Article 250 Grounding & Bonding

2y ago
33 Views
2 Downloads
1.03 MB
17 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Rosemary Rios
Transcription

Article 250 Grounding & BondingAMERICAN ELECTRICAL INSTITUTEN16 W23217 Stone Ridge Dr.Waukesha, WI 53188855-780-5046www.AEItraining.comDISCLAIMER NOTE: This course is APPROVED for continuing education to renew yourelectrical license and is not intended to replace or supersede any state or local adopted codes

AMERICAN ELECTRICAL INSTITUTE 2015   77Article 250 Grounding & BondingArticle 250.1 Scope.Article 250 is organized into 10 different parts that deal with specific requirements with regards to bondingand grounding. The specific parts are as follows:(I) General(II) System Grounding(III) Grounding Electrode System and Grounding electrode Conductor(IV) Enclosure, raceway, and service Cable Grounding(V) Bonding(VI) Equipment grounding and Equipment grounding Conductors(VII) Methods of Equipment Grounding(VIII) Direct Current Systems(IX) Instruments, Meters, Relays(X) Grounding of Systems and Circuits of over 1000 VoltsArticle 250.2 Supply Side Bonding JumperThis definition was added in the 2011 code cycle and states: A conductor installed on the supply side of aservice or within a service equipment enclosure(s), or for a separately derived system that ensures the requiredelectrical conductivity between metal parts required to be electrically connected.250.3 Application of Other Articles. The 2014 Coderequires for other articles applying to particularcases of installation of conductors and equipment,grounding and bonding requirements are identifiedin Table 250.3 that are in addition to, or modificationsof, those of this article.250.4 (A)(1) Electrical System Grounding. Electricalsystems that are grounded are required to beconnected to earth in a manner that will limit thevoltage imposed by lightning, line surges, orunintentional contact with higher-voltage linesand that will stabilize the voltage to earth duringnormal operation.250.4(A)(4) Bonding of Electrically Conductive Materials and other Equipment. Normally non–current-carryingelectrically conductive materials that are likely to become energized shall be connected together and to theelectrical supply source in a manner that establishes an effective ground fault current path.250.6 (A) Arrangement to Prevent Objectionable Current. The grounding of electrical systems, circuitconductors, surge arresters, surge-protective devices, and conductive normally non–current-carrying metalparts of equipment shall be installed and arranged in a manner that will prevent objectionable current.250.6 (C) Temporary Currents Not Classified as Objectionable Currents. Temporary currents resulting fromabnormal conditions, such as ground faults, shall not be classified as objectionable current for the purposesspecified in 250.6(A) and (B).

78     AMERICAN ELECTRICAL INSTITUTE 2015Exam Questions1. A new hospital is being built that has a 13,800 voltmain. The grounding and bonding for this scenariowould be referenced in part .A. VB. IVC. IXD. X2. An instrument transformer is required to be connectedto an equipment grounding conductor, and specificrequirements to accomplish this activity would belocated in part of article 250.A. IXB. XC. VIID. IV3. While working at an aluminum smelter, you are askedto do all the grounding for a 200 volt direct currentcrane. What part of article 250 should be referenced?A. VB. VIIIC. IXD. X4. If you wanted to know the method of exactly how toground cord and plug connected equipment, partwould be used.A. IXB. IC. VIID. II5. The equipment grounding conductor required toserve a 400 amp panel would be determined in partof article 250.A. VIB. IVC. XD. IX6. Information as to ensure electrical continuity and thecapacity to conduct any fault current that might beimposed through bonding would be referenced inpart of article 250.A. IVB. IIIC. VID. V7. How many parts is Article 250 comprised of?A) 7B) 10C) 5D) 88. What section of Article 250 describes the scope of thearticle?A) 250.6 (C)B) 250.4(A)(4)C) 250.2D) 250.19. What part of Article 250 would you find the correctmethod of bonding enclosures?A) VB) VIC) IVD) III10. When looking for some basic general information inarticle 250 like definitions and basic objectives, partof this article is where you would look.A. IIB. IC. IIID. IV11. The supply side bonding jumper ensures electricalbetween metal parts.A. CurrentB. VoltageC. ConductivityD. Power12. Grounded systems are required to be connected toearth in such a way as to limit voltage due to .A. Unintentional contact with higher-voltage linesB. Lightning strikesC. Line surgesD. All listed answers13. What table in the National Electrical Code would youfind specific bonding requirements?A. Article 230B. Article 670C. Article 250.3D. No listed answer

AMERICAN ELECTRICAL INSTITUTE 2015   7914. Non-current metal parts are required to be installedto prevent .A. Dust build upB. HeatC. Objectionable currentD. Spikes16. True or False? An effective ground fault current pathshall be established if non-current carrying conductivematerials are likely to become energized and shall beconnected together.A. TrueB. False15. Article 250.6(A. and (B).classifies ground faults as .A. Objectionable currentB. Temporary currentsC. Impaired currentD. Stray currents250.6 (E) Isolation of Objectionable Direct-Current Ground Currents. Where isolation of objectionable dcground currents from cathodic protection systems is required, a listed ac coupling/dc isolating device shall bepermitted in the equipment grounding conductor path to provide an effective return path for ac ground-faultcurrent while blocking dc current.250.8 (B) Methods Not Permitted. Article 250 requires the connection devices or fittings that depend solelyon solder shall not be used.250.12 Clean Surfaces. The 2014 code requires nonconductive coatings (such as paint, lacquer, and enamel) onequipment to be grounded shall be removed from threads and other contact surfaces to ensure good electricalcontinuity or be connected by means of fittings designed so as to make such removal unnecessary.250.20 (A) Alternating-Current Systems of Less Than 50 Volts. As required bythis code, alternating-current systems of less than 50 volts shall be groundedunder any of the following conditions:(1) Where supplied by transformers, if the transformer supply system exceeds150 volts to ground(2) Where supplied by transformers, if the transformer supply system is ungrounded(3) Where installed outside as overhead conductors250.20 (C) Alternating-Current Systems of 1 kV and Over. As described by article250, alternating-current systems supplying mobile or portable equipment shallbe grounded as specified in 250.188. Where supplying other than mobile orportable equipment, such systems shall be permitted to be grounded.250.20 (D) Impedance Grounded Neutral Systems. Impedance groundedneutral systems shall be grounded in accordance with 250.36 or 250.186.250.21(C) Ground Detectors. MarkingSubsection (C) was added in the 2014 Code. This section requires ungrounded systems to be marked at thesource of the first disconnecting means. The marking at this location shall read “Ungrounded System " and themarking must be legible and able to withstand the environment where it is located.250.24(C)(1)&(2) Grounded Conductor Brought to Service Equipment.Some verbiage changes have taken place with regards to this article concerning the grounded conductor. Wheninstalled in a single raceway, the grounded conductor cannot be smaller than the grounding electrode conductorselected from 250.66; moreover, the grounded conductor is not required to be larger than the ungrounded conductors.If the ungrounded service conductors are installed in parallel in more than one raceway, then the groundedconductor must be installed in parallel as well. Table 250.66 will be used to select the grounded conductor basedon the size of the largest service entrance conductors and shall not be smaller than 1/0 when run in parallel.

80     AMERICAN ELECTRICAL INSTITUTE 2015Exam Questions17. If isolation of objectionable DC current is required, itis must be installed in the path.A. Equipment grounding conductorB. Grounding conductorC. Grounded conductorD. Bonding jumper23. Ungrounded systems are required to be marked atthe disconnecting means.A. NewB. FirstC. SecondD. Last18. A fitting used to connect a grounding system thatdepends solely on solder be used.A. WillB. ShallC. CanD. Shall not24. When marking ungrounded systems, the markingshall legibly read " ".A. Ungrounded systemB. Do not touchC. Look outD. Open system19. Equipment that is being grounded is required to havecoatings removed at the point of connection.A. LacquerB. PaintC. EnamelD. All listed answers25. Would it be considered acceptable or a violation tomark an ungrounded system located in a wet corrosiveenvironment with un-protected normal paper?A. AcceptableB. Violation20. An AC system that operates at 50 volts or less mustbe grounded if .A. Installed outside as overhead conductorsB. Supplied by transformers, if the transformer supplysystem is ungroundedC. Supplied by transformers, if the transformer supplysystem exceeds 150 volts to groundD. All listed answers21. An AC system that operates at 1200 volts and suppliesportable equipment is required to be grounded inaccordance with .A. 250.66B. 250.188C. 250.122D. 250.52(A)22. The grounding for an impedance grounded neutralsystem has option(s).A. 4B. 3C. 2D. 126. In a single raceway, the grounded conductor cannotbe sized smaller than the .A. Grounded conductorB. Ungrounded conductorC. Grounding electrode conductorD. Equipment grounding conductor27. True or False? The grounded conductor is required tobe larger than the ungrounded conductors.A. TrueB. False28. The grounding electrode conductor is sized usingtable .A. 310.16B. 250.122C. 250.66D. 430.16629. Is it required or suggested that when the ungroundedconductors are run in parallel, the grounded conductorwill also be run in parallel.A. RequiredB. Suggested

AMERICAN ELECTRICAL INSTITUTE 2015   8130. What is the smallest size conductor that can be usedfor the grounded conductor when it is run in parallel?A. #1B. # 2C. # 3D. 1/0250.30 Grounding Separately Derived Alternating Current Systems. Informational Note 1A new informational note has been added which states on site generators are not considered a separately derivedsystem if the grounded conductor (neutral) is solidly connected to the service supplied grounded conductor.What would make a generator a separately derived system is if a transfer switch also switched the groundedconductor (neutral). A transformer is always considered a separately derived system.250.30(C) Grounding Separately Derived AlternatingCurrent Systems. Outdoor SourceIf a separately derived system is located outside, aconnection to one or more grounding electrodesis required at the source to comply with 250.50.The reason for connecting grounding electrodesto separately derived systems at the source is toprotect them from lightning strikes and other voltagespikes that could cause damage to such sourceslike transformers and generators. By connectinggrounding electrodes to sources in this manner, wecan limit possible damage from these voltage spikes.250.32(B)(1) Buildings or Structure supplied by a feeder or branch circuit.This section requires that when a branch circuit or feeder is run to a building to supply power, a separate equipmentgrounding conductor is required to be run with that circuit or feeder. The equipment grounding conductor canbe sized using table 250.122. The grounded conductor cannot be used for this purpose in new construction.250.52(A)(1) Grounding Electrodes. Electrodes permitted for Grounding. Metal Underground Water Pipe.A metal water pipe is considered a grounding electrode if it is in contact with the earth for a minimum of 10ft.Additionally, the grounding electrode conductor is still required to connect to the metal water pipe within 5 ftof where it enters the building. The 5 ft connection rule has been moved to 250.68(C) since the 5 ft of water pipeextending out of the building is considered more of a grounding electrode conductor since it is no longer indirect contact with the earth and that portion is not considered a grounding electrode. Only the actual buriedwater pipe in direct connection with the earth is considered the grounding electrode.Exam Questions31. To make a generator considered a separately derivedsystem, a transfer switch needs to switch theconductor.A. UngroundedB. GroundingC. GroundedD. Phase32. A transformer is always considered a .A. Branch circuitB. Separately derived systemC. Utility operated deviceD. Generator

82     AMERICAN ELECTRICAL INSTITUTE 201533. The grounding electrode connections need to bemade at the location.A. PoleB. LastC. PropertyD. Source34. Grounding electrode systems help protect sourceequipment like transformers and generators fromvoltage .A. SpikesB. LagsC. DrainsD. Systems37. The grounded conductor can be used to ground abuilding in a new construction situation.A. TrueB. False38. A metal water pipe that has a minimum offt in direct contact with the earth is consideredgrounding electrode.A. 8B. 7C. 10D. 535. Would it be considered acceptable or a violation torun an equipment grounding conductor with a circuitthat is feeding a detached garage.A. AcceptableB. Violation39. The grounding electrode conductor is required to connectto a buried metal water pipe within ft of where itenters a building barring the use of any exceptions.A. 5B. 6C. 8D. 1036. An equipment grounding conductor shall be sizedusing table .A. 310.15aB. 250.66C. 250.122D. 310.1640. The part of a metal water pipe that extends into abuilding could now be considered a .A. ElectrodeB. Grounding electrodeC. Grounding electrode conductorD. Bonding jumperArticle 250.52(A)(2) Metal frame of The Building or Structure.Metal frames of buildings and structures can be used as a groundingelectrode if at least one structural member is in direct contact withthe earth for a minimum of 10 ft. encased or not in concrete andthe hold down bolts for a column directly connect to a concreteencased electrode.Article 250.52(A)(3) Concrete-Encased Electrode.This section concerning concrete encased electrodes has been revised.A 1/2 in diameter 20 ft. long bare or galvanized steel reinforced baris considered a concrete encased electrode. Separate pieces of rebartied together that equal 20 ft. would also meet the requirementsof a concrete encased electrode. If rebar is not available, a bare #4copper conductor at least 20 ft long can also be used as a groundingelectrode if it is encased in a minimum of 2 inches of concrete layingvertically or horizontally in a footing or column as long as the footingis in direct contact with the earth.A new informational note has been added that indicates concretewith a vapor barrier or other film that separates the concrete fromthe earth is not considered in direct contact with the earth.

AMERICAN ELECTRICAL INSTITUTE 2015   83Article 250.53(A)(3) Grounding Electrode Installation. Rod, Pipe and Plate electrodes. SupplementalElectrode RequiredThis general rule requires when a plate electrode, pipe, or driven rod is used as an electrode, a supplementalelectrode is required. The electrodes listed in 250.52(A)(2) through (A)(8) can be used as a supplementalelectrode. When using a ground rod or pipe as the supplemental electrode, it shall be spaced a minimum of 6ft. away from the first electrode.Exception: If using a single electrode and the resistance is 25 ohms or less, then a supplemental electrode willnot be required.250.53 (D) (1) Continuity. The 2011 code requires that the continuity of the grounding path or the bondingconnection to interior piping shall not rely on water meters or filtering devices and similar equipment.250.53 (H) Plate Electrode. Article 250 requires plate electrodes to be installed not less than 750 mm (30 in.)below the surface of the earth.Exam Questions41. Building steel can be used as a grounding electrode ifat least ft. of the structure is in direct contactwith the earth.A. 6B. 8C. 9 ½D. 1042. Metal frames of buildings and structures can be usedas a grounding electrode if at least one structuralmember is in direct contact with the earth for aminimum of ft. encased.A. 10B. 6C. 10D. 543. Hold down bolts used to secure a building columncan be used as a grounding electrode if the bolts areconnected to the .A. EarthB. ConcreteC. A PVC pipeD. Concrete encased electrode44. A piece of rebar 20 ft. long meets the requirement fora concrete encased electrode provided the rebar is aminimum in diameter.A. 1/4 inB. 3/8 inC. 1/2 inD. 3/16 in45. A concrete encased electrode must be a minimum offt. long.A. 20B. 17C. 18D. 1646. Would it be considered acceptable or a violation totie 2 11' pieces of rebar together with tie wire and usethat as a concrete encased electrode provided the 2pieces of rebar tied together were over 20' and therebar was 1/2 inches in diameter.A. AcceptableB. Violation47. A piece of # bare copper conductor could beused as a concrete encased electrode provided it wasencased in the minimum amount of concrete required.A. 8B. 6C. 4D. 1048. If a continuous piece of number 4 bare copper conductorwas used instead of a piece of rebar for a concreteencased electrode, the number 4 wire needs to beencased in a minimum of inches of concrete.A. 2B. 1C. 1 1/2D. 1/2

84     AMERICAN ELECTRICAL INSTITUTE 201549. When referring a concrete encased electrode, theconcrete in which an electrode is encased does nothave to be in direct contact with the earth.A. TrueB. False50. When using a plate, pipe, or driven rod as an electrode,a supplemental electrode is .A. PurchasedB. SuggestedC. PromotedD. Required51. When using a rod or pipe supplemental electrode, itshall be spaced a minimum of ft. from thefirst electrode.A. 8B. 4C. 6D. 253. If a single electrode has a resistance of ohmsor less, than a supplemental electrode is not required.A. 43B. 27C. 30D. 2554. Continuity of the grounding path or bondingconnection to interior piping shall not rely on:A. Both B and CB. Water metersC. Filtering devices and similar equipmentD. Neither A nor B55. A plate electrode shall not be installed less thaninches below the surface of the earth.A. 48 inchesB. 36 inchesC. 30 inchesD. 24 inches52. The electrodes listed in can be used asa supplemental electrode.A. 210.42(A)(2.) through (A)(8)B. 250.52(A)(2) through (A)(8)C. 250.53(A)(3) though (A)(9)D. No listed answersArticle 250.64(B) Grounding Electrode Conductor Installation. Securing and protection against Physical DamageGrounding Electrode Conductors are now permitted to be installed through framing members. This revisiontakes into consideration that the framing members adequately protect the grounding electrode conductorfrom physical damage.Article 250.64(D)(1) grounding Electrode Installation. Service with Multiple Disconnecting means Enclosures.Common Grounding Electrode Conductor and tapsA service that has multiple grounding electrode taps due to multiple disconnects shall connect to a commongrounding electrode conductor that is connected to a common busbar for these connections. The busbarshall be at least 1/4 in. x 2 in. aluminum or copper and shall be securely fastened in an accessible location. Theconnections to this busbar shall be made by a listed connector or by exothermic welding.Article 250.68(C) Conductor and Bonding Jumper Connection to Grounding Electrodes. Metallic Water Pipeand Structural MetalThis section allows a buried metal water pipe that enters a building within 5 ft. to bond directly to building steelthat is above ground. This provides a path to the grounding electrode and provides a way to tie everything intothe grounding electrode system.The metal water pipe within 5 ft of entering the building is now permitted to be used as a conductor path to connectall electrodes together that are part of the grounding electrode system. The buried metal water pipe that is in contactwith the earth can only be considered an electrode if it is in direct contact with the earth for a minimum of 10 ft.

AMERICAN ELECTRICAL INSTITUTE 2015   85250.92(B) Method of Bonding at the service. This sectionrequires bonding jumpers to be used around reducing washers,oversized eccentric and concentric knockouts for conduits thatcontain service conductors. The code calls this an “impairedconnection” and the use of bonding jumpers is required aroundsuch connections. Service conductors do not have overcurrentprotection ahead of them so it is extremely important to ensurea low impedance path for any fault currents that may occur. Thissection now clarifies that bonding around reducing washers,oversized eccentric, and concentric knockouts are now requiredwhen raceways contain service conductors.250.94 Bonding for other systems. An intersystem bondingtermination point is required to be accessible to bond systemscovered in 770 and Chapter 8. This point shall be installedexternal to enclosures at the service equipment or meteringequipment enclosures as well as at the disconnecting meansfor other buildings and structures. Intersystem Bondingterminations are required to comply with 6 different provisionsas listed in 250.94 of this code.250.98 Bonding Loosely Jointed Metal Raceways. Expansionfittings and telescoping sections of metal raceways to bemade electrically continuous by equipment bonding jumpersor other means.250.102(A) Material. Article 250 requires bonding jumpers to be made of copper or other corrosion-resistantmaterial. A bonding jumper shall be a wire, bus, screw, or similar suitable conductor.Exam Questions56. Would it be acceptable or a violation to run thegrounding electrode conductor for a 400 amp servicethrough metal stud framing members?A. AcceptableB. Violation57. If a service has multiple disconnecting enclosures,then all the grounding electrode taps need to connectto a common .A. Grounded conductorB. Grounding electrode conductorC. Equipment grounding conductorD. Phase conductor58. When multiple electrode taps connect to a commonbusbar where the grounding electrode conductor isalso connected, the busbar shall be a minimum of.A. 1/4 in. x 2 in.B. 1/2 in. x 2 in.C. 1 in. x 3 in.D. 2 in. x 2 in.59. When connecting grounding electrode taps to acommon busbar where the common groundingelectrode conductor is also connected, the approvedmethod for attachment to the common busbar is bya connector or exothermic welding.A. CO/ALB. DesignedC. CopperD. Listed

86     AMERICAN ELECTRICAL INSTITUTE 201560. When using a common busbar for multiple groundingelectrode taps connected to a common groundingelectrode conductor, the busbar shall be located inan location.A. OpenB. GuardedC. AccessibleD. Shielded64. Using reducing washers, oversized concentric oreccentric knockouts without any bonding jumpers forconduits that contain service conductors is known asa (an) connection.A. GroundedB. ImpairedC. SolidD. Bonding61. The code allows a buried metal water pipe entering abuilding within ft. to tie directly to buildingsteel as to provide a path to the grounding electrode.A. 6B. 5C. 7D. 1065. An intersystem bonding point is required to beto the metering and service equipment.A. InternalB. ExternalC. IntegralD. All listed answers62. For a metal water pipe to be considered a groundingelectrode, it must be in direct contact with the earthfor a minimum of ft.A. 2B. 5C. 9D. 1063. If installing a conduit that has service conductorsinside using reducing washers, the use of ais now required to ensure a low impedance path forany fault currents.A. Lock nutB. Meyer’s hubC. Bonding jumperD. All listed answers66. This code has different requirements forinter system bondingA. 3B. 5C. 6D. 767. If using an expansion joint on a 2” aluminum conduit,the code requires a (an) to be installed aroundthe expansion joint.A. Equipment bonding jumperB. Equipment grounding conductorC. Grounding jumperD. Both C and B68. A bonding jumper can be a .A. WireB. BusC. ScrewD. All listed answers250.102(C)(1)&(2) Size Supply-side Bonding Jumper. The supply side bonding jumper is installed beforethe service equipment overcurrent protective device and provides electrical conductivity between the metalparts of the service equipment. The supply side Bonding jumper is required to be sized using table 250.102(C)(1). If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, then asrequired by this code, the supply side bonding jumper shall be no less than 12 ½ percent of the area of thelargest ungrounded supply conductor set.250.102 (E) Installation. Article 250 allows bonding jumpers or conductors and equipment bonding jumpersto be installed inside or outside of a raceway or an enclosure.250.102 (E)(1) Inside a Raceway or an Enclosure. If installed inside a raceway, equipment bonding jumpersand bonding jumpers or conductors must comply with the requirements of 250.119 and 250.148.

AMERICAN ELECTRICAL INSTITUTE 2015   87250.102 (E)(2) Outside a Raceway or anEnclosure. Article 250 requires if installed on theoutside of a raceway, the length of a bondingjumper or conductor or equipment bondingjumper shall not exceed 1.8 m (6 ft) and shallbe routed with the raceway or enclosure.250.104(A)(1) General. Metal water pipingsystem installed in or attached to a buildingor structure is required to be bonded to theservice equipment enclosure, the groundedconductor at the service, the groundingelectrode conductor where of sufficient size, orto the one or more grounding electrodes used.250.104(C) Structural steel. Bonding of pipingsystems and exposed structural steel. Interconnected structural steel that is likely to become energized is required bythis code to be bonded to the service equipment enclosure, grounding electrode, grounding electrode conductor(if of sufficient size), and the grounded conductor at the service. This bonding jumper is required to be sized usingtable 250.66 and is based on the largest ungrounded branch circuit or feeder. Bonding jumper points of attachmentare required to be accessible unless allowed by 250.68(A) Exception No. 2 to be covered by fireproofing material.250.106 Lightning Protection Systems. The lightning protection system ground terminals to be bonded tothe building or structure grounding electrode system.Exam Questions69. Table is used to size the supply side bondingjumper.A. 250.122B. 250.102(C)(1)C. 250.104D. 250.12170. If you are installing 2000 Kcmil aluminum ungroundedsupply conductors for a service, the supply sidebonding jumper needs to be sized not less than% of the largest supply conductor set.A. 13B. 12 ¼C. 12 ½D. 1071. A set of 1250 kcmil copper ungrounded serviceentrance conductors in a single raceway would requirea copper supply side bonding jumper.A. 1/0B. 3/0C. 4/0D. # 272. Would it be considered acceptable or a violation ofthis code to install a bonding jumper outside of araceway.A. AcceptableB. Violation73. A bonding jumper is required to comply withif installed in a raceway.A. 250.118B. 250.119 and 250.148C. 250.66 and 250.122D. No listed answer74. An equipment bonding jumper installed outside ofa raceway cannot exceed feet.A. 6B. 5C. 4D. 3

88     AMERICAN ELECTRICAL INSTITUTE 201575. A metal water pipe in a strip mall is required to beconnected to the .A. Grounded conductor at the serviceB. Grounding electrodesC. Service equipment enclosureD. All listed answers77. The steel of a structure that is likely to becomeenergized is required by this code to be .A. WeldedB. BondedC. PlatedD. Coated76. True or False? The points of attachment for bondingjumpers are always required to accessible.A. TrueB. False78. The lightning protection system of an office buildingis required to be connected to the .A. Grounding electrode systemB. Service enclosureC. Meter canD. All listed answers250.119 Identification of Equipment Grounding Conductors. In general, an equipment grounding conductors shallbe permitted to be bare, covered, or insulated. Individually covered or insulated equipment grounding conductorsshall have a continuous outer finish that is either green or green with one or more yellow stripes except as permittedin this section. Conductors with insulation or individual covering that is green, green with one or more yellow stripes,or otherwise identified as permitted by this section shall not be used for ungrounded or grounded circuit conductors.250.120 (B) Aluminum and Copper-Clad Aluminum Conductors. Article 250 allows equipment groundingconductors of bare or insulated aluminum or copper-clad aluminum to be used. Bare conductors shall not comein direct contact with masonry or the earth or where subject to corrosive conditions. Aluminum or copper-cladaluminum conductors shall not be terminated within 450 mm (18 in.) of the earth.250.120 (C) Equipment grounding conductorssmaller than 6 AWG. Where not routed withcircuit conductors as permitted in 250.130(C)and 250.134(B) Exception No. 2, equipmentgrounding conductors smaller than 6 AWGshall be protected from physical damage byan identified raceway or cable armor unlessinstalled within hollow spaces of the framingmembers of buildings or structures and wherenot subject to physical damage.250.121 Use of Equipment GroundingConductors. An Equipment GroundingConductor shall not be used as a GroundingElectrode Conductor. This new section wasadded to the 2011 Code to clarify that theEquipment Grounding Conductor and Grounding Electrode Conductors serve 2 different purposes. The groundingelectrode conductor is sized using table 250

Article 250.1 Scope. Article 250 is organized into 10 different parts that deal with specific requirements with regards to bonding and grounding. The specific parts are as follows: (I) General (II) System Grounding (III) Grounding Electrode System and Grounding electrode Conductor (IV) En

Related Documents:

Grounding Study and Analysis: Substation Grounding Practices Grounding Concepts - GPR and Touch Potential AEP Innovative Grounding Study Methods Grounding Installation: Traditional Approach and Challenges Grounding Application and Installation Change Management Testing: Grounding Integrity Testing Conclusion and .

Mar 26, 2019 · Coming to terms with NEC Article 250 Grounding & Bonding Grounding Electrode (Ground Rod Installation) Separately Derived System Grounding Portable and Vechicle Mounted Generators Multiple Sources of Supply (12 ft. Rule) Ground-Fault Current &am

Amendments to the Louisiana Constitution of 1974 Article I Article II Article III Article IV Article V Article VI Article VII Article VIII Article IX Article X Article XI Article XII Article XIII Article XIV Article I: Declaration of Rights Election Ballot # Author Bill/Act # Amendment Sec. Votes for % For Votes Against %

NEC Table 250.122 - Minimum size equipment grounding conductors for grounding raceway and equipment Table 2 – Minimum size equipment grounding conductors for grounding raceway and equipment Aluminum Cable Tray Systems Table 392.60(A) – Metal area requiremen

grounding electrode grounding electrode conductor neutral 208y/120v panel or disconnect supply side isolated netural bonding jumpers terminal note: the supply side bonding jumpers and the grounding electrode conductor shall be sized per nec table 250.66. n g a b c equipment grounding 480v conductor no. description date 2 addendum 5 1/10/22 2

Grounding & Bonding 1 Grounding & Bonding — Why it is done And How to Install Properly . Because 250.26 of the Code requires the neutral conductor of a single-phase, 3-wire system to be grounded, in our example, the electrician will normally use a bare copper wire to connect the neutral conductor (often called the grounded conductor) to a .File Size: 1MB

Modern Chemistry 1 Chemical Bonding CHAPTER 6 Chemical Bonding SECTION 1 Introduction to Chemical Bonding OBJECTIVES 1. Define Chemical bond. 2. Explain why most atoms form chemical bonds. 3. Describe ionic and covalent bonding. 4. Explain why most chemical bonding is neither purely ionic or purley 5. Classify bonding type according to .

AGMA American Gear Manufacturers Association AIA American Institute of Architects. AISI American Iron and Steel Institute ANSI American National Standards Institute, Inc. AREA American Railway Engineering Association ASCE American Society of Civil Engineers ASME American Society of Mechanical Engineers ASTM American Society for Testing and .