Medium Voltage Circuit Breaker Course Chapter 4.0

2y ago
17 Views
2 Downloads
4.33 MB
8 Pages
Last View : 13d ago
Last Download : 3m ago
Upload by : Rosa Marty
Transcription

Medium Voltage Circuit Breaker CourseChapter 4.0Student Manual4.0Circuit Breaker CubicleCIRCUIT BREAKER CUBICLELearning ObjectivesThe circuit breaker cubicle is the component of the switchgear that holds the circuitbreaker, and the controls and cabling for the distribution system.As a result of this lesson you will be able to:1. Understand the components of the cubicle2. Understand the function of the shutter assembly3. Describe the positions of a breaker during the racking operation4. Understand and explain the test position5. Explain the function of the truck-actuated switch6. Understand the operation of the mechanism operated Switch4.1WHY CIRCUIT BREAKERS ARE REMOVABLEThe circuit breaker is removed from the cubicle to allow for the complete isolation ofloads from sources, for personnel safety during component maintenance, and forrepair. Circuit breakers of the same rating are generally interchangeable; allowing analternate circuit breaker to be installed while the original is maintained.When a circuit breaker is removed for system repairs a ground truck may beinstalled in the compartment to connect the de-energized equipment to ground. Theground truck is a breaker frame with bushings only and a ground bus, the bus side isrun to ground and with the truck in the breaker position there is no danger ofenergizing the circuit.4.2MEDIUM VOLTAGE BREAKER CELL COMPONENTSThe following components are common to most cubicles; this example is an ABBHK cubicle. USNRCShutter: the fiberglass barrier that isolates the live bus connections to the cell(Figure 4-1).4-1Rev 0

Medium Voltage Circuit Breaker CourseChapter 4.0Student Manual 4.3Circuit Breaker CubiclePrimary Disconnects: the disconnects that connect the power to thebreaker (Figure 4-3).Secondary Disconnects: the disconnects that connects the control power(Figure 4-2.) Guide rail: the rail that guides the breaker into the cell (Figure 4-5). Ground Bar: the ground connecting point to the breaker frame (Figure 42). CT’s: current transformers located on the primary bus. Transform thecurrent down to a manageable value for instrumentation (Figure 4-4). Instrumentation Relays: relays mounted in the door of the cell that monitorthe voltage and current. Rejection Plate: prevent racking the wrong breaker into the cubicle(Figure 4-2). Breaker Positions: markings that show position of the breaker, such as,connected, disconnected and testing (Figure 4-5).SWITCHGEAR AUXILIARY SWITCHES (figure 4-6)A number of different types of auxiliary switches are used to indicate the positionof the circuit breaker contacts and readiness of the circuit breaker for operationand also to provide additional electrical interlocks. These are mechanismoperated and truck operated auxiliary switches.4.3.1 Mechanism-Operated Control Auxiliary Switches (MOC switch)MOC switches are operated directly from the breaker mechanism someswitches are mounted on the circuit breaker but normally they aremounted in the switchboard enclosure and linked mechanically to thecircuit breaker. Figure 4-6 shows a common MOC arrangement on aWestinghouse DHP cubicle.USNRC4-2Rev 0

Medium Voltage Circuit Breaker CourseChapter 4.0Student ManualCircuit Breaker Cubicle4.3.2 Truck-Operated Contact Auxiliary Switches (TOC switch)TOC auxiliary switches are mounted in the circuit breaker compartment andoperate when the circuit breaker is moved to the operating position. TOCswitches may be used for interlocking and remote position indication.4.4INTERNAL CONTROL WIRINGThe circuit breaker control wiring originates at the secondary disconnects andterminates at meters, relays, and control circuits.4.5RACKING INTERLOCKSAll breakers have interlocks on the racking mechanism or in the switchboard toprevent the breaker being racked in or out when closed. These interlocks will tripthe breaker if a close operation is attempted while racking the breaker in or out. Theinterlock will also prevent insertion of the racking tool until the breaker is tripped.4.6RACKING POSITIONSA racking mechanism also called a levering device is the mechanism used to insertand remove the circuit breaker from the circuit breaker compartment. Most circuitbreakers are racked in manually by a racking tool, which looks like a large speedwrench with a special end to fit on to the breaker-racking device (Figure 4-5). Thegeneral electric vertical lift Magne-Blast breakers are racked in by an electric rackingmotor but can also be inserted with a manual-racking handle.The racking operation is potentially one of the most dangerous breaker evolutions; ifthe breaker safety interlocks fail the breaker can explode. Because of this dangermany plants are starting to use remote racking systems to perform the breakerracking operation.All circuit breakers have two main positions connect and disconnect, some breakersalso have a test and a withdrawn position. USNRCDisconnect Position: In this position the breaker is completely off the bus anddisconnected from the secondary disconnect. The breaker should be able tobe removed from the cubicle but may need to have a latch holding it in thisposition.4-3Rev 0

Medium Voltage Circuit Breaker CourseChapter 4.0Student ManualCircuit Breaker Cubicle Connect Position: In this position the breaker primary and secondarydisconnects are completely inserted and control power is available to thebreaker. Test Position: The definition of the test position is the primary disconnectsare disconnected from the cubicle bus, and the secondary disconnect isconnected and control power is available to operate the breaker.In this position the breaker can be operated electrically to verify operationbut since the bus is not connected the equipment will not be energized. 4.7Withdrawn Position: Circuit breakers with racking mechanism as part of thebreaker may have a position beyond disconnect. In this position the rackingmechanism interlocks the mechanism and puts the breaker in a locked outposition where the close and trip latch is engaged.RACKING SHUTTERThe racking shutter is a mechanism, which covers the cubicle side primary buswhen the breaker is racked out and removed. The shutter prevents easy accessto the live portion of the cubicle bus work when the breaker is removed from theswitchboard.As the breaker is racked into the cubicle a roller or shaft will engage the shutteractuating arm and lift the shutter from the primary bus opening. When removingthe breaker the shutter will re-close and cover the primary opening.USNRC4-4Rev 0

Medium Voltage Circuit Breaker CourseChapter 4.0Student ManualCircuit Breaker CubicleSHUTTERFigure 4-1 Shutter assemblySecondaryDisconnectRejection PlateGround BusFigure 4-2 Stationary secondary disconnectUSNRC4-5Rev 0

Medium Voltage Circuit Breaker CourseChapter 4.0Student ManualCircuit Breaker CubiclePrimary DisconnectsFIGURE 4-3 HK Primary disconnectsFigure 4-4 Instrumentation current transformersUSNRC4-6Rev 0

Student Manual Circuit Breaker Cubicle USNRC 4-1 Rev 0 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker,

Related Documents:

Circuit-breaker with RHE RHD Circuit-breaker with HTC Circuit-breaker with LTC Circuit-breaker with FLD A IP 40 IP 20 IP 40 IP 40 IP 40 IP 40 B IP 20 IP 20 IP 20 IP 40 IP 30 IP 20 (1) During installation of the electrical accessories Weights A1 [Kg] A2 [Kg] A3 [Kg] Circuit-breaker 1 pole 0.245 0.37 - Circuit-breaker 2 poles 0.47 0.73 - Circuit .

Example of Medium Voltage Circuit breaker HV Circuit Breaker - Type AIS SF 6 Circuit Breaker. . Colors illustrate the voltage distribution calculated by 3D simulation. HV Circuit Breaker - Type Voltage withstand of . voltages up to 72.5 kV and possibly 145 kV.

Content Products Trends in High Voltage Circuit Breaker Technology 4 Dead Tank Based Compact Switchgear 8 Bypass Circuit-Breaker for 800 kV DC 13 1200 kV AC substations:Full-scale products and integrated solutions 19 Circuit-Breaker Platform for 550 kV 27 Siemens High-Voltage Circuit-Breakers for Use at Low Temperatures 34 3AP4/5 High-Voltage Circuit-Breaker for 800 kV 41

electronic trip circuit breaker A circuit breaker which uses current sensors and electronic circuitry to sense, measure and respond to current levels. fixed-mounted circuit breaker A circuit breaker so mounted that it cannot be removed without removing primary and sometimes secondary connections and/or mounting supports.

Magnum DS Power Circuit Breakers Renewal Parts and Accessories Procedure for Identifying Breaker Type MDS Type Breaker A Low voltage air circuit breaker family name B Breaker family designation number C Breaker frame size in amperes D Interrupting capacity rating E Accessories F Catalog number The Catalog Number is a 25-digit number located on the

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489 Data Sheet The miniature circuit breaker SU200 M is ABB's solution for UL 489 branch circuit protection up to 480 Y/277 V AC and 96 V DC. This circuit breaker is an all-round device for AC and DC applications for universal use in North

circuit breaker, either ACB or MCCB. You will know how to read the Technical Catalogues and find the information you need to properly choose the circuit breaker and protection unit for your application. You will understand how to select the right ordering codes for a circuit breaker and its accessories. Contents Basics What is a circuit breaker

Herbal Medicinal I. Plants, Medicinal Hak pengarang dan penerbit dilindungi Undang-undang Cetakan Pertama. 2014 Pengarang : Tjandra Yoga Aditama Dicetak oleh : Lembaga Penerbit Balitbangkes (LPB) Jl. Percetakan Negara No. 29 Tlp. 021-4261088 website : terbitan.litbang.depkes.go.id e-mail : LPB@litbang.depkes.go.id. JAMU & KESEHATAN Prof dr Tjandra Yoga Aditama Sp P(K), MARS, DTM&H, DTCE .