Rosemount 1151 Smart Pressure Transmitter

2y ago
19 Views
2 Downloads
6.24 MB
158 Pages
Last View : 13d ago
Last Download : 3m ago
Upload by : Wade Mabry
Transcription

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151 Smart Pressure Transmitterwww.rosemount.com

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151Rosemount 1151 SmartPressure TransmitterNOTICERead this manual before working with the product. For personal and system safety, andfor optimum product performance, make sure you thoroughly understand the contentsbefore installing, using, or maintaining this product.For technical assistance, contacts are listed below:Customer CentralTechnical support, quoting, and order-related questions.United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)Asia Pacific- 65 777 8211Europe/ Middle East/ Africa - 49 (8153) 9390North American Response CenterEquipment service needs.1-800-654-7768 (24 hours—includes Canada)Outside of these areas, contact your local Rosemount representative.The products described in this document are NOT designed for nuclear-qualifiedapplications.Using non-nuclear qualified products in applications that require nuclear-qualifiedhardware or products may cause inaccurate readings.For information on Rosemount nuclear-qualified products, contact your local RosemountSales Representative.May be protected by one or more of the following U.S. Patent Nos. 4,804,958; 4,866,435;4,878,012; 4,988,990; 5,083,091; 5,094,109; 5,237,285; Des. 317,266; Des. 318,432. MexicoPats. Pend. 6057,912237. May depend on model. Other foreign patents issued and pending.www.rosemount.com

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151Table of ContentsSECTION 1IntroductionUsing This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2SECTION 2TransmitterFunctionsOverview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Warnings () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Commissioning the Transmitter on the Bench. . . . . . . . . . . . . . . . 2-1Setting Hardware Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Commissioning the Rosemount 1151 with aHART-Based Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Wiring Diagrams (Bench Hook-up) . . . . . . . . . . . . . . . . . . . . . . . . 2-3Testing the Equipment and the Loop . . . . . . . . . . . . . . . . . . . . . . 2-3Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5Wiring Diagrams (Field Hook-up) . . . . . . . . . . . . . . . . . . . . . . . . . 2-6Common Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7Configure the Analog Output Parameters . . . . . . . . . . . . . . . . . . . 2-7Calibrate the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12Digital to Analog Converter Trim . . . . . . . . . . . . . . . . . . . . . . . . . 2-16Advanced Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17Multidrop Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18SECTION 3InstallationOverview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Access Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Mechanical Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8Mounting Requirements (for Steam, Liquid, Gas) . . . . . . . . . . . . . 3-8Process Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10Mounting Brackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11Conduit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15Hazardous Locations Certifications . . . . . . . . . . . . . . . . . . . . . . . 3-16Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16Installation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17Mounting Brackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17Analog Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17LCD Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20TOC-1

Reference ManualRosemount 115100809-0100-4593, Rev CAJune 2007SECTION 4TroubleshootingOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Warnings () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Disassembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Reassembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6Optional Plug-in Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8Sensor Module Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8Returning Rosemount Products and/or Materials. . . . . . . . . . . . . . 4-9SECTION 5Specifications andReference DataFunctional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8Rosemount 1151LT Process Wetted Parts . . . . . . . . . . . . . . . . . . 5-9Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-111151 Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-191151LT Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26Specifications and Reference Data for Options. . . . . . . . . . . . . . . . . 5-29LCD Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29Hazardous Locations Certifications . . . . . . . . . . . . . . . . . . . . . . . 5-29Terminal Block Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30APPENDIX AHART CommunicatorIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Warnings () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Connections and Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4Communicator Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5Function Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6Alphanumeric and Shift Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6HART Fast Key Sequences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7HART Fast Key Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7Menus and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7Online Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8Diagnostic Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8APPENDIX BRosemount 268CommunicatorIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1Connections and hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4Communicator Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5Dedicated Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5Alphanumeric and Shift Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6Function Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6Fast Key Sequence Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . B-7Fast Key Sequence Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7Diagnostics Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8TOC-2

Reference Manual00809-0100-4593, Rev CAJune 2007APPENDIX CRetrofitting theRosemount 1151TransmitterRosemount 1151Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1Warnings () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1Retrofitting overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2Removing the Analog Electronics Assembly . . . . . . . . . . . . . . . . . . . C-2Installing the Smart Retrofit Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-10Characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-13Before Characterizing the Transmitter. . . . . . . . . . . . . . . . . . . . . C-13Characterizing with a Rosemount 275 Communicator . . . . . . . . C-14Characterization with a Rosemount 268 Communicator . . . . . . . C-14APPENDIX DApprovalDrawingsAPPENDIX EGlossaryINDEXTOC-3

Reference ManualRosemount 1151TOC-400809-0100-4593, Rev CAJune 2007

Reference Manual00809-0100-4593, Rev CAJune 2007Section 1Rosemount 1151IntroductionUsing This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2USING THIS MANUALThis manual provides information on installation, operation, and maintenanceof Rosemount 1151 Smart Pressure Transmitters. The rest of this manual isorganized into the following sections:Section 2–Transmitter FunctionsThis section describes the Rosemount 1151 software functions, configurationparameters, and other on-line variables.Section 3–InstallationThis section provides mechanical and electrical installation instructions.Section 4–TroubleshootingThis section provides troubleshooting techniques for diagnostic messagesassociated with the transmitter.Section 5–Specifications and Reference DataThis section provides reference and specification data for Rosemount 1151Smart Pressure Transmitters.Appendix A–HART CommunicatorThis appendix contains a communicator overview, a HART Communicatormenu tree for the Rosemount 1151 Smart Pressure Transmitters, and a tableof HART Communicator fast key sequences. A table of diagnostic messagesassociated with this communicator is also included.Appendix B–Rosemount 268 CommunicatorThis appendix contains a communicator overview, a Rosemount 268Communicator menu tree for the Rosemount 1151 Smart PressureTransmitters, and a table of Rosemount 268 fast key sequences. A table ofdiagnostic messages associated with this communicator is also included.Appendix C–Retrofitting the Rosemount 1151 TransmitterThis section describes how the Rosemount Smart Retrofit Kit can be used toretrofit a Rosemount 1151AP, DP, GP, HP, or LT transmitter with 4-20 mA dclinear or square root output.Appendix D–Approval DrawingsThis appendix contains intrinsic safety drawings.GlossaryThis section provides brief definitions of the terms used in this manual.IndexThis section provides a comprehensive index.www.rosemount.com

Reference ManualRosemount 1151MODELS COVERED00809-0100-4593, Rev CAJune 2007This manual provides basic installation, commissioning, and troubleshootinginformation for the following Rosemount 1151 Smart Pressure Transmitters:Rosemount 1151DP—Differential Pressure TransmitterMeasures differential pressure from 2 inH2O to 1,000 psi (0.497 to 6895 kPa).Rosemount 1151HP—Differential Pressure Transmitter for High LinePressuresProvides high line pressure from 10 inH2O to 300 psi (2.49 to 2068 kPa).Rosemount 1151GP—Gage Pressure TransmitterMeasures gage pressure from 2 inH2O to 1,000 psi (0.497 to 41369 kPa).Rosemount 1151AP—Absolute Pressure TransmitterMeasures absolute pressure from 10 inH2O to 1,000 psi (2.49 to 6895 kPa).Rosemount 1151LT—Flange-Mounted Liquid Level TransmitterProvides precise level and specific gravity measurements from 25 to 2,770inH2O (6.2 to 690 kPa) for a wide variety of tank configurations.1-2

Reference Manual00809-0100-4593, Rev CAJune 2007Section 2Rosemount 1151Transmitter FunctionsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1OVERVIEWThis section contains information on commissioning and operatingRosemount 1151 Smart Pressure Transmitters. Instructions for settingtransmitter switches (prior to installation) and explanations of softwarefunctions are provided in this section.Fast key sequences are listed for each software function. Please refer toAppendices A and B for more information on fast key sequences and othercommunicator operations.SAFETY MESSAGESWarnings ()Procedures and instructions in this section that raise potential safety issuesare indicated by a warning symbol ( ). Refer to the following warningmessages before performing an operation preceded by this symbol.Explosions can result in death or serious injury. Before connecting a communicator inan explosive atmosphere, make sure the instruments in the loop are installed inaccordance with intrinsically safe or nonincendive field wiring practices.Commissioning theTransmitter on the BenchCommissioning consists of testing the transmitter, testing the loop, andverifying transmitter configuration data. Rosemount 1151 Smart PressureTransmitters may be commissioned either before or after installation. Werecommend commissioning the transmitter on the bench before installation.This ensures that all transmitter components are in good working order andheightens familiarity with the device.To avoid exposing the transmitter electronics to the plant environment afterinstallation, set the failure mode and transmitter security switches during thecommissioning stage on the bench.Setting HardwareSwitcheswww.rosemount.comThe Rosemount 1151 Smart Pressure Transmitter contains hardwareswitches that provide user-selectable operation of the failure mode andtransmitter security. The switches are located on the electronics assembly justinside the electronics housing cover, as shown in Figure 2-1.

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151Fail Safe Mode SwitchFigure 2-1.Transmitter Switch Locations.Transmitter Security SwitchNOTEUser-selectable switches areshown in default positionFailure Mode Alarm SwitchAs part of its normal operation, the Rosemount 1151 Smart continuouslymonitors its own operation. This automatic diagnostic routine is a timed seriesof checks repeated continuously.The electronics faceplate (Part No. 01151-0934-xxxx) has HI and LOuser-selectable failure mode settings. If the diagnostic routine detects a failurein the transmitter in analog output, the transmitter either drives its outputbelow 3.8 mA or above 21.0 mA, depending on the position of the failuremode alarm switch.NOTEWith multidrop (digital) output, the analog output remains at 4 mA, even whena diagnostic failure is detected. This is true for both the HI and LO fail modeswitch settings. A bit is enabled in the digital word to indicate a diagnosticfailure.Transmitter Security (Write-Protection Switch)Once the transmitter has been configured, it may be desirable to protect theconfiguration data from changes. The electronics assembly is equipped with aswitch labeled SECURITY. Figure 2-1 shows the switch location on the circuitside of the electronics housing. In the ON position, the switch prevents theaccidental or deliberate change of configuration data. To enable the sendingof configuration data, simply return the transmitter security switch to the OFFposition.NOTEThe transmitter security switch must be in the OFF position beforeconfiguration changes can be made to the transmitter configuration.2-2

Reference Manual00809-0100-4593, Rev CAJune 2007Commissioning theRosemount 1151 with aHART-BasedCommunicatorRosemount 1151Before putting the Rosemount 1151 Smart Pressure Transmitter intooperation, commission the instrument using a HART-based communicator.To commission on the bench, connect a 17 to 45 V dc power supply and acurrent meter, such as the Rosemount 282 Validator. Make connections asshown in Figure 2-2. The power supplied to the transmitter should not dropbelow the transmitter lift-off voltage. If the transmitter is being configuredwhen the power drops below the lift-off voltage, the configuration informationmay not be interpreted correctly by the transmitter.NOTETo enable communication, a resistance of at least 250 Ω must be presentbetween the communicator loop connection and the power supply.Wiring Diagrams(Bench Hook-up)After the bench equipment is connected as shown in Figure 2-2, turn on theHART-based communicator by pressing the ON/OFF key. The communicatorwill search for a HART-compatible device and will indicate when theconnection is made. If the connection is not made, the communicator willindicate that no device was found. If this occurs, refer to Section 4Troubleshooting.Figure 2-2. Bench Hook-up.24 V dcPowerSupplyRL 250 CurrentMeterNOTEAn alternate location to connect an ammeter is on the set of terminals labeled“TEST.” Connect the positive lead of the ammeter to the positive test terminal,and the negative lead of the ammeter to the negative test terminal.Testing the Equipmentand the LoopTest functions verify that the transmitter, the communicator, and the loop arein good working order. Testing is recommended whenever component failureor a problem with loop performance is suspected.Communicator TestA communicator test is performed to ensure the communicator is workingproperly. Both the HART Communicator 275 and the Rosemount 268Communicator perform self-tests after being turned on. If a problem isdetected, the communicator will list a diagnostic message. Refer toAppendices A and B for diagnostic messages associated with thecommunicator.2-3

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151Transmitter TestHART Comm.1, 2, 1, 1Rosemount 268F2, F2Although the Rosemount 1151 Smart Pressure Transmitter performscontinuous self-diagnostics, a more extensive diagnostic routine can beinitiated with the transmitter test function. The transmitter test routine canidentify an electronics failure.If the transmitter test detects a problem, messages to indicate the source ofthe problem are displayed.Loop TestHART Comm.1, 2, 2Rosemount 268F2, F3The loop test allows verification of the output of the transmitter, the integrity ofthe loop, and the operation of any recorders or similar devices. Ifcommissioning the transmitter on the bench, repeat this test after thetransmitter has been installed in the field.A reminder appears to set the loop to manual. Do so and proceed. The nextdisplay selects a discrete milliampere transmitter output level. To commandthe transmitter to output 4 mA, for example, select 4 mA. Check the currentmeter installed in the test loop to verify that it reads 4 mA. If so, end the looptest. If the output is not 4 mA, then the receiving meter is malfunctioning or thetransmitter requires a digital trim as described on page 2-12.Review Configuration DataHART Comm.1, 5Rosemount 268Review KeyReview of the transmitter factory configuration data is recommended.Checking the Transmitter OutputHART Comm.2Rosemount 268PVProcess variable readings can be obtained in engineering units andmilliamperes. If the milliampere display does not agree with the actual loopreading given by a multimeter, a 4–20 mA trim is required.The last step of start-up and commissioning is to check the transmitter output.Obtain process variable readings in engineering units and milliamperes. If thisdisplay does not agree with the actual loop reading given by a multimeter, a4–20 mA trim is required (see page 2-19).Range PointsHART Comm.1, 3, 3Rosemount 268F3, F2, F1The Rosemount 1151 Smart 4 and 20 mA range points can be viewed andedited with these fast key sequences.2-4

Reference Manual00809-0100-4593, Rev CAJune 2007Calibration OverviewRosemount 1151Complete calibration of the Rosemount 1151 Smart Pressure Transmitterinvolves the following tasks:Configuring the Analog Output Parameters Setting process variable units (page 2-7) Reranging (page 2-7) Setting output type (page 2-10) Setting damping (page 2-12)Calibrating the Sensor Full trim (page 2-12) Zero trim (page 2-13)Calibrating the 4–20 mA Output 4–20 mA output trim (page 2-16) or 4–20 mA output trim using other scale (page 2-17)Figure 2-3. Rosemount 1151Transmitter Data Flow withCalibration Options.(Transmitter Ranged 0 to 100 inH2O)Transmitter Electronics ModuleSensor100 inH2OInputPressureInput DeviceMicroprocessorDigital onsAnalog-to-DigitalSignalConversion20.00 mAAnalog OutputSensorSignalOutput DeviceNOTES1) Value on PV line should equalthe input pressure2) Value on AO line should equalthe output device reading3051:PT-4001Online1 Device Setup2 PV100.00 inH2O3 AO20.00 mA4 LRV0.00 inH2O5 URV100.00 inH2OFigure 2-3 illustrates the Rosemount 1151 transmitter data flow. This data flowcan be summarized in four major steps:1. A change in pressure is measured by a change in the sensor output(Sensor Signal).2. The sensor signal is converted to a digital format that can be understoodby the microprocessor (Analog-to-Digital Signal Conversion).3. Corrections are performed in the microprocessor to obtain a digitalrepresentation of the process input (Digital PV).4. The Digital PV is converted to an analog value(Digital-to-Analog Signal Conversion).2-5

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151Figure 2-3 also identifies the approximate transmitter location for eachcalibration task. Note that the data flows from left to right, and a parameterchange affects all values to the right of the changed parameter.Not all calibration procedures should be performed for each Rosemount 1151transmitter. Furthermore, some procedures are appropriate for benchcalibration but should not be performed during field calibration. Table 2-1identifies the recommended calibration procedures for each type ofRosemount 1151 transmitter for both bench and field calibration.Table 2-1. Recommended Calibration 1GP1151HP1151LT1151APBench Calibration Tasks1. Set output configuration parameters:a) Set the Transmitter Range Points.b) Set the Output Units.c) Set the Output Type (linear or square root).d) Set the Damping Value.2. Optional: Perform a Full Sensor Trim—Pressure source required.3. Optional: Perform an Analog Output Trim—Multimeter required.Standard Bench Calibration,except step 2:2. Optional: Perform a Full Sensor Trim ifequipment is available (accurate absolutepressure source required); otherwise,perform the Low Trim Value section ofFull Sensor Trim procedure.Field Calibration Tasks1) Reconfigure parameters if necessary.2) Zero trim the transmitter to compensatefor mounting position effects or staticpressure effects.1) Reconfigure parameters if necessary.2) Perform Low Trim Value section ofFull Sensor Trim procedure to correct formounting position effects.NOTEA HART-based communicator is required for all sensor and output trim procedures.Wiring Diagrams(Field Hook-up)Figure 2-4. Rosemount 1151 FieldWiring Diagram.OptionalChartRecorderRosemount 1151 SmartPressure TransmitterRL nal Loop may be grounded at anypoint or left ungrounded.2-6NOTEA HART Interface may be connected at any termination point in theloop. Signal loop must have 250 ohms minimum load forcommunications.

Reference Manual00809-0100-4593, Rev CAJune 2007Common FunctionsRosemount 1151The following tasks are a common part of a transmitter commissioning.Setting the Loop to ManualWhen preparing to send or request data that would disrupt the loop or changethe output of the transmitter, set the loop to manual. Both the HARTCommunicator 275 and the Rosemount 268 will prompt for this setting whennecessary. Keep in mind that simply acknowledging this prompter does notset the loop to manual. It is only a reminder; the loop must be set to manual asa separate operation.Change Non-Output Related InformationThe Rosemount 1151 Smart contains several configuration parameters thatdo not directly affect the transmitter output. These parameters include: Date Descriptor Message Meter typeSending Data to the TransmitterHART Comm.NoteRosemount 268F3, F4Whenever transmitter configuration data is updated with a HART-basedcommunicator, the entered data must be sent to the transmitter memory.NOTEDepending on the task, an option to enter the data (or end changes and enterthe data) will appear at the end of the configuration function. Follow theon-screen prompts to complete the send data function.Review the transmitter memory to ensure that configuration changes havebeen entered.Configure the AnalogOutput ParametersSetting UnitsHART Comm.1, 3Rosemount 268F3, F2By setting the output units, a process can be monitored using the specifiedunits. This is important if a plant uses units which differ from those preset byRosemount Inc. Output units can be selected from among 14 output options: inH20 inHg ftH20 mmH20 mmHg psi bar mbar g/cm2 kg/cm2 Pa kPa torr atmRerangingOne of the most common configuration tasks involves reranging thetransmitter 4 and 20 mA points.2-7

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151Reranging matches the transmitter range points with the applied processpressures. It can be performed three ways: using the communicator only,using the communicator and a reference pressure, or using the integral zeroand span buttons and a reference pressure.To decide which method is appropriate, consider the following: Reranging with only the communicator changes the analog 4 and 20mA points independently without a pressure input.This means that when you change either the 4 or 20 mA setting, you alsochange the span. For instance:If the transmitter is ranged so that4 mA 0 inH2O, and20 mA 100 inH2O,and you change the 4 mA setting to 50 inH2O using the communicator only,the new settings are:4 mA 50 inH2O, and20 mA 100 inH2O.Note that the span was also changed from 100 inH2O to 50 inH2O, while the20 mA setpoint remained at 100 inH2O.To obtain reverse output, simply set the 4 mA point at a greater numericalvalue than the 20 mA point. Using the above example, setting the 4 mA pointat 100 inH2O and the 20 mA point at 0 inH2O will result in reverse output.NOTEThe 4 and 20 mA output is based on the transmitter's existing digitalcalibration. Before reranging with the keypad, make sure the transmitter iscorrectly interpreting the process variable input. To match the transmitter'sreading in engineering units to plant standard, use the sensor trim functionunder “Digital Trim” in this section. Reranging with a pressure input and the communicator maintains thesame analog span. Reranging with a pressure input and the zero and span buttonsmaintains the same analog span.For instance, if the transmitter is ranged so that:4 mA 0 inH2O, and20 mA 100 inH2O,and you then change the 4 mA setting to 50 inH2O using the communicator (orbuttons) and a pressure input, the new settings are:4 mA 50 inH2O20 mA 150 inH2OThe 100 inH2O span is maintained.It is also important to note that when using a pressure source, the 4 and 20mA setpoints are based on the transmitter’s interpretation of the pressureinput provided. It is possible that when a plant standard is input, thetransmitter reads it as a slightly different value. Although the 4 and 20 mAsetpoints will operate properly within these applied settings, the transmitter’sdigital output in engineering units may indicate a slightly different value.2-8

Reference Manual00809-0100-4593, Rev CAJune 2007Rosemount 1151The sensor trim function under “Digital Trim” can be used to match thetransmitter’s reading in engineering units to your plant standard, therebyeliminating any discrepancy.NOTEReranging only the 4 mA or the 20 mA with a pressure input will maintain theinitial span width.NOTEDo not rearing the transmitter such that the 4 and 20 mA range points—upperrange value (URV) and lower range value (LRV)—are outside the high andlow digital sensor trim values. To optimize performance, the digital trim spanshould be equal to or slightly greater than the 4–20 mA span.Reranging with a Communicator OnlyHART Comm.1, 2, 3, 1, 1Rosemount 268F

Rosemount 1151 Commissioning the Rosemount 1151 with a HART-Based Communicator Before putting the Rosemount 1151 Smart Pressure Transmitter into operation, commission the instrument using a HART-based communicator. To commission on the bench, connect a 17 to 45 V dc power supply and a current meter, such as the Rosemount 282 Validator.

Related Documents:

www.rosemount.com 00825-0100-4593X Quick Installation Guide 00825-0100-4593, Rev AB September 2006 Rosemount 1151 HART Rosemount 1151 Smart Pressure Transmitter

www.rosemount.com 00825-0100-4360N Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Connect the Wiring and Power Up Step 4: Set Switches Step 5: Configuration Step 6: Trim the Transmitter Product Certifications Start End Rosemount 1151 Pressure .

Section 6–Retrofitting the Rosemount 1151 Transmitter This section describes how the Rosemount Smart Retrofit Kit can be used to retrofit a Rosemount 1151AP, DP, GP, HP, or LT transmitter with 4-20 mA linear or square root output. Appendix A–Reference Information This appendix supplies reference and specification data, as well as orderingFile Size: 8MBPage Count: 176

Rosemount 3051 www.rosemount.com 00825-0100-4797G Quick Installation Guide 00825-0100-4797, Rev EA June 2010 Rosemount 3051 Pressure Transmitter with Profibus-PA Rosemount 3051CF Series Flowmeter Transmitter with Profibus-PA Start End Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Set the Jumpers

Rosemount 3051S/3051/2051/3095 Rosemount 1151 D C D Rosemount 3051S/3051/2051/3095 Rosemount 1151 Februari 2019. 8 Snelstartgids 2.6 Montagerichting inline-druktransmitter De drukpoort aan de lage kant (ref. atmosferische druk) op de inline-verschildruktransmitter bevindt zich in de hals van de transmitter, achter

Rosemount 3051S/3051/2051/3095 Rosemount 1151 D C D 00825-0100-4001_RevJD.fm Page 6 Thursday, September 8, 2016 3:40 AM. Quick Start Guide 7 September 2016 1.7 In-line gage transmitter orientation The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing.

Rosemount 3051S/3051/2051/3095 Rosemount 1151 D C D. July 2016 8 Quick Start Guide 2.6 In-line gage transmitter orientation The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing.

Rumki Basu, (2004) Public Administration: Concepts and Theories, Sterling Publication, Delhi. 22. Bhogale Shantaram, (2006) Lokprashasanache Siddhant aani Kaeryapadhati, Kailas Prakashan, Aurangabad. 23. Patil B. B., Public Administration (Marathi), Phadake Prakashan, Kolhapur, 2004. 8 SYLLABUS FOR TYBA POLITICAL SCIENCE (S-4) INTERNATIONAL POLITICS Course Rationale: This paper deals with .