Fire Alarm Control Panel IFC-3030 Programming Manual

2y ago
2 Views
1 Downloads
1.85 MB
156 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Randy Pettway
Transcription

Fire Alarm Control PanelIFC-3030Programming ManualDocument 5202508/05/2005P/N 52025:C ECN 05-126C

Fire Alarm System LimitationsWhile a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!An automatic fire alarm system—typically made up ofsmoke detectors, heat detectors, manual pull stations, audiblewarning devices, and a fire alarm control panel with remotenotification capability—can provide early warning of a developing fire. Such a system, however, does not assure protectionagainst property damage or loss of life resulting from a fire.The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following therecommendations of the current edition of the National FireProtection Association Standard 72 (NFPA 72), manufacturer'srecommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of SystemSmoke Detectors, which is made available at no charge to allinstalling dealers. A study by the Federal Emergency Management Agency (an agency of the United States government)indicated that smoke detectors may not go off in as many as35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warningor protection against fire. A fire alarm system may not providetimely or adequate warning, or simply may not function, for avariety of reasons:Smoke detectors may not sense fire where smoke cannotreach the detectors such as in chimneys, in or behind walls, onroofs, or on the other side of closed doors. Smoke detectorsalso may not sense a fire on another level or floor of a building.A second-floor detector, for example, may not sense a firstfloor or basement fire.Particles of combustion or “smoke” from a developing firemay not reach the sensing chambers of smoke detectorsbecause: Barriers such as closed or partially closed doors, walls, orchimneys may inhibit particle or smoke flow. Smoke particles may become “cold,” stratify, and not reachthe ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by airoutlets. Smoke particles may be drawn into air returns beforereaching the detector.The amount of “smoke” present may be insufficient to alarmsmoke detectors. Smoke detectors are designed to alarm atvarious levels of smoke density. If such density levels are notcreated by a developing fire at the location of detectors, thedetectors will not go into alarm.Smoke detectors, even when working properly, have sensinglimitations. Detectors that have photoelectronic sensingchambers tend to detect smoldering fires better than flamingfires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming firesbetter than smoldering fires. Because fires develop in differentways and are often unpredictable in their growth, neither typeof detector is necessarily best and a given type of detectormay not provide adequate warning of a fire.Smoke detectors cannot be expected to provide adequatewarning of fires caused by arson, children playing withmatches (especially in bedrooms), smoking in bed, and violentexplosions (caused by escaping gas, improper storage offlammable materials, etc.).2Heat detectors do not sense particles of combustion andalarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-riseheat detectors may be subject to reduced sensitivity over time.For this reason, the rate-of-rise feature of each detectorshould be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protectproperty, not life.IMPORTANT! Smoke detectors must be installed in thesame room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not solocated, a developing fire may damage the alarm system, crippling its ability to report a fire.Audible warning devices such as bells may not alert peopleif these devices are located on the other side of closed orpartly open doors or are located on another floor of a building.Any warning device may fail to alert people with a disability orthose who have recently consumed drugs, alcohol or medication. Please note that: Strobes can, under certain circumstances, cause seizuresin people with conditions such as epilepsy. Studies have shown that certain people, even when theyhear a fire alarm signal, do not respond or comprehend themeaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise tomake people aware of fire alarm signals and instruct themon the proper reaction to alarm signals. In rare instances, the sounding of a warning device cancause temporary or permanent hearing loss.A fire alarm system will not operate without any electricalpower. If AC power fails, the system will operate from standbybatteries only for a specified time and only if the batteries havebeen properly maintained and replaced regularly.Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.Telephone lines needed to transmit alarm signals from apremise to a central monitoring station may be out of serviceor temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system inexcellent working order, ongoing maintenance is required perthe manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall befollowed. Environments with large amounts of dust, dirt orhigh air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduledmonthly or as required by National and/or local fire codes andshould be performed by authorized professional fire alarminstallers only. Adequate written records of all inspectionsshould be kept.Precau-L-1-2005.fmIFC-3030 Programming Manual — P/N 52025:C 08/05/2005

Installation PrecautionsAdherence to the following will aid in problem-free installation with long-term reliability:WARNING - Several different sources of power can beconnected to the fire alarm control panel. Disconnect allsources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit isenergized. Do not attempt to install, service, or operate thisunit until manuals are read and understood.CAUTION - System Re-acceptance Test after SoftwareChanges: To ensure proper system operation, this productmust be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition ordeletion of system components, or after any modification,repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions knownto be affected by a change must be 100% tested. In addition,to ensure that other operations are not inadvertently affected,at least 10% of initiating devices that are not directly affectedby the change, up to a maximum of 50 devices, must also betested and proper system operation verified.This system meets NFPA requirements for operation at 0-49ºC/32-120º F and at a relative humidity (non condensing) of85% at 30 C (86 F) per NFPA, and 93% 2% at 32 C 2 C(89.6 F 1.1 F) per ULC. However, the useful life of the system's standby batteries and the electronic components may beadversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and itsperipherals be installed in an environment with a normal roomtemperature of 15-27º C/60-80º F.Like all solid state electronic devices, this system mayoperate erratically or can be damaged when subjected to lightning induced transients. Although no system is completelyimmune from lightning transients and interference, propergrounding will reduce susceptibility. Overhead or outside aerialwiring is not recommended, due to an increased susceptibilityto nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.Disconnect AC power and batteries prior to removing orinserting circuit boards. Failure to do so can damage circuits.Remove all electronic assemblies prior to any drilling, filing,reaming, or punching of the enclosure. When possible, makeall cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminalcontact pressure and difficulty with screw terminal removal.This system contains static-sensitive components.Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from thebody. Use static suppressive packaging to protect electronicassemblies removed from the unit.Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed toavoid damage to the control panel and associated equipment.FACP operation and reliability depend upon proper installation.Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a10% I.R. drop from the specified device voltage.Precau-L-4-2005.fmFCC WarningWARNING: This equipment generates, uses, and canradiate radio frequency energy and if not installed andused in accordance with the instruction manual maycause interference to radio communications. It has beentested and found to comply with the limits for class Acomputing devices pursuant to Subpart B of Part 15 ofFCC Rules, which is designed to provide reasonableprotection against such interference when devices areoperated in a commercial environment. Operation of thisequipment in a residential area is likely to cause interference, in which case the user will be required to correctthe interference at his or her own expense.Canadian RequirementsThis digital apparatus does not exceed the Class A limitsfor radiation noise emissions from digital apparatus setout in the Radio Interference Regulations of the Canadian Department of Communications.Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans leReglement sur le brouillage radioelectrique edicte par leministere des Communications du Canada.HARSH , NIS , Notifier Integrated Systems , NOTI FIRE NET , and ONYXWorks are all trademarks; and FlashScan , NION , NOTIFIER ,ONYX , UniNet , VeriFire , and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarksof the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company. 2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.IFC-3030 Programming Manual — P/N 52025:C 08/05/20053

Documentation FeedbackYour feedback helps us keep our documentation up-to-date and accurate. If you have any commentsor suggestions about our online Help or printed manuals, you can email us.Please include the following information: Product name and version number (if applicable)Printed manual or online HelpTopic Title (for online Help)Page number (for printed manual)Brief description of content you think should be improved or correctedYour suggestion for how to correct/improve documentationSend email messages to:FireSystems.TechPubs@honeywell.comPlease note this email address is for documentation feedback only. If you have any technical issues,please contact Technical Services.4IFC-3030 Programming Manual — P/N 52025:C 08/05/2005

Table of ContentsSection 1: General Information. 91.1: About This Manual .91.2: Supplemental Information .101.3: Introduction to the Control Panel .111.3.1: Features.111.4: Navigating Menu and Programming Screens .111.5: Basic Procedure .121.6: Getting Started .121.6.1: Password Change.12Section 2: Main Menu . 152.1: Event Counts Display .152.2: Multiple Event List .152.3: History Display (History Select Screen).152.4: Read Status .162.5: Program/Alter Status.162.6: Printer Functions.16Section 3: Program . 173.1: General Information.173.2: Panel Program.183.2.1: Panel Program Menu (1).183.2.2: Network Parameters .193.2.3: Panel Settings .213.2.4: Panel Timers (Menu 1) .233.2.5: Panel Timers (Menu 2) .253.2.6: LCD Programming .263.2.7: ACS Programming .263.2.8: Supervision .303.3: Panel Program Menu (2).313.3.1: Password Change.313.3.2: Weekly Occupancy Schedule .313.3.3: Remote Display Menu .323.3.4: Loop Configuration .333.3.5: Custom Action Message.353.3.6: Event Logging .363.3.7: Holiday Menu .363.4: Point Program .373.4.1: Detector Point .383.4.2: Module Point .433.4.3: Panel Circuit Module.473.4.4: General Zone .513.4.5: Releasing Zone .513.4.6: Logic Zone.523.4.7: Trouble Zone .553.4.8: Annunciator Board Label .563.5: Delete Program .563.6: Autoprogram Menu .583.6.1: To Create a New Program .583.6.2: To Add/Delete Devices from the Program .583.6.3: Confirmation Screens .59Section 4: Alter Status. 654.1: Disable/Enable Point Selection.654.2: Disable/Enable .66IFC-3030 Programming Manual — P/N 52025:C 08/05/20055

Table of Contents4.3: Detector Sensitivity.674.3.1: Sensitivity Select .674.4: Clear Verify Counters .694.5: Clear History .694.6: Walk Test.704.6.1: Walk Test Menu .724.6.2: Walk Test Loops Parameters .734.6.3: Advanced Walk Test Activation.734.6.4: Devices Test Selection.744.7: Program Time/Date.754.8: Control On/Off Point Select.764.8.1: Control Off.764.8.2: Control On .77Section 5: Service Screens. 795.1: Version Information .795.2: Power-up Screen .805.3: Bootloader Screen .815.3.1: LCD-160 Download Menu .815.3.2: Loop Download Menu .825.4: Download Screen .835.5: Application Corrupt Screen .83Appendix A: Menu Hierarchy. 85A.1: Screens Overview .85Appendix B: Releasing Applications . 89B.1: Releasing Zones .89B.2: NFPA Releasing Applications.90B.3: Abort Switches .90B.3.1: ULI Abort Switch.92B.3.2: IRI Abort Switch .93B.3.3: NYC Abort Switch.94B.3.4: AHJ Abort Switch .96B.3.5: Cross Zones.97B.3.6: Using Type Codes for Releasing Zones.98B.4: Miscellaneous.112B.4.1: Initiating Devices .112B.4.2: Warning Sounders.112B.4.3: Auxiliary Control Functions .112B.4.4: ACS Annunciation .112Appendix C: Special Zone Outputs. 113C.1: Presignal and Positive Alarm Sequence (PAS) .113C.1.1: What is Presignal and PAS?.113C.1.2: Selecting Presignal and PAS Outputs .113C.2: Coding Functions for Panel Circuit Outputs .114Appendix D: AWACS Applications. 115D.1: AWACS Overview .115D.2: AWACS Features .115D.2.1: Drift Compensation and Smoothing .115D.2.2: Maintenance Warnings – Three Levels .116D.2.3: Self-Optimizing Pre-Alarm.117D.2.4: Detector Sensitivity.117D.2.5: Cooperative Multi-Detector Sensing .118D.3: Pre-Alarm.118D.3.1: Definition .1186IFC-3030 Programming Manual — P/N 52025:C 08/05/2005

Table of ContentsD.3.2: Alert Level .118D.3.3: Action Level .119D.4: Detector Sensitivity Settings.119D.4.1: How to Select Pre-Alarm and Alarm Sensitivity.119D.4.2: To Test Detectors Set Below 0.50% Obscuration per Foot.121D.5: Detector Status Display.121D.5.1: Detector Maintenance Display .121D.5.2: Print a Detector Maintenance Report .122D.5.3: To Interpret a Detector Status Display or Maintenance Report .122Appendix E: CBE: Zones and Equations. 125E.1: Zones .125E.2: Equation

IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 3 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all so

Related Documents:

addressable fire alarm control panel 2 loop addressable fire alarm control panel 4 loop addressable fire alarm control panel 6 loop addressable fire alarm control panel 8 loop addressable fire alarm control panel product code: m.u.yan.00016 product code: m.u.yan.00018 battery included product code: m.u.yan.00020 product code: m.u.yan.00022

Sigma Alpha Epsilon Fraternity IFC 3.030 16 All Fraternity 3.002 Alpha Sigma Phi Fraternity IFC 2.972 17 All Campus Male 2.990 Sigma Chi Fraternity IFC 2.957 18 Theta Xi Fraternity IFC 2.946 19 Omega Psi Phi Fraternity, Inc. Fraternity NPHC 2.938 20 Pi Kappa Alpha Fraternity IFC 2.878 21 Pi Kappa Phi Fraternity IFC 2.846 22

national fire alarm code, and section 13.7. 2006 nf pa 1. fire alarm system installation and maintenance shal l be in accordance with nfpa 72, national fire alarm code, and 2006 nfpa 1. 13.7.1.4.9.8 audibility. the alarm signal shall be a distinctive sound, which is not used for any other purpose other than the fire alarm. alarm-signaling

Alarm 1 is a ‘Sound Once’ alarm, and Alarm 2 is an ‘Everyday’ alarm. Alarm 1 Setting/Alarm 2 Setting Press the ‘Alarm 1’ button (Ref.4) or ‘Alarm 2’ button (Ref.5) to activate alarm settings. ‘OFF’ will begin lashing on the screen. Select Alarm 1 or 2 b

Run Card Requirements Continued Structure Fire goes to 7th Alarm and all 7 Alarm and all 7 Alarms are required. Brush Fire goes to 7th Alarm and all 7 Alarm and all 7 alarms are required. All other incident types can go to 4th Alarm Alarm and minimum of 2nd alarm is required.alarm is required. When a Compan

NFS2-640 Intelligent Addressable Fire Alarm System Intelligent Fire Alarm Control Panels dn-7111:b † A-13 NFS2-640 7111pho2.jpg General The NFS2-640 intelligent Fire Alarm Control Panel is part of the ONYX Series of Fire Alarm Controls from NOTIFIER. As a stand-alone small-to-large system, or as a File Size: 710KBPage Count: 10

DETECTION ZONE 11 DETECTION ZONE 12 ALARM ZONE 1 ALARM ZONE 2 ALARM ZONE 3 ALARM ZONE 4 Alarm Zones An alarm zone is clearly defined within the standard but generally is an area of the building coinciding with the fire compartment boundaries. There must be a clear break between these alarm zones to ensure alert and evacuation messages are not .

CAO Monitoring Report C-I-R6-Y12-F160 1 MONITORING REPORT CAO Audit of IFC CAO Compliance C-I-R6-Y12-F160 January 14, 2015 Monitoring of IFC’s Response to: CAO Audit of IFC Investment in Coastal Gujarat Power Limited, India Office of the Compliance Advisor Ombudsman (CAO) for the International Finance Corporation (IFC)