COMMUNICATIONS - Smu.edu

3m ago
8 Views
0 Downloads
7.79 MB
85 Pages
Last View : 1d ago
Last Download : n/a
Upload by : Konnor Frawley
Transcription

COMMUNICATIONS Introduction Unless otherwise directed, the Voice and Data Consultant will be part of the Design Team. The Consultant shall meet with the end users, determine their voice and data needs, device locations and provide locations for construction drawings. The drawings must then be submitted to the OIT Department for review and compliance with campus standards and criteria. Division of Responsibility OFP&M shall engage a SMU OIT Registered Communication Distribution Design (RCDD) to support the project and be the main SMU OIT point of contact for the project. The Design Team is to provide and coordinate a layout of voice and data systems in accordance with established Campus OIT guidelines and submit to SMU OIT for approval. The Design Team shall provide drawings, and the Contractor is to provide items and services as directed in Telephones specification. Voice and Data work shall be bid and awarded by mutual agreement between SMU OIT and OFP&M as follows: Voice and Data to be bid as part of construction or separate as determined by SMU OIT/ OFP&M. OFP&M will require Contractor to provide separate subcontractor bids for voice and data work. Sub-bids shall be solicited from SMU OIT/ OFP&M pre-qualified bidders only (consult with OFP&M for list of pre-qualified Voice/Data subcontractors). Contractor’s subcontractor bids to be turned over to SMU OIT/OFP&M for review and evaluation. OFP&M and Campus OIT to determine subcontractor bidder, to which Contractor or SMU will award the subcontract. Materials, General: All new construction shall have a Cat 5 Ethernet Cable as well as a 110-volt power connection at the controller location. DIVISION 27 Structured Cabling Systems PART 1 - GENERAL Last Revision: December 2021 Communications 1 of 85

1.1 A. 1.2 REFERENCES Incorporate by reference the applicable portions of the following specifications, standards, codes into this specification section. 1. General: 1) National Electrical Code (NEC) 2) National Electrical Safety Code (NESC) 3) Occupational Safety and Health Act (OSHA) 2. Communications: 1) ANSI/TIA/EIA - 455: Fiber Optic Test Standards 2) ANSI/TIA/EIA - 526: Optical Fiber Systems Test Procedures 3) ANSI/TIA/EIA - 568-B: Commercial Building Telecommunications Cabling Standard 4) ANSI/TIA/EIA - 569: Commercial Building Standard for Telecommunication Pathways and Spaces 5) ANSI/TIA/EIA - 606: The Administration Standard for the Telecommunications Infrastructure of Commercial Buildings 6) ANSI/TIA/EIA - 607: Commercial Building Grounding and Bonding Requirements for Telecommunications 7) ANSI/TIA/EIA - 758: Customer-Owned Outside Plant Telecommunications Cabling Standard 8) ISO/IEC IS 11801: Generic Cabling for Customer Premises 9) BICSI: BICSI Telecommunications Cabling Installation Manual 10) BICSI: BICSI Telecommunications Distribution Methods Manual (TDMM) 11) BICSI: BICSI Customer-Owned Outside Plant Design Manual DEFINITIONS A. “OSP-SCS” shall mean Outside Plant - Structured Cabling Systems. The OSP-SCS is defined as all required equipment and materials including, but not limited to, ANSI/TIA/EIA and ISO/IEC compliant copper and fiber optic cable (multimode and singlemode), connectors, splices, splice closures and other incidental and miscellaneous equipment and materials as required for a fully operational, tested, and warranted system. B. “MH” shall mean Maintenance Holes or Hand holes used for the routing of communications cables. C. “TMGB” shall mean Telecommunications Main Grounding Busbar. There is typically one TMGB per building, located in the main telecommunications room. This busbar is directly bonded to the electrical service ground by the electrical contractor. (Shall be installed by the electrical contractor.) D. “TGB” shall mean Telecommunications Grounding Busbar. There is typically one TGB per telecommunications room. The TGB is connected both to the TMGB and to building structural steel or other permanent metallic systems. (Shall be installed by the electrical contractor.) Last Revision: December 2021 Communications 2 of 85

E. “TBB” shall mean Telecommunications Bonding Backbone. The TBB is a conductor used to connect TMGBs to TGBs. (Shall be installed by the electrical contractor.) F. “EMT” shall mean Electric Metallic Tubing. For entry conduits and tunnel raceway. (Shall be installed by the electrical contractor.) G. “PVC” shall mean Polyvinyl Chloride Pipe. For buried conduits. (Shall be installed by the electrical contractor.) H. “BEP” shall mean Building Entrance Protection. For Lightning Protection after OSP enter a building. I. “MDF” shall mean Main Distribution Frame. Located in Patterson Data Center and the University Data Center. J. “BDF” shall mean Building Distribution Frame. Houses the telecomm equipment for the building and connects to Patterson and University Data Center MDF. K. “IDF” shall mean Intermediate Distribution Frame. Connects floors in a building to the building BDF. L. “UDC” shall mean University Data Center. M. “MSH” shall mean Main Splice Hub. N. “ISH” shall mean Intermediate Splice Hub. PART 2 - OUTSIDE CABLE PLANT 2.1 SUMMARY A. This standard is intended for all “standard” installations at the Dallas campus and is not intended to address special installations that are sometimes encountered and addressed on an individual basis. B. This section includes specifications of Customer-Owned Outside Plant Communications cabling, terminations, pathways, installation methods and hardware specifications that apply to the Outside Plant Structured Cabling System. C. The work shall include all materials, equipment and apparatus not specifically mentioned herein or noted on the construction documents but which are necessary to make a complete working ANSI/TIA/EIA and ISO/IEC compliant OSP-SCS. D. 2.2 A. SUBMITTAL INFORMATION Product Data Submittals: Provide submittal information for review before materials are procured and delivered to the job site. Provide data for all in scope products at the same time. Last Revision: December 2021 Communications 3 of 85

1. 2. Submit a letter stating that the materials will be provided as specified, and specifically listing any items that that are recommended alternates to the specified materials. For those items noted as “equal to,” and which are not being provided as specifically named, submit standard manufacturer's cut sheets, along with a request to substitute said item and a description detailing the reason for the alternate. B. Quality Assurance Submittals: Provide submittal information for review as follows: 1. Cable routing and grouping plan: 1. Submit shop drawings representing the cable routing and grouping along with written documentation that the Contractor has reviewed the routing and grouping plans, and that the routing and grouping meets codes, regulations and standards. 2. When changes are proposed to the routing and grouping plans, coordinate with the SMU Infrastructure Design Engineer prior to installation for approval. 2. Submit a list of test equipment for use in verifying the installation of the OSP-SCS. The test equipment shall meet the criteria as defined in PART 4.8 – TESTING. 1. Submit for each testing device: 1) Manufacturer and model number. 2) Documentation showing date and outcome of last manufacture recalibration. 3) Provide documentation from the manufacturer showing software revision. C. Closeout Submittals: Provide submittal information for review as follows: 1. As-Builts - Maintain at the job site a minimum of one set of As-Built Drawings. As-Built Drawings shall consist of markups of all drop locations and pathways. 1. Document all changes to the OSP-SCS from that originally shown on the Contract Documents. 2. Keep As-Builts at the job site and make available to the Owner at any time. 3. Keep As-Builts current throughout the course of construction. 4. Provide the Owner a set of As-Builts at the time of project completion. 2.3 A. QUALITY ASSURANCE Contractor Qualifications: Prior to bidding the project, submit: 1. The Bidding Contractor must be a preferred CommScope vendor. 2. Provide documentation from the OSP-SCS manufacturer demonstrating that the Contractor is trained and certified by BICSI, Uniprise and CommScope Solutions to install, test, and maintain the OSP-SCS to provide the Manufacturer’s Warranty (see PART 2.4 - WARRANTY). 1) BICSI Technician (for general understanding of all cabling codes, standards and best practices) 2) Uniprise/CommScope Solutions (for fiber and copper) Last Revision: December 2021 Communications 4 of 85

3. 4. 5. B. 2.4 Provide documentation indicating that the awarded contractor will have a minimum of one BICSI Technician, Uniprise and CommScope Solutions manufacturer-trained and manufacturer-certified employee perform installation, testing, and firestop installations. Provide documentation indicating that the awarded contractor will have all Uniprise and CommScope Solutions manufacturer-trained and certified employees performing installations/terminations/testing of any copper and/or fiber optic media. Provide documentation demonstrating that the awarded contractor employs a minimum of one Registered Communications Distribution Designer (RCDD), certified by and in current good standing with BICSI. The RCDD shall be a direct full-time employee of the awarded contractor (i.e. an RCDD consultant/sub-contractor to the awarded contractor is not acceptable). The document shall also declare that the awarded contractor will continue to employ a minimum of one RCDD throughout the duration of the project. The awarded contractor’s employees directly involved with the supervision, installation, testing, and certification of the OSP-SCS shall be trained and certified by Uniprise and CommScope Solutions. Training and certifications by employee type are required as shown below: 1. Supervisors/Project Foremen: All (100%) shall be a certified BICSI Technician and manufacture trained/certified for installation and testing of Uniprise/CommScope Solutions products. 2. Installation Technicians: All (100%) shall be manufacture trained/certified for installation Uniprise/CommScope Solutions products. WARRANTY A. Contractor Warranty: 1. Provide a contractor-endorsed ten-year service warranty against defects in materials and workmanship. 1. Provide labor referable to the fulfillment of this warranty at no cost to the Owner. 1) The Contractor Warranty period shall commence upon Owner signoff of the work. B. OSP-SCS Manufacturer Warranty: 1. Provide an OSP-SCS Manufacturer extended product, performance, application, and labor warranty that shall warrant all passive components used in the OSP-SCS. Additionally, this warranty shall cover components not manufactured by the OSP-SCS Manufacturer, but approved by the OSP-SCS Manufacturer for use in the OSP-SCS. The OSP-SCS manufacturer warranty shall warrant: 1) That the products will be free from manufacturing defects in materials. 2) That the cabling materials of the installed system shall meet or exceed the specification of ANSI/TIA/EIA 568-B and exceed ISO/IEC 11801 standards. Last Revision: December 2021 Communications 5 of 85

3) 2. 3. 4. That the system shall support both current and future applications that use the ANSI/TIA/EIA 568-B and ISO/IEC 11801 component and link/channel specifications for OSP-SCS cabling. Provide materials and labor referable to the fulfillment of this warranty at no cost to the Owner. The OSP-SCS Manufacturer Warranty shall be provided by the selected OSP-SCS Manufacturer and shall be: 1) Uniprise/CommScope Solutions 10-year System Warranty for the fiber optic plant. 2) Provide a copy of the warranty registration document to the Owner at the time of submittal to Uniprise/CommScope Solutions. The OSP-SCS Manufacturer Warranty period shall begin upon a Warranty Certificate being issued by the manufacturer. The Warranty Certificate shall be issued no later than three months after Owner acceptance of the installation. PART 3 - PRODUCTS 3.1 GENERAL A. Unless otherwise noted, provide items as specified. “equal to” or equivalent items are not acceptable without prior approval from the SMU Infrastructure Design Engineer. B. Physically verify existing site conditions prior to work start, including but not limited to lengths and condition of conduit and/or pathway (including tunnels, maintenance holes and hand holes) to be used for routing outside plant cabling. Pre-cut materials of insufficient length are the responsibility of the contractor. C. OSP-SCS components shall be manufactured by a single manufacturer where possible. Components shall not be intermixed between different manufacturers unless the manufacturer of the OSP-SCS has listed (in writing) another manufacturer’s component as an “Approved Alternative Product” and will warrant the “Approved Alternative Product” as part of the OSP-SCS Manufacturer Warranty (see PART 2.4 WARRANTY). D. Bid only OSP-SCS Manufacturer for which the contractor is certified. The OSP-SCS Manufacturer shall be the following. Substitution is not acceptable: 1. SMU Infrastructure Design Engineer approved multipair copper cable 2. CommScope (for fiber optic cabling) E. The OSP-SCS installation shall be engineered “end-to-end” – the system and all of its components shall be engineered to function together as a single, continuous transmission path. 3.2 A. PATHWAYS AND RACEWAY Acceptable fiber raceway: 1. Innerduct: Last Revision: December 2021 Communications 6 of 85

1) 2. 3. 4. Last Revision: December 2021 Outside Plant: Corrugated, bright orange, and rated for outdoor duct installation. a) 1” Diameter b) 1-1/2” Diameter 2) Intrabuilding: Corrugated, bright orange or white, and rated for indoor installation. a) 1” Diameter - plenum rated b) 1-1/4” Diameter - plenum rated Innerduct is not required if plenum, armored steam rated fiber applies. Conduit and Duct Requirements: 1) All conduits and cable ducts placed for SMU will be clean and free of moisture prior to acceptance by the SMU OIT department. A letter of certification shall be provided by the conduit or cable duct installation contractor verifying the testing and condition of the conduits. 2) All innerduct and conduit pathways must have pull strings and/or ropes installed by the contractor at the time of conduit pathway installation. 3) Conduit Composition: a) Conduits placed in tunnels shall be metallic. (EMT) b) Buried conduits can be schedule 40 PVC (or better) with pull boxes and/or hand holes. (All bends/sweeps must be metallic) 4) A minimum of (3) 4-inch entry conduits from the outside utility tunnel, pull box or maintenance vault that terminates above the finished floor in the building BDF, however there may be buildings that require more capacity based upon specific system requirements and population density. The entrance capacity for all new buildings should be verified with the SMU Infrastructure Design Engineer. 5) Bends and Sweeps: a) A standard of 10 times the outside diameter of the installed conduit shall be followed. (For instance: A four-inch conduit must have a 40-inch 90 degree sweeping bend applied.) 6) Pull Boxes and Hand Holes: a) Size vs. Pipe Size b) Indoor: A pull box will be placed every 100 feet of conduit or after 180 degrees of bends and/or sweeps have been met. c) Outdoor: A pull box/hand hole will be placed after every 300 feet of conduit if no significant bends/sweeps are made. For every 90 degrees of bends/sweeps, 50% of the total conduit length between pull box/hand hole will be subtracted. (For instance: A conduit path with a 90-degree turn will have a pull box and/or hand hole placed after 150 feet of the conduit path.) Buried Conduits: 1) 1 inch is the minimum acceptable conduit size for outdoor device locations, however there may be locations that require more capacity based upon specific system requirements or port density. The entrance capacity for all new buildings should be verified with the SMU Infrastructure Design Engineer. 2) Buried conduit pathways must have pull strings or ropes installed by the contractor at the time of conduit pathway installation. Communications 7 of 85

3) 5. 6. 3.3 A. Depth: a) 24 inches below the surface is the minimum accepted. b) 30 inches below the surface is acceptable. c) 36 inches below the surface is preferred. 4) A yellow marker tape is to be placed 12 inches below the surface running the length of the conduit path. 5) Separation shall be 12 inches minimum, 18 inches preferred from any electrical equipment or lines. 6) Conduit Composition: a) Schedule 40 PVC with pull boxes or hand holes will be acceptable. (All bends/sweeps must be metallic). b) LB’s, electrical or steam elbows will NOT be accepted in a nonaccessible conduit path. c) LB’s are sometimes used to enter building. These instances will be addressed and approved on an individual basis by the SMU Infrastructure Design Engineer. 7) Trenching: Structure of trench and fill materials a) Layer 1 (Base Fill): A porous material suitable for drainage. b) Layer 2 (Conduit): Installation of approved conduits. c) Layer 3 (50/50 mix): mix of base fill and clean fill. d) Layer 4 (Clean Fill): To the surface. e) A yellow marker tape is to be placed 12 inches below the surface running the length of the conduit path. f) Compaction testing: 90% native ground, 95% roadways. Tunnel Environments: 1) Space Requirements: a) Appropriate access shall be installed allowing an able-bodied individual to move in and out of the tunnel space. b) Access hatches and grates must have a locking mechanism or the ability to have a pad lock installed. c) Separation distances d) A separation of 12 inches minimum shall be maintained. 18 inches preferred from electrical equipment and electrical lines running parallel. e) Tunnel temperatures are not to exceed 176 degrees Fahrenheit or fall below -49 degrees Fahrenheit. If tunnel temperatures do not meet the requirements, proper ventilation and/or insulation will need to be installed. Vaults: 1) Racking points shall be provide on all usable sides of the vault. CABLING METHODS Cabling in Buried Conduits: 1. Direct Buried Cable Composition: 1) Must be gel filled (encapsulated) and meet outside plant specifications. 2. Lightning Protection: Last Revision: December 2021 Communications 8 of 85

1) 3. BETs shall be placed at each end of the OSP-SCS. Cables must terminate on BETs after 50 feet from entry unless a ridged conduit path is provided from the entry point to the termination point. From BET, continue the circuit with the approved plenum rated cable to the buildings BDF if necessary. 2) See section 3.4 (TERMINATION EQUIPMENT) for detailed hardware specifications. Splicing: 1) Copper: A buried splice case is not acceptable; splice casing must be placed in a dry, accessible location. 2) Fiber: All fiber runs are to be continuous. The only approved splicing locations are: a) Data Centers b) MSH’s (Main Splice Hubs) c) ISH’s (Intermediate Splice Hubs) d) BDF’s (Building Distribution Frames) e) IDF’s (Intermediate Distribution Frames) B. Direct Burial Cabling (is NOT acceptable). All cabling must be in a protective pathway. C. Aerial (not an SMU preferred cabling method) 1. Route and Pathway: Contact the SMU Infrastructure Design Engineer prior to any aerial installations. 2. Lightning Protection: 1) BETs shall be placed at each end of the OSP-SCS. Cables must terminate on BETs after 50 feet from entry unless a ridged conduit path is provided from the entry point to the termination point. From BET, continue the circuit with the approved plenum rated cable to the buildings BDF if necessary. 2) See section 3.4 (TERMINATION EQUIPMENT) for detailed hardware specifications. 3. Aerial Cable Composition: 1) Must meet outside plant specifications. 4. Support Cable: 1) A metallic stranded cable may be required to support the aerial cable across utility poles and attach to the end user building. 2) Contact the SMU Infrastructure Design Engineer prior to any stranded cable installations for specification on where to secure to the poles and user buildings. 3.4 A. TERMINATION EQUIPMENT Voice Backbone - Copper Building Entrance Protectors (BETs) in Patterson Data Center (MDF), University Data Center (MDF), MSH’s, ISH’s and BDF’s. Complete with 25-foot minimum stub and plug-in gas protector modules (3BIE) for each pair terminated on the chassis. BEPs shall be manufactured by the following manufacturer: 1. For Circa Enterprises, Inc. – Patterson Data Center (MDF): 1) 1880B1 Series with 3BIE gas protectors a) 50-pair to be terminated: 1880B1-50A Last Revision: December 2021 Communications 9 of 85

B. Copper Splice Closures: Closures shall be re-enterable without compromising the integrity of the housing. Splice closures shall not require special tooling for entry and sealing of the closure. 1. Outdoor: Splice closure shall be watertight and sealable. 1) Closures shall be: a) 3M or a better built casing is acceptable. 2) Encapsulation: Water blocking compound shall be injected per manufacturer’s recommendation. 2. Indoor: 1) Closures shall be: a) 3M or a better built casing is acceptable. C. Fiber Splice Closures: 1. Outdoor: Unacceptable. All fiber splicing is to take place in rack mounted fiber shelves in the: 1) University Data Center 2) Patterson Data Center 3) MSH’s 4) ISH’s 5) BDF’s 6) IDF’s D. Fiber Shelves: 1. Patterson Data Center (MDF), University Data Center (MDF), MSH’s, ISH’s: 1) CommScope Solutions fiber shelf with CommScope pigtails fusion spliced, LC Connectors. Use high density coupler panel. 2) CommScope Solutions fiber shelf with CommScope pigtails fusion spliced, LC Connectors. Use high density coupler panel. 2. Building BDF: 1. CommScope Solutions fiber shelf with G2 Modules 2. CommScope Solutions fiber shelf with G2 Modules E. Fiber Connector Panels: (BDF & MDF) 1. 6 strand- 62.5um MM strands assigned by OIT as Fire fiber are to be fusion spliced through the building BDF, directly onto the OSP 62.5um MM fiber strands inside the BDF fiber shelf. Contact SMU Infrastructure Design Engineer for details. 2. All SM strands assigned by OIT as Data fiber are to be fusion splice to (LC) pigtails with CommScope high density coupler panels. 3.5 A. CABLE Outdoor Cable: Rated for outdoor and steam tunnel use, duct installation, aerial, and/or direct buried conduit installation as dictated by the construction documents. 1. Fiber Optic Cable: All-dielectric, meeting or exceeding ANSI/TIA/EIA and industry standards. Cables and fan-out kits shall be manufactured by the selected OSP-SCS Manufacturer: 1) CommScope Solutions Multimode: All-dielectric, multimode graded index, 62.5/125um multimode. Last Revision: December 2021 Communications 10 of 85

2) 3) 3.6 A. CommScope Solutions Singlemode: All-dielectric, singlemode graded index, 8/125um singlemode. Copper Cable: a) For Backbone: Shielded, 24-AWG solid copper conductors insulated with color coding. Minimum pair count of 50 unless otherwise specified in the Contract Documents. LABELING AND ADMINISTRATION Labels 1. 2. Labeling scheme as directed by the SMU OIT Infrastructure Design Engineer. As recommended in ANSI/TIA/EIA 606. Permanent (i.e. not subject to fading), permanently affixed, typed, and created by a label maker or an approved equivalent software-based label making machine. Handwritten labels are not acceptable. PART 4 - EXECUTION 4.1 GENERAL A. The contractor is responsible for the safety of the public and workers in accordance with all applicable rules, regulations, building codes and city ordinances. B. All work shall comply with applicable safety rules and regulations including OSHA. All work shall comply with the requirements of the National Electrical Safety Code (NESC) and the NEC except where local codes and/or regulations are more stringent, in which case the local codes and/or regulations shall supersede. C. All work shall comply with the requirements, recommendations and best practices of the product manufacturers. D. Replace and/or repair to original (or better) condition any existing structures, materials, equipment, inadvertently demolished or damaged by the contractor during the course of the project at no additional cost to the Owner. E. Remove surplus material and trash from the job site and dispose of legally. 4.2 A. RACEWAY Outside Plant Innerduct (see section 3.2 - PATHWAYS AND RACEWAY for detailed specifications): 1. Provide sufficient innerduct slack in all pull boxes, hand holes and maintenance vaults to allow for innerduct shrinkage after stretching during installation. 2. Rack the innerduct securely inside maintenance holes and handholes. If existing maintenance holes and handholes have insufficient racking to support new cabling, provide racking. Last Revision: December 2021 Communications 11 of 85

4.3 A. 4.4 TERMINATION EQUIPMENT Copper Building Entrance Terminals: Provide BETs for the required 50 pair multi pair copper backbone. Install BETs per manufacturer’s instructions. 1. Connect each BET’s ground lug to the nearest TGB with a #6 AWG copper grounding conductor. GROUNDING AND BONDING A. All grounding and bonding shall comply with the ANSI/TIA/EIA-607 standard and NEC Article 250-96. B. Bond all metal telecommunications equipment to the closest TGB or the closest grounding conductor if in the OSP-SCS. C. Remove paint on hardware to ensure that bonding to a bare metallic surface. 4.5 A. CABLE A. Last Revision: December 2021 General (applicable to all cable types): 1. Once received, test fiber optic cable while still on the reel, and test again before installation. Do not install faulty fiber optic cables. Replace faulty cables at no additional cost to the owner. 1) Test shall conform to the procedures as stated in section 4.7 TESTING at the end of this section. 2. Install cables adhering to the ANSI/TIA/EIA requirements, BICSI practices, and the manufacturers recommendations. Adhere to the requirements outlined in the manufacturer’s recommendations and ANSI/TIA/EIA Standards pertaining to bending radius, pulling tension, other mechanical stresses, and pulling speed. 1) On runs of 300 feet or more, monitor pulling tension. Monitoring devices: a) Breakaway Link b) In-Line Tension Meter c) Tugger (Winch) with calibrated maximum tension 3. Cable splices are unacceptable unless instructed by the SMU Infrastructure Design Engineer. 4. New Duct Banks; Utilize the lowest conduits first and work up as installations progress. 5. Where applicable, utilize the same duct position when entering and exiting a maintenance hole or handhole. Do not change duct elevations when traversing a pull point to avoid cable damage. 6. Maintain enough cable slack in the tunnel systems, and each maintenance hole or hand hole to properly rack the cabling. 7. Use pulling compound or lubricant where applicable. 8. Provide a service loop in the BDF/MDF long enough to reach the furthest point in the room in the case of termination equipment relocation. A minimum of a 25-foot slack loop is required. (Placing the service loops near the tunnel entry to conserve cable rack space is acceptable.) 9. Cabling on the backboards: Communications 12 of 85

1) 10. 11. Route cabling as close as possible to the edges of the backboard or corners to maintain adequate usable mounting surface for terminal boxes and equipment. 2) Support cables so as not to put strain on the equipment upon which the cables are terminated. Cabling in the Telecommunications Rooms: 1) Dress cabling neatly on ladder rack in bundles of twelve cables each and loosely secure cable to the ladder rack with Velcro. Building Entrance Conduits: Seal all conduits that enter the building from the outside plant environment to prevent moisture, gases and rodents from entering the facility. B. Copper Cable: 1. Provide a 50 pair copper cable at minimum, pair count may exceed 50 pair in some cases, contact the SMU Infrastructure Design Engineer for details on the specific project. 1) New Construction: Each building is required to have a campus feeder with a minimum pair count of 50. An increased pair count may apply on an individual basis that will be determined by the projected requirements for the building. 2) Renovations/Remodels: Existing copper will be reused if possible. A new multi pair copper cable may be needed to bring the pair count up to 50 pair. An increased pair count may apply on an individual basis that will be determined by the projected requirements for the building. 2. Test copper cable on the reel upon delivery to the job site, prior to installation. Attach the test results to the reel. Do not install faulty cables. Replace faulty cables at no additional cost to the Owner. 3. Terminate all pairs within the multipair cable. Unterminated cable pairs are unacceptable. 4. Shielded cable, bond the shield a ground lug on both ends of the cable the bond to the Building Entrance Protector. 5. Copper splices are unacceptable except where specified by the SMU Infrastructure Design Engineer. 6. Lighting protection for copper- If copper cables extend beyond the buildings cone of protection, the OIT approved lightning protection must be installed to ensure proper performance/protection. Lightning protection must be UTP category 6, 4 pair POE capable. C. Fiber Cable: 1. Provide fiber optic cable in quantities, strand counts, and types (singlemode, multimode, or composite multimode/singlemode (hybrid)), as shown on the Contract Documents. 1) New Construction: Each main campus building is to be connected to the nearest MSH/ISH where a fusion splice will be required to connect the new fiber to the existing fiber which will complete the tie to Patterson Hall Data Center (MDF) and well as the University Data Center (5555 N. Central Expressway). Contractor shall install fiber containing a minimum of (6) strands of 62.5 (direct to Fire Panel)/125um multimode fiber and (48) strands of 8/125um Last Revi

1) ANSI/TIA/EIA - 455: Fiber Optic Test Standards 2) ANSI/TIA/EIA - 526: Optical Fiber Systems Test Procedures 3) ANSI/TIA/EIA - 568-B: Commercial Building Telecommunications Cabling Standard 4) ANSI/TIA/EIA - 569: Commercial Building Standard for Telecommunication Pathways and Spaces 5) ANSI/TIA/EIA - 606: The Administration Standard for the

Related Documents:

SMU Data Science Review Volume 3 Number 1 Article 4 2020 QLIME-A Quadratic Local Interpretable Model-Agnostic Explanation Approach Steven Bramhall Southern Methodist University, sbramhall@smu.edu Hayley Horn hhorn@smu.edu Michael Tieu mtieu@smu.edu Nibhrat Lohia Southern Methodist University, nlohia@smu.edu

SMU Data Science Review Volume 3 Number 1 Article 5 2020 Demand Forecasting for Alcoholic Beverage Distribution Lei Jiang Southern Methodist University, leij@smu.edu Kristen M. Rollins Southern Methodist University, kmrollins@smu.edu Meredith Ludlow Southern Methodist University, mludlow@smu.edu Bivin Sadler

Cox School of Business Southern Methodist University PO Box 750333 Dallas, TX 75275-0333 Email: communications@cox.smu.edu Website: cox.smu.edu Communications Office: 214.768.4474 Fax: 214.768.3267 President: Paul Buckley Director of Client Services: Cory Davies Account Supervisor: Ashley Carlisle

level with SMU instruments. 2450 icon-based menu. Fourth-Generation, All-in-One SMU Instrument The 2450 is the fourth-generation member of Keithley’s award-winning SourceMeter family of SMU instruments

The Storage Management Utility (SMU) is a web-based application for configuring, monitoring, and managing the storage system. The SMU is a web-based interface (WBI). Each controller module in the storage syst em contains a web server, which is access ed when you sign in to the SMU. You about using the CLI, see the CLI Reference Guide. content.

SMU FACTS 2013-2014 A nationally ranked private university with seven degree-granting schools, SMU is a distinguished center for teaching and research located near the heart of Dallas. SMU's 11,000 students benefit from small classes, leadership opportunities, international study and innovative programs.

SMU PHYSICS 1303: Introduction to Mechanics Stephen Sekula1 1Southern Methodist University Dallas, TX, USA SPRING, 2019 S. Sekula (SMU) SMU — PHYS 1303 SPRING, 2019 1

SMU Data Science Review Volume 1 Number 4 Article 7 2018 Comparative Study of Sentiment Analysis with Product Reviews Using Machine Learning and Lexicon-Based Approaches Heidi Nguyen Southern Methodist University, hqnguyen@smu.edu Aravind Veluchamy Southern Methodist University, aveluchamy@mail.smu.edu Mamadou Diop