dudley

What is the Primary Line voltage of a Delta-Wye connected transformer with a secondary line voltage of 230 volts, secondary line current of 25 amps, and primary line current of 6.25 amps Answer 1. Ratio Primary amps / Secondary amps 25/6.25 4 2. Secondary Line to Secondary Phase 230 / 1.732 132.8v 3. Primary Phase volts using .

Related Documents:

applications including generator step-up (GSU) transformers, substation step-down transformers, auto transformers, HVDC converter transformers, rectifier transformers, arc furnace transformers, railway traction transformers, shunt reactors, phase shifting transformers and r

7.8 Distribution transformers 707 7.9 Scott and Le Blanc connected transformers 729 7.10 Rectifier transformers 736 7.11 AC arc furnace transformers 739 7.12 Traction transformers 745 7.13 Generator neutral earthing transformers 750 7.14 Transformers for electrostatic precipitators 756 7.15 Series reactors 758 8 Transformer enquiries and .

2.5 MVA and a voltage up to 36 kV are referred to as distribution transformers; all transformers of higher ratings are classified as power transformers. 0.05-2.5 2.5-3000 .10-20 36 36-1500 36 Rated power Max. operating voltage [MVA] [kV] Oil distribution transformers GEAFOL-cast-resin transformers Power transformers 5/13- 5 .

Ferrers, Elizabeth , Lady Ferrers of Groby Edward Grey Grey, Sir John Elizabeth Wydeville (Woodville), also wife of King Edward IV Grey, Thomas Cecily Bonville, Lady Harington and Bonville Grey, Thomas Faris, 2nd ed. Dudley 3 John Dudley, 3rd Lord Dudley Dudley, Capt. Henry _ Ashton. There is not record of any children.

- IEC 61558 – Dry Power Transformers 1.3. Construction This dry type transformer is normally produced according to standards mentioned above. Upon request transformers can be manufactured according to other standards (e.g. standards on ship transformers, isolation transformers for medical use and protection transformers.

cation and for the testing of the transformers. – IEC 61378-1 (ed. 2.0): 2011, converter transformers, Part 1, Transformers for industrial applications – IEC 60076 series for power transformers and IEC 60076-11 for dry-type transformers – IEEE Std, C57.18.10-1998, IEEE Standard Practices and Requirements for Semiconductor Power Rectifier

Transformers (Dry-Type). CSA C9-M1981: Dry-Type Transformers. CSA C22.2 No. 66: Specialty Transformers. CSA 802-94: Maximum Losses for Distribution, Power and Dry-Type Transformers. NEMA TP-2: Standard Test Method for Measuring the Energy Consumption of Distribution Transformers. NEMA TP-3 Catalogue Product Name UL Standard 1 UL/cUL File Number .

Instrument . Transformers. 731. 736 737. 735. g. Multilin. 729 Digital Energy. Instrument Transformers. 738 739. 739 Instrument Transformers. Control Power Transformers 5kV to 38kV - Indoor type. Current Transducers 600 Volt Class IEC - Rated Instrument Transformers