Installation Requirements - Flexibleduct

3y ago
23 Views
3 Downloads
1.54 MB
12 Pages
Last View : 15d ago
Last Download : 3m ago
Upload by : Julius Prosser
Transcription

4Installation Requirements4.1 Code Referencef.Air Connectors (does not apply to Air Ducts)shall not be installed in lengths greater than14 ft. [4.3 m] for any given run; shall not passthrough any wall, partition or enclosure of avertical shaft with a 1 hour or more fireresistive rating; shall not pass through floors.g.Shall not penetrate walls where fire dampersare required.h.Shall not be used outdoors unless specificallydesigned to withstand exposure to directsunlight and the weathering elements.i.Shall not be used to vent appliances forcooking, heating and clothes drying unlessapproved and recommended by the appliancemanufacturer.j.Shall not be installed in concrete, buriedbelow grade or in contact with the ground.The “authority having jurisdiction” should bereferenced to determine what law, ordinance or codeshall apply in the use of flexible duct.Ducts conforming to NFPA 90A or 90B shall meet thefollowing requirements:a.b.c.Shall be tested in accordance with Sections7 to 23 of Underwriters Laboratories Standardfor Factory-Made Air Ducts and AirConnectors, UL 181.Shall be installed in accordance with theconditions of their listing.Shall be installed within the limitations of theapplicable NFPA 90A or 90B Standard.4.2 Installation Restrictionsand Use Limitations9ADC Flexible Duct Performance & Installation Standards, 5th EditionThere are specific restrictions and limitations related tothe use of flexible ducts. Some are due to NFPAStandards, model codes and various state/local codes.Others are due to end use performance where theproduct was not designed for that specific use. Some,but not all inclusive, are as follows:a.Shall not be used for vertical risers servingmore than two stories in height.b.Shall not be used in systems with entering airtemperature higher than 250 F[121 C].c.Shall be installed in accordance with theconditions of their listing.d.When installed in a fire-rated floor/roof ceilingassembly, ducts shall conform with the designof the tested fire-resistive assembly.e.Shall be interrupted at the immediate area ofoperation of electric, fossil fuel or solarenergy collection heat sources to meet listedequipment clearances specified.4.3 GeneralThe routing of flexible duct, the number of bends, thedegrees in each bend, and the amount of sag ordirection changes (snaking) allowed between supportjoints will have serious effects on system performancedue to the increased resistance each introduces (SeeFig 6 & 7). Use the minimum length of flexible duct tomake connections (See Section 4.5). Excess length offlexible duct shall not be installed to allow for possiblefuture relocations of air terminal devices.Avoid installations where exposure to direct sunlightcan occur, e.g. turbine vents, sky lights, canopywindows, etc. Prolonged exposure to sunlight willcause degradation of the vapor barrier. Directexposure to UV light from a source lamp installedwithin the HVAC system will cause degradation ofsome inner core/liner materials.Terminal devices shall be supported independently ofthe flexible duct.Repair torn or damaged vapor barrier/jacket with ducttape listed and labeled to Standard UL 181B. If internalcore is penetrated, replace flexible duct or treat as aconnection.

Installation Requirements . . . continued4.4 Installation and UsageInstall ducts fully extended. Do not install in thecompressed state or use excess length as this willnoticeably increase friction losses. (Refer to Section4.5 for more specific information regarding pressureloss and duct sizing.)Figure 7 - Excess length and tight bend radiusincreases pressure drop andreduces airflow.The bend radius at the center line of ducts shall beequal to or greater than one duct diameter (SeeFigures 8 and 11). Sharper bends increase pressuredrop significantly and reduce airflow.Figure 8 - Correct. Minimum 1 duct diameterbend radius reduces pressure dropand improves air flow.Avoid incidental contact with metal fixtures, waterlines, pipes, or conduits. Do not install near hotequipment (e.g. furnaces, boilers, steam pipes, etc.)that is above the recommended flexible duct usetemperature.Figure 9 - Incorrect. Contact with steam pipes.10ADC Flexible Duct Performance & Installation Standards, 5th EditionFigure 6 - Minimum duct length and bendradius reduces pressure drop andimproves airflow.Do not bend ducts across a sharp corner of buildingmaterials such as joists or truss supports.

Installation Requirements . . . continued4.5 Duct Sizing and RoutingThe combined friction and dynamic pressure lossesshall be taken into consideration to properly size anyduct. Pressure losses caused by the roughness of theduct wall resisting air movement are know as frictionlosses. Pressure losses when air flow changesdirection, as caused by bends or when air flows acrossother system components, are known as dynamiclosses.Key points to prevent undersizing or oversizing offlexible ducts and achieve the designed air deliveryperformance:a.Use a proven method of duct sizing, one thathas taken into consideration both friction anddynamic losses.If a flexible duct is not fully extended, thefriction rate increases proportionally with thecompression (See Fig. 10).When a flexible duct is fully extended, it issaid to have no more than 4% longitudinalcompression and the published friction ratemay be used for duct sizing calculations (0 4% 1 x Friction Rate).For 15% longitudinal compression the frictionrate can increase by a factor of two (15% 2x Friction Rate).For longitudinal compression of 30% thefriction rate can increase as much as fourtimes (30% 4 x Friction Rate).Design the flexible duct system per therequirements of ACCA, Manual D(Residential) and Manual Q (Commercial).Properly take into account duct length, bendlosses, sagging or routing expectations, fittinglosses, etc.11ADC Flexible Duct Performance & Installation Standards, 5th Editionb.Have a good understanding of and properlyuse the air friction chart.Do not use data for round sheet metal duct.Since all flexible ducts are not alike, use theflexible duct manufacturer’s air friction lossdata to size the ducts whenever possible.If no data is available, use the generic flexibleduct friction loss chart in ACCA Manual D.c.Use the minimum length of flexible ductneeded to make the connections.Install ducts extended to their fullest lengthwithout compression. Due to the helicalconfiguration of flexible duct inner cores,excess longitudinal compression candramatically affect the pressure drop.Figure 10 - Compressed duct (not fully ex-tended) increases friction rate.

Installation Requirements . . . continuedd.Keep bends greater than or equal to one (1)duct diameter bend radius.Care shall be taken to minimize sagging orsnaking of the duct between supports andminimize pressure loss caused by excessivedirection changes to the airflow.Figure 1312Figure 11e.Properly route and support the flexible ductruns.Figure 12Figure 14ADC Flexible Duct Performance & Installation Standards, 5th EditionDucts shall not be crimped against joist ortruss members, pipes, wires, etc. as this increases pressure loss and reduces air flow.

Installation Requirements . . . continuedf.Properly account for bends in the duct runs.A 90-degree bend has pressure drop equal toapproximately twenty (20) lineal feet of flexible duct. So each 90-degree bend will addtwenty (20) equivalent feet to the length usedfor sizing calculations.Figure 1613ADC Flexible Duct Performance & Installation Standards, 5th EditionA 180-degree offset has pressure drop equalto about forty (40) lineal feet of flexible duct.Add forty (40) equivalent feet to the length foreach sharp 180-degree offset.Figure 15A gradual 45-degree bend has pressure dropequal to about ten (10) lineal feet of flexibleduct. Add ten (10) equivalent feet to thelength for each gradual bend (see Fig. 16).Figure 17

Installation Requirements . . . continuedDuct fittings and any bends and turns in flexible ductall produce a resistance to airflow. This resistancecreates a pressure drop measured in inches watercolumn (IWC) which is physically equivalent to thepressure drop produced by a straight section of duct.So the total pressure drop for any duct run equals thesum of the fitting pressure drops and the pressure dropof the straight duct section.The worksheet for determining the total pressure dropof the duct run depicted in Figure 18 will look like this:To determine the correct duct size, take into accountthe total equivalent length of the duct run, includingentrance and exit losses from the plenum to the ductand from the duct into the terminal device, the addedlength due to any bends, and the total length of theduct itself.Total Equivalent Length 124 ft.Use ACCA Manual D (App. 3) equivalent length valuesfor bends and fittings.The equivalent length values for bends & fittingsrepresented above are default values from ACCAManual D and based on 900 fpm at 0.08 IWC/100’ forsupply ducts and 700 fpm at 0.08 IWC/100’ for returnducts.A typical duct run from plenum to terminal device isillustrated in Figure 18.Entrance fitting Total duct length 2 x 45 bends (2 x 10’) 1 x 90 bend (1 x 20’) Exit fitting 35 ft.14 ft.20 ft.20 ft.35 ft.Although the distance from plenum to terminal end inthis example is approximately 12 feet, the totalequivalent length used to determine the correct ductdiameter would be 124 feet.14ADC Flexible Duct Performance & Installation Standards, 5th EditionFigure 18

Installation Requirements . . . continued4.6 Supporting Flexible DuctFlexible duct shall be supported at manufacturer’srecommended intervals, but at no greater distancethan 4’ [1.2 m]. Supporting shall be provided so thatthe maximum centerline sag is ½ " per foot [42 mm permeter] of spacing between supports (See Fig 19). Aconnection to rigid duct or equipment may beconsidered a support joint.15Hanger or saddle material in contact with the flexibleduct shall be of sufficient width to prevent anyrestriction of the internal diameter of the duct whenthe weight of the supported section rests on thehanger or saddle material. In no case will the materialcontacting the flexible duct be less than 1½ ” [38 mm]wide (See Fig 21).Figure 21ADC Flexible Duct Performance & Installation Standards, 5th EditionFigure 19Long horizontal duct runs with sharp bends shall haveadditional supports before and after the bendapproximately one duct diameter from the center lineof the bend (See Fig 20).Figure 22Figure 20Do not secure support straps in a manner thatcompresses the inner core and constricts the air flow.Care shall be taken to insure the vapor barrier andinsulation material are not excessively compressedby the support straps. Compressing the insulationcould lead to condensation at the point of contactbetween the duct and the strap or saddle material.

Installation Requirements . . . continuedFactory installed suspension systems integral to theflexible duct are an acceptable alternative hangingmethod when manufacturer’s recommended procedures are followed.Support the duct between a metal connection andbend by allowing the duct to extend straight for at leastone duct diameter before making the bend. This willavoid possible damage of the flexible duct by the edgeof the metal collar and allow for efficient air flow andfitting performance (See Fig 25).Figure 2316Figure 25Vertically installed ductsshall be stabilized bysupport straps at a max.of 6’ [1.8 m] on center.Figure 24Note:Factory-made air ducts may not be used for vertical risersin air duct systems serving more than two adjacent stories.Figure 26ADC Flexible Duct Performance & Installation Standards, 5th EditionFlexible ducts may rest on ceiling joists or trusssupports. Maximum spacing between supports shallnot exceed the maximum spacing per manufacturer’sinstallation instruction.

Installation Requirements . . . continued4.7 Connecting, Joining and SplicingFlexible DuctsAll connections, joints and splices shall be made inaccordance with the manufacturer’s installationinstructions.Standardized installation instructions conforming to theconnecting and sealing requirements of the nationalbuilding codes and this standard are shown inSections 4.7.1 through 4.7.3.Section 4.7.1 - “Installation Instructions for Air Ductsand Air Connectors - Nonmetallic With PlainEnds” (uses tape and clamp to seal and secure theduct core to the fitting).Section 4.7.2 - “Alternate Installation Instructions forAir Ducts and Air Connectors - Nonmetallic With PlainEnds” (uses mastic and clamp to seal and secure theduct core to the fitting).17Section 4.7.3 - “Installation Instructions for Air Ductsand Air Connectors - Metallic With Plain Ends (optionaluse of tape or mastic and metal screws to seal andsecure the duct core to the fitting).ADC Flexible Duct Performance & Installation Standards, 5th EditionDue to the wide variety of ducts and duct assemblieswith special end treatments (factory installed fittings,taped ends, crimped metal ends, etc.), only thesestandardized installation instructions are shown.Always reference the manufacturer’s installationinstructions for more detailed requirements.All tapes, mastics, and nonmetallic clamps used forfield installation of flexible ducts shall be listed andlabeled to Standard UL 181B - Closure Systems forUse With Flexible Air Ducts and Air Connectors.Sheet metal fittings to which flexible ducts with plainends are attached shall be beaded and have aminimum of 2 inches [50 mm] collar length. Beads areoptional for fittings when using metal worm-gearclamps or when attaching metallic flexible ducts usingsheet metal screws.Sheet metal sleeves used for joining two sections offlexible duct with plain ends shall be a minimum of 4inches [100 mm] in length and beaded on each end.Beads are optional for sleeves when using metalworm-gear clamps or when joining metallic flexibleducts using sheet metal screws.Flexible ducts secured with nonmetallic clamps shallbe limited to 6 inches w.g. [1500 Pa] positive pressure.

Installation Requirements . . . continued4.7.1Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with Plain EndsConnections - Using Tape and FastenersSplices - Using Tape and Fasteners1. After desired length is determined, cut completelyaround and through duct with knife or scissors. Cutwire with wire cutters. Fold back jacket and insulation.1. Fold back jacket and insulation from core. Butt twocores together on a 4" [100 mm] min. length metalsleeve.2. Slide at least 1" [25 mm] of core over fitting andpast the bead. Seal core to collar with at least 2 wrapsof duct tape. Secure connection with clamp placedover the core and tape and past the bead.2. Tape cores together with at least 2 wraps of ducttape. Secure connection with 2 clamps placed over thetaped core ends and past the beads.183. Pull jacket and insulation back over cores. Tapejackets together with at least 2 wraps of duct tape.NOTES:1.2.3.4.For uninsulated air ducts and air connectors, disregard references to insulation and jacket.Use beaded sheet metal fittings and sleeves when using nonmetallic clamps.Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”.Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”.Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.ADC Flexible Duct Performance & Installation Standards, 5th Edition3. Pull jacket and insulation back over core. Tapejacket with at least 2 wraps of duct tape. A clamp maybe used in place of or in combination with the ducttape.

Installation Requirements . . . continued4.7.2Alternate Installation Instructions for Air Ducts and Air Connectors - Nonmetallic withPlain EndsConnections and Splices - Using Mastic and FastenersStep 1After desired length is determined, cut completely around andthrough duct with knife or scissors. Cut wire with wire cutters.Pull back jacket and insulation from core.Step 2Apply mastic approximately 2" [50 mm] wide uniformly aroundthe collar of the metal fitting or over the ends of a 4" [100 mm]min. length metal sleeve. Reference data on mastic containerfor application rate, application thickness, cure times andhandling information.Step 3Slide at least 2" [50 mm] of core over the fitting or sleeve endsand past the bead.19ADC Flexible Duct Performance & Installation Standards, 5th EditionStep 4Secure core to collar with a clamp applied past the bead.Secure cores to sleeve ends with 2 clamps applied past thebeads.Step 5Pull jacket and insulation back over core ends. Tape jacket(s)with at least 2 wraps of duct tape. A clamp may be used inplace of or in combination with the duct tape.NOTES:1.2.3.4.5.For uninsulated air ducts and air connectors, disregard references to insulation and jacket.Use beaded sheet metal fittings and sleeves when using nonmetallic clamps.Use mastics listed and labeled in accordance with Standard UL 181B and marked “181B-M” on container.Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”.Nonmetallic clamps shall be listed and labeled in accordance with standard UL 181B and marked “181B-C”.Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.

Installation Requirements . . . continued4.7.3Installation Instruction for Air Ducts and Air Connectors - Metallic with Plain EndsConnections and Splices - Using Tape or Mastic and Sheet Metal Screws1. After cutting duct to desired length, fold back jacketand insulation exposing core. Trim core ends squarelyusing suitable metal shears. Determine optionalsealing method (Steps 2 or 5) before proceeding.4. Secure to collar/sleeve using #8 sheet metalscrews spaced equally around circumference. Use 3screws for diameters under 12" [300 mm] and 5screws for diameters 12" [300 mm] and over.2. When mastics are required and for pressures 4"w.g. [1000 Pa] and over, seal joint with mastic applieduniformly to the outside surface of collar/sleeve.(Disregard this step when not using mastics and proceed to Step 3).5. For pressures under 4" w.g. [1000 Pa] seal jointusing 2 wraps of duct tape applied over screw headsand spirally lapping tape to collar/sleeve. (Disregardthis step when using mastics per Step 2).206. Pull jacket and insulation back over core. Tapejacket with 2 wraps of duct tape. A clamp may be usedin place of or in combination with the duct tape.NOTES:1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.2. Use mastics listed and labeled to Standard UL 181B and marked”181B-M” on container.3. Use tapes listed and labeled to Standard UL 181B and marked “181B-FX”.4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”.ADC Flexible Duct Performance & Installation Standards, 5th Edition3. Slide at least 1" [25 mm] of core over metal collarfor attaching duct to take off or over ends of a 4" [100mm] metal sleeve for splicing 2 lengths of duct.

4.5 Duct Sizing and Routing The combined friction and dynamic pressure losses shall be taken into consideration to properly size any duct. Pressure losses caused by the roughness of the duct wall resisting air movement are know as friction losses. Pressure losses when air flow changes direction, as caused by bends or when air flows across

Related Documents:

5.3. STAFInst Uninstall 6. Platform Installation Notes 6.1. Linux installation 6.2. AIX installation 6.3. HP-UX IA64 64-bit installation 6.4. IBM i 32-bit (previously known as i5/OS or OS/400) installation 6.5. z/OS installation 6.6. FreeBSD installation 6.7. Mac OS X installation 6.8. Solaris installation 7. Environment Variable Settings 7.1.

10.0 system installation - roof insulation 10.1-10.4 - ssr work points 10.5-10.6 - panel installation 10.7-10.12 - alternate ice damming weatherseal 10.3 - ssr module strip installation 10.14-10.15 - endlap installation 10.16-10.18 - ridge installation 10.19-10.30 11.0 fascia conditions - eave fascia installation 11.1 - eave gutter installation .

I9291 Remote Start/Keyless Entry Transmitter Installation I9292 Windshield Washer Solvent Heater Package Installation I9293 Multimedia Player Interface Module Package Installation I9294 Rearview Camera Package Installation I9295 Cellular Telephone Package Installation I9300 Roof Rack/Rail/Panel Installation

Antifreeze Solutions in Home Fire Sprinkler Systems 100138.04.000 May 28, 2010 CODE CONSULTANTS, INC. Page 1 Executive Summary NFPA 13, Standard for the Installation of Sprinkler Systems, has included guidance on the use of antifreeze solutions in fire sprinkler systems since the 1940 edition.1 Antifreeze solutions may be used in fire sprinkler systems where the piping system, or File Size: 942KBPage Count: 100Explore furtherNFPA 13: Standard for the Installation of Sprinkler .archive.orgNFPA 13: Standard for the Installation of Sprinkler Systemswww.nfpa.orgNFPA 13-2010: Installation of Sprinkler Systems (The .rtmconsultants.comNFPA 13 Standard For The Installation Of Sprinkler Systems .nfpa13.engineeringdesignresources. NFPA 13-2019: Installation of Sprinkler Systems Standard .blog.ansi.orgRecommended to you b

This installation manual is part of and shipped with the unit, and contains information on its safe installation. Read this installation manual completely before installing the unit. This installation manual must be kept available to installers at all times at the installation loca- tion. Keep this installation manual on hand throughout

NetWrix Non-Owner Mailbox Access Reporter for Exchange Installation Guide . Disk 50MB physical disk space for the installation 200MB physical disk space for the installation 3.2. Software Requirements . The following requirements apply to the environment that you are going to monitor: Table 3: Target Machines Requirements

Apr 02, 2011 · – Writing Requirements using EARS Templates Requirements Specifications - Writing Requirements Documents – IEEE 830 Standard for Software Requirements Specif ications . Warhammer 40k – Blood Ravens battle cry 14. Requirements Elicitation Tasks P

School Transport Contract Awards 2015 This notice includes information on mainstream school transport contracts awarded for operation from 16 August 2015. The prices specified in the notice are based on the annualised price at the time of award. There were three “rounds” of tender. In a number of cases contracts were awarded on the basis of package bids. These contracts are denoted by a (P .