Fire Detection &Alarm DevicesConventional IGN Addressable Series ADX Addressable Series

CONTENTSIGN Series Addressable3Intelligent Addressable Fire Alarm Control Panel .3Manual Call Point & Hold Off Switch .5Intelligent Addressable Optical Smoke Detector .6 .7Intelligent Dual Heat DetectorIntelligent Smoke & Heat Detector 7 .8Addressable Sounder Strobe 9Addressable Sounder .10Intelligent Sounder Strobe .11Loop Passive Repeater12Beam Detector .Addressable Input Module 13Addressable Single Input / Output Module .14Addressable Dual Input / Output Module .16 .18Addressable Zone Monitor Module .19Power Supply Unit20Isolator Module .Handheld Programmer .ADX Series UL Addressable Fire Alarm System2122Arius Addressable Fire Alarm Control Panel .22Arius Network LCD Annunciator .23Arius Serial LCD Annunciator .24Addressable Manual Pull Station .25Intelligent Smoke Detector 26 27Intelligent Multisensor 28Dual Relay Module .29Fast Response Contact Module 30Conventional Zone Input Module 31 32Short Circuit Isolator .33Selectable Candela Evacuation Signals .34 .35 35 36Intelligent Heat DetectorSupervised Output ModuleConventional Fire Alarm SystemFire Alarm Control PanelManual Call PointFire Alarm Bell .Conventional Sounder Strobe36 .36 .37Conventional Heat Detectors .37Conventional Multisensor38Conventional Smoke DetectorsExtinguishant Control Panel . 39Hold Off Switch .41BRISTOL Fire Alarm & Devices Datasheets Rev. 02

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemIntelligent Addressable Fire Alarm Control PanelEN 54-21330h(cl-l)The IGN comprise of a alarm control equipment toFEATURES offer flexibility in both designand operation. The System ismodular concept for easytailoring of system design, toUsingadvancemicroprocessortechnology with Large memory capacity Enhance user interface combining LCDTouch screen and keypad access Support real time visual algorithmthe project. The IGN Intelligent Fire Alarm Control Panel is designed Enhance false alarm preventionand manufactured to meet the requirement of BS EN54 Part 2&4. Keypad and PC programming Support Multiple interface protocol suchmeet the full requirements ofas USB/Ethernet/CanFiber OpticThe IGN is designed to provide early warning fire detection, to quicklyidentify the location of fire and provide user definable text informingthe occupants of the building of potential smoke spread. Simultane- Support Loop Powered devices for extrasaving on cable costously, the IGN will alert and evacuate the occupants, and control allnecessary auxiliary command functions such as elevator control, airBus/Serial/RS485/ Built-InPrinterand160LEDIndicatorshandling shut down, gas shut off & damper control, as per the causeand effects requirements configured though Command Builder Set-up.SYSTEM CAPACITYCOMMISSIONING ADVANTAGES Up to 4 loop (6 loop standalone) Auto Enrolling of Devices Support 254 Devices (1,524 ideal) Loop Mapping with color coding status Network up to 512 Node Monitor device mismatch and dual address Programmable Capacityconflict Zones up to 3000Command Builder to create requirements for Sounders Groups 1-1000 Other Groups 1001- 2000 Built-in 160 LED Zones Indicatorfire event scenario With Loop protection against power surge One-man test with On/Off sounder Programming ProtectionBRISTOL Fire Alarm & Devices Datasheets Rev. 03Zones

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemTechnical DataMODEL SeriesIGN-250StandardEN54-2: 1997 A1: 2006 & EN54-4: 1997 A1: 2002 A2: 2006Maximum Loop4 with Network Card, 6 StandaloneInput Voltage240VAC 10%-15%, 50/60HzInput Current Consumption1APSU Output to CIE24.5 to 28.5 VDCBatteries2 x 12V / 24AHPanel to panel communicationCan Bus [loop]Number of Panels512Interface PortUSB, RS485, RS232 Serial, EthernetMemory [Non-Volatile]1,000 Fire Events, 10,000 General EventZones3,000 programmableTotal Group3,000 programmable: Sounder 1,000/Common 2,000Protocol/AddressingT&A, Value range from 1 to 254ProtectionBuilt-in 4kV Surge protectionPower rating16 to 24VdcCabling1.2Km Max Length / 2 x 1.5mm2 solid core Fire resistanceProgrammable Relays4 circuits: Normally Open/CloseProgrammable Input1 Circuit: Power limited 24VdcProgrammable Auxiliary Power19 t0 28 VDC (Note: Current Limited)Fixed Outputs (FPE/Sounder)2 Circuits: 18 t0 28 VDC (Note: Current Limited)Indicator24 LED Status/ 16 Zone IndicatorDisplay7" TFT Touch ScreenKeypad5 Brigade buttons and Programming KeypadMaterial / ColorFlat sheet Metal / with outer glass door, Orange stripeDimension Lx W x H530 mm x 490 mm x 135 mmWeight16.70 KgHumidity0 to 95% Relative Humidity, Non condensingBRISTOL Fire Alarm & Devices Datasheets Rev. 04

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemAlarm DevicesAlarm Devices in Fire Detection and Alarm System are devices that are activated during presence of fire to provide noticeto the concerned people in form of audio or visual signals. Though in some cases, signals are already directed to the firedepartment. BRISTOL offers audio/visual alarm devices that comply to international and local standards.Manual Call PointThe IGN-8401Addressable Manual Call point use a non-breakable glass which is designedto press under light pressure triggering the call point into an alarm condition, with LED indicator mounted onto the front face to simplify the location of an operated call point. Safeto press and no hammer is required. The protected flap on the lower part is used for resetthrough supplied special tool.Technical SpecificationsMODELIGN-8401ComplianceEN 54-11:2001 A1:2005Input Voltage24VDC [16V to 28V]Current ConsumptionStandby 0.6mA, Alarm: 1.8mAProtocol/AddressingT&A, Value range from 1 to 254IndicatorSingle LED / 360 degree VisualMaterial / ColorFireproof ABS / RED Glossy finishingDimension / Height89 mm x 93 mm x 35 mmWeight102g (with Base), 80g (without Base)ClassType A, IndoorsOperating Temperature-10 C to 55 CHumidity0 to 95% Relative Humidity, Non condensingBRISTOL Fire Alarm & Devices Datasheets Rev. 0Features5 EN 54-11:2001 A1:2005 LPCB Approved Using microprocessor technology Digital addressing Non-breakable glass and hammerless Safe to operate and easy to reset Surface mounted, indoor application

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemDetectorsDetectors are equipment designed to monitor presence of fire which is manifested by heat and smoke. Heat detectorscan be classified as fixed-temperature, rising-heat or combination of both while smoke detectors work either by opticaldetection or by ionization. BRISTOL Detectors are designed with great regard to quality and comply to international andlocal standards.FeaturesIntelligent Addressable Optical SmokeDetector LPCB Approved Using microprocessor technology with memory capacityup to 10 eventsThe IGN-7401 Intelligent Addressable Optical Smoke Detector isthe ideal device for most applications, due to its spiffing linear responseto a wide variety of different types of smoke patterns. The unit manufactured the sensitivity requirement of EN 54 part 7, European Standard.The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs. The unit incorporates an intelligentprocessor that provides Algorithm map, inbuilt A/D converter, Drift compensation, and Self-Diagnosis and History log.MODEL Analogue sending and digital addressing Provide real time algorithm to the control panel Smart linear drift compensation Onsite adjustable parameter 360-degree visual indicator Removable chamber against dust and small insect Ancillary remote indicator output Aesthetically pleasing designIGN-7401StandardEN54-7 :2000 A1:2002 A2:2006Input Voltage24VDC [16V to 28V]Current ConsumptionStandby 0.6mA, Alarm: 4mAProtocol/AddressingT&A, Value range from 1 to 254SensitivityAs per stipulated standardIndicatorSingle LED / 360 degree VisualMaterial / ColorABS / White Glossy finishingDimension / HeightDiameter 99.7 mm / 57 mmWeight145g (with Base), 90g (without Base)Operating Temperature-10 C to 50 CHumidity0 to 95% Relative Humidity, Non condensingApprovalEN54-7:2000 A1:2002 A2:2006 ComplianceBRISTOL Fire Alarm & Devices Datasheets Rev. 0EN 54-21330h(cl-l)60832-CPR-F1702Y17

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemIntelligent Dual Heat DetectorThe IGN-7402 Intelligent Fixed and Rate of Rise Heat Detector is reliable forapplication in places where may have high dust level or smoky environ-Intelligent Smoke & Heat Detectorments, making a normal smoke detector undesirable. The unit manufac-The IGN-7402 Intelligent Fixed and Rate of Rise Heat Detector is relia-tured base on the sensitivity requirement of EN 54 part 5, European Stand-ble for application in places where may have high dust level orard. The unit is aesthetically pleasing with unobtrusive design that will com-smoky environments, making a normal smoke detector undesirable.plement modern building designs. The unit incorporates an intelligentThe unit manufactured base on the sensitivity requirement of EN 54processor that provides inbuilt A/D converter, and Self-Diagnosis andpart 5, European Standard. The unit is aesthetically pleasing withHistory log.unobtrusive design that will complement modern building designs.The unit incorporates an intelligent processor that provides inbuilt A/Dconverter, and Self-Diagnosis and History log.EN 403ComplianceEN54-5 :2000 A1:2002ComplianceEN54-29Input Voltage24VDC [16V to 28V]Input Voltage24VDC [16V to 28V]Current ConsumptionStandby 0.6mA, Alarm: 4mACurrent ConsumptionStandby 0.6mA, Alarm: 4mAProtocol/AddressingT&A, Value range from 1 to 254Protocol/AddressingT&A, Value range from 1 to 254A1RSmoke SensitivityAs per stipulated standardSingle LED / 360 degree VisualHeat Class TypeA2RMaterial / ColorABS / White Glossy finishingIndicatorSingle LED / 360 degree VisualDimension / HeightDiameter 99.7 mm / 57 mmMaterial / ColorABS / White Glossy finishing127g (with Base), 72g (without Base)Dimension / HeightDiameter 99.7 mm / 57 mm-10 C to 50 CWeight145g (with Base), 90g (without Base)0 to 95% Relative Humidity, Non condensingOperating Temperature-10 C to 50 CHumidity0 to 95% Relative Humidity, Non con-MODELHeat Class TypeIndicatorWeightOperating TemperatureHumidityBRISTOL Fire Alarm & Devices Datasheets Rev. 07

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemBeam DetectorIGN-C7404 Reflective Beam Detector has built in Laser beam pointing andDigital guide display for real user friendly alignment method. The Laser beampointing accurately point the exact location where to mount mirror and withadditional digital guide display allows to monitor and guide on the actual lightintensity between the mirror and detector which cannot be seen by our naked eye making it more easy and convenient in alignment -12:2002Operating Voltage20 V to 28 V DCCurrent ParametersStandby:23mA Commission:56mA Alarm:33mAFeaturesLevel 1: 2.6 dB High SensitivityBeam Sensor Sensitivity [viaEncoder] EN54-12 Certified Hassle free alignment, built with digitalLevel 3: 5.8 dB Low SensitivitySpan 1: 8 to 20 meters Short Path (1x mirror reflector required)guide display and laser beam pointing Employ single-ended design throughreflective mirror Beam Pathway Length [viaEncoder]Four ranges wide monitoring from 8-100Three users programing sensitivityadjustment Built-in microprocessor Self-diagnosis function can monitor forinternal faults Automaticcompensationforfactorsweakening received signals, such as dustcontamination, positional movement andageing of the transmitter Fire and Fault interfacing relays Attractive and pleasing appearance Real User friendly alignment methodBRISTOL Fire Alarm & Devices Datasheets Rev. 0Span 2: 20 to 40 meters Short Path (1x mirror reflector required)Span 3: 40 to 70 meters Normal Path (4x mirror reflector required)Span 4: 70 to 100 meters Long Path (4x mirror reflector required)meters via encoder Level 2: 3.8 dB Medium SensitivityBeam Path Angle 0.5º DirectionalAlignment GuideLaser Beam PointerDigital Display GuideNixie TubeLED Indicator GuideRed: Fire; Yellow: Fault; Green: AlignmentReset TimeLess than 2 Second (Power Cut)Relay Capacity [Fire & Fault]Normally Open/ 2.0 A; 30 VDCMaterial / ColorABS / WhiteDimension / WeightL:190.87 x W:126.87 x H:91.96 mm / 440 gmWeight0.130 Kg with baseAccessoriesMounting Bracket/ IGN-C7404R 4 x Mirror ReflectorOperating Temperature /ProtectionRating-10 C to 55 C / IP30 [IP66 glue seal-For permanent fixing]Humidity0 to 95% Relative Humidity, Non condensing8

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemAddressable Sounder StrobeThe Addressable Sounder & Strobe are alarm warning device used to notify persons in the vicinity of the occurrence fire emergency in order the person to takeappropriate measures. The unit adopt multi-application device starting from thetypes, parameters and wiring layout in single unit. The AVI-6401 can change intodifferent alarm warning types such as sounder-strobe type, sounder type or strobetype using programming tool. In addition, parameters can be configured according to the requirement which include alarm tone from 17 different tones, singleaddress or dual address mode and also setting of power mode to low currentconsumption in a simple programming.AVI-6401Technical SpecificationsAVI-6401StandardInput VoltageTypical CurrentFeaturesEN54-3:2001 A1:2002 A2:2006 EN54-3:2001 A1:2002 A2:2006 ComplianceLoop Power: 24VDC [18V to 27.5V] Built-in MCU processor and digital addressing 17 tones Programmable sound output Programmable types such as Sounder-Strobe, Sounder orStrobe aloneLoop: Standby 0.6mA, Alarm: 1.5mASaving CurrentStandby 1.2mA, Alarm: 9mAProtocol/AddressingT&A, Value range from 1 to 254 Programmable Evacuate or Pre-alarm/Evacuate signalTones17 Tones (refers to Manual) Low and normal consumption modeAddress SequenceSingle Address: Evacuate tone One or Two addresses modeDual Address:1st Alert Tone / 2nd Evacuate tone 10 Highlights LED status clusterStrobe Light10 Highlights LED Onsite Adjustable ParametersMaterial / ColorABS / Red Glossy finishing Loop or external power inputDimensionDiameter 110 mm / 39.6 (with Base) Aesthetically pleasing designWeight176g (with Base), 110g (Without Base) Universal mounting with fix base for simple installationIngress Protection RatingIP21ClassType A, IndoorsOperating Temperature-10 C to 50 CHumidity0 to 95% Relative Humidity, NoncondensingBRISTOL Fire Alarm & Devices Datasheets Rev. 09

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemAddressable SounderAVI-6402The AVI-6402 Addressable Sounder Strobe is alarm warningdevice used to notify persons in the vicinity of the occurrenceTechnical Specificationfire emergency in order the person to take appropriatemeasures. The unit adopt multi-application device startingStandardfrom the types, parameters and wiring layout in single unit. TheAVI-6402 can change into different alarm warning types suchInput Voltageas sounder-strobe type, sounder type or strobe type usingprogramming tool. In addition, parameters can be configuredTypical Currentaccording to the requirement which include alarm tone from17 different tones, single address or dual address mode andalso setting of power mode to low current consumption in asimple programming.AVI-6402Features EN54-3 Compliance Built-in MCU processor and digital addressing 17 tones Programmable sound output Programmable Evacuate or Pre-alarm/Evacuate signal Low and normal consumption mode One or Two addresses mode Onsite Adjustable Parameters Loop or external power input Aesthetically pleasing design Universal mounting with fix base for simpleinstallationBRISTOL Fire Alarm & Devices Datasheets Rev. 010EN54-3:Loop Power: 24VDC [18V to 27.5V]Loop: Standby 0.6mA, Alarm: 1.5mASaving CurrentStandby 1.2mA, Alarm: 4mAProtocol/AddressingT&A, Value range from 1 to 254Tones17 Tones (refers to Manual)Address SequenceSingle Address: Evacuate toneDual Address:1st Alert Tone / 2nd Evacuate toneMaterial / ColorABS / Red Glossy finishingDimensionDiameter 110 mm / 39.6 (with Base)Weight180g (with Base), 114g (Without Base)Ingress Protection RatingIP21ClassType A, IndoorsOperating Temperature-10 C to 50 CHumidity0 to 95% Relative Humidity, Noncondensing

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemIntelligent Sounder StrobeThe AVI-6403 Intelligent Sounder Strobe is alarmwarning device used to notify persons in the vicinityof the occurrence fire emergency in order the person to take appropriate measures. The unit adoptmulti-application device starting from the types,parameters and wiring layout in single unit. The AVI6403 can change into different alarm warning typessuch as sounder-strobe type, sounder type or strobeAVI-6403type using programming tool. In addition, parameters can be configured according to the requirement which include alarm tone from 17 differentTechnical Specificationtones, single address or dual address mode andalso setting of power mode to low current consumption in a simple programming.StandardInput VoltageFeatures EN54-3 Compliance Built-in MCU processor and digital addressing 17 tones Programmable sound output Programmable types such as Sounder-Strobe,Sounder or Strobe alone Programmable Evacuate or Pre-alarm/Evacuatesignal Low and normal consumption mode One or Two addresses mode 10 Highlights LED status cluster Onsite Adjustable Parameters Loop or external power input Aesthetically pleasing design Universal mounting with fix base for simple installationBRISTOL Fire Alarm & Devices Datasheets Rev. 0Typical CurrentEN54-3Loop Power: 24VDC [18V to 27.5V]Loop: Standby 0.6mA, Alarm: 1.5mASaving CurrentStandby 1.2mA, Alarm: 9mAProtocol/AddressingT&A, Value range from 1 to 254Address SequenceSingle Address: Evacuate toneDual Address:1st Alert Tone / 2nd Evacuate toneStrobe Light10 Highlights LEDMaterial / ColorABS / Red Glossy finishingDimensionL:152.5 x W:88.5 x H46.75 mm (without Base)Weight184g (with Base), 124g (Without Base)Ingress Protection RatingIP21ClassType A, IndoorsOperating Temperature-10 C to 50 CHumidity0 to 95% Relative Humidity, Noncondensing11

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemLoop Passive RepeaterIGN-5096 LCD Repeater Panel is designed with built-in MCU processor to display exactfire event messages from the control panel and fast relay response with simultaneousaudible and visual signal output. This repeater panel can also program to limit the zonedisplay from All Zones into a particular zone or three adjacent zones through the panelkey buttons. The unit is connected through the communication loop of IGN Intelligentcontrol panel along with the devices and can install up to 254 units per loop. The repeater panel can be used whenever there is a need to relay information to multipoint informing key personnel.FeaturesMODELIGN-5096StandardEN 54-2: 1997 A1: 2006Input VoltageLoop Power: 24VDC [16V to 28V]Current ConsumptionLoop: Standby 1mA, Alarm: 1.2mAExternal PSU: Standby 25mA, Alarm: 80mAMemory CapacityUp to 300 fire event historyNumber per loop EN54-2 Compliance Loop Fire display passive repeater panel Built-in MCU processor and digital addressing Fast response of audible and visible signalfrom the panel Direct access common keys such as MUTE, UP,DOWN and BROWSE.Up to 254 units (ideal) Programmable Zone Display such as All Zone,Single Zone and Three Adjacent ZoneMaterial / ColorABS / White Glossy finishing LED status indicatorDimension180mm x 110 mm x44 mm Onsite Adjustable ParameterWeight300g (with Base), 256g (without Base) Loop sited wiring with external 24V supplyOperating Temperature0 C to 40 C Compact size and aesthetically pleasing designHumidity0 to 95% Relative Humidity, Noncondensing Surface mounting with fix base for simple installationModule and Wiring DetailsTerminal DescriptionZ1 Signal In ( )Z1 Signal Out ( )Z2 Signal In (-)Z2 Signal Out (-)D1 External Power Supply In ( )Fig.1 LCD Repeater Panel StructureD2 External Power Supply In (-)D1 External Power Supply Out ( )D2 External Power Supply Out (-)Fig.2 Wiring DetailsBRISTOL Fire Alarm & Devices Datasheets Rev. 012

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemAddressable Input Module,The IM-8410 Addressable Input Module is used to acknowledge normally open monitor signal from interface equipment then sendingcommunication signal to the control panel, ideally for monitoring sprinkler system, pressure switch, position switch, signal valves andother third party equipment such as conventional panel.MODELListedIM 8410IM 8410LPCB PendingComplianceEN54-18:2005/AC2007Power RatingInput VoltageCurrent Consumption EN54-18 Compliance LPCB Pending Built-in MCU processor and digital addressing Fire or Supervisory signal configuration 24VDC [16V to 28V]Standby 0.6mA, Alarm: 1.0mAModuleProtocol/AddressingInput RelayT&A, Value range from 1 to 254Normally Open dry contactInput Resistance5.1Kohms/ ¼ WIndicator StatusNormal: Single blink/Active: Steady/Fault: Double BlinkInput cable monitoredMaterial / ColorABS / White Glossy finishing Normally open configurationDimension LED status indicatorWeight Loop powered device Aesthetically pleasing design Surface mounting with fix base for simple installation155g (with Base), 85g (without Base)ClassType A, IndoorsOperating Temperature-10 C to 50 CIngress Protection RatingIP30Humidity0 to 95% Relative Humidity, Non condensingModule and Wiring DetailsBRISTOL Fire Alarm & Devices Datasheets Rev. 0108 mm x 86 mm x38 mm13

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemAddressable Single Input / Output Module , IM 8412The IM 8412 Addressable Single Input/output Module is characterized as one input or outputvolt free relay and control module. The unit is normally used for overriding equipment such aslift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMSand etc. The unit has built-in feedback signal feature, according to the pre-configured interface module command fire scenario, the alarm controller send out start command to theequipment required to start. After receiving the command, output module enables its relay tochange state. Once the module is under control and operated a confirmation signal will besending back to the alarm controller. In addition, the unit incorporates an intelligent processorthat provides automatic monitoring for both open and short circuit of the input signal line.MODELIM 8412ListedLPCB / CE-CPRComplianceEN54-18:2005Power RatingInput VoltageLoop Power:24VDC [16V to 28V]; External PSU: 20 to 28VDCCurrent ConsumptionStandby 0.6mA, Alarm: 1.6mA; External PSU: Standby 0.6mA,Features EN54-18:2005 Compliance LPCB Approved Built-in MCU processor and digital addressing 24Vdc/3A Output relay contact andControl module Input Fire or Supervisory signal configuration108 mm x 86 mm x38 mm LED status indicator170g (with Base), 92g (without Base) Onsite Adjustable ParameterOperating Temperature-10 C to 50 C Loop or external power inputIngress Protection RatingIP30 Aesthetically pleasing design0 to 95% Relative Humidity, Noncondensing Surface mounting with fix base for simpleinstallationModuleProtocol/AddressingT&A, Value range from 1 to 254Input RelayNormally Open dry contactInput Resistance5.1Kohms/ ¼ WIndicator StatusNormal: Single blink/Active: Steady/Fault: Double BlinkMaterial / ColorABS / White Glossy finishingDimensionWeightHumidityModule and Wiring DetailsTerminal DescriptionBRISTOL Fire Alarm & Devices Datasheets Rev. 014Z1 Signal In ( )D1 External Power Supply In ( )Z1 Signal Out ( )D2 External Power Supply In (-)Z2 Signal In (-)D3 Not UseZ2 Signal Out (-)D4 Not UseRET Input CableCOM Output CableG Input CableNO, NC Output Cable

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemModule and Wiring DetailsFigure 1: Input Wiring DetailsFigure 2: Relay Output Wiring DetailsNote: Change the parameter Input Check into 3Y(Loop Powered) mostly used(Loop Powered)Figure 3: Control Output Wiring DetailsFigure 4: Control Output with Feedback(Required External Power Supply)Signal Wiring Details(Required External Power Supply)BRISTOL Fire Alarm & Devices Datasheets Rev. 015

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemAddressable Dual Input / Output Module , IM 8413The IM-8413 Addressable Dual Input/output Module is characterized as two inputs or outputs volt free relay and control module. The unit is normally usedfor overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMS and etc. The unit has builtin feedback signal feature, according to the pre-configured interface module command fire scenario, the alarm controller send out start command tothe equipment required to start. After receiving the command, output module enables its relay to change state. Once the module is under control andoperated a confirmation signal will be sending back to the alarm controller. In addition, the unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input signal line.MODELListedIM 8413LPCB PendingComplianceEN54-18:2005/AC2007Power RatingFeaturesInput VoltageLoop Power:24VDC [16V to 28V]; External PSU: 20 to 28VDCCurrent ConsumptionStandby 0.6mA, Alarm: 1.6mA; External PSU: Standby 0.6mA,IM 8413 EN54-18 Compliance Built-in MCU processor and digital addressing Two circuits 24Vdc/3A Output relay contact and Control module Two circuits Input Fire or Supervisory signalconfiguration Dis/Enable Input and output cable monitored LED status indicator Onsite Adjustable Parameter Loop or external power input Aesthetically pleasing design Surface mounting with fix base for simpleinstallationControl Output Voltage24VDC / 3A rating (per circuit)ModuleProtocol/AddressingInput RelayT&A, Value range from 1 to 254Normally Open dry contactInput Resistance5.1Kohms/ ¼ WIndicator StatusNormal: Single blink/Active: Steady/Fault: Double BlinkMaterial / ColorABS / White Glossy finishingDimension108 mm x 86 mm x38 mmWeight182g (with Base), 100g (without Base)Operating Temperature-10 C to 50 CIngress Protection RatingIP30Humidity0 to 95% Relative Humidity, NoncondensingTerminal DescriptionModule and Wiring DetailsZ1 Signal In ( )D1 External Power Supply In ( )Z1 Signal Out ( )D2 External Power Supply In (-)Z2 Signal In (-)D3 Not UseZ2 Signal Out (-)D4 Not UseRET Input CableCOM1 Output Cable (Circuit1)G1 Input CableNO1, NC Output CableG2 Input Cable (Circuit1)RET 2 Input Cable (Circuit 2)COM2 Output Cable (Circuit 2)NO2 Output Cable (Circuit 2)BRISTOL Fire Alarm & Devices Datasheets Rev. 016

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemModule and Wiring DetailsFigure 1: Input Wiring DetailsFigure 2: Relay Output Wiring DetailsNote: Change the parameter Input Check into 3Y(Loop Powered) mostly used(Loop Powered)Figure 3: Control Output Wiring DetailsFigure 4: Control Output with Feedback(Required External Power Supply)Signal Wiring Details(Required External Power Supply)BRISTOL Fire Alarm & Devices Datasheets Rev. 017

IGN SERIES ADDRESSABLEFire Alarm & Detection SystemIsolator Module , IM 8414The IM-8414 manufactured base on the requirement of EN 54MODELpart 17, European Standard. In the event of short circuit onthe detection loop the IM-8414 Isolators either side of theListedloop will detect the problem and open circuit and isolatesCompliancethe faulty part of the loop, enabling other devises on theunaffected part of the loop to operate normally. The moduleIM 8414LPCB / CE-CPREN54-17:2005Power Ratingwill continue to monitor for the fault to be repaired, once theInput Voltagefault is cleared the isolator will automatically reinstate theCurrent Consumptioneffected part of the loop.Maximum Open Voltage (V SO MAX)11VMinimum Open Voltage (V SO MIN)8VMaximum Close Voltage (V SC M 8414Minimum Close Voltage (V SC MIN)Maximum Continuous Current (I C MAX)24VDC [16V to 28V]Standby 0.15mA, Alarm: 1.8Ma1.4V500mAMaximum Transient Output Current (I S MAX)5mAMaximum Leakage Current (I L MAX)2mAMax closed impedance (Z C MAX)0.65ohmsModuleFeaturesProtocol/Addressing EN54-17:2005 ComplianceNumber of monitored LPCB ApprovedOutput Impedance In the event of a short circuit isolates faulty parts ofthe loop.Indicator Status Automatically resetting once the fault has beenclearedMaterial / ColorDimension Can monitor up to 70 devicesWeight LED status indicatorIngress Protection Rating Loop powered device Aesthetically pleasing design Surface

Alarm Devices in Fire Detection and Alarm System are devices that are activated during presence of fire to provide notice to the concerned people in form of audio or visual signals. Though in some cases, signals are already directed to the fire department. BRISTOL offers audio/visual alarm devices that comply to international and local standards.

Related Documents:

DETECTION ZONE 11 DETECTION ZONE 12 ALARM ZONE 1 ALARM ZONE 2 ALARM ZONE 3 ALARM ZONE 4 Alarm Zones An alarm zone is clearly defined within the standard but generally is an area of the building coinciding with the fire compartment boundaries. There must be a clear break between these alarm zones to ensure alert and evacuation messages are not .

PSI AP Physics 1 Name_ Multiple Choice 1. Two&sound&sources&S 1∧&S p;Hz&and250&Hz.&Whenwe& esult&is:& (A) great&&&&&(C)&The&same&&&&&

Argilla Almond&David Arrivederci&ragazzi Malle&L. Artemis&Fowl ColferD. Ascoltail&mio&cuore Pitzorno&B. ASSASSINATION Sgardoli&G. Auschwitzero&il&numero&220545 AveyD. di&mare Salgari&E. Avventurain&Egitto Pederiali&G. Avventure&di&storie AA.&VV. Baby&sitter&blues Murail&Marie]Aude Bambini&di&farina FineAnna

2.7 UL - 268 UL Standard for Safety Smoke Detectors for Fire Alarm Systems 2.8 EN 54/22 Fire detection and fire alarm systems. Resettable line‐type heat detectors 2.9 EN 54/20 Fire detection and fire alarm systems. Aspirating Smoke detectors 2.10 IS 15519:2004 Water Mist Fire Protection Systems-System Design, Installation

The program, which was designed to push sales of Goodyear Aquatred tires, was targeted at sales associates and managers at 900 company-owned stores and service centers, which were divided into two equal groups of nearly identical performance. For every 12 tires they sold, one group received cash rewards and the other received

Alarm 1 is a ‘Sound Once’ alarm, and Alarm 2 is an ‘Everyday’ alarm. Alarm 1 Setting/Alarm 2 Setting Press the ‘Alarm 1’ button (Ref.4) or ‘Alarm 2’ button (Ref.5) to activate alarm settings. ‘OFF’ will begin lashing on the screen. Select Alarm 1 or 2 b

addressable fire alarm control panel 2 loop addressable fire alarm control panel 4 loop addressable fire alarm control panel 6 loop addressable fire alarm control panel 8 loop addressable fire alarm control panel product code: m.u.yan.00016 product code: m.u.yan.00018 battery included product code: m.u.yan.00020 product code: m.u.yan.00022

API 526 provides effective discharge areas for a range of sizes in terms of letter designations, “D” through “T.” 3.19 Flutter Fluttering is where the PRV is open but the dynamics of the system cause abnormal, rapid reciprocating motion of the moveable parts of the PRV. During the fluttering, the disk does not contact the seat but reciprocates at the frequency of the flutter. 3.19 .