Daikin VRVInstallation & CommissioningParticipant Guide

Daikin VRV Installation & CommissioningAgendaTraining ModulesTraining MaterialsSimulator Exercises

VRV I&C 1-Day Training AgendaClass IntroductionTraining Agenda & Handout ReviewVRV Prod. & Tech Review presentationBasic VRV Installation presentationVRVIII Component Control Wiring ExercisesBasic VRV RC Installation & Configuration presentationRemote Controller Simulator ExercisesVRVIII Commissioning Guide presentationVRVIII Commissioning Exercises – PCB SimulatorClass wrap-upTraining SurveysTraining End

Training Modules and MaterialsSlide Presentation ModulesVRV Prod & Tech Intro ReviewVRV Basic InstallationBasic VRV Remote Controller Installation & ConfigurationVRVIII Commissioning GuideMaterialsSimulatorsRemote Controller CD or DACA Controls Simulator BoxVRVIII Control PCB CDPrinted HandoutsVRVIII / VRVIII-S Service ManualsVRV-WIII Service Manual (optional)VRV RC Install & Config. BookletBasic VRV InstallationDIII-Net Wiring Quiz & Component Wiring ExercisesVRV Field SettingsVRVIII Commissioning Guide bookletVRV-WIII Commissioning Guide bookletMisc. MaterialsColored Pens or Pencils (Black – Blue – Red)Extra DIII-Net Wiring Quiz & Component Wiring Exercises

DIII-Net Control Wiring ExercisesExercise #1Write in your answers1. VRV DIII-Net Control Wire Specification:Indicate the DIII-Net Control Wire Specification2. Control Terminal Designations on VRVIII HP & HR Condensers:Indicate the Control Terminal Designations3. Control Terminal Designations on BSVQ Single Branch Selector Boxes:Indicate the Control Terminal Designations4. Control Terminal Designations on VRV Fan Coils:Indicate the Control Terminal Designations5. Control Terminal Designations on BRC1E71 and BRC2A71 Remote Controllers:Indicate the Control Terminal Designations

DIII-Net Control Wiring ExercisesDIII‐Net Wiring Exercise ExampleDraw in each circuit using a different color pencil or pen fromcomponent terminal to component terminal to indicate each controlcircuit – Indicate the “Daisy‐chain” wiring where required.## #### #### #### #### #### ##

DIII-Net Control Wiring ExercisesExercise #26 Ton Heat Pump with 3 zonesZone 1RXYQ72PBTJFXAQ18PVJUF1 F2F1 F2INF1 F2OUTQ1 Q2P1 P2Zone 2FXAQ18PVJUT1 T2F1 F2P1 P2Zone 3FXAQ18PVJUT1 T2F1 F2P1 P2FXAQ18PVJUT1 T2F1 F2P1 P2T1 T2

DIII-Net Control Wiring ExercisesExercise #312 Ton Manifolded Heat Pump with3 zones and i-Touch Multi-Zone ControllerRXYQ72PBYDRXYQ72PBYDZone 1F1 F2F1 F2INF1 F2OUTQ1 Q2F1 F2INF1 F2OUTP1 P2T1 T2Q1 Q2i-TouchZone 2F1 F2P1 P2T1 T2Zone 3F1 F2P1 P2T1 T2

DIII-Net Control Wiring ExercisesExercise #46 Ton Heat Recovery with 4 zonesREYQ72PBTJZone 1Zone 2Zone 3FXAQ18PVJUFXAQ18PVJUFXAQ18PVJUF1 F2P1 P2T1 T2F1 F2BSBoxF1 F2INF1 F2OUTQ1 Q2F1 F2OUTF1 F2INP1 P2T1 T2F1 F2BSBoxF1 F2OUTF1 F2INP1 P2Zone 4FXAQ18PVJUT1 T2F1 F2BSBoxF1 F2OUTF1 F2INP1 P2BSBoxF1 F2OUTF1 F2INT1 T2

DIII-Net Control Wiring ExercisesExercise #56 Ton Heat Recovery with 2 ZonesZone 1REYQ72PBTJFXAQ18PVJUF1 F2P1 P2T1 T2Zone 2FXAQ18PVJUF1 F2P1 P2FXAQ18PVJUT1 T2F1 F2P1 P2FXAQ18PVJUT1 T2F1 F2BSBoxF1 F2INF1 F2OUTQ1 Q2F1 F2OUTF1 F2INP1 P2BSBoxF1 F2OUTF1 F2INT1 T2

VRV SimulatorBRC1E71 Remote ControllerSimulator ExercisesTurn Controller Simulator ON or load Controller Simulator CDVerify the power-up sequence on the NAV Remote ControllerChange the Main Display from “STANDARD” to “DETAILED”Room TempDate & TimeDay of weekUse the “Field Settings Table” handout sheet for the following exercisesChange the Field Setting for “Priority of thermistor sensors for spacetemperature control” TO:“Only the Return Air Thermistor will be used”Change the “T1 T2” Field Setting TO: “ON/OFF” OperationVerify Field Setting Changes

VRV SimulatorVRVIII PCB “CD” Simulator CommissioningVRVIII Commissioning GuidePg. 44 Verify “Initialization” OperationPg. 56 Counting Indoor Fan Coil UnitsPg. 58 “Forced Fan On” ModePg. 60 Counting Branch Selector BoxesPg. 75 “Additional Refrigerant Charge” ModePg. 106 “Refrigerant Recovery/Evacuation” ModePg. 91 Initiate “Check Operation” Mode

4/23/2014 2014 Daikin North America, LLCSlide 1Introduction to DaikinA History of Integrity, Quality, Growth,and Cutting Edge Technology 2014 Daikin North America, LLCSlide 21

4/23/2014 Basic understanding of Daikin’s history Understand Daikin’s position in the global marketplace Understand Daikin’s commitment to the environment andthe industry Know what other resources are available to you and how touse them to your advantage Understand where to go for sales and technical supportSlide 3 2014 Daikin North America, LLCAbout DaikinIntroduction 2014 Daikin North America, LLCSlide 42

4/23/2014Daikin is a comprehensive global HVAC manufacturer offeringextensive products, including ducted and ductless air‐conditioning andheat pump systems for residential and commercial applications as wellas large‐sized HVAC systems for buildings and factories.Slide 5 2014 Daikin North America, t VRV system192419581982Beginsresearch onflourinerefrigerantsDevelopedfirst multi‐port mini‐split system19331969LaunchedAlthermaand 26‐SEERQuaternitySystem2009LaunchedVRV (VRVII & VRV‐S)in NorthAmericaAcquiredGoodmanManufacturing20122006 2014 Daikin North America, LLCSlide 63

4/23/20142014 Daikin ReleasesVRV IV 2014 Daikin North America, LLC Daikin is committed to providing homes, businesses andindustry with the most efficient HVAC solutions to meet yourcooling and heating needs, today and in the future. We are keenly aware of our responsibility to protect theenvironment in everything we do, and all our policies,practices and processes are developed and implementedwith environmental sustainability at their heart. We conductour business in accordance with green principles because itmakes sound economical, as well as ecological sense. 2014 Daikin North America, LLCSlide 7Slide 84

4/23/2014As the only company in the world dedicated to heating and air conditioning systemsand refrigerants, almost 90% of Daikin’s core business is focused on HVAC‐R. Daikinleads the way in energy efficiency, individualized comfort, and quality and is the #1 inHVAC manufacturing sales worldwide.17 Billion USDWorld %Other38%28%11%Europe, MiddleEast, & AfricaChina, SoutheastAsia, & OceaniaNorth, Central,& SouthAmerica 2014 Daikin North America, LLCSlide 9Who has made the largest investment in the North AmericanHVAC industry over the last 8 years? Daikin. 2014 Daikin North America, LLCSlide 105

4/23/2014 2014 Daikin North America, LLCSlide 11 Recover – Recycle – Reclaim – Reuse Partnerships with AHRI, ASHRAE and others 2014 Daikin North America, LLCSlide 126

4/23/2014Reduce CO² with Heat Pump SystemsFossil FuelsHeat PumpsSlide 13 2014 Daikin North America, LLCDaikin North AmericaIntroduction 2014 Daikin North America, LLCSlide 147

4/23/2014Our vision is to be the premier provider of the highest qualityair conditioning products, systems, services, and solutions inNorth America by focusing on outstanding, long‐term customerservice.To accomplish this, we will continue to hire the best people,always conduct our business easily and fairly, and operate withthe highest degree of integrity in all business practices.In order to attract and retain the best people, we are committedto providing the best training and creating an atmosphere ofteamwork where we help each other grow. 2014 Daikin North America, LLCSlide 15Daikin North AmericaTechnical Service & Training CenterCarrollton, TX 2014 Daikin North America, LLCSlide 168

4/23/2014Daikin North AmericaWestern Regional Sales & Training CenterIrvine, CA 2014 Daikin North America, LLCSlide 17Daikin North AmericaEastern Regional Sales & Training CenterLong Island City in Queens, NY 2014 Daikin North America, LLCSlide 189

4/23/2014 2014 Daikin North America, LLC 2014 Daikin North America, LLCSlide 19Slide 2010

ZOKNMARTXCE: Central RegionNE: North East RegionSE: South East RegionSO: Southern RegionWC: West CoastSCALMSGALASO 2014 Daikin North America, LLCSEFLSlide 21 Literature Brochures Leaflets Submittals Manuals Engineering Service Installation Website www.Daikinac.com Daikin Representativesand Sales Support Network 2014 Daikin North America, LLCSlide 2211

4/23/2014 Software Tools VRV Xpress Energy Calc TRL Technical Reference Library Spare Parts Bank Dr. Daikin Daikin eQuip App Training Product & Applications by Product Line Installation & Commissioning Service & Troubleshooting Sales Training General Courses Technical Support Email: techsupport@daikinac.com or servicerequest@daikinac.com 2014 Daikin North America, LLC Slide 23Daikin eQuip is designed for both smart phones and tablets. It placesinformation in your hands quickly and easily for all of your on‐the‐goneeds. Whether you’re a Daikin partner, dealer, engineer, or just interestedin the Daikin product, you can: SEARCH product information to quickly access and download your mostreferenced documents. SEND key information via email or text message (SMS) for immediate sharing. RETRIEVE instant updates for the most up‐to‐date news and information onDaikin AC.Search for Daikin eQuip in the APP store orAndroid Market! 2014 Daikin North America, LLCSlide 2412

4/23/2014 Basic understanding of Daikin’s history Understand Daikin’s position in the global marketplace Understand Daikin’s commitment to the environment andthe industry Know what other resources are available to you and how touse them to your advantage Understand where to go for sales and technical support 2014 Daikin North America, LLCThank YouPT‐INF‐1211‐PP0‐01C 2014 Daikin North America, LLCSlide 25PT‐RLC‐1306‐PP ‐01ASlide 2613

4/23/2014Slide 1 2013 Daikin North America, LLCPiping & R‐410AField Practices for Piping and ChargingDaikin Air Conditioning Equipment 2013 Daikin North America, LLCSlide 21

4/23/2014 Refrigerant recovery and the atmosphere Properties of R‐410A PVE oil Identify line set components Daikin dedicated tools Flared connections 2013 Daikin North America, LLC Brazing Standing pressure test and leak testing Triple evacuation process Pipe insulation Importance of liquid charging 2013 Daikin North America, LLCSlide 3Slide 42

4/23/2014Recover – Recycle – Reclaim ‐ ReuseDaikin cares for our environmentSlide 5 2013 Daikin North America, LLCR‐410A 2013 Daikin North America, LLCSlide 63

4/23/2014 Developed since 1991Ozone friendly ‐ No ChlorineLower Significant ODP than R22Near Azeotrope50/50 MixtureTemperature Glide .02 FNot compatible with mineral oilsGenerally non toxic, non flammableNearAzeotropeSlide 7 2013 Daikin North America, LLC Recovery cylinder must be rated for R‐410A 400 PSIG Service Pressure Rated 800 PSIG Test Pressure Rated DOT BA400, DOT BW400R‐410AStore refrigerants in a clean, dry area outof direct sunlight. Never heat cylindersabove 125 F(52 C). 2013 Daikin North America, LLCSlide 84

4/23/2014 Asphyxia Heavier than air Products of Decomposition Skin Irritant Frostbite Storage below 125 F ASHRAE111HMIS 1Do not leak test with air20NFPA 704 2013 Daikin North America, LLCSlide 9Pressure is approximately 60% higher than with R‐22Adequate tools and service devices needed 2013 Daikin North America, LLCSlide 105

4/23/2014Working with PVE OilSlide 11 2013 Daikin North America, LLCR‐410A & Mineral Oil 2013 Daikin North America, LLCR‐410A & PVE OilSlide 126

4/23/2014 PVE oil is optimal for systems that do not use line set driers Compatible with all HFC Refrigerants Excellent anti‐wear properties Better solubility with process fluids Superior Resistance to Cap tube blockage Better lubricity Optimal for non‐drier systems Very Hygroscopic but with no hydrolysis Moisture easily removedSlide 13 2013 Daikin North America, LLCRefrigerant Lines 2013 Daikin North America, LLCSlide 147

4/23/2014Only install driers, oil traps, shut off valves or any other linecomponents in your piping work if instructed to do so in theIOM documents – if no instruction, it’s because it is NOTnecessary (for Daikin).The only acceptable piping is ACR (copper) type tubing whichis dehydrated and sealed at both ends. 2013 Daikin North America, LLCSlide 15We do not recommend Isolation Valves be installed in Daikinsystems; however, there are times when the specifications requirethem: Compatibility with R‐410A and PVE (Polyvinylether) oil Temperature operation range of ‐40 F to 300 F Working pressure of 550 PSIG, capable of handling up to 700PSIG Full flow valve with 0 pressure drop Bi‐directional flow Brazed connections Service port in valve body 2013 Daikin North America, LLCSlide 168

4/23/2014100 F x 100 ft x 12 in./ft. x 0.0000094 in./in./F 1.128 in.Reference: The Copper Tube Handbook published by Copper.org ‐ the #1 resource for technical and professional informationregarding copper and copper alloys.Slide 17 2013 Daikin North America, LLCPoint of tensionClampsNoMovement 2013 Daikin North America, LLCAlternativeMovementSlide 189

4/23/2014Slide 19 2013 Daikin North America, LLC50 F 2013 Daikin North America, LLC186 FSlide 2010

4/23/2014Refrigerant Line InsulationSlide 21 2013 Daikin North America, LLC 2013 Daikin North America, LLCRefrigerant piping must bemaintained cleanDuring the course ofinstallation, the refrigerantlines should beoccasionally blown outwith dry nitrogen to driveout any particulate debrisWhen the piping is notconnected to the indoorand outdoor units, theends must be properlysealedSlide 2211

4/23/2014ALL pipe work must beinsulated along its full runusing 3/4” Wall Insulationminimum.Take extra care to cover theflare nuts on the fan coilsusing the insulationprovided or condensationwill occur causing waterleaks.The liquid line must be insulatedAlways follow local codesCould cause excessivesubcooling.Slide 23 2013 Daikin North America, LLCInsulation of support brackets 2013 Daikin North America, LLCSlide 2412

4/23/2014Keep copper ends sealed to preventdebris from settling in the piping.Pinched & brazedCapped or tapedWhen the refrigerant lines are not connected and dormant duringconstruction there are two recommended methods of sealing the ends 30 days cap or tape the ends 30 days pinch and braze the endsSlide 25 2013 Daikin North America, LLCTools 2013 Daikin North America, LLCSlide 2613

4/23/2014 All of our serviceconnections are 5/16” Dedicated manifold R‐410A Rated up to 550and 800 PSIG 5/16” hose connectionsHose Pressure 800 PSIG Rated 2013 Daikin North America, LLC 2013 Daikin North America, LLCSlide 27Slide 2814

4/23/2014Torque Wrench KitPart No. TLTWSM 2013 Daikin North America, LLC Service Tool KitDACA‐99S TK‐1Slide 29Pump capacity should be aminimum of 6 cfmVacuum pump should have acheck valvePump must be kept properlymaintainedChange pump oil frequently 2013 Daikin North America, LLCSlide 3015

4/23/2014 As driers are not used in VRV refrigerant lines it is imperative to properlyevacuate the system to remove all moisture to insure a dry systemAll Daikin systems must be triple evacuated down to 500 microns or less The moisture level can only be determined with an accurate microngauge Never evacuate a refrigeration system using atmospheric pressurealone500m 2013 Daikin North America, LLC Slide 31Daikin systems are charged with R‐410A refrigerant by weight based onthe length of the liquid lines All liquid lines should be measured as accurately as possible to insureoptimum system performance Each liquid line diameter is multiplied by a factor per measured foot of pipinglength The refrigerant charge is designated as the “Additional Refrigerant Charge” A good digital scale must be used to properly weigh in the liquid R‐410Arefrigerant 2013 Daikin North America, LLCSlide 3216

4/23/20145/16” ValveCore RemovalTool w/sideportMetric Hex Keys3/8”Nitrogen RegulatorRated 750‐1000 PSIG1/4”Slide 33 2013 Daikin North America, LLCFlaring 2013 Daikin North America, LLCSlide 3417

4/23/2014Proper deburring is critical to a successful flareSlide 35 2013 Daikin North America, LLC“B” depth for ¼”pipeGo / No GoBFlaringBlockADACA‐FSG‐1“B” depth for all other sizesDimension “A” requirementDimension “B” RequirementPipe SizeDimensionPipe SizeDimension1/4”9.1mm1/4”1 mm3/8”13.2mm3/8”2 mm1/2”16.6mm1/2”2 mm5/8”19.7mm5/8”2 mm3/4”24.0mm3/4”2 mm 2013 Daikin North America, LLCSlide 3618

4/23/2014BrazingSlide 37 2013 Daikin North America, LLCDry Nitrogen MUST be used during all brazing(Pressure regulated to 1.5 to 3 PSIG) to preventoxidation formation Tape in Schrader Fitting Set Nitrogen regulator to1.5 – 3 PSIG Leave other end of pipeopen 2013 Daikin North America, LLCSlide 3819

4/23/2014Pressure Test & EvacuationSlide 39 2013 Daikin North America, LLCVerify all stop valves are securely closed before pressure test550 psiMax. pressure for anysystem installed with one ormore FXTQ Air Handlers450 psiOR325 psi150 psi3 Min 2013 Daikin North America, LLC5 Min24 Hr24 HrSlide 4020

4/23/2014Use commercial liquid leakdetector 2013 Daikin North America, LLCSlide 41What is a micron as a unit of measurement for a vacuum? 2013 Daikin North America, LLCSlide 4221

4/23/2014Daikin Recommends Triple Evacuation Evacuate the system to 4000 microns and hold for 15minutes Break vacuum with dry nitrogen to a pressure of 2‐3 PSIGand hold for 20 minutes Evacuate to 1500 microns and hold for 20 minutes Break vacuum with dry nitrogen to a pressure of 2‐3 PSIGand hold for 20 minutes Evacuate below 500 microns and hold for 60 minutesSlide 43 2013 Daikin North America, LLCAtmosphericpressureVacuumService portsShutoff valveVacuum pumpmineral oil level 2013 Daikin North America, LLCSlide 4422

4/23/2014System Refrigerant Charging 2013 Daikin North America, LLCSlide 45Weigh in additional refrigerant with digital scales Calculate charge based on total line length x lb/ft ofdiameter. Check with each model for correct multiplier. 2013 Daikin North America, LLCSlide 4623

4/23/2014 The ozone is only part of the equation in refrigerant containment andrecycling. R‐410A is a very efficient blended refrigerant but it requires knowledgeand skills to be used correctly and safely. Daikin chose PVE as for its properties and easier system dehydration. Daikin does not require dryers, sight glasses, or oil traps on systeminstallations. Expansion must be taken into consideration to prevent fractures or cracksin the gas lines due to temperature increases. Daikin recommends a dedicated tool set including gauges for working onDaikin equipment. 2013 Daikin North America, LLC R‐410A systems require a different flaring block for making flaredconnections. Dry nitrogen purge while brazing prevents oxidation inside of the lines. Pressure test and evacuation must be completed according to bestpractices in the industry. All lines must be insulated including the liquid and the condensate lines. Daikin requires R‐410A to be charged as a liquid and a complete recoveryand recharge in the event of a leak. 2013 Daikin North America, LLCSlide 47Slide 4824

4/23/2014Thank YouPT‐CAP‐1305‐PP0‐01C 2013 Daikin North America, LLCPT‐RLC‐1306‐PP ‐01ASlide 4925

1/18/2013DAIKIN VRVProduct & Technology IntroductionReviewRESIDENTIAL LIGHT COMMERCIAL COMMERCIALTraining DepartmentSeptember 2012 2012 Daikin ACDaikin VRV ConceptWhat is VRV ? Variable - System capacity varies with loadRefrigerant - R-410A Direct Expansion SystemVolume - Refrigerant flow regulated by EEV’sand a variable speed compressorVRV - Daikin Registered trademarkIntroduced in 1982 – Worlds first VRF systemOver 1 million installations worldwideOver 25,000 systems in the US and CanadaMultiple Indoor units connected to onecondenser systemAir Cooled and Water Cooled systemsUltra high comfort control and efficiencySlide 2 2012 Daikin AC1

1/18/2013Daikin VRV conceptMultiple Fan Coil Control Inverter Daikin VRVDaikin VRV incorporatesmultiple technologies to provideultra high energy savings,comfort control and reliabilityMultiple indoor fan coils connected toa single refrigerant networkInverter control system to modulatesystem capacity as loads changeHeat Pump & Heat Recoverysystems1Slide 3 2012 Daikin ACDAIKIN VRV Product &Technology IntroductionVRV System ModelsVRVIII-S VRVIII VRV-WIII Condensers & Indoor Units 2012 Daikin AC2

1/18/2013VRV Systems208/230 vac Single Phase Heat Pump3 Ton & 4 Ton ModelsUp to 14.9 SEER / HSPF 9.1Slide 5 2012 Daikin ACVRV NomenclatureVRVIII‐SVRVIII-SHeat PumpRXY MQ 36/48 PTJUUL listed for US marketvoltage208 - 230V 1ph 60HzRevisionCooling CapacityRefrigerant R410ATrunk-shaped VRV systemRXY: Heat PumpSlide 6 2012 Daikin AC3

1/18/2013VRV SystemsVRVIII‐S Heat PumpRXYMQ36&48P208/230vac 1Ph - 30 amp power to Outdoor UnitOutdoor unit Models: 36,000 & 48,000 Btu/hSingle Inverter scroll compressorIndoor unit capacities 7,000 to 48,000 Btu/hSingle 2-Pipe refrigerant circuitConnection of up to 6 or 8 indoor unitsConnection ratio of 50% to 130% possible1000’ - Maximum refrigerant piping lengthOperating Range – Cool: 23 to 115 F Heat: 0 to 77 F7Slide 7 2012 Daikin ACSlide 8 2012 Daikin ACVRV Systems208/230 & 460vac Three PhaseHeat Pump & Heat Recovery Models6 to 30 Ton Systems4

1/18/2013VRV NomenclatureVRVIIIRXYHeat PumpQ ##PB TJ or YD460vac 3ph 60Hz208/230vac 3ph 60HzRevisionCooling CapacityRefrigerant R410AAir Cooled Heat PumpHeat Pump condensers are manufactured to be single piped or manifolded (Excl. RXYQ144PBTJ)Slide 9 2012 Daikin ACVRV NomenclatureVRVIIIREYHeat Recovery Single PipedQ ## PB TJ or YD460vac 3ph 60Hz208/230vac 3ph 60HzRevisionCooling CapacityRefrigerant R410AAir Cooled Heat RecoveryREYQ Heat Recovery condensers are manufactured to be single piped only: 6,8,10 & 12 ton (Excl. REYQ144PBYD)Slide 10 2012 Daikin AC5

1/18/2013VRV NomenclatureVRVIIIHeat Recovery Manifolded ModuleREM Q ##PB TJ or YD460vac 3ph 60Hz208/230vac 3ph 60HzRevisionCooling CapacityRefrigerant R410AAir Cooled Heat RecoveryManifolded ModuleREMQ Heat Recovery condensers are manufactured to be manifolded only: 6,8,10 & 12 ton (Excl. REYQ144PBTJ)Slide 11 2012 Daikin ACVRV SystemsVRV IIIRXYQ & REY(M)Q208/230vac 3ph and 460vac 3ph modelsHeat Pump and Heat Recovery modelsDual scroll compressors – 1 Inverter and 1 StandardExcl. 6 ton HP & HR units & 12 ton 208/230vac. unitsSystem capacities: HP 6 – 30 Ton / HR 6 – 28 TonConnection of up to 62 indoor unitsConnection ratio of 50% to 200% possible3,280’ - Maximum refrigerant piping lengthOperating Range: Cool: 23 to 115 F Heat: 0 to 77 F6Slide 12 2012 Daikin AC6

1/18/2013VRV Systems208/230 vac. 3 Phase460 vac. 3 PhaseHeat Pump / Heat Recovery6 to 21 Ton SystemsSlide 13 2012 Daikin ACVRV NomenclatureVRV-WIIIRWEY Q 72/84P TJ YD U or N460vac 3ph 60Hz208/230vac 3ph 60HzRevisionCooling CapacityRefrigerant - R410AWater-cooled typeSame unit model is used for Heat Pump - Heat Recovery & Geothermal operation.Slide 14 2012 Daikin AC7

1/18/2013VRV SystemsVRV-WIIIWater Cooled RWEYQ P208/230vac & 460vac 3 phase models6 & 7 ton single condenser modelsHeat Pump / Heat Recovery operationGeothermalSingle inverter scroll compressorSystem capacities: 6 to 21 tonStandard EWT: 60 F to 113 FGeothermal EWT: 14 F (heat)Max. refrigerant piping length: 980 ft.Connection of up to 12 – 32 fan coilsStandard connection ratio: 50% to 130%Interior Installation OnlyField Configured Geothermal Operation6Slide 15 2012 Daikin ACVRV SystemsIndoor Units3’X3’ Ceiling Cassette6 & 8 Ton MedStatic Ducted2’X2’ Ceiling CassetteWallmount100% Outside AirProcessing Unit12 Types55 ModelsMed StaticDC DuctedEnergy RecoveryVentilatorLow Static SlimDuct ConcealedUnitary DuctedExposed & Concealed Floor StandingCeiling SuspendedAll 208/230vac 1 Phase poweredSlide 16 2012 Daikin AC8

1/18/2013DAIKIN VRV Product &Technology IntroductionVRV Basic Controls 2012 Daikin ACVRV Basic ControlsLocal Remote ControllersBRC1E71BRC2A71Navigation Remote II – NET 16vdc digital control networkSlide 18 2012 Daikin AC9

1/18/2013VRV Basic ControlsRemote SensorKRCS01-1B (4B)VRV Fan Coil Units incorporate a built‐in return air thermistortemperature sensor as standard (excl. FXTQ)KRCS01‐1B (4B) Remote Sensor is offered to replace the return air thermistorwhen:Outside fresh air is brought in to the fan coil return airCeiling height of fan coil return is 13ft or moreAbove ceiling plenum return is usedStandard 39ft cable ‐ Plenum Rated 40ft and 80ft cable optionalNOTE:KRCS01-4B Remote Sensor Kit for FXMQ P, FXFQ P and FXTQ Fan Coil Units4Slide 19 2012 Daikin ACDAIKIN VRV Product &Technology IntroductionVRV System TypesHeat Pump / Heat Recovery 2012 Daikin AC10

1/18/2013VRV Heat Pump SystemsAll indoor fan coil units operate in the same mode, Heat or CoolVRVIII-SVRV WIIIORORFXMQ MDucted unitVRV IIIRXYQ2 – Pipe Refrigerant CircuitHP/LP GasLiquidFXMQ PDC Ducted UnitBRCIE71ProgrammableFXFQ P Round FlowOne Remote Controller is configured as the system MasterSlide 21 2012 Daikin ACVRV Heat Pump SystemsRefNet ComponentsDaikin has designed RefNet YBranch and Headers to beused for branching off fromthe main refrigerant lines.Split the refrigerantcircuitBranch off to the indoorfan coilsRefNets are engineered tocontrol turbulence andmaintain flow through therefrigerant system.RefNets are provided in 4capacity KitsHeat Pump KitLiq. & HP/LP GasRefNets MUST be installed inspecific positionsY Branch:Level / UP / DOWNHeader – Level Only3RefNet “Y” Branch – GasRefNet “Y” Branch LiquidRefNet Header 4-portRefNet Header 8-portGasLiquidSlide 22 2012 Daikin AC11

1/18/2013VRV Heat Pump SystemsDaikin DIII-Net ArchitectureHeat PumpTransmission wiringThe DIII‐Net communications is proprietary to Daikin VRV systemsSimple 2 conductor wire, non polarity sensitive, 16vdc communications circuit16/18 awg. 2-conductor stranded, non-shieldedDaisy chain wiring to all system componentsMaximum system control wire length: 6,600 ft.Slide 23 2012 Daikin ACVRV Heat Pump SystemsControl Circuit Terminal DesignationsAll VRV Fan CoilsFan Coil Control Terminal CircuitsP1 P2 – Fan Coil to Remote ControllerRemote Controller power supply and data transferF1 F2 – Communications from condenser to all Fan CoilsT1 T2 – Forced Off (Default N.O.) External ContactsCondenser Control Terminal CircuitsF1 F2 In – Condenser to Fan CoilsF1 F2 Out – Multi-Zone ControliTouchiTouch ManagerGateway – LON Works or BACnetQ1 Q2 (VRVIII & VRV-WIII) – Manifolded ModulesVRVIII – VRV-WIII1VRVIII-SSlide 24 2012 Daikin AC12

1/18/2013VRV Heat Pump SystemsOperation Mode ChangeoverHeat Pump controlled fan coils all operate in the same mode and requireone Remote Controller to be configured as the MasterThe Master remote controller determines the system mode of operation (Cool,Dry, Heat, Fan) based on the Heat and Cool setpoints or user selected mode.The Master RC determines the mode that the slaves can operate under:Master in Cool or DrySlaves: Cool, Dry and Fan are availableMaster in Heat modeSlaves: Heat and Fan are availableMaster in Fan modeSlaves: Fan is AvailableHeat PumpSlaveMasterSlaveSlave4SlaveSlide 25 2012 Daikin ACVRV Heat Recovery SystemsIndoor fan coil units operate in simultaneous Heat and Cool modesVRV IIIREYQ/REMQVRV WIIIORFXMQ MDucted unitFXMQ PDC Ducted UnitBranch Selector Box3 – Pipe Refrigerant CircuitSuction GasLiquidHP/LP GasBRCIE71ProgrammableFXFQ P Round FlowSlide 26 2012 Daikin AC13

1/18/2013VRV Heat Recovery SystemsBranch Selector BoxProvides Heating/Cooling changeoverto the connected fan coil or fan coilsEEV refrigerant controlBrazed refrigerant connections208/230vac 1 ph. powered208-230vac.Single Port Model Numbers:BSVQ36PVJU 36,000 Btu - Up to 5 FC’sBSVQ60PVJU 60,000 Btu - Up to 8 FC’sBSVQ96PVJU 96,000 Btu - Up to 8 FC’sLiquid pipeEEVEEV’sHP/LP Gas PipeSuction gas pipe1Slide 27 2012 Daikin ACVRV Heat Recovery SystemsOperation Mode ChangeoverWhen two or more Fan Coils with dedicated Remote Controllersare connected to one BS-Box, one of the Remote Controllers mustbe configured as the MasterMaster determines the BS-Box operation modeThe Slave indoor units follow the Master’s operation modeHeat sterSlide 28 2012 Daikin AC14

1/18/2013VRV Heat Recovery SystemsBranch Selector Control CircuitsTransmission wiringBSVQ PF1 F2 INBS-BoxBS-BoxBS-BoxBS-BoxSame 2 conductor control wire used to connect all Branch Selectors to CondenserF1 F2 In daisy chain wired from Condenser terminal block to F1 F2 Out on BranchSelectorsF1 F2 In from Branch Selector to F1 F2 on connected fan coil(s)1Slide 29 2012 Daikin ACDAIKIN VRV Product &Technology IntroductionVRV Refrigerant PipingLengths 2012 Daikin AC15

1/18/2013VRV Refrigerant PipingRefNet Piping Length RequirementsThe Standard maximum distance from thefirst RefNet to the farthest fan coil is 130ft.Exception: VRV III can be extended to 295ft from thefirst RefNet to the farthest fan coil: rules applyAll Branch runs must be 130ft or less from a RefNet“Y” or RefNet Header, to the fan coil.No requirement for Branch Selector Box130 ft.4Slide 31 2012 Daikin ACDAIKIN VRV Product &Technology IntroductionVRV Basic SystemControl Operations 2012 Daikin AC16

1/18/2013VRV Basic System ControlCompressor Capacity ControlInverter ControlAdjusts compressor speed (capacity)up or down to correct deviation fromthe target pressure values (systemload)37 Applied Capacity StepsCondenser ControlCOOL OperationControl SystemSets Target low & high pressurevalues at the CondenserSets the Target evap. & cond.Temps in the indoor Fan CoilsLocal Remote Controllers in

and refrigerants, almost 90% of Daikin’s core business is focused on HVAC‐R. Daikin leads the way in ene

Related Documents:

Daikin VRV Installation and Commissioning 1-day or 2-day training be utilized to provide comprehensive training to HVAC installation professionals. Log on to the Daikin University website for full training information. Along with the factory training, the Daikin

Daikin VRV Sizing & Simulation Plug-in User Guide IES Virtual Environment 2013 . . The selected condenser displays the Daikin model reference, when multiple VRV systems have been created, click each condenser in turn to view the associated fan coil information in the System & Fan Coil . VRV module will re-select the required sized units.

VRV Air Conditioning System is the world's first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982. VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call "variable refrigerant volume." VRV is a trade mark of Daikin Industries, Ltd. S

VRV Air Conditioning System is the world's first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982. VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call "variable refrigerant volume." VRV is a trade mark of Daikin Industries, Ltd. Dealer

3. Hi-VRV The complete air conditioning system 44 Variable Refrigerant Volume 46 VRV Inverter heat pump series 46 VRV Heat recovery series 47 VRV Plus series using R-407C 48 VRV Plus series using R-22 49 VRV Indoor units 50 Heat Recovery Ventilation 57

VRV IV HP VRV IV HR ASHRAE 90.1 2016 Air Cooled HP ASHRAE 90.1 2016 Air Cooled HP. 7. SYSTEM OVERVIEW. Simple Modular Design. The Features of . VRV. Features & Benefits to Using . VRV . The benefits of . VRV. equipment can be categorized by three core features: Drei ct expansoi n systems (those . that use refrigerant to directly . condition the .

VRV-WIII › Availableinheatpumpand heat recovery 1987 Introduction the original VRV air conditioning system to Europe, invented by Daikin in 1982 › Ex 1991 Introduce VRV heat recovery Simultaneous cooling and heating 1994 Awarded ISO9001 certification 2004 Expand to light commercia

The Daikin VRV T-Series Water Cooled is a flexible and modular energy saving alternative to traditional centralized equipment solutions such a Chilled Water System or Water Source Heat Pumps (WSHP). The VRV T-Series Water Cooled provides all of the attributes of an Air-cooled VRV