Product Catalog Sintesis Air-Cooled Chillers Model RTAF

1y ago
14 Views
2 Downloads
2.79 MB
72 Pages
Last View : 30d ago
Last Download : 3m ago
Upload by : Nixon Dill
Transcription

Product CatalogSintesis Air-Cooled ChillersModel RTAF115 to 520 Nominal TonsApril 2022RLC-PRC049K-EN

IntroductionThe new Trane Sintesis model RTAF chiller is the result of a search for higher reliability,higher energy efficiency, and lower sound levels for today’s environment.Sintesis is the newest member of Ingersoll Rand’s EcoWise portfolio ofproducts, designed to lower environmental impact with next-generation, lowglobal warming potential (GWP) refrigerant and high efficiency operation.Sintesis chillers are designed to operate with either R-134a or DuPont Opteon (R-513A), anext generation refrigerant with 55 percent lower GWP than R-134a.The Sintesis chiller uses the proven design of the Trane helical-rotary compressor, whichembraces all of the design features that have made theTrane helical-rotary compressor liquidchillers such a success since 1987.Sintesis chillers offers high reliability coupled with greatly improved energy efficiency, andimproved acoustical performance, due to its advanced design, low-speed, direct- drivecompressor, and proven Sintesis performance. The major advantages of the Sintesis chillerare: High reliability Lower sound level Higher energy efficiency at full load & part loadThe Sintesis model RTAF chiller is an industrial-grade design, built for both the industrial andcommercial markets. It is ideal for schools, hotels, hospitals, retailers, office buildings, andindustrial applications.CopyrightThis document and the information in it are the property of Trane, and may not be used orreproduced in whole or in part without written permission. Trane reserves the right to revise thispublication at any time, and to make changes to its content without obligation to notify anyperson of such revision or change.TrademarksAll trademarks referenced in this document are the trademarks of their respective owners.Revision History Updated fan data due to supplier change. Affected chapters include: 2022 TraneUpdated to Symbio 800 Controls.–General Data–Features and Benefits–Controls–Dimensions–Mechanical SpecificationsUpdated field wiring diagrams.RLC-PRC049K-EN

Table of ContentsFeatures and Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Sintesis Helical Rotary Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Capacity Control and Load Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Close Spacing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Factory Testing Means Trouble-Free Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Integrated Rapid Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Rapid Restart Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Microchannel Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6CHIL Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Precision Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Unit Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Water Treatment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Effect of Altitude on Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Ambient Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Water Flow Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Water Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Variable Flow in the Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Series Chiller Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Typical Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Multiple Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Free-Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Thermal Battery Cooling System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Unit Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Unit Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Free-Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21RLC-PRC049K-EN3

Table of ContentsControls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Symbio 800 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Tracer AdaptiView TD7 Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22System Integration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Symbio 800 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Integrated Comfort System (ICS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Customer Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Service Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Base Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Option Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Certified AHRI Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Condenser and Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Compressor and Lube Oil System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Adaptive Frequency Drive (AFD) Compressor Starter . . . . . . . . . . . . . . . . . . . . . . . . . . 65Chilled Water Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Factory Mounted Flow Proving and Flow Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Application Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Electrical Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Control Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Other Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 684RLC-PRC049K-EN

Features and BenefitsSintesis Helical Rotary Compressor Unequaled-reliability. The Sintesis Trane helical-rotary compressor is designed, built, andtested to the same demanding and rugged standards as the Trane scroll compressors, thecentrifugal compressors, and the previous generation helical-rotary compressors used inboth air- and water-cooled chillers for more than 30 years. Years of research and testing. The Trane helical-rotary compressor has amassed thousandsof hours of testing, much of it at severe operating conditions beyond normal commercial airconditioning applications. Proven track record. The Trane Company is the world’s largest manufacturer of large helicalrotary compressors used for refrigeration. Over 300,000 compressors worldwide have provenTrane helical- rotary compressor reliability. Resistance to liquid slugging. The robust design of the compressor can ingest amounts ofliquid refrigerant that normally would severely damage compressor. Fewer moving parts. The helical- rotary compressor has only two rotating parts: the malerotor and the female rotor. Direct-drive, low-speed, semi- hermetic compressor for high efficiency and high reliability. Suction-gas-cooled motor. The motor operates at lower temperatures for longer motor life. Five minute start-to-start and two minute stop-to-start anti-recycle timer allows forcloserwater- loop temperature control.Capacity Control and Load MatchingThe combination unloading system onTrane helical- rotary compressors uses the adaptivefrequency drive for the majority of the unloading function.This allows the compressor tomodulate infinitely, to exactly match building load and to maintain chilled-water supplytemperatures within 0.5 F [ 0.3 C] of the set point. Helical- rotary chillers that rely on steppedcapacity control must run at a capacity equal to or greater than the load, and typically can onlymaintain water temperature to around 2 F [ 1 C]. Much of this excess capacity is lost becauseovercooling goes toward removing building latent heat, causing the building to be dried beyondnormal comfort requirements.The combination of the variable unloading valve plus the adaptive frequency drive allow exactload matching and excellent efficiencies at full load and part load.Figure 1. Cutaway of a compressorRLC-PRC049K-EN5

Features and BenefitsClose Spacing InstallationThe Sintesis chiller is minimally affected in many restricted air flow situations due to itsadvanced Adaptive Control microprocessor, which has the ability to understand the operatingenvironment of the chiller and adapt to it by first optimizing its performance and then staying online through abnormal conditions. Consult your sales engineer for more details.Factory Testing Means Trouble-Free Start-upAll Sintesis chillers are given a complete functional test at the factory. This computer-basedtest program completely checks the sensors, wiring, electrical components, microprocessorfunction, communication capability, expansion valve performance, and fans. In addition, eachcompressor is run-tested to verify capacity and efficiency. The result of this test program is thatthe chiller arrives at the job site fully tested and ready for operation.Integrated Rapid RestartBringing a chiller back online rapidly after a loss of power is critical to operations in missioncritical environments like data centers and hospitals which demand the highest levels ofreliability.A loss of cooling capacity can be costly, which is why Trane chillers are designed and engineeredfor Rapid Restart. In the event of a power interruption, the chiller will start a compressor beforethe front panel display is fully powered up eliminating the need for UPS. This not only helps thechiller get back online faster, but it also provides a simple and reliable solution to minimize therisks of financially devastating damage to assets caused by overheating due to a power loss.Of course, the truest test of a chiller’s restart capabilities is the amount of time it takes to resumefull-load cooling, and this is where the chiller really shines. An 80 percent cooling load can beachieved in less than 2.5 minutes after power restoration—your assurance that the coolingcapacity your equipment requires is just a few minutes away.Rapid Restart TestAfter completion of a standard full load witness test, power to the chiller will be cut and thenreapplied to demonstrate the chiller’s rapid restart capabilities for disaster relief.Microchannel Condenser CoilMicrochannel condensing coils are all-aluminum coils with fully-brazed construction. This designreduces risk of leaks and provides increased coil rigidity — making them more rugged on thejobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow forexceptional heat transfer. Microchannel all-aluminum construction provides several additionalbenefits: 6Light weight (simplifies coil handling)Easy to recycleMinimize galvanic corrosionRLC-PRC049K-EN

Features and BenefitsCHIL EvaporatorCompact - High performance - Integrated design - Low refrigerant charge (CHIL) evaporatoroptimizes the flow of refrigerant for excellent heat transfer and minimizes the volume ofrefrigerant used.Figure 2. CHIL evaporator, 115 to 270 ton units, 2-passCircuit 1RefrigerantOutCircuit 2RefrigerantOutReturnWaterboxCircuit 1Refrigerant InSupplyWaterboxCircuit 2Refrigerant InFigure 3. CHIL evaporator, 280 to 520 tons, 1-passFansSintesis chillers use Electronically Commutated (EC) fans in order to reduce powerconsumption at full load and at part load. EC fans allow a significant reduction of sound level anda better operation of the chiller at low ambient conditions.Precision Control RLC-PRC049K-ENNew 7 inch color touch screen display with graphics7

Features and Benefits Powered by Symbio 800 industry-leading control algorithms– 8Enhanced flow management provides unmatched system performance in variable flowwater systemsAdaptive Control keeps the chiller running in extreme conditions–Tight set point control–Graphical trending–Maximized chiller updateBACnet , Modbus , LonTalk , communications protocol interface available without theneed for gatewaysRLC-PRC049K-EN

Application ConsiderationsCertain application constraints should be considered when sizing, selecting, and installing Tranechillers. Unit and system reliability is often dependent on properly and completely complyingwith these considerations. When the application varies from the guidelines presented, it shouldbe reviewed with your local sales engineer.N o t e : The terms water and solution are used interchangeably in the following paragraphs.Unit SizingIntentionally oversizing a unit to ensure adequate capacity is not recommended. Erratic systemoperation and excessive compressor cycling are often a direct result of an oversized chiller. Inaddition, an oversized unit is usually more expensive to purchase, install, and operate. Ifoversizing is desired, consider using two units.Water TreatmentThe use of untreated or improperly treated water may result in scaling, erosion, corrosion, andalgae or slime buildup. This will adversely affect heat transfer between the water and systemcomponents. Proper water treatment must be determined locally and depends on the type ofsystem and local water characteristics.Neither salt nor brackish water is recommended for use in Trane air-cooled chillers. Use of eitherwill lead to a shortened life. Trane encourages the employment of a qualified water treatmentspecialist, familiar with local water conditions, to assist in the establishment of a proper watertreatment program.Foreign matter in the chilled water system can also increase pressure drop and, consequently,reduce water flow. For this reason it is important to thoroughly flush all water piping to the unitbefore making the final piping connections to the unit.Effect of Altitude on CapacityAt elevations substantially above sea level, the decreased air density will decrease condensercapacity and, therefore, unit capacity and efficiency.Ambient LimitationsTrane chillers are designed for year-round operation over a range of ambient temperatures. Foroperation outside of these ranges, contact the local sales office. Standard Ambient Range 14 to 115 F (-10 to 46 C) Low Ambient Range -4 to 115 F (-20 to 46 C) High Ambient Range 14 to 130 F (-10 to 54.4 C) Wide Ambient Range -4 to 130 F (-20 to 54.4 C)The minimum ambient temperatures are based on still conditions (winds not exceeding fivemph). Greater wind speeds will result in a drop in head pressure, therefore increasing theminimum starting and operating ambient temperature. The AdaptiveFrequency microprocessor will attempt to keep the chiller on-line when high or low ambient conditionsexist, making every effort to avoid nuisance trip-outs and provide the maximum allowabletonnage.Water Flow LimitsThe minimum water flow rates are given in the General Data chapter of this catalog. Evaporatorflow rates below the tabulated values will result in laminar flow causing freeze-up problems,scaling, stratification and poor control.RLC-PRC049K-EN9

Application ConsiderationsThe maximum evaporator water flow rate is also given in General Data. Flow rates exceedingthose listed may result in very high pressure drop across the evaporator and/or excessive tubeerosion.N o t e : Flow rates in the general data tables are for water only. They do not include freezeinhibitors.Flow Rates Out of RangeMany process cooling jobs require flow rates that cannot be met with the minimum andmaximum published values within the evaporator. A simple piping change can alleviate thisproblem. For example: a plastic injection molding process requires 80 gpm (5.0 l/s) of 50 F (10 C)water and returns that water at 60 F (15.6 C). The selected chiller can operate at thesetemperatures, but has a minimum flow rate of 120 pgm (7.6 l/s). The system layout in the figurebelow can satisfy the process.Figure 4. Flow rate out of range systems solution50 F79.3 gpm50 F120.5 gpmPUMP79.3 gpm50 F39.7 gpmLOAD56.7 F120.5 gpmPUMP60 FFlow ProvingTrane provides a factory-installed water flow switch monitored by Symbio 800 controller whichprotects the chiller from operating in loss of flow conditions.Flow ControlTrane requires the chilled water flow control in conjunction with the Sintesis Chiller to be doneby the chiller. This will allow the chiller to protect itself in potentially harmful conditions.Variable Flow in the EvaporatorVariable Primary Flow (VPF) systems present building owners with several cost-saving benefitswhen compared with Primary/Secondary chilled water systems. The most obvious cost savingsresults from eliminating the constant volume chiller pump(s), which in turn eliminates the relatedexpenses of the associated piping connections (material, labor), and electrical service and switchgear. In addition to the installed cost advantage, building owners often cite pump related energysavings as the reasons that prompted them to select a VPF system.The chiller is capable of handling variable evaporator flow without losing control of the leavingwater temperature.The microprocessor and capacity control algorithms are designed to handle a10 percent change in water flow rate per minute while maintaining a 2 F (1.1 C) leaving watertemperature control accuracy. The chiller tolerates up to 30 percent per minute water flowvariation as long as the flow is equal or above the minimum flow rate requirement.With the help of a software analysis tool such as System Analyzer , DOE-2 orTRACE ,anticipated energy savings can be determined, and used to justify variable primary flow in aparticular application. Existing constant flow chilled water systems may be relatively easilyconverted to VPF and benefit greatly from the inherent efficiency advantages.10RLC-PRC049K-EN

Application ConsiderationsWater TemperatureLeaving Water Temperature LimitsTrane chillers have distinct leaving water categories: Standard, with a leaving solution range of 40 to 68 F (4.4 to 20 C) Low temperature process cooling, with leaving solution less than 40 F (4.4 C) Ice-making, with a leaving solution range of 10.4 to 68 F (-12 to 20 C)Since leaving solution temperatures below 40 F (4.4 C) result in suction temperature at or belowthe freezing point of water, a glycol solution is required for all low temperature and ice-makingmachines. Ice making control includes dual setpoints and safeties for ice making and standardcooling capabilities. Consult your local Trane account manager for applications or selectionsinvolving low temperature or ice making machines.The maximum water temperature that can be circulated through the evaporator when the unit isnot operating is 125 F (52 C). Evaporator damage may result above this temperature.Leaving Water Temperature Out of RangeMany process cooling jobs require temperature ranges that cannot be met with the minimumand maximum published values for the chiller. A simple piping change can alleviate thisproblem. For example, a laboratory load requires 120 gpm (7.6 l/s) of water entering the processat 85 F (29.4 C) and returning at 95 F (35 C). The chiller’s maximum leaving chilled watertemperature of 64 F (18 C) prevents direct supply to the load. In the example shown, both thechiller and process flow rates are equal, however, this is not necessary. For example, if the chillerhad a higher flow rate, there would be more water bypassing and mixing with warm waterreturning to the chiller.Figure 5. Temperature out of range system solution85 F120.5 gpm60 F35 gpm60 F120.5 gpmPUMP95 F85.5 gpmLOAD60 F85.5 gpm70 F120.5 gpmPUMP60 F95 FVariable Flow in the EvaporatorAn attractive chilled water system option may be a variable primary flow (VPF) system. VPFsystems present building owners with several cost saving benefits that are directly related to thepumps. The most obvious cost savings result from eliminating the secondary distribution pump,which in turn avoids the expense incurred with the associated piping connections (material,labor), electrical service, and variable frequency drive. Building owners often cite pump relatedenergy savings as the reason that prompted them to install a VPF system.The evaporator on the chiller can withstand up to 50 percent water flow reduction as long as thisflow is equal to or above the minimum flow rate requirements. For applications in which systemenergy savings is most important and tight temperature control is classified as 2 F (1.1 C), upto 30 percent changes in flow per minute are possible.With the help of a software analysis tool such as System Analyzer , DOE-2 or TRACE , you candetermine whether the anticipated energy savings justify the use of variable primary flow in aparticular application. It may also be easier to apply variable primary flow in an existing chilledRLC-PRC049K-EN11

Application Considerationswater plant. Unlike the "decoupled" system design, the bypass can be positioned at variouspoints in the chilled water loop and an additional pump is unnecessary.Series Chiller ArrangementsAnother energy saving strategy is to design the system around chillers arranged in series. Theactual savings possible with such strategies depends on the application dynamics and should beresearched by consulting your Trane Systems Solutions Representative and applying ananalysis tool from the Trace software family. It is possible to operate a pair of chillers moreefficiently in a series chiller arrangement than in a parallel arrangement. It is also possible toachieve higher entering to leaving chiller differentials, which may, in turn, provide theopportunity for lower chilled water design temperature, lower design flow, and resultinginstallation and operational cost savings. The Trane screw compressor also has excellentcapabilities for “lift,” which provides an opportunity for savings on the evaporator water loop.Series chiller arrangements can be controlled in several ways. The figure below shows a strategywhere each chiller is trying to achieve the system design set point. If the cooling load is less than50 percent of the systems capabilities, either chiller can fulfill the demand. As system loadsincrease, the Chiller 2 becomes preferentially loaded as it attempts to meet the leaving chilledwater setpoint. Chiller 1 will finish cooling the leaving water from Chiller 2 down to the systemdesign setpoint.Staggering the chiller set points is another control technique that works well for preferentiallyloading Chiller 1. If the cooling load is less than 50 percent of the system capacity, Chiller 1 wouldbe able to satisfy the entire call for cooling. As system loads increase, Chiller 2 is started to meetany portion of the load that Chiller 1 can not meet.Figure 6. Typical series chiller arrangementChiller 2Setpoint 42 F (5.6 C)58 F(14.4 C)Chiller 1Setpoint 42 F (5.6 C)Variabledependingon loadBlendingValve42 F (5.6 C)Typical Water PipingAll building water piping must be flushed prior to making final connections to the chiller. Toreduce heat loss and prevent condensation, insulation should be applied. Expansion tanks arealso usually required so that chilled water volume changes can be accommodated.Avoidance of Short Water LoopsAdequate chilled water system water volume is an important system design parameter becauseit provides for stable chilled water temperature control and helps limit unacceptable short cyclingof chiller compressors.The chiller’s temperature control sensor is located in the waterbox. This location allows thebuilding to act as a buffer to slow the rate of change of the system water temperature. If there isnot a sufficient volume of water in the system to provide an adequate buffer, temperature controlcan suffer, resulting in erratic system operation and excessive compressor cycling.Typically, a two-minute water loop circulation time is sufficient to prevent short water loopissues. Therefore, as a guideline, ensure the volume of water in the chilled water loop equals orexceeds two times the evaporator flow rate. For systems with a rapidly changing load profile theamount of volume should be increased.12RLC-PRC049K-EN

Application ConsiderationsIf the installed system volume does not meet the above recommendations, the following itemsshould be given careful consideration to increase the volume of water in the system and,therefore, reduce the rate of change of the return water temperature. A volume buffer tank located in the return water piping. Larger system supply and return header piping (which also reduces system pressure dropand pump energy use).Minimum Water Volume for a Process ApplicationIf a chiller is attached to an on/off load such as a process load, it may be difficult for the controllerto respond quickly enough to the very rapid change in return solution temperature if the systemhas only the minimum water volume recommended. Such systems may cause chiller lowtemperature safety trips or in the extreme case evaporator freezing. In this case, it may benecessary to add or increase the size of the mixing tank in the return line.Multiple Unit OperationWhenever two or more units are used on one chilled water loop, Trane recommends that theiroperation be coordinated with a higher level system controller for optimum system efficiencyand reliability. The Trane Tracer system has advanced chilled plant control capabilitiesdesigned to provide such o

Sintesis Air-Cooled Chillers Model RTAF 115 to 520 Nominal Tons 2022 Trane RLC-PRC049K-EN . embraces all of the design features that have made theTrane helical-rotary compressor liquid chillers such a success since 1987. Sintesis chillers offers high reliability coupled with greatly improved energy efficiency, and

Related Documents:

Sintesis Air-Cooled Chillers Model RTAF 115 to 520 Nominal Tons Product Catalog 2019 Ingersoll Rand RLC-PRC049H-EN Introduction The new Trane Sintesis model RTAF chiller is the result of a search for higher reliability, higher energy efficiency, and lower sound levels for today's environment.

Air Cooled Chiller Air Air 2 Air Air 6 AIR COOLED CHILLERS Air-cooled chillers are refrigeration machines that remove heat from cooling loads using chilled water and reject this heat into the atmosphere using refrigerant. THEY ALL HAVE fans, condenser coils, and compressors. Air-cooled chillers are used to provide cooling for human comfort and electronic equipment as well as industrial process .

Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 80 F chilled water. MAXIMUM SERIES † Air & Water-Cooled † 1/4 to 40 Tons † 20 F to 80 F † Using Non-Ozone Depleting Refrigerants 10 ton air-cooled model 10 ton water-cooled model 2 ton water-cooled model 1 ton air-cooled model

ACH Air-Cooled, Horizontal Air Flow ACV Air-Cooled, Vertical Air Flow ACR Air-Cooled Remote Condenser WCC Water-Cooled Condenser Digit 6 — Chilled Water System P Recirculating System, Tank and Pump M Single Pass Chiller Unit (no tank and pump) Digit 7 — Cabinet Type H Horizontal Low Profile V Vertical Upright

Air-Cooled Chiller The use of air-cooled chillers in process and comfort cooling applications has been steadily increasing in recent years. The air-cooled chiller has evolved from a packaged product, with few options, to a fully customizable unit that can be tailored to meet specific application and job site requirements. High-efficiency air-cooled

MECANISMOS M.C. IGNACIO ARRIOJA CÁRDENAS Página 1 UNIDAD V SÍNTESIS DE MECANISMOS 5.1 INTRODUCCIÓN A LA SÍNTESIS DE MECANISMOS. El término síntesis cinemática se ref

Vanguard Air-Cooled V-Twin Specifications Performance Curves 14 HP Vanguard Air-Cooled V-Twin 16 HP Vanguard Air-Cooled V-Twin 15.0 5.2 Kilowatt 7.5 8.2 9.0 9.7 10.4 111.2 111.9 14.0 13.0 12.0 11.0 10.0 9.0 8.0 7.0 16.0 6.7 6.0 HP 1800 2000 2200 24002600 2800 3000 3200 3400 3600 17.0 12.7 REVOLUTIONS PER MINUTE RATED GROSS BHP MAXIMUM .

Tourism and Hospitality Terms published in 1996 according to which Cultural tourism: General term referring to leisure trav el motivated by one or more aspects of the culture of a particular area. ('Dictionary of Travel, Tour ism and Hospitality Terms', 1996). One of the most diverse and specific definitions from the 1990s is provided by ICOMOS (International Scientific Committee on Cultural .