Work bookThe standard IEC 61439 in practice

Work book on the seminar delivered by ABBThe standard IEC 61439Basic standards(definitions of personal protection, calculation and test procedures, assessment bases)IEC 60364-4-41IEC / TR 60664-2-1IEC 60529Protection against electric shockInsulation co-ordinationTest devices and test proceduresRequirements for specialinstallations or locationsIEC 60364-7.Installation and connection ofswitchgear and distribution boardsIEC 60364-7-729Operation of electrical installationsEN 50110Low-voltage switchgear andcontrolgear ASSEMBLIES- Protection against electric shock- Protection against unintentionaldirect contact withhazardous live partsEN 50274Safety of machinery,electrical equipment of machinesand mechanisms.Part 1. General requirementsIEC 60204-1Installation and implementation provisionsIEC 61439-1, IEC 61439-2IEC 61439-3Prepared by:Matthias KratzkeJürgen DufnerWork book 2CPC 000 305 B01011

Notes22CPC 000 313 B0101 Work book

Work bookContentsBlue Pages5 – 10Foreword / introduction5Parts of the standard6Why a new standard?7How can the original manufacturer or the manufacturer verify thesafety of an ASSEMBLY?White PagesBuilding / manufacture of the distribution board117111921213Chapter 4 – Routine verificationRoutine verification8How can a low-voltage switchgear and controlgearASSEMBLY be realized safely?Chapter 3 – Building / manufacture of the distribution boardChapter 5 – CE conformity declaration911 - 122CE conformity declarationYellow Pages123 – 165Symbols and abbreviations12311Comparisons and effects in connection with different standards12313Minimum requirements for the type plate – example ABB125Protection against electric shock (IEC 60364-4-41)15Panel Design Configurator software – new article127Overvoltage categories17Panel Design Configurator software – export/import user article data129Characteristics and explanations19Temperature rise verification up to 630 A – solution example131Check list25Data collection tables133Electrical circuits and loads27Verification of temperature rise up to 630 A139Characteristics and explanations29Design verification part I141Main circuits31Design verification part II143Check list35Unit test protocol14537Unit test protocol checklist14739Conformity assessment checklist16141Declaration of conformity163Check list45Examples STRIEBEL & JOHN165Operating and servicing49Our solutions for internal forms of separation50Internal forms of separation51Characteristics and explanations53Check list55Chapter 1 – Collecting the requisite dataConnection to the electrical systemElectrical systems and protective systemsInstallation and environmental conditionsTypical conditions of installations of ASSEMBLIESProtection against mechanical impactsChapter 2 – Distribution board design and design verificationDistribution board design and design verification57Requirements arising from the standard59Characteristics and explanations61Verification of temperature rises67Example calculation74Temperature rise verification up to 630 A75Temperature rise verification pursuant to DIN EN 6089081Verification of the short-circuit withstand strength87Short circuit – key terms89Verification of the Short-circuit withstand strength91Short-circuit current at the supply position95Transformer nominal values table109Characteristics and explanations111Devices from other manufacturers113Form sheet examples115Work book 2CPC 000 305 B0101345

Notes42CPC 000 313 B0101 Work book

Foreword / introductionThis document is designed to assist you and enables us to secure ourcommon success.1This workbook contains general information and proposals for designing, planning and building low voltage switchgear and controlgearASSEMBLIES in compliance with the applicable laws, directives andprovisions.Basic knowledge in electrical engineering is essential for planning lowvoltage switchgear and controlgear ASSEMBLIES.This workbook includes general and special information which isessential for safe, reliable and economical low voltage switchgear andcontrolgear ASSEMBLY operation.In addition, the topics designed to protect people and assets arebeing dealt with.Distribution boards in the low voltage networkDistribution boards serve as link between electrical appliances andusers.They form the visible part of an electrical system and represent theelectrical company having installed the ASSEMBLY.The requirements in terms of flexibility and safety for distributionboards are particularly high:––––Personal protectionProperty protectionHigh operational and functional safetyEase of useSolid design to prevent unprofitable investment:– Optimum adaptability to use cases– Cooperation between user / planner / manufacturerto balance specifications and costsWork book 2CPC 000 313 B01015

Parts of the standard6StandardTitleEditionIEC 61439-0GuidelineApril 2013IEC 61439-1General rules08/14/2011IEC 61439-2Power switchgear and controlgear ASSEMBLIES08/19/2011IEC 61439-3Distribution boards intended to be operated by ordinary persons02/16/2012IEC 61439-4ASSEMBLIES for construction sites11/15/2012IEC 61439-5Assemblies for power distribution in public networks08/25/2014IEC 61439-6Busbar trunking systems05/23/2012PrestandardIEC/TS 61439-7Assemblies for specific applications such as marinas, campingsites, market squares, electric vehicle charging stations and similar02/19/20142CPC 000 305 L0101 Work book

Why a new standard?Who is the manufacturer?Health of the individual is regarded as fundamentalasset within the economic space of the EuropeanUnion.The EU-Commission has therefore made it its goalto elaborate directives, which are then transposedinto national law by Member States.Thus, the low voltage directive is implemented inthe German Product Safety Act.Next to the German Product Safety Act, there isthe Product Liability Act which is designed to protect the user in case of damages.duced a defective product to the market and thatthere is causality between the defective product,the violation of legal rights and the damage. Thequestion whether a manufacturer is responsible forproduct defects puts an unacceptable burden ofproof on the injured party.1This is the reason why a reversed burden of proofis applied here. Meaning that the manufacturer hasto prove that the product was free from defectsin design, workmanship and instructions uponmarketing.Both laws pursue safety targets and are designedto protect people, livestock and property.Regarding product liability for example, injuredparties will only have to demonstrate that their legal rights have been violated and that this violationled to a loss and that the manufacturer has intro-The new standard precisely defines the responsibilities for a marketedproduct. It differentiates between original manufacturer and ASSEMBLY manufacturer.BuildersBuildersSystem manufacturerOriginal manufacturerBuildersASSEMBLYManufacturerWork book 2CPC 000 305 L01017

How can the original manufacturer or the manufacturer verify thesafety of an ASSEMBLY?The new standard describes three design verification processes for ASSEMBLIES and requires aroutine verification for every marketed product.TestingCalculation / measurementApplication of constructive rulessuch as– electrical– mechanical– thermal tests in accordancewith the requirements specified in the standardsuch as– Calculating of temperaturerises or of short-circuit forces– Measurement of clearancesand creepage distancessuch as– specified dimensions– test steps– ASSEMBLY sequencesbased on tested referencedesignsmanufacturer will become original manufacturer for that alteration and will have to carry outthe design verification in accordance with thedescribed procedures.These processes are essentially implementedby the original manufacturer. In case that theASSEMBLY manufacturer does not install anASSEMBLY in compliance with the instructionsof the original manufacturer, the ASSEMBLYIEC 61439ASSEMBLYOriginal manufacturerDesign verification through the original manufacturerTestingCalculation / measurementrulesThe ASSEMBLY manufacturer may:– Proceed to final ASSEMBLY as provided for by the original manufacturer– Deviate from the provisions of the original manufacturer and will thus become originalmanufacturer for this alteration.Routine verificationOperational switchgear ASSEMBLIESThe ASSEMBLY manufacturer always has to implement the routine verification.8Application of constructivePower switchgear and controlgear ASSEMBLIESASSEMBLY manufacturerOriginal manufacturerLow-voltage ASSEMBLY2CPC 000 313 B0101 Work book

How can a low-voltage switchgear and controlgear ASSEMBLY berealized safely?The new standard does not only precisely define the responsibilities ofthe market participants, but also specifies the dimensions of low-voltageswitchgear and controlgear ASSEMBLIES.1In addition it presents the possibilities and limits for the market participants inorder to guarantee to the user safe low-voltage switchgear and controlgearASSEMBLIES.It is also designed to specify the documentation required for low-voltageswitchgear and controlgear ASSEMBLIES and/orthe required verifications.Which are the dimensioning specifications enabling design verification?One important aspect emphasised in the IEC 61439 is the earthing system asthis has important consequences for planing the electrical circuits.Work book 2CPC 000 313 B01019

Notes102CPC 000 313 B0101 Work book

Chapter 1 – collecting the requisite dataConnection to the electrical systemHow are ASSEMBLIES dimensioned?1ASSEMBLIES are dimensioned through the definition of interfacevalues.Installation and3 environmental conditionsOperating and4 servicingConnection to the1 electrical systemCircuits and2 loads1) Connection to the electrical system2) Electrical cicuits and loads––––––– Distribution circuits for load-sidesubdistribution panels– Final circuitsNominal voltage of the incoming supplyElectrical systemRated currentShort-circuit withstand strengthOvervoltageConnecting cable3) Installation and environmental conditions– Indoor installations– Outdoor installations– Dimensions for transport and installation4) Operating and servicingOperation through:– Device activation– Access controlWork book 2CPC 000 313 B010111

2CPC 000 305 L0101 Work book

Connection to the electrical systemElectrical systems and protective systemsEvaluation of the types of earthing for systems, and protectivemeasures in low voltage switchgear ASSEMBLIES1TN systemBenefits:Fast shut-up in case of faults and/or Short-circuits, lowest risk to peopleand propertyDisadvantages:High line and cabling overheads due to installed protective conductor,every fault leads to system downtimesPreferred application:Power plants, public power supply and gridsTT systemBenefits:Minor overheads for installed lines and cabling,different touch voltages acceptable for some areas, combination optionswith TN systemDisadvantages:Complex system earthing ( 2 Ω), compulsory equipotential bonding forevery buildingPreferred application:Agricultural for livestock farmingIT systemBenefits:Minor overheads for installed lines and cabling,high availability of supply:1. Fault is only signalled2. Fault is disconnectedDisadvantages:Required continuous equipment insulation to the voltage between thephase conductors Equipotential bonding necessaryPreferred application:Hospitals, industryDouble insulationBenefits:Highest safety level, combination with other systems possibleDisadvantages:Double insulation of the equipment is only economic for small-scaleconsumers. For thermal equipment there is a fire risk due to theinsulation materialPreferred application:Domestic, electrical distribution boards and small-scale equipmentProtection by extra low voltageBenefits:No risks in case of contactDisadvantages:Limited economic equipment performance, special powercircuit requirementsPreferred application:Small appliancesWork book 2CPC 000 313 B010113

Notes142CPC 000 313 B0101 Work book

Connection to the electrical systemProtection against electric shock (IEC 60364-4-41)Protection measures must include– a suitable combination of two independent protections, i.e. one basic protection and one faultprotection, or– one reinforced protection causing the basic protection (protection against direct contact)and the fault protection (protection against indirect contact).1Generally, the following protective measures are allowed:– Protection by automatically disconnecting the power supply (section 4-41);– Protection by double or reinforced insulation (section 4-42);– Protection by protective separation of a consumer device (section 4-43);– Protection by low voltage by SELV or PELV (section 4-44);4-41 Protective measure: Automatic disconnection of the power supplyAutomatic disconnection of the power supply is a protective measure designed to:– ensure basic protection (protection against direct contact) by basic insulation of the live parts or bycovering or sheathing in line with ANNEX A and– and fault protection (protection against indirect contact) by protective equipotential bonding by themain earthing bar and automatic disconnection in case of faults, [ ]4-42 Protective measure: Double or reinforced insulationDouble or reinforced insulation is a protective measure designed to:– ensure basic protection (protection against direct contact) by basic insulation and fault protection(protection against indirect contact) by an additional insulationor– ensure basic protection and fault protection by a reinforced insulation between live parts andaccessible parts.Protection classesProtection class IThe protection target of protection class I is achieved by insulation of the live parts andconnection of the accessible metal parts to the protective conductor.The protective conductor terminal is identified by .P rotection class IIThe protection target of protection class II is achieved by double insulation.Protection class II is identified by ,.Work book 2CPC 000 313 B010115

Notes162CPC 000 313 B0101 Work book

Connection to the electrical systemOvervoltage categoriesOvervoltage protection in buildingsOvervoltages can result from switching operations in the energy supply systemor in own electrical systems. Overvoltages are then transferred via the system(supply lines and own electrical installations) and may then reach sensitive enddevices, which might then be damaged or destroyed.1There are two types of overvoltage:– Overvoltage generated by switching operations ("switching overvoltage") or byatmospheric influences– Overvoltage generated by direct lightning strikes or lightning strikes in directvicinity of a physical structureThe following types of surge arresters exist for buildings:1.External lightning protection2.Surge arresters in the precounter sector (Type 1)3.Surge arresters in the distribution boards (Type 2)4.Surge arresters for end devices5.Surge arresters for PV systems6.Surge arresters in data engineering and communicationOvervoltage categoriesCategory to describe overvoltages that might be generated by lightning orswitching operations at the place of installation.The following categories are used to describe overvoltages:I Equipment with reduced lightning impulse withstand voltage for aconnection to power circuits equipped with surge arrester systems(e.g. electronic appliances)IIConsumers connected to fixed installations (e.g. electronic tools)III Equipment with special availability requirements and protected bylightning arrestersIV Use of equipment directly at the installation connection point.Direct lightning strikes are possible (e.g. meter panels)Work book 2CPC 000 313 B010117

Notes182CPC 000 313 B0101 Work book

Connection to the electrical systemCharacteristics and explanationsNominal values are defined in DIN 40200 and specify a suitable, rounded parameter value used todescribe or to identify an element, a group or installation. (Example: a general informationdescribing a motor: Nominal current 25 A/nominal voltage 400 V)1Rated values are defined as applicable parameter value at specific operating conditions which aredefined by the manufacturer of a given component, group or installation.(Example: Rated current of 630 A of a fuse switch disconnector for fuse links accordingto DIN 43620 size 3 at a rated operational voltage of 690 V and a rated insulation voltageof 690 V.)Connection of the incoming cables From below From above Copper or aluminium conductor Connection using terminal blocks Single-core cable Multi-core cable / number /section in mm² Connection to equipment / connection using terminal blocksWork book 2CPC 000 313 B010119

NotesInsert the applicable voltage values into the installation scheme.202CPC 000 305 L0101 Work book

Connection to the electrical systemCharacteristics and explanationsRated voltage Un. is the highest stated nominal voltage of a system (AC voltage (effective) or DC voltage) to which themain circuits are designed.For multi-phase systems this is the voltage between the phase conductors.1Rated operational voltage Ue. is the stated voltage value defining the use together with the rated current. In main circuits therated operational current refers to the design of the main contact and to the arc quenching behaviourof the switching device. In terms of their main current switching devices are only tested up to 105 %of the rated operational voltage. The operating voltage of a low voltage switchgear and controlgearASSEMBLY must not exceed this value.For multi-phase systems this is the voltage between the phase conductors.Rated impulse voltage Uimp of the ASSEMBLYThe rated impulse withstand voltage must be equal or greater than the specified transient overvoltagevalues generated in the electrical system to which the circuit is to be connected.Rated frequency ƒn :. is the frequency value stated by the ASSEMBLY manufacturer to which the ASSEMBLY is assignedand to which the operating conditions refer. NOTE: A number or a range of rated frequencies can beassigned to a circuit and be rated for AC or DC power.The limits are between 98 % and 102 % of the rated frequency.In practice, the usual rated frequency is 50 Hz.Under 0 Hz (DC current), special switching devices with specific arc quenching systems are needed.Busbars can support higher loads.Under 16 2/3 Hz the switching devices for 50 Hz have reduced switching capacities.A switching device's switching capacity is reduced at 400 Hz due to the shorter arc quenching time.Busbars can only support reduced loads due to the skin effect.The rated current for busbars under a rated frequency above 50 Hz is calculated by the followingformula:In rated current; Inf rated current under a defined frequency; fn rated frequency; fN nominalfrequency of the system to which the low voltage switchgear and controlgear ASSEMBLY is to beconnectedWork book 2CPC 000 305 L010121

NotesInsert the applicable current values into the installation scheme.222CPC 000 305 L0101 Work book

Connection to the electrical systemCharacteristics and explanationsRated current of the switchgear ASSEMBLY InA. is the current value stated by the manufacturer which can be supported without exceeding thedefined temperature rise limits.1Uninfluenced short-circuit current Icp. is the effective value of that current which would flow if the incoming line of a circuit would beshort-circuited by a conductor in direct vicinity of the connections of the switchgear ASSEMBLY (forthe strength and duration of the short-circuit current, see 10.11.5.4)Rated peak withstand current Ipk. is the highest short-circuit current peak value stated by the ASSEMBLY manufacturer that can bewithstood under specified conditions.Rated short-time withstand current Icw. is the effective value of the short-time current stated by the ASSEMBLY manufacturer , that can bewithstood under specified

Panel Design Configurator software – export/import user article data 129 Temperature rise verification up to 630 A – solution example 131 Data collection tables 133 Verification of temperature rise up to 630 A 139 Design verification part I 141 Design verification part II 143 Unit test protocol 145 Unit test protocol checklist 147

Related Documents:

IEC 61215 IEC 61730 PV Modules Manufacturer IEC 62941 IEC 62093 IEC 62109 Solar TrackerIEC 62817 PV Modules PV inverters IEC 62548 or IEC/TS 62738 Applicable Standard IEC 62446-1 IEC 61724-1 IEC 61724-2 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/TS 62738 IEC 62548 or IEC/

May 02, 2018 · D. Program Evaluation ͟The organization has provided a description of the framework for how each program will be evaluated. The framework should include all the elements below: ͟The evaluation methods are cost-effective for the organization ͟Quantitative and qualitative data is being collected (at Basics tier, data collection must have begun)

Silat is a combative art of self-defense and survival rooted from Matay archipelago. It was traced at thé early of Langkasuka Kingdom (2nd century CE) till thé reign of Melaka (Malaysia) Sultanate era (13th century). Silat has now evolved to become part of social culture and tradition with thé appearance of a fine physical and spiritual .

IEC has formed IECRE for Renewable Energy System verification - Component quality (IEC 61215, IEC 61730, IEC 62891, IEC 62109, IEC 62093, IEC 61439, IEC 60947, IEC 60269, new?) - System: - Design (IEC TS 62548, IEC 60364-7-712, IEC 61634-9-1, IEC 62738) - Installation (IEC 62548, IEC 60364-7-712)

On an exceptional basis, Member States may request UNESCO to provide thé candidates with access to thé platform so they can complète thé form by themselves. Thèse requests must be addressed to esd rize unesco. or by 15 A ril 2021 UNESCO will provide thé nomineewith accessto thé platform via their émail address.

̶The leading indicator of employee engagement is based on the quality of the relationship between employee and supervisor Empower your managers! ̶Help them understand the impact on the organization ̶Share important changes, plan options, tasks, and deadlines ̶Provide key messages and talking points ̶Prepare them to answer employee questions

Dr. Sunita Bharatwal** Dr. Pawan Garga*** Abstract Customer satisfaction is derived from thè functionalities and values, a product or Service can provide. The current study aims to segregate thè dimensions of ordine Service quality and gather insights on its impact on web shopping. The trends of purchases have

IEC 61869-9, IEC 62351 (all parts), IEC 62439-1:2010, IEC 62439-3:2010, IEC 81346 (all parts), IEC TS 62351- 1, IEC TS 62351- 2, IEC TS 62351- 4, IEC TS 62351- 5, Cigre JWG 34./35.11, IEC 60044 (all parts), IEC 60050 (all parts), IEC 60270:2000, IEC 60654-4:1987, IEC 60694:1