Quick Start Guide00825-0400-2654, Rev DBMay 2021Rosemount 214C Sensor

Quick Start GuideMay 2021ContentsAbout this guide.3Wiring diagram for RTDs. 5Wiring diagram for thermocouples. 6Additional RTD specifications. 7Additional thermocouple specifications. 9Product certifications. 10Declaration of Conformity.23China RoHS. 252Emerson.com/Rosemount

May 20211Quick Start GuideAbout this guideThis guide provides basic guidelines for Rosemount 214C Sensor models. Ifthe sensor was ordered assembled to a temperature thermowell ortransmitter, see the appropriate product literature for information onconfiguration and hazardous locations certifications.1.1Safety messagesNOTICEComplications can arise when the sensors and the transmitters to which theyare assembled are certified to compatible, but each has different approvals.Be aware of the following situations: If an I.S. approved Rosemount 214C Sensor is ordered with a housing, atransmitter enclosed in that housing may have a different I.S. approvalrating. Refer to the transmitter IS certificate if applicable. If a sensor and transmitter have different certifications, or if either hasmore certifications than the other, installation must comply with themost restrictive requirements required by either component. This isespecially (but not exclusively) relevant when combination approvals areordered on either the sensor or transmitter. Review certifications onboth the sensor and transmitter for installation requirements and ensureinstallation of the sensor/transmitter assembly complies with a singlecertification that is shared by both of these components and that meetsthe requirements of the application.WARNINGExplosionExplosions could result in death or serious injury.Installation of sensor in an explosive environment must be in accordancewith appropriate local, national, and international standards, codes, andpractices.Quick Start Guide3

Quick Start GuideMay 2021WARNINGConduit/cable entriesUnless marked, the conduit/cable entries in the housing use a ½–14 NPTthread form. Entries marked “M20” are M20 1.5 thread form. Ondevices with multiple conduit entries, all entries will have the samethread form. Only use plugs, adapters, glands, or conduit with acompatible thread form when closing these entries.When installing in a hazardous location, use only appropriately listed orEx certified plugs, glands, or adapters in cable/conduit entries.Only use plugs, adapters, glands, or conduit with a compatible threadform when closing these entries.Physical accessUnauthorized personnel may potentially cause significant damage to and/ormisconfiguration of end users’ equipment. This could be intentional orunintentional and needs to be protected against.Physical security is an important part of any security program andfundamental to protecting your system. Restrict physical access byunauthorized personnel to protect end users’ assets. This is true for allsystems used within the facility.CAUTIONRefer to Product Certification section of this Quick Start Guidedocumentation.4Emerson.com/Rosemount

May 20212Quick Start GuideWiring diagram for RTDsFigure 2-1: RTD Lead Wire Configuration per IEC 60751 - Single To configure a single element, 4-wire RTD as a 3-wire system, connect onlyone white lead. Insulate or terminate the unused white lead in a manner thatprevents shorting to the ground. To configure a single element, 4-wire RTDas a 2-wire system, connect matching colored wires first and then connectthe paired wires to the terminal.Figure 2-2: RTD Lead Wire Configuration per IEC 60751 - Dual Element3-wireBlackBlackYellowRedRedWhiteQuick Start Guide5

Quick Start Guide3May 2021Wiring diagram for thermocouplesFigure 3-1: Thermocouple Lead Wire ConfigurationSingle thermocouple, 2-wireDual thermocouple, 4-wire(–)(–)( )( )(–)( )Table 3-1: Thermocouple Wire ColorIEC 60584 ThemocoupleTypeASTM E230 ThermocouplePOS ( )NEG (-)POS ( )NEG iteBlueRedNoteDual thermocouple sensors are shipped with one pair of the wires shrinkwrapped together.6Emerson.com/Rosemount

May 20214Quick Start GuideAdditional RTD specificationsNoteAll specifications in this section apply to all RTDs unless noted otherwise. AllRTDs meet and/or exceed type and routine tests for sensors/thermometersper IEC 60751:2008.4.1Insulation resistance1000 MΩ minimum insulation resistance when measured at 500 VDC atroom temperature.4.2Insulation resistance at elevated temperatureInsulation resistance at elevated temperatures for sensor types RT, RH, andRW are tested and meet requirements according to IEC 60751:2008 6.5.1.4.3Time responseSensor response time tested in flowing water according to IEC 60751:20086.5.2.Sensor type RT: T50 average 8.5 seconds; T90 average 22.9 secondsSensor type RH: T50 average 9.15 seconds; T90 average 24.1 secondsSensor type RW: T50 average 9.0 seconds; T90 average 24.4 seconds4.4StabilityStability at upper temperature limit tested and meets requirementsaccording to IEC 60751:2008 6.5.3.4.5Effects of temperature cyclingEffect of temperature cycling tested and meets requirements according toIEC 60751:2008 6.5.5.4.6HysteresisEffect of hysteresis tested and meets requirements according to IEC60751:2008 6.5.6.4.7Self heatingSelf-heating tested and meets requirements according to IEC 60751:20086.5.7.Quick Start Guide7

Quick Start Guide4.8May 2021Process immersionMinimum immersion depth tested according to IEC 60751:2008 6.5.8.Sensor type RT, single: Minimum immersion depth 30 mmSensor type RT, dual: Minimum immersion depth 45 mmSensor type RH, single and dual: Minimum immersion depth 40 mmSensor type RW, single and dual: Minimum immersion depth 50 mm4.9Vibration limitsVibration tested according to IEC 60751:2008 6.6.4.Sensor type RT ordered with VR1: Meets 10 g vibration between 20 and 500Hz for 150 hours.Sensor type RT and RH: Meets 3 g vibration between 20 and 500 Hz for 150hours.Sensor type RW: Meets 1 g vibration between 20 and 500 Hz for 150 hours.4.108Functional specificationsPowerOvervoltage Category IEnvironmentalPollution Degree 4Emerson.com/Rosemount

May 20215Quick Start GuideAdditional thermocouple specificationsNoteAll specifications in this section apply to all thermocouple types unless notedotherwise. All thermocouples meet and/or exceed type and routine tests forsensors/thermometers per IEC 61515:2016.5.1Insulation resistance1000 MΩ minimum insulation resistance when measured at 500 VDC atroom temperature.5.2Time responseSensor response time tested in flowing water according to IEC 61515:20165.3.2.8.Grounded: T50 average 1.9 seconds; T90 average 4.0 secondsUngrounded: T50 average 2.8 seconds; T90 average 7.3 seconds5.3Process immersionMinimum immersion depth tested according to IEC 60751:2008 6.5.8.Grounded thermocouples: Minimum immersion depth 5 mmUngrounded thermocouples: Minimum immersion depth 10 mm5.4ContinuityElectrical continuity and polarity are tested and meet requirementsaccording to IEC 61515:2016 5.3.2.5.5Functional specificationsPowerOvervoltage Category IEnvironmentalPollution Degree 4Quick Start Guide9

Quick Start Guide6May 2021Product certificationsRev 2.7European Directive informationA copy of the EU Declaration of Conformity can be found at the end of theQuick Start Guide. The most recent revision of the EU Declaration ofConformity can be found at Emerson.com/Rosemount.Ordinary Location CertificationThe Rosemount 214C has been examined and tested to determine that thedesign meets the basic electrical, mechanical, and fire protectionrequirements by a nationally recognized test laboratory (NRTL) as accreditedby the Federal Occupational Safety and Health Administration (OSHA).NoteThe terminal strip in the Aluminum with Terminal Strip (AT1 or AT3)connection head requires sensor lead wires to have a wire termination (Ex:Bootlace ferrule or spade lug).North AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code(CEC) permit the use of Division marked equipment in Zones and Zonemarked equipment in Divisions. The markings must be suitable for the areaclassification, gas, and temperature class. This information is clearly definedin the respective codes.6.1North America6.1.1E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate 70044744Standards FM 3600:2011, FM 3615:2006, UL 50E:2007, UL61010-1:2010, ANSI/ISA 60529:2004MarkingsXP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6(-50 C Ta 80 C), T5 (-50 C Ta 95 C); Seal notrequired; installed per Rosemount drawing 00214-1030; Type4X† and IP 66/67; Vmax 35 VDC, 750 mWmaxSpecial Conditions for Safe Use (X):1. Flameproof joints are not intended for repair.2. Cable entries must be used which maintain the ingress protection ofthe enclosure. Unused cable entries must be filled with suitableblanking plugs.10Emerson.com/Rosemount

May 20216.1.2Quick Start GuideN5 USA Division 2 (NI)Certificate 70044744Standards FM 3600:2011, FM 3611:2004, UL 50E:2007, UL61010-1:2010, ANSI/ISA 60529:2004Markings6.1.3NI CL I, DIV 2, GP A, B, C, D; T6 (-50 C Ta 80 C), T5 (-50 C Ta 95 C); installed per Rosemount drawing 00214-1030;Type 4X† and IP 66/67; Vmax 35 VDC, 750 mWmaxE6 Canada Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate 70044744Standards CAN/CSA C22.2 No. 0:2010, CAN/CSA No. 25-1966 (R2000),CAN/CSA C22.2 No. 30-M1986 (R2012), CAN/CSA C22.2 No.94-M1991 (R2011), CAN/CSA C22.2 No. 61010-1:2012MarkingsXP CL I, DIV 1, GP B*, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T6(-50 C Ta 80 C), T5 (-50 C Ta 95 C); Seal notrequired; installed per Rosemount drawing 00214-1030; Type4X† and IP 66/67; Vmax 35 VDC, 750 mWmaxSpecial Conditions for Safe Use (X):1. Flameproof joints are not intended for repair.2. Cable entries must be used which maintain the ingress protection ofthe enclosure. Unused cable entries must be filled with suitableblanking plugs.6.1.4N6 Canada Division 2Certificate 70044744Standards CAN/CSA C22.2 No. 0:2010, CAN/CSA C22.2 No. 94-M1991(R2011), CAN/CSA No. 213-M1987 (R2013), CAN/CSA C22.2No. 61010-1:2012MarkingsCL I, DIV 2, GP A, B, C, D; T6; (–50 C Ta 80 C), T5 (–50 C Ta 95 C); installed per Rosemount drawing 00214-1030;Type 4X† and IP 66/67; Vmax 35 VDC, 750 mWmax†Spring loaded indicator has reduced ingress and dust ratings. Spring loadedsensors must be installed in a thermowell to maintain dust and ingressratings. Un-painted aluminum enclosures are Type 4 rated. *Assembly is notCanada Explosionproof (E6) rated to Group B if the AT1 (Aluminum withTerminal Strip) connection head is used.Quick Start Guide11

Quick Start GuideMay 20216.2Europe6.2.1E1 ATEX FlameproofCertificateDEKRA 19ATEX0076 XStandardsEN IEC 60079-0: 2018, EN 60079-1: 2014MarkingsII 2 G Ex db IIC T6 T1 Gb, (-60 C Ta 80 C)Special Conditions for Safe Use (X):1. Flameproof joints are not intended for repair.2. Non-Standard Paint options may cause risk from electrostaticdischarge. Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more information.3. When provided on their own, the adapter style sensors must beassembled to a suitable Ex db enclosure with a free internal volumeno greater than 550 cm3.4. Guard DIN sensors against impacts greater than 4J.Process temperaturerange ( C)(1)Ambient temperaturerange ( C)(1)Temperature class-60 C to 80 C-60 C to 80 CT6-60 C to 95 C-60 C to 80 CT5-60 C to 130 C-60 C to 80 CT4-60 C to 195 C-60 C to 80 CT3-60 C to 290 C-60 C to 80 CT2-60 C to 440 C-60 C to 80 CT1(1) Min. process temperature and min. ambient temperature is limited to-50 C for models with enclosure designation “AD1” or “SD1”6.2.2I1 ATEX Intrinsic SafetyCertificate Baseefa16ATEX0101XStandards EN 60079-0:2012 A11:2013, EN 60079-11:2012MarkingsII 1 G Ex ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE)Thermocouples; Pi 500 mW12T6 -60 C Ta 70 CEmerson.com/Rosemount

May 2021Quick Start GuideRTDs; Pi 192 mWT6 -60 C Ta 70 CRTDs; Pi 290 mWT6 -60 C Ta 60 CT5 -60 C Ta 70 CSpecial Conditions for Safe Use (X):The equipment must be installed in an enclosure which affords it a degree ofingress protection of at least IP20.6.2.3N1 ATEX Zone 2CertificateBAS00ATEX3145StandardsEN 60079-0:2012 A11:2013, EN 60079-15:2010Markings6.2.4II 3 G Ex nA IIC T5 Gc (-40 C Ta 70 C)ND ATEX Dust IgnitionproofCertificateDEKRA 19ATEX0076 XStandardsEN IEC 60079-0:2018, EN 60079-31:2014MarkingsII 2 D Ex tb IIIC T130 C Db, (-60 C Ta 80 C)Special Conditions for Safe Use (X):1. Non-Standard Paint options may cause risk from electrostaticdischarge. Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more information.2. When provided on their own, the adapter style sensors must beassembled to a suitable Ex tb enclosure with a free internal volumeno greater than 550 cm3.3. The spring loaded adapter style sensors and DIN style sensors mustbe installed in a thermowell to maintain Ex tb protection.4. The contact indicating adapter style sensor does not meet therequirements for type of protection “tb”.Process temperaturerange ( C)(1)Ambient temperaturerange ( C)(1)Maximum surfacetemperature “T”-60 C to 100 C-60 C to 80 CT130 C(1) Min. process temperature and min. ambient temperature is limited to-50 C for models with enclosure designation “AD1” or “SD1”.Quick Start Guide13

Quick Start GuideMay 20216.3International6.3.1E7 IECEx FlameproofCertificateIECEx DEK 19.0041XStandardsIEC 60079-0: 2017, IEC 60079-1: 2014MarkingsEx db IIC T6 T1 Gb (-60 C Ta 80 C)Special Conditions for Safe Use (X):1. Flameproof joints are not intended for repair.2. Non-Standard Paint options may cause risk from electrostaticdischarge. Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more information.3. When provided on their own, the adapter style sensors must beassembled to a suitable Ex db enclosure with a free internal volumeno greater than 550 cm3.4. Guard DIN sensors against impacts greater than 4J.Process temperaturerange ( C)(1)Ambient temperaturerange ( C)(1)Temperature class-60 C to 80 C-60 C to 80 CT6-60 C to 95 C-60 C to 80 CT5-60 C to 130 C-60 C to 80 CT4-60 C to 195 C-60 C to 80 CT3-60 C to 290 C-60 C to 80 CT2-60 C to 440 C-60 C to 80 CT1(1) Min. process temperature and min. ambient temperature is limited to-50 C for models with enclosure designation “AD1” or “SD1”.6.3.2I7 IECEx Intrinsic SafetyCertificateIECEx BAS 16.0077XStandardsIEC 60079-0:2011, IEC 60079-11:2011MarkingsEx ia IIC T5/T6 Ga (SEE CERTIFICATE FOR SCHEDULE)Thermocouples; Pi 500 mW14T6 -60 C Ta 70 CEmerson.com/Rosemount

May 2021Quick Start GuideRTDs; Pi 192 mWT6 -60 C Ta 70 CRTDs; Pi 290 mWT6 -60 C Ta 60 CT5 -60 C Ta 70 CSpecial Condition for Safe Use (X):The equipment must be installed in an enclosure which affords it a degree ofingress protection of at least IP20.6.3.36.3.4N7 IECEx Zone 2CertificateIECEx BAS 07.0055StandardsIEC 60079-0:2011, IEC 60079-15:2010MarkingsEx nA IIC T5 Gc; T5 (–40 C Ta 70 C)NK IECEx Dust IgnitionproofCertificateIECEx DEK 19.0041XStandardsIEC 60079-0:2017 and IEC 60079-31:2013MarkingsEx tb IIIC T130 C Db, (-60 C Ta 80 C)Special Conditions for Safe Use (X):1. Non-Standard Paint options may cause risk from electrostaticdischarge. Avoid installations that cause electrostatic build-up onpainted surfaces, and only clean the painted surfaces with a dampcloth. If paint is ordered through a special option code, contact themanufacturer for more information2. When provided on their own, the adapter style sensors must beassembled to a suitable Ex tb enclosure with a free internal volumeno greater than 550 cm3.3. The spring loaded adapter style sensors and DIN style sensors mustbe installed in a thermowell to maintain Ex tb protection.4. The contact indicating adapter style sensor does not meet therequirements for type of protection “tb”.Process temperaturerange ( C)(1)Ambient temperaturerange ( C)(1)Maximum surfacetemperature “T”-60 C to 100 C-60 C to 80 CT130 C(1) Min. process temperature and min. ambient temperature is limited to-50 C for models with enclosure designation “AD1” or “SD1”.Quick Start Guide15

Quick Start GuideMay 20216.4Brazil6.4.1E2 Brazil Flameproof & Dust IgnitionproofCertificate UL-BR 17.0199XStandards ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-1:2016,ABNT NBR IEC 60079-31:2014MarkingsEx db IIC T6 T1 Gb T6 (-50 C Ta 80 C), T5 (-50 C Ta 95 C), T4 T1 (-50 C Ta 100 C); Ex tb IIIC T130 C Db(-50 C Ta 100 C)Special Conditions for Safe Use (X):1. Refer to certificate for details regarding process and ambienttemperature limits.2. When the Rosemount 214C Sensor is provided with an enclosurewith a display cover, the maximum ambient shall be 95 C.3. The non-metallic label on the device may store an electrostaticcharge and become a source of ignition in Group III atmospheres.Care shall be taken to reduce electrostatic build-up. For example, thenon-metallic label may be rubbed with a damp cloth.4. The display covers were impacted at 4 J according to a low risk ofmechanical danger. Guard the display covers against impact energiesgreater than 4J.5. Flameproof joints are not intended for repair.6. The stand-alone Rosemount 214C Sensors without an enclosuremust be assembled to a suitable Ex certified enclosure of a volume nogreater than 0.55 L to maintain the types of protection “db” and“tb”.7. The spring loaded sensors and DIN sensors must be installed in athermowell to maintain IP6X ratings.8. Contact indicating sensors do not meet requirements for protectiontype “Ex tb” and therefore are not “Ex tb” rated on this certificate.6.4.2I2 Brazil Intrinsic SafetyCertificate UL-BR 18.0257XStandards ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013Markings16Ex ia IIC T6 T5 Ga Thermocouples: Pi 500 mW, T6 (-60 C Ta 70 C) RTDs: Pi 192 mW, T6 (-60 C Ta 70 C) Pi 290 mW, T6 (-60 C Ta 60 C), T5 (-60 C Ta 70 C)Emerson.com/Rosemount

May 2021Quick Start GuideSpecial Conditions for Safe Use (X):The equipment must be installed in an enclosure which affords it a degree ofingress protection of at least IP20.6.5China6.5.1E3 China FlameproofCertificate GYJ17.1010X (CCC 认证)Standards GB 3836.1-2010, GB 3836.2-2010, GB 12476.1-2013, GB12476.5-2013MarkingsEx d IIC T6 T1 Gb, Ex tD A21 IP6X T130 C*Dust Ignitionproof approvals/markings are only available through the K3option �:1. �商.2. �项1. AT1、AJ1、AJ2AR2、SR2T6-50 Ta 80 -50 Ta 80 T5-50 Ta 95 -50 Ta 95 T4 T1-50 Ta 100 -50 Ta 95 T130 -50 Ta 100 -50 Ta 95 2. ��类型AR2,SR2Quick Start Guide扩展长度无扩展过程温度( )气体粉尘T6T5T4T3T2T1T130 5570959595959517

Quick Start GuideMay 110110任何长度85100135200300450130AJ23. �应可靠接地.4. �用的有害气体.5. �定的防爆检验机构按检验认可、具有 Ex d ⅡC Gb,Ex tD A21 IP6X �余电缆引入口须用堵封件有效密封.6. ��语.7. ��压缩空气吹扫.8. ��故障,以杜绝损坏现象的发生.9. �境 第 13 �”、GB/T3836.15-2017“爆炸性环境 第 15 �、GB/T3836.16-2017“爆炸性环境 第 16 ��险环境电力装置施工及验收规范”和 �规定。6.5.218I3 China Intrinsic SafetyCertificateGYJ18.1024X (CCC 认证)StandardsGB 3836.1-2010, GB 3836.4-2010, GB 3836.20-2010MarkingsEx ia IIC T5/T6 GaEmerson.com/Rosemount

May 2021Quick Start ��:产品必须安装于具有IP20 ��用注意事项1. �:传感器类型最大输入功率 -60 70 RTD192T6-60 70 RTD290T6-60 60 T5-60 70 2. 效参数Ui (V)Ii (mA)Pi (mW)Ci (pF)Li (nH)6010050075600最高输出电压Uo (V)最大输出电流Io (mA)最大输出功率Po �最大输入功率Ui (V)Ii (mA)Pi (mW)Ci (pF)Li (nH)60100192/29075600最大内部等效参数3. �说明书要求,接线端子不得接错.4. ��故障,以杜绝损坏现象的发生.Quick Start Guide19

Quick Start GuideMay 20215. �境 第 13 �气设备 第 15 �气设备 第 16 �外)”、GB3836.18-2010“爆炸性环境 第 18 .6.5.3N3 China Zone 2CertificateGYJ18.1025 (CCC 认证)StandardsGB 3836.1-2010, GB 3836.8-2014MarkingsEx nA IIC T5 Gc, T5 (-40 C Ta 70 C)产品使用注意事项1. 产品使用环境温度为:-40 70 2. 输入参数:类型输入参数 Ui变送器42.4 V热电阻端子5V热电偶端子0V3. �块:型号防爆合格证编号644 系列GYJ15.1502248 系列GYJ15.10894. �指定的防爆检验机构检验认可、具有 Ex e ⅡC Gb 或 Ex nR ⅡC Gc �护等级达到IP54 (符合 GB4208-2008 标准要求)以上.5. ��故障,以杜绝损坏现象的发生.6. �境 第 13 �气设备 第 15 部20Emerson.com/Rosemount

May 2021Quick Start 电气设备 第 16 �外)”和 ��的有关规定.6.6Korea6.6.1EP Korea FlameproofCertificate 17-KA4BO-0305XMarkingsEx d IIC T6 T1, T6 (-50 C Ta 80 C), T5 (-50 C Ta 95 C), T4 T1 (-50 C Ta 100 C)Special Condition for Safe Use (X):Refer to certificate for Special Conditions for Safe Use.6.6.2IP Korea Intrinsic SafetyCertificate17-KA4BO-0304XMarkingsEx ia IIC T6/T5Special Condition for Safe Use (X):Refer to certificate for details regarding process and ambient temperaturelimits as well as Special Conditions for Safe Use.6.6.3KP Korea Flameproof, Dust Ignitionproof, and Intrinsic SafetyCertificate 17-KA4BO-0306X in addition to the EP and IP certificatenumbersMarkingsEx tb IIIC T130 C, T130 C (-50 C Ta 100 C) in addition tothe markings for EP and IPSpecial Condition for Safe Use (X):Refer to certificate for details regarding process and ambient temperaturelimits as well as Special Conditions for Safe Use.6.7Russia6.7.1EM Technical Regulation Customs Union TR CU 012/2011 (EAC)FlameproofMarkings 1Ex db IIC T6 T1 Gb X, T6 (–55 C Ta 80 C), T5 (–55 C Ta 95 C), T4 T1 (–55 C Ta 100 C)Quick Start Guide21

Quick Start GuideMay 2021Special Condition for Safe Use (X):Refer to certificate for Special Conditions for Safe Use.6.7.2IM Technical Regulation Customs Union TR CU 012/2011 (EAC)Intrinsic SafetyMarkings0Ex ia IIC T5,T6 Ga XSpecial Condition for Safe Use (X):Refer to certificate for details regarding process and ambient temperaturelimits as well as Special Conditions for Safe Use.6.7.3KM Technical Regulation Customs Union TR CU 012/2011 (EAC)Flameproof, Dust-Ignitionproof, and Intrinsic SafetyMarkings Ex tb IIIC T130 C Db X in addition to the markings above for EMand IM.Special Condition for Safe Use (X):Refer to certificate for details regarding process and ambient temperaturelimits as well as Special Conditions for Safe Use.6.822CombinationsK1Combination of E1, I1, N1, and NDK3Combination of E3, I3, and N3K7Combination of E7, I7, N7, and NKKACombination of E1 and E6KBCombination of E5 and E6KCCombination of E1 and E5KDCombination of E1, E5, and E6KECombination of E1, E5, E6, and E7KMCombination of EM and IMKNCombination of N1, N5, N6, and N7KPCombination of EP and IPEmerson.com/Rosemount

May 20217Quick Start GuideDeclaration of ConformityQuick Start Guide23

Quick Start Guide24May 2021Emerson.com/Rosemount

May 20218Quick Start GuideChina RoHS 214C2/9/2021ਜ਼ᴹChina RoHS ᧗ 䍘䎵䗷ᴰབྷ ᓖ䲀٬Ⲵ䜘Ԧරਧࡇ㺘 214C Temperature SensorList of 214C Temperature Sensor Parts with China RoHS Concentration above MCVsᴹᇣ 䍘 / Hazardous Substances 䫵 Lead(Pb) Mercury(Hg)䭹 Cadmium(Cd) ޝ ԧ䬜 HexavalentChromium(Cr 6)ཊ 㚄㤟 Polybrominatedbiphenyls(PBB)ཊ 㚄㤟䟊Polybrominateddiphenyl ethers(PBDE)༣փ㓴ԦHousingAssembly OOOOOOՐᝏಘ㓴ԦSensorAssembly OOOOOO䜘Ԧ Part Name ᵜ㺘Ṭ ᦞ SJ/T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ/T11364.O: Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿൷վҾGB/T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limitrequirement of GB/T 26572.X: Ѫ൘䈕䜘Ԧᡰ֯ Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа ൷䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB/T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part isabove the limit requirement of GB/T 26572.䜘Ԧ Part Name ༣փ㓴ԦHousingAssembly Quick Start Guide㓴㻵༷Ԧ䈤᰾ Spare Parts Descriptions for Assemblies ᆀཆ༣ Electrical Housing25

Quick Start Guide26May 2021Emerson.com/Rosemount

May 2021Quick Start GuideQuick Start Guide27

*00825-0400-2654*Quick Start Guide00825-0400-2654, Rev. DBMay 2021 2021 Emerson. All rights reserved.Emerson Terms and Conditions of Sale areavailable upon request. The Emerson logois a trademark and service mark ofEmerson Electric Co. Rosemount is a markof one of the Emerson family ofcompanies. All other marks are theproperty of their respective owners.

per IEC 60751:2008. 4.1 Insulation resistance. 1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature. 4.2 Insulation resistance at elevated temperature. Insulation resistance at elevated temperatures for sensor types RT, RH, and RW are tested and meet requirements according to

Related Documents:

Product Data Sheet January 2017 00813-0500-2654, Rev BB Rosemount 214C Temperature Sensors Primary product benefits High accuracy resistance temperature detectors (RTD) and various thermocouple types offered in a variety of element configurations Calibration capabilities for increased measurement accuracy for RTDs

Rosemount 3051S 305 A11 N/A 306 A11 N/A 304 A12 N/A Rosemount 3051/2051 305 N/A S5 306 N/A S5 304 N/A S6 Rosemount 2088 305 N/A N/A 306 N/A S5 304 N/A N/A Rosemount 4088 305 A11 N/A 306 A11 N/A 304 A12 N/A. Procedure. 1. Specify a completed Rosemount transmitter model number by referencing the applica

Rosemount 3051S 305 A11 N/A 306 A11 N/A 304 A12 N/A Rosemount 3051/2051 305 N/A S5 306 N/A S5 304 N/A S6 Rosemount 2088 305 N/A N/A 306 N/A S5 304 N/A N/A Rosemount 4088 305 A11 N/A 306 A11 N/A 304 A12 N/A. Procedure. 1. Specify a completed Rosemount transmitter model number by referencing the applica

A11(12)(13) Assemble to Rosemount 305 Integral Manifold A12(12) Assemble to Rosemount 304 or AMF manifold with 316 SST traditional flange C11(12) Assemble to Rosemount 405C or 405P Primary Element D11(12) Assemble to Rosemount 1195 Integral Orifice and 305 Manifold EA2(12) Assemble to Rosemount 485 or 405A Annubar

A11(5) Assemble to Rosemount 305 Manifold Assemble to Rosemount 306 Manifold A12(5) Assemble to Rosemount 304 or AMF Manifold with SST Traditional Flange N/A B11(5)(6) Assemble to One Rosemount 1199 Remote Diaphragm Seal with SST transmitter flange Assemble to One Rosemount 1199 Remote Diaphragm

Rosemount 644 Smart Temperature Transmitters may be protected by one or more U.S. Patents pending. Other foreign patents pending. Rosemount 644 Hardware Revision . Rosemount 644 Head Transmitter. Rosemount 644. Rosemount 644. Reference Manual 00809-0100-4728, Rev JA. January 2004

Rosemount 3051 www.rosemount.com 00825-0100-4797G Quick Installation Guide 00825-0100-4797, Rev EA June 2010 Rosemount 3051 Pressure Transmitter with Profibus-PA Rosemount 3051CF Series Flowmeter Transmitter with Profibus-PA Start End Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Set the Jumpers

Rosemount 3051S/3051/2051/3095 Rosemount 1151 D C D Rosemount 3051S/3051/2051/3095 Rosemount 1151 Februari 2019. 8 Snelstartgids 2.6 Montagerichting inline-druktransmitter De drukpoort aan de lage kant (ref. atmosferische druk) op de inline-verschildruktransmitter bevindt zich in de hals van de transmitter, achter