Power Defense Time Current Curve Frame 4 - PD4

2y ago
9 Views
2 Downloads
1.30 MB
34 Pages
Last View : 3d ago
Last Download : 3m ago
Upload by : Maxine Vice
Transcription

Technical Data TD012066ENEffective November 2019Supersedes November 2018Time current curves Power Defense MCCBFrame 4 thermal-magnetic and PXR electronic trip unitsStandards: UL, CSA, IEC, le1.2.3.4.5.6.PageRevision notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Breaker catalog number convention. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electronic trip unit catalog number convention. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Magnetic trip unit thermal catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Symmetrical RMS interruption ratings (kA) for each breaker frame. . . . . . . . . . . . . . . . . . . . . . . .Curve notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .344555LabelsFigure 1. Power Defense frame 4 trip unit front labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6PXR electronic trip unit curvesFigure 2. PXR 20D / PXR 25 - I2t long delay and flat short delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 3. PXR 20 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 4. PXR 20D / PXR 25 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 5. PXR 20 I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 6. PXR 20D / PXR 25 - I4t long delay and flat short delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 7. PXR 20D / PXR 25 - ground (earth) flat delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 8. PXR 20D / PXR 25 - ground (earth) I2t delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 9. PXR 20 - ground (earth) flat delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 10. PXR 20 - ground (earth) I2t delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 11. PXR 20D / PXR 25 - instantaneous and override for 800A frame . . . . . . . . . . . . . . . . . . . . . . . 16Figure 12. PXR 20D / PXR 25 - instantaneous (1000A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 13. PXR 20 / PXR 10 - instantaneous (800A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Figure 14. PXR 20 / PXR 10 - instantaneous and override 1000A frame . . . . . . . . . . . . . . . . . . . . . . . . . 19Figure 15. PXR 20 / PXR 20D / PXR 25 - maintenance mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 16. PXR 10 LI 800A frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Figure 17. PXR 10 LI 1000A frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Figure 18. PXR 10 LSI profile for short flat curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 19. PXR 10 LSI profile for I2t short curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Technical Data TD012066ENEffective November 2019Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Thermal magnetic trip unit curvesFigure 20. Fixed thermal adjustable magnetic 300A-600A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Figure 21. Fixed thermal adjustable magnetic 700A-800A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 22. Adjustable thermal adjustable magnetic 630A-1000A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Peak let through curvesFigure 23. 240V let through current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 24. 240V peak let through energy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 25. 415V-480V let through current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 26. 415V-480V let through energy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 27. 600V let through current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Figure 28. 600V let through energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2EATON www.eaton.com282930313233

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019Table 1. Revision notesNote: Unless noted below, all curves remain unchanged from their prior revision.Revision1Power Defense frame 4 initial release2Short delay tolerances adjusted for phase and ground on I2t slopes.Curve numberPageDate11/2019EATON www.eaton.com3

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019This information is provided only as an aid to understand the catalog numbers.It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available.Table 2. Catalog number conventionPDG4 3 M 0800 P2M JTerminals includedBreaker familyPDG4 Frame 4 global UL /CSA / IEC / GBPDF4 Frame 4 global-100%UL / CSA / IEC / GB(uses PDG trip units)PDC4 Frame 4 IEC / GBN No terminalsTrip unit typeInterruptingrating designatorkA at480 V (UL)Icu/cs(kA) at415 V (IEC)G 3536/36K 5050/50M 6570/53N -70/70Continuouscurrent rating0300 300 A0350 350 AT## Thermal magnetic tripunit (1)J Line and load terminalsV## 50 C calibrated thermalmagnetic trip unit (1)L Load only terminalsK Line only terminalsB## PXR 10 (1)0400 400 AE## PXR 20 (1)0500 500 AD## PXR 20D (1)0600 600 AP## PXR 25 (1)0630 630 AKNS Molded case switch0700 700 ASNN Switch disconnector0800 800 A1000 1000 APoles3 3 pole4 4 pole with 100%neutral protection6 4 pole with 60%neutral protection0 4 pole with 0%neutral protectionNote: 1 See catalog for ## (protection type and available configured options).Table 3. Electronic trip unit catalog number conventionPDG4 x PXR 3 0800 D 2 WFeaturesStyle familyPDG4 Frame 4 global UL /CSA / IEC / GB forPDG and PDF breakersPDC4 Frame 4 IEC / GB forPDC and PDF breakersN NoneTrip unitPXR Electronic trip unitAmpere frame rating0800 800 A framePoles1000 1000 A frame3 3 polesAccessoriesx Breaker accessory4 4 poles withprogrammableneutral protectionETU trip unit styleB PXR 10E PXR 20D PXR 20DP PXR 25R RelaysZ ZSI, relaysM Modbus, relaysC CAM interface, relaysD Modbus, CAM interface, relaysW ZSI & ModbusX ZSI, CAM interface, relaysY ZSI, Modbus, CAM interface,relaysETU protection style1 LI (PXR10 IEC only)2 LSI3 LSIG4 LSI ARMS5 LSIG ARMSNote: IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.4EATON www.eaton.com

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019Table 4. Magnetic trip unit thermal catalog number conventionPDC4 x TFA 3 0800Style familyPDG4 Frame 4 Global UL /CSA / IEC / GBPDC4 Frame 3 IEC / GBAccessoriesx Breaker accessoryAmpere frame ratingTrip unitTFA Thermal fixed adjustable magnetic0300 300 A frameTAA Thermal adjustableadjustable magnetic0400 400 A frameVFA Thermal fixed 50%Ccalibratedadjustable magnetic0500 500 A frameVAA Thermal adjustable50% C calibratedadjustable magnetic0350 350 A frame0450 450 A frame0600 600 A frame0630 630 A frame0700 700 A frame0800 800 A frame1000 1000 A framePoles3 3 pole4 4 pole with 100%neutral protection6 4 pole with 60%neutral protection0 4 pole with 0%neutral protectionNote: IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.Table 5. Symmetrical RMS interruption ratings (kA) for each breaker oballyrated(UL 52510-22PDF4xM10065351007050503015-25IEC / -25PDC4xN (1000A)---10070-6535---Globallyrated*800A frame unless notedTable 6. Curve notes1.These curves apply for 50Hz and 60Hz applications2.The maximum voltage rating for the frame style is stated in Table 5.3.These curves are comprehensive for Power Defense style circuit breakers including frame sizes, ratings and constructions stated.4.The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current. The bottom of the time band is the minimum commit to trip time.5.The end of the curve is determined by the application or the interrupting rating of the circuit breaker.6.Thermal magnetic trip unit calibration based on 40ºC ambient, cold start. Tested with 4 feet of rated wire (75ºC) per terminal. Tested in open air with current in all poles.7.Thermal magnetic trip unit instantaneous calibration based on single pole testing.8.All electronic trip units have an over temperature protection feature that will trip the breaker when the internal temperature of the ETU is over 105ºC9All time current data for PXR is based on 3 phase testing.EATON www.eaton.com5

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019LabelsPXR 25 and PXR 20D – unit with LSIG protection and maintenance mode picturedPXR 20 – unit with LSIG protection and maintenance mode picturedPXR 10 – unit with LSI protection picturedFixed thermal, adjustable magnetic unit picturedFigure 1. Power Defense frame 4 trip unit front labelsNote: Trip unit drawings in Figure 1 are representative of the face plates provided. Values on the trip unit dials will changebased upon the specific breaker and trip unit. Refer to the time current curve of the breaker or the PXR User Guide for thespecific settings.6EATON www.eaton.com

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019CurvesPXR 20D / PXR 25- I2t Long Delay and Flat Short Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25①1000PDGPDF800 APDC800 APDC1000 AMin.Max.320 A800 A320 A800 A400 A1000 ANotes:1 Long delay pickup is 110% of the Ir setting with 5% tolerance. Ir is set from min to max at stepsof 10A.2. Long delay time settings adjustable from 0.5s- 24s at steps of 0.1s with 0%/-30% tolerance.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x 8.0x at steps of 0.1x with 5% tolerance.5. Short delay time settings adjustable from 0.050s- 0.500s at steps of 0.010s with tolerance asfollows: ime delay settings 0.500s to 0.200shave tolerances of 0%/-20%, time delay settings between 0.190s to 0.160s have tolerancesof 0%/-30%, .and time delay settings between0.150s to 0.100s have tolerances of 0%/-40%and time delay settings between 0.090s to 0.050shave tolerances of 0/-50%.6. If the long delay time is projected to be fasterthan the short delay time, the long delay triptime will go no faster than the short delay timevalue.7. With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.②100Time in SecondsIrsettingtr se ngrange10810.5④1.5Isdse ngrangetsd se ng range80.10.050.010.1110100Current in Mul ples of Long Delay Se ng (I r)Figure 2. PXR 20D / PXR 25 - I2t long delay and flat short delayNovember 2019EATON www.eaton.com7

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20 - I2t Long Delay and Flat Short Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20①1000②Time in Seconds1001.5232.51PDGPDF800 APDC800 APDC1000 A12345678910320 A350 A400 A450 A500 A550 A600 A630 A700 A800 A320 A400 A450 A500 A550 A600 A630 A700 A750 A800 A400 A550 A630 A700 A750 A800 A850 A900 A950 A1000 ANotes:1. Long delay pickup is 110% of the Ir setting with 5% tolerance.2. Long celay time settings as shown have 0%/30% tolerance.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. Short delay pickup settings as shown have 5%tolerance.5. Short delay time settings are shown with tolerances.6. If the long delay time is projected to be fasterthan the short delay time, the long delay triptime will go no faster than the short delay timevalue.7. With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 0.010.1110100Current in Mul ples of Long Delay Se ng (I r)Figure 3. PXR 20 - I2t long delay and flat short delay8EATON www.eaton.comNovember 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25①1000②Time in Secondstr settingrange10Isdsettingrange1.5PDGPDF800 APDC800 APDC1000 AMin.Max.320 A800 A320 A800 A400 A1000 ANotes:1 Long delay pickup is 110% of the Ir setting with 5% tolerance. Ir is set from min to max at stepsof 10 A.2. Long delay time settings adjustable from 0.5s- 24s at steps of 0.1s with 0%/-30% tolerance.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x 8.0x at steps of 0.1x with 5% tolerance.5. Short Delay I2t slope time settings adjustablefrom 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings0.300s to 0.200s have tolerances of 0/-30%,time delay settings between 0.190s to 0.160shave tolerances of 0/-30%, and time delay settings between 0.150s to 0.100s have tolerancesof 0/-40% and time delay settings between0.090s to 0.067s have tolerances of 0/-50%.After approximately 8x the I2t slope will go flatand those times have tolerances as follows: timedelay settings 0.300s to 0.200s have tolerancesof 0/-20%, time delay settings between 0.190sto 0.160s have tolerances of 0/-30%, and timedelay settings between 0.150s to 0.100s havetolerances of 0/-40% and time delay settingsbetween 0.090s to 0.050s have tolerances of 0/50%.6. If the long delay time is projected to be fasterthan the short delay time, the long delay triptime will go no faster than the short delay timevalue.7 With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.100④Irsetting810.3tsd setting range0.1⑤0.0670.010.1110100Current in Multiples of Long Delay Setting (I r)Figure 4. PXR 20D / PXR 25 - I2t long delay and I2t short delayNovember 2019EATON www.eaton.com9

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR20 - I2t Long Delay and I2t Short Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20①1000②PDGPDF800 APDC800 APDC1000 A12345678910320 A350 A400 A450 A500 A550 A600 A630 A700 A800 A320 A400 A450 A500 A550 A600 A630 A700 A750 A800 A400 A550 A630 A700 A750 A800 A850 A900 A950 A1000 ANotes:1. Long delay pickup is 110% of the Ir setting with 5% tolerance.2. Long celay time settings as shown have 0%/30% tolerance.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. Short delay pickup settings as shown have 5%tolerance.5. Short delay time settings are shown with tolerances.6. If the long delay time is projected to be fasterthan the short delay time, the long delay triptime will go no faster than the short delay timevalue.7. With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.100Time in 0670.010.1110100Current in Multiples of Long Delay Setting (I r)Figure 5. PXR 20 I2t long delay and I2t short delay10EATON www.eaton.comNovember 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20D / PXR 25 - I4t Long Delay and Flat Short Delay Curves100000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25①10000Time in Secondstr setting②range101④1.5IsdsettingrangePDGPDF800 APDC800 APDC1000 AMin.Max.320 A800 A320 A800 A400 A1000 ANotes:1. Long delay pickup is 110% of the Ir setting with 5% tolerance. Ir is set from min to max at stepsof 10 A2. Long delay time settings adjustable from 0.5s - 7sat steps of 0.1s with 0%/-30% tolerance.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. Short delay pickup settings adjustable from 1.5x 8.0x at steps of 0.1x with 5% tolerance.5. Short delay time settings adjustable from 0.050s- 0.500s at steps of 0.010s with tolerances asfollows: time delay settings 0.500s to 0.200shave tolerances of 0/-20%, time delay settingsbetween 0.190s to 0.160s have tolerances of 0/-30%, and time delay settings between 0.150sto 0.100s have tolerances of 0/-40% and timedelay settings between 0.090s to 0.050s havetolerances of 0/-50%.6. If the long delay time is projected to be fasterthan the short delay time, the long delay triptime will go no faster than the short delay timevalue.7. With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.1000100Irsetting80.5tsd setting range0.10.050.010.1110100Current in Multiples of Long Delay Pickup (Ir)Figure 6. PXR 20D / PXR 25 - I4t long delay and flat short delayNovember 2019EATON www.eaton.com11

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20D / PXR 25 - Ground (Earth) Flat Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25Notes:1. Ground pickup settings adjustable from 0.2x - 1.0xat steps of 0.010x for residual sensing with atolerance of 10%.2 Ground time delay settings adjustable from0.100s – 1.00s at steps of 0.010s with tolerancesas follows: time delay settings 1.00s to 0.200shave tolerances of 0/-20%, time delay settingsbetween 0.190s to 0.160s have tolerances of 0/30%, and time delay settings between 0.150s to0.100s have tolerances of 0/-40%.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4 With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.Time in Seconds1000100100.2Igsettingrange1.0①11.0tg setting range0.10.010.10.1110Current in Multiples of Rating(In)Figure 7. PXR 20D / PXR 25 ground (earth) flat delay12EATON www.eaton.comNovember 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR20D / PXR25 - Ground (Earth) I2T Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25Notes:1. Ground pickup settings adjustable from 0.2x - 1.0xat steps of 0.010x for residual sensing with atolerance of 10%.2. Ground I2t slope time settings are adjustable from0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings0.300s to 0.200s have tolerances of 0/-30%,time delay settings between 0.190s to 0.160shave tolerances of 0/-30%, and time delay settings between 0.150s to 0.100s have tolerancesof 0/-40% and time delay settings between0.090s to 0.067s have tolerances of 20%/-50%.After approximately 1x the I2t slope will go flatand those times have tolerances as follows: timedelay settings 0.300s to 0.200s have tolerancesof 0/-20%, time delay settings between 0.190sto 0.160s have tolerances of 0/-30%, and timedelay settings between 0.150s to 0.100s havetolerances of 0/-40% and time delay settingsbetween 0.090s to 0.050s have tolerances of 20%/-50%.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4 With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.Time in Seconds1000100100.2Igsettingrange①1.010.3tg setting range0.10.0670.010.1110Current in Multiples of Rating(In)Figure 8. PXR 20D / PXR 25 - ground (earth) I2t delayNovember 2019EATON www.eaton.com13

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20 - Ground (Earth) Flat Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 20Notes:1. Ground pickup settings as shown are for residualsensing with a tolerance of 10%.2. Ground slope flat time setting are shown withtolerances.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50HzTime in 30.20.150.10.010.10.1110Current in Multiples of Rating(In)Figure 9. PXR 20 - ground (earth) flat delay14EATON www.eaton.comNovember 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR20 - Ground (Earth) I2T Delay Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert Release-PXR 20Notes:1. Ground pickup settings as shown are for residualsensing with a tolerance of 10%.2. Ground I2t flat time setting are shown with tolerances.3. If thermal memory is enabled, trip times may beshorter than indicated in this curve.4. With ZSI enabled and no auxiliary power, trippingtimes for 3-phase faults will be a maximum of60ms for 60Hz and 63ms for 50Hz.Time in 10.1110Current in Multiples of Rating(In)Figure 10. PXR 20 - ground (earth) I2t delayNovember 2019EATON www.eaton.com15

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20D / PXR 25 - 800A Frame Instantaneous Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25Notes:1. The instantaneous pickup settings adjustable from2x – 8.5x(max) at steps of 0.10x with a 10%tolerance.2 For high fault current levels a fixed instantaneousoverride is provided at 6800 A and has a 15%tolerance.1000Time in Seconds100①Max8.5210800A Frame Override Curve10IiSettingrange1Time in Seconds10.10.10.01110Current in Multiples of Rating (In)0.011000②1001000Current in AmpsFigure 11. PXR 20D / PXR 25 -instantaneous and override for 800A frame16EATON www.eaton.com1000010000November 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20D / PXR 25 - 1000A Frame Instantaneous Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20D / PXR 25Notes:1. The instantaneous pickup settings adjustable from2x – 8x(max) at steps of 0.10x with a 10% tolerance.2. For high fault current levels a fixed instantaneousoverride is provided at 8000 A and has a 15%tolerance.1000Time in Seconds100①Max8210101000A Frame Override CurveIiSettingrange1Time in Seconds10.10.10.011100.011000 100Current in Multiples of Rating (In)Figure 12. PXR 20D / PXR 25 - instantaneous (1000A)②1000Current inAmps1000010000November 2019EATON www.eaton.com17

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20 / PXR 10 - 800A Frame Instantaneous Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20 / PXR 10Notes:1. The instantaneous pickup settings as shown witha 10% tolerance.2. For high fault current levels a fixed instantaneousoverride is provided at 6800 A and has a 15%tolerance.1000100Time in Seconds①2346810571Max8.57.5Time in Seconds16.50.10.10.01110Current in Multiples of Rating (In)0.011000Figure 13. PXR 20 / PXR 10 - instantaneous (800A)18800A Frame Override Curve10EATON www.eaton.com②100Current in 1000Amps1000010000November 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 20 / PXR 10 - 1000A Frame Instantaneous Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20 / PXR 10Notes:1. The instantaneous pickup settings as shown witha 10% tolerance.2. For high fault current levels a fixed instantaneousoverride is provided at 8000 A and has a 15%tolerance.1000Time in Seconds100①2346Max81010571Time in Seconds16.57.50.10.10.011000A Frame Override Curve1100.011000 100Current in Multiples of Rating (In)Figure 14. PXR 20 / PXR 10 - instantaneous and override 1000A frame②Current in1000Amps 1000010000November 2019EATON www.eaton.com19

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 201910000PXR 20 / PXR 20D / PXR 25 - Maintenance Mode CurvesTime current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert ReleasePXR 20 / PXR 20D / PXR 25Notes:1. Maintenance mode pickup settings have a 20%tolerance.1000Time in Seconds1001062.514100.10.0181①101001000Current in Multiples of Rating (In)Figure 15. PXR 20 / PXR 20D / PXR 25 - maintenance mode20EATON www.eaton.comNovember 2019

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 10 - 800A, I2t Long Delay, Instantaneous, Override Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 10Trip unit style: LI①1000②Time in Seconds100IrsettingPDGPDF800 APDC800 A12345678910320 A350 A400 A450 A500 A550 A600 A630 A700 A800 A320 A400 A450 A500 A550 A600 A630 A700 A750 A800 ANotes:1. Long delay pickup is 110% of the Ir setting with 5% tolerance.2. Long delay time settings has 0%/-30%tolerance.3. Instantaneous pickup settings have 10%tolerance.4. For high fault current levels a fixed instantaneousoverride is provided at 6800 A and has a 15%tolerance.5. If thermal memory is enabled, trip times may beshorter than indicated in this 100000Current in AmperesFigure 16. PXR 10 LI 800A frameNovember 2019EATON www.eaton.com21

Time current curves Power Defense MCCB Frame 4 thermal-magnetic and PXR electronic trip units Standards: UL, CSA, IEC, CCC Technical Data TD012066ENEffective November 2019PXR 10 - 1000A, I2t Long Delay, Instantaneous, Override Curves10000Time current curvesPower Defense circuit breakersStyle: Frame 4Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 10Trip unit style: LI①1000②Time in Seconds100IrsettingPDC1000 A12345678910400 A550 A630 A700 A750 A800 A850 A900 A950 A1000 ANotes:1. Long delay pickup is 110% of the Ir setting with 5% tolerance.2. Long delay time settings has 0%/-30% tolerance.3. Instantaneous pickup settings have 10% tolerance.4. Fo

T## Thermal magnetic trip unit (1) V## 50 C calibrated thermal magnetic trip unit (1) B## PXR 10 (1) E## PXR 20 (1) D## PXR 20D (1) P## PXR 25 (1) KNS Molded case switch SNN Switch disconnector Poles 3 3 poles 4 4 poles with programmable neutral protection Trip unit PXR Electronic trip unit Ampere frame rating 0800 800 .

Related Documents:

behringer ultra-curve pro dsp 24 a/d- d/a dsp ultra-curve pro ultra- curve pro 1.1 behringer ultra-curve pro 24 ad/da 24 dsp ultra-curve pro dsp8024 smd (surface mounted device) iso9000 ultra-curve pro 1.2 ultra-curve pro ultra-curve pro 19 2u 10 ultra-curve pro ultra-curve pro iec . 7 ultra-curve pro dsp8024 .

Defense Advanced Research Projects Agency. Defense Commissary Agency. Defense Contract Audit Agency. Defense Contract Management Agency * Defense Finance and Accounting Service. Defense Health Agency * Defense Information Systems Agency * Defense Intelligence Agency * Defense Legal Services Agency. Defense Logistics Agency * Defense POW/MIA .

Research, Development, Test and Evaluation, Defense-Wide Defense Advanced Research Projects Agency Volume 1 Missile Defense Agency Volume 2 . Defense Contract Management Agency Volume 5 Defense Threat Reduction Agency Volume 5 The Joint Staff Volume 5 Defense Information Systems Agency Volume 5 Defense Technical Information Center Volume 5 .

Figure 5 (below) shows a B Trip Curve overlaid onto the chart. The three major components of the Trip Curve are: 1. Thermal Trip Curve. This is the trip curve for the bi-metallic strip, which is designed for slower overcurrents to allow for in rush/startup, as described above. 2. Magnetic Trip Curve. This is the trip curve for the coil or solenoid.

Koch middle-one fifth curve (Fig. 8a) and Koch middle one-sixth curve (Fig. 9a) has dimensions 1.113 and 1.086 respectively that are smaller than the conventional Koch curve. (a) Koch left one-third curve with Generator (b) Koch left one-third Snowflake Fig. 5: Koch Left One-Third Curve and Koch Snowflake for (r1, r2, r3) (1/3,1/3,1/3)

The efficiency curve shows the efficiency of the pump. The efficiency curve is an average curve of all the pump types shown in the chart. The efficiency of pumps with reduced-diameter impellers is approx. 2 % lower than the efficiency curve shown in the chart. Pump type, number of poles and frequency. QH curve

Creating a new design curve from brushing over a French curve is simply a matter of generating a sub-curve [10] from the formula-tion of the digital French curve. Editing design curves using French curves is based on the premise that the section of the design curve being edited has the same general shape and position in space as the

French Defense - Minor Variations French Defense - Advance Variation French Defense - Tarrasch Variation: 3.Nd2 French Defense - Various 3.Nc3 Variations French Defense - Winawer Variation: 3.Nc3 Bb4 Caro-Kann Defense - Main Lines: 3.Nc3 dxe4 4.Nxe4 Caro-Kann Defense - Panov Attack