Energi Savr Node For 0–10 V With Softswitch SPEC (369241)

2y ago
32 Views
2 Downloads
2.27 MB
15 Pages
Last View : 18d ago
Last Download : 3m ago
Upload by : Brady Himes
Transcription

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 1 11.30.20Energi Savr Node for 0–10 VEnergi Savr Node with SoftswitchThe Energi Savr Node (ESN) family is a group of modularproducts for the control of lighting and other loads. Thisdocument describes the following products: ESN unit for 0 –10 V- (models QSN-4T16-S —0 –10 V- Control / Softswitch) Softswitch ESN unit (models QSN-4S16-S — Softswitch) FeaturesDefault configuration requires no commissioning.Programming using integral interface on the ESN unit.Four occupancy sensor inputs for automated control oflights in 4 zones.Four daylight sensor inputs automatically adjust lightlevels based on the amount of natural light enteringthrough the windows.Four IR receiver inputs for personal control.Four inputs for IEC PELV / NEC Class 2 dry contactswitches.Includes QS control link for seamless integration of lights,control stations, and QS sensor modules.Softswitch technology yields 1,000,000 cycle relaylifetime.Contact Lutron for compatibility with Quantum system.System ExampleWiredDaylightSensors(up to 4)1,2Load Input Feeds (4)120–277 V WiredOccupancySensors(up to 4)1Switched Load Outputs (4)16 A Softswitch 120–277 V Control Power120–277 V OR0–10 V Channels (4)QSN-4T16-SWirelessCommunicationQS linkWired DaylightSensors (up to 4)2seeTouch QSWallstationESNProgrammingInterface Job Name:Job Number:IR TransmitterRadio Powr SavrOccupancySensor (up to 10per QSM)Pico WirelessController(up to 10 perQSM)Radio Powr SavrDaylight Sensor(up to 10 per QSM)2Wired Wallstationor IR receivers (up to 4)ContactClosureInputORQSMWired OccupancySensors (up to 4)EmergencyContactClosureInputWiredWallstationor IR Receivers(up to 4)1ORIEC PELV /NECR Class 2Dry ContactSwitch (up to 4)(by others)S P E C I F I C AT I O N S U B M I T TA LModel Numbers:ORIR TransmitterNotes:1 Up to 4 wired sensors total (of any type).2 The maximum number of daylight sensors (wired andwireless) that an ESN unit can support isfour (1 per zone).Page1

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 2 11.30.20SpecificationsRegulatory Approvals UL Listed CSA NOM Lutron Quality Systems registered to ISO 9001:2015 Complies with requirements for use in other spacesused for environmental air (plenums) perNEC 2014 300.22(C)(3) Meets the Canadian National Building Code plenumrequirements for a concealed space used as a plenumwithin a floor or roof assembly For commercial use, Class A only PowerControl Power: 120 V ; 220–240 V ; 277 V 50 / 60 HzLightning strike protection meets ANSI / IEEE standard62.41-1991. Can withstand voltage surges of up to6,000 V and current surges of up to 3,000 ACurrent draw: 0.5 A max10-year power failure memory: restores lighting to levelsprior to power interruptionLatching relays keep previously illuminated zones onwhen control power feed is lostEnvironmentAmbient Temperature Operating Range: 32 ºF to 104 ºF(0 ºC to 40 ºC)Relative humidity: less than 90% non-condensingFor indoor use onlyThermal dissipation: 40 BTU/hrTerminal Wiring Control Power Wiring: 14 AWG to 12 AWG (2.5 mm2 to4.0 mm2) Load Wiring: 14 AWG to 12 AWG (2.5 mm2 to 4.0 mm2) 0–10 V- Wiring: 20 AWG to 12 AWG (0.5 mm2 to 4.0 mm2) Input Group Wiring: 20 AWG to 12 AWG (0.5 mm2 to4.0 mm2) — maximum wire run length to each input notto exceed 150 ft (46 m) QS Link Wiring: 22 AWG to 12 AWG (0.5 mm2 to4.0 mm2) Contact Closure Wiring: 20 AWG to 12 AWG (0.5 mm2to 4.0 mm2) Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Physical Design and Mounting NEMA Type 1, IP-20 protection Surface mount Load Types (relay ratings)16 A Tungsten, 120 to 277 V 16 A AC General Use, 120 to 277 V 16 A Electric Discharge Lamp (ballast),120 to 277 V 16 A Inductive, 120 to 277 V 0.5 HP, 120 V 1.5 HP, 220 to 277 V Works with all ballasts and drivers that provide a currentsource that is compliant to IEC 60629Annex E.2, and whose inrush current does not exceedNEMA410 standards for electronic ballast/driverInput Default AssociationsGroup 1Group 2Group 3Group 4Inputs/OutputsZone ccPhotoIRSwitchCCIEmergency CCIXXXXZone 2Zone 3Zone 4XXXXXXXXXXXXXXXXXXXXSoftswitch: 120 V to 277 V Softswitch relay is rated for 16 A continuous use perchannel, which is the maximum continuous load for a20 A Overcurrent Protection Device (Branch Breaker). Patented Softswitch circuit eliminates arcing atmechanical contacts when loads are switched.Extends relay life to an average of 1,000,000 cycles(on / off) for resistive, capacitive, or inductive sources. Relay is mechanically held.Page2

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 3 11.30.20Specifications (continued)0–10 V- Product Ratings(QSN-4T16-S) Each output sinks up to 50 mA maximum. Each output sinks current only (load device mustprovide 10 V- supply). Provides an IEC PELV / NEC Class 2 isolated 0–10 Voutput signal that conforms to IEC 60929. Occupancy sensor must provide a dry contactclosure or solid-state output. Additional occupancy sensors can be used with theESN device. Refer to the “Programming Options andFeatures” table for system rules.seeTouch QS Controls seeTouch QS wallstations can be configured tocontrol ESN unit scenes or zones.Occupancy Sensors In zone toggle mode, zone buttons can be assigned to oneor more zones on any ESN unit connected to the QS Link.Up to 16 occupancy sensors can be programmed to In scene mode, wallstations can be assigned to onethe ESN device.or more ESN units connected to the QS Link.Manual Programming: up to 4 occupancy sensors wired LED indicator displays zone or scene status.directly to the ESN device, up to 4 occupancy sensorsTable 1: seeTouch QS Wallstation Configurationswired to a QS Sensor Module (QSM), and up to 10wireless occupancy sensors through the same QSM; the# Buttonstotal programmed to the ESN device cannot exceed 16.Wallstation Function 12357HHD (iPod / iPhone) Programming: up to 16 occupancyZone Toggle sensors from any source (wired directly to the ESNScene1, Off1, Off 1, 2 1-4, N/A(toggle)OffOffdevice, wired to any other ESN device, or wired / wirelessfrom any QSM on the QS link); the total programmed toIR Wallstation or Receiver Inputthe ESN device cannot exceed 16. Four inputs for IR receivers or wallstations for control ofUse Lutron occupancy sensors to control one or morelighting zones can be connected directly to the ESN unit.zones. UseLutron CC-4BRL-WH wallstations to control oneUse Lutron occupancy sensors in vacancy modeor more zones.to automatically turn the lights off in an area after it UseLutron EC-DIR-WH ceiling-mount sensors tobecomes vacant.control one or more zones.Each zone can be programmed to automatically turn Upto four additional wired wallstations or IR receiversthe lights on when occupied and turn the lights off whencan be assigned when associated with a QSM.vacant. Associateadditional QSMs and sensors/controlsEach wired occupancy input can power one Lutronwith ESN unit when programming with an Apple iPodoccupancy sensor.touch or iPhone. Refer to "Programming Options"Each occupied scene and unoccupied scene can besection for details.programmed independently.Lutron occupancy sensors can be programmed toautomatically turn the lights on in area when it becomesoccupied and turn the lights off in an area after itbecomes vacant.Each of the four occupancy inputs can power one Lutronoccupant sensor.Each area’s occupied scene and unoccupied scene canbe programmed independently. Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page3

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 4 11.30.20Specifications (continued)Daylight Sensors Lutron daylight sensors allow daylight harvesting withprogrammable effect on light output. Four daylight sensors can be connected directly to theESN unit. Use Lutron EC-DIR-WH sensors to control one or morezones. Alternatively, up to four sensors (Lutron Wired DaylightSensors or Radio Powr Savr Daylight Sensors) can beassigned when associated with a QSM. The maximum number of Lutron daylight sensors (wiredor wireless), either wired directly to the unit or indirectly(associated with a QSM) cannot exceed four. Associate additional QSMs and sensors/controls withESN unit when programming with an Apple iPod touchor iPhone. Refer to "Programming Options" section fordetails. Emergency Contact Closure Input By default, contact closure input from LutronEmergency Lighting Interface (LUT-ELI-3PH), security,or fire alarm systems turns all zones on to full outputwhen emergency state is detected. Emergency contact closure input is normally closed(NC). The ESN unit is shipped with a jumper preinstalled. Response of each zone is configurable. Attached devices, by default, will go to maximumoutput and ignore control inputs. No operations will be allowed until emergency signalis cleared. The attached device must provide a dry contactclosure or solid-state output. Input is miswire-protected up to 36 V-. Emergency CCI cannot control other ESN units.Contact Closure Input (CCI)Functionality with GRAFIK Eye QSDefault behavior: ESN unit follows GRAFIK Eye QS scene activationsActivate scenes using momentary or maintained closures when associated with the GRAFIK Eye QS.from an external device such as a timeclock. ESN unit responds to commands initiated by theStart or stop Afterhours Mode using a maintainedGRAFIK Eye QS astronomic time clock whenclosure.associated with the GRAFIK Eye QS.The attached device must provide a dry contact closure ESN unit operates in afterhours mode whenor solid-state output.associated with a GRAFIK Eye QS that is in afterhoursConfigurable for Normally-Open (NO) or Normally-Closed mode.(NC) operation.Functionality with QSE-IOInput is miswire-protected up to 36 V-. ESN unit responds to scene commands initiated bythe QSE-IO, if the QSE-IO DIP switches have been setto either scene selection mode, zone toggle mode,partition mode, or occupancy sensor mode.Functionality with QSE-CI-NWK-E Integrate ESN unit with touchscreens, PCs, A / Vsystems, or other digital systems and devices. Recall scenes and set/adjust zone levels. Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page4

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 5 11.30.20Specifications (continued)IEC PELV / NEC Class 2 Dry Contact SwitchesQSM (QS Sensor Module) Four inputs for IEC PELV / NEC Class 2 dry contactswitches can be assigned to turn on and off one ormore zones. Configure for momentary or maintained operation. Use the QSM to integrate Radio Powr SavrOccupancy sensors, Radio Powr Savr Daylightsensors, and Pico Wireless Controllers to controlzones on the ESN unit. Associate1 QSM per ESN unit with manualQS Link Limitsprogramming.Each ESN unit can provide up to 14 Power Draw Units Associate multiple QSMs per ESN unit with Apple(PDUs) for other QS devices. Refer to the QS LinkiPod touch or iPhone programming (requiresPower Draw Unit specification submittal (LutronQSE-CI-AP-D and Wi-Fi router). See "ProgrammingP/N 369405) for more information concerning PDUs.Options" for details.The QS Link can have up to 100 devices and 100 zones. Assign up to 10 Radio Powr Savr Occupancy sensorsEach ESN unit counts as 1 device towards theper ESN unit via QSM.100 device limit. Assign up to 4 Radio Powr Savr Daylight sensors perEach ESN unit counts as 4 zones towards theESN unit via QSM.100 zone limit. Assign up to 10 Pico Wireless Controllers per ESNunit via QSM. The sensors and Pico Wireless Controllers associatedwith the QSM should be mounted within 60 ft (18 m)line of sight, or 30 ft (9 m) through walls, of the QSM. Wire and power up to 4 wired sensors per QSM– Daylight Sensors– Occupancy Sensors– Infrared (IR) Receivers or Wallstations Refer to QSM Specification Submittal for moreinformation. Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page5

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 6 11.30.20Programming OptionsManual Programming: Use buttons on the front of the ESN unit. Use manual programming in installations with only one ESN unit and with one QSM or fewer on the QS link. HHD ProgrammingRequires ESN Programming Interface (QSE-CI-AP-D).Requires Apple iPod touch or iPhone mobile digital device.Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multipleESN units and QSMs in the QS link.Wireless router only required for programming with an Apple iPod touch or iPhone.ESN UnitESN UnitESN UnitQSMQSMQSMDedicated EthernetConnection for ESNunits1,2AppleiPod touch oriPhone mobiledigital deviceWirelessRouter(by others)QS LinkQS LinkESN ProgrammingInterfaceQSE-CI-AP-D1 Standard CAT5/CAT5E cable: Total length not to exceed 300 ft (100 m)2 Note: ESN units are not designed to exist on an open network.Connection to an open network could result in reduced performance andEthernet connectivity issues. Wireless router may be removed for normal operation. Ethernet connection may be made via an ESN Programming Interface (QSE-CI-AP-D) or an ESN QS unit withintegral Ethernet jack. Lutron recommends that an ESN Programming Interface (or ESN QS unit with Ethernet jack) be wired to anEthernet jack in the space for ease of access and proximity to power for the wireless router. Works with any standard wireless router that supports multicast packets. Apple iPod touch or iPhone can program all ESN QS units connected to an ESN Programming Interface via the QSLink (except when part of a Quantum system). ESN app is required and is available from the Apple App Store Store online marketplace. Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page6

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 7 11.30.20Programming Options and FeaturesHHD Programming:Manual ProgrammingNot more than 1ESN units connected to 1 QSLinkQSMs connected to 1 QS link Not more than 1Wired Occupancy SensorsSystem Limits4 connected directly to ESN unitUp to 4 wired to QSMCan be assigned to Any zone(s) on the ESN unitOccupancy DependencySupportedNoWireless Occupancy SensorsSystem LimitsAssociate 10 occupancy sensors to QSMto control zones on the ESN unitCan be assigned to Any zone(s) on the ESN unitOccupancy DependencySupportedNoWired Daylight SensorsSystem LimitsMaximum of 1 daylight sensor per zone4 connect directly to the ESN unitAdditional daylight sensors can connect tothe QSMCan be assigned to Any zone(s) on the ESN unitDisable daylighting in ScenesNoWireless Daylight SensorsSystem LimitsMaximum of 1 daylight sensor per zoneAssociate wireless daylight sensors to theQSMCan be assigned to Any zone(s) on the ESN unitDisable daylighting in ScenesNo Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers: Requires ESN Programming InterfaceQSE-CI-AP-D Requires Apple iPod touch or iPhone mobiledigital deviceMultiple—100 QS devices and 100 zone limits applyMultiple—100 QS devices limit appliesUp to 100 total occupancy sensors per QS link(wired wireless)Zones on ESN unit or share to other ESN units on sameQS linkYesUp to 100 total occupancy sensors per QS link(wired wireless)Zones on ESN unit or share to other ESN units on sameQS linkYesMaximum of 2 daylight sensors per zoneUp to 100 total daylight sensors per QS link(wired wireless)Zones on ESN unit or share to other ESN units on sameQS linkYesMaximum of 2 daylight sensors per zoneAssociate up to 10 wireless daylight sensors per QSMUp to 100 total daylight sensors per QS link(wired wireless)Zones on ESN unit or share to other ESN units on sameQS linkYesPage7

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 8 11.30.20Programming Options and Features (continued)HHD Programming:Manual ProgrammingPico Wireless ControllersSystem LimitsAssociate 10 Pico wireless controllers toQSM to control zones on the ESN unitCan be assigned to Any zone on the local ESN unitIR Receivers and WallstationsSystem Limits4 connect directly to the ESN unitUp to 4 wired to the QSMCan be assigned to Any zone on the local ESN unit Requires ESN Programming InterfaceQSE-CI-AP-D Requires Apple iPod touch or iPhone mobiledigital deviceUp to 100 total controls per QS link (wired wallstations,Pico wireless controllers, IR receivers)Zones on ESN unit or share to other ESN units onsame QS linkUp to 100 total controls per QS link (wired wallstations,Pico wireless controllers, IR receivers)Zones on ESN unit or share to other ESN units onsame QS linkNEC dry contact Switches InputsCan be assigned to Any zone(s) on the connected ESNAny zone(s) on the connected ESNContact Closure InputCan be assigned to Any zone(s) on the ESN unitAny or all local ESN unit zonesFunctions Sweep to off Enable/disable afterhours Turn on to preset and turn off Sweep to off Enable/disable afterhours Turn on to preset and turn offAfterhours Configurationafterhours timeout – 15 minutesblink-warn timeout – 5 minutesAfterhours timeout and blink-warntimeouts are configurableEmergency Contact Closure InputCan be assigned to Any zone(s) on the ESN unitEmergency Light levelConfigurable Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Any or all local ESN zonesConfigurablePage8

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 9 11.30.20Programming Options and Features (continued)HHD Programming:Manual ProgrammingseeTouch QS wallstationsScene Keypads assigned to Any zone(s) on the ESN unitScene off keypads assigned Any zone(s) on the ESN unitto Zone toggle keypad buttonsAny zone(s) on the ESN unitassigned to Change Keypad to Scene orYesZoneChanging keypads to shade,Nopanic, fine tune Requires ESN Programming InterfaceQSE-CI-AP-D Requires Apple iPod touch or iPhone mobiledigital deviceAny zone(s) on one or more ESN units on the QS linkAny zone(s) on one or more ESN units on the QS linkAny zone(s) on on or more ESN units on the linkYesYesZone Configuration ParametersLoad type0-10, 10-0, or switchedHigh-end trimAdjustableLow-end trimAdjustableAbsolute minimum levelAdjustable0-10, 10-0, or ble scenesScenes 1-16Scenes 1-16GRAFIK Eye QSN/AShare scenes, timeclock events, or afterhours eventsto ESN units on QS LinkQSE-IOScene, zone toggle, occupancyScene, zone toggle, occupancyQSE-CI-NWK-EYesYes Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page9

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 10 11.30.20Mechanical DimensionsAll dimensions shown as in .50(190.50)0.88(22.23)3.14(79.71)1.00(25.40)Do notuse sideknockoutsLine Voltage Shield11.25(285.75)13.25(336.55)0.20 (5.16)diameter Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page10

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 11 11.30.20Wiring: QS LinkOnly terminals 1, 3, and 4 connectedbetween devices that supply PDUsCOMAll 4 terminals connected to QS linkdevices that consume PDUsCOM 24 VMUXMUXMUXMUXTerminal 2 NEVER connectedbetween devices that supply PDUsDevices thatsupply PDUsDevices thatconsume PDUsQS Link;all 4 terminalsQS Link;no terminal 2Terminal 2 ( 24 V)NEVER connected*ESN QS unitTerminal 2 ( 24 V)NEVER QSKeypadQSInput/OutputInterfaceWiredQSKeypadQS Link;all 4 terminalsQS Link;no terminal 2Terminal 2 ( 24 V)NEVER connected*QSInput/OutputInterfaceESN QS unitQSLinkpowersupply**QS Link;all 4 terminalsQS Link Wiring Rules* Terminal 2 ( 24 V) should NEVER be connected between devices that supply PDUs.** For QS Link power supply wiring connection details, refer to the installation instructionsfor the specific power supply model being used. Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page11

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 12 11.30.20Wiring: IEC PELV / NECR Class 2 InputsNOTE: There are four input groups. Each group has thesame inputs as shown in the diagram below.20VCom – CommonSwitch – IEC PELV / NEC Class 2IR – IR Receiver*Daylight – Daylight SensorCOMGroup 2 shownIRGroup 1 BlackIRTransmitterRedNote: Maximum wirerun length to eachinput not to exceed150 ft (46 m).YellowOcc – Occupancy Sensor20 V – 20 V-LUTRONInput Group Wiring: 20 AWG to 12 AWG(0.5 mm2 to 4.0 mm2) Strip length: 1/4 in (6 mm) Torque: 5 in lb (0.5 N m) Job Name:Job Number:Daylight/ Occupancy IEC PELV / NEC IR ReceiverIR Sensor*SensorClass 2or WiredDry ContactWallstation*Switch* Note: Only one IR device may be connected per input. Ifthe IR signal from a daylight sensor is connected, a wallcontrol may not be connected to the same input, andvice-versa.** Connect the gray wire on -R model occupancy sensors.S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page12

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 13 11.30.20Wiring: Contact Closure Inputs (CCI and Emerg)CCI – Contact Closure InputCom – CommonCom – CommonEmerg – EmergencyContact Closure Wiring: 20 AWG to 12 AWG(0.5 mm2 to 4.0 mm2) Strip length: 1/4 in (6 mm) Torque: 5 in lb (0.5 N m) Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers:Page13

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 14 11.30.20Wiring Diagram: Example A – 4 circuits, multiple eutralLOADNeutralLOADNeutral WiresHotNeutralZone Switching:120–277 V Switched Hot (4B)Hot Feed (4A)Switched Hot (3B)Hot Feed (3A)Switched Hot (2B)Hot Feed (2A)Switched Hot (1B)GroundLugHot Feed (1A)GroundDistributionPanelLoad Wiring: Two (2) 14 AWG to12 AWG (2.5 mm2to 4.0 mm2) Strip length: 3/8 in(8.5 mm) Torque: 7 in-lb(0.79 N m)0–10 V- Wiring(QSN-4T16-S)0–10 V- Zones:(QSN-4T16-S)0-10 V- Wiring (QSN-4T16-S)20 AWG to 12 AWG (0.5 mm2 to 4.0 mm2)Strip length: 1/4 in (6 mm)Torque: 5 in-lb (0.5 N m)0-10 V- control wires for zones 1-4 can be installedusing NECR Class 1 or Class 2 wiring methods. 0-10 V- zones 1-4 are not isolated from each other. Negative (–) terminals are not internally connectedto each other - both positive ( ) and negative (–)connections must be made. Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers: Follow all national and local codes for separationrequirements. If any pair of 0-10 V- control wires are installedusing NECR Class 1 wiring methods, then thesewires must be physically separated from allother Class 2 wiring in the Energi Savr Node inaccordance with NECR guidance on separation ofClass 1 and 2 wires. If one pair of 0-10 V- control wires are wired usingNECR Class 1 wiring methods, then all pairs of0-10 V- control wires must be installed using NECRClass 1 wiring methods.Page14

Energi Savr NodeQSN0–10 V-/Softswitch Fixture Controllers369241n 15 11.30.20Wiring Diagram: Example B – 4 circuits, single feedDistributionPanel AHotNeutralGroundLOADLOADLOADNeutral WiresDistributionPanel BGroundLug“A” Terminals JumperedHotNeutralGroundZone Switching:120-277 V Switched Hot (4B)Switched Hot (3B)Switched Hot (2B)Hot Feed (1A)Switched Hot (1B)LOADLoad Wiring: Two (2) 14 AWG to12 AWG (2.5 mm2to 4.0 mm2) Strip length: 3/8 in(8.5 mm) Torque: 7 in-lb(0.79 N m)0-10 V- Wiring(QSN-4T16-S)0-10 V- Zones:(QSN-4T16-S) )Lutron, Lutron, Softswitch, seeTouch, Pico,Quantum, Energi Savr Node, Radio Powr Savr, andGRAFIK Eye are trademarks or registered trademarksof Lutron Electronics Co., Inc. in the US and/or othercountries.Apple, iPhone, and iPod touch are trademarks of AppleInc., registered in the U.S. and other countries.App Store is a service mark of Apple, Inc Job Name:Job Number:S P E C I F I C AT I O N S U B M I T TA LModel Numbers: 0-10 V Wiring (QSN-4T16-S)20 AWG to 12 AWG (0.5 mm2 to 4.0 mm2)Strip length: 1/4 in (6 mm)Torque: 5 in-lb (0.5 N m)Connect only IEC PELV / NEC Class 2 circuits orconnect only non-IEC PELV / NEC Class 2 circuits to0-10 V- zones 1-4.0-10 V- zones 1-4 are not isolated from each other.Negative (–) terminals are not internally connectedto each other - both positive ( ) and negative (–)connections must be made.Follow all national and local codes for separationrequirements.Page15

Energi Savr Node QSN 0–10fiV-/Softswitch Fixture Controllers Energi Savr Node for 0–10 V-369241n 1 11.30.20 Energi Savr Node with Softswitch The Energi Savr Node (ESN) family is a group of modular products for the control of lighting and oth

Related Documents:

Energi Savr Node QSN-4A5-S PRO LED Phase Adaptive Fixture Controller 3691137b 1 05.04.20 Energi Savr Node PRO LED Phase Adaptive The Energi Savr Node (ESN) family is a group of modular products for the control of lighting and other loads. This document describes the following product: QSN-4A5

GRAFIK Eye QS. 75 Energi Savr Node QS / DALI. 79 Energi Savr Node QS / Int'l 0-10V. 83 Energi Savr Node QS / EcoSyste. m 87 Energi Savr Node QS / 0-10V. 91 seeTouch Keypad. s 95 seeTouch QS International Keypads. 98 Sivoia QS Shades 101 . Programming Control Interface (SZ-CI-PRG). For a l

Energi Savr Node with Softswitch The Energi Savr Node (ESN) family is a group of modular products for the control of lighting, receptacles, and other loads. . Wired Wallstation or IR receivers (up to 4) IEC PELV/NEC Class 2 Dry-Contact Switch (up to 4) (by others) seeTouch QS W

The Energi Savr Node with Softswitch module can be used to switch third-party ballasts and other non-dim loads, as well as connect wired and wireless occupancy/vacancy sensors, daylight sensors, and wallstations to manage light in a variety of spaces. Ideal for retrofits and new construction, each Energi Savr Node with Softswitch

Diktat Mesin Konversi Energi ini memaparkan teori dasar konversi energi. Pada bab awal dipaparkan sumber-sumber energi yang mendasari teori mesin konversi energi. Fokus pembahasan di dalam buku ajar MKE ini adalah mesin mesin yang mengkonversi sumber-sumber energi yang tersedia di alam untuk menghasilkan energi yang dapat dimanfaatkan.

Menjelaskan Proses-Proses Mesin Konversi Energi Page 2 Gambar 1.1. Bentuk Energi Mekanik pada sebuah Mobil Balap 2. Energi potensial adalah energi yang tersimpan pada benda karena kedudukannya. Sebagai contoh, energi potensial air adalah energi yang dimiliki air karena ketinggiannya dari permukaan.

Semua energi yang dapat di perbaharui dan bahkan energi pada bahan bakar fosil, kecuali energi pasang surut dan panas bumi berasal dari matahari. Matahari meradiasi 1,74 x 1017 Kilowatt jam energi ke bumi setiap jam. Dengan kata lain, bumi ini menerima daya 1,74 x 1017 watt. Sekitar 1-2% dari energi tersebut diubah menjadi energi angin.

Kirsty Harris (Anglia Ruskin University) Now and in Ireland. Chair: Beatrice Turner (Newcastle University) Exile, Emigration and Reintegration: The journeys of three United Irish poets . Jennifer Orr (Trinity College Dublin) Cross-cultural borrowings and colonial tensions in the elegies on the death of Robert . Emmet . Alison Morgan (University of Salford) Anacreontic Imports: Thomas Moore and .