Product Manual - Standing Seam Panels - EaveEA01A/SB, High Side Eave DetailEA01/AA, Standard Gutter Detail with Gutter Clip AttachmentEA01C/AA, Standard Gutter Detail with Gutter Clip AttachmentEA01CA/AO, Standard Gutter Detail at OverhangEA01CB/AO, Oversize Gutter Detail at OverhangEA01E/AA, Oversize Gutter DetailEA01E/AO, Oversize Gutter Detail at Open SidewallEA01T/SB, Eave DetailEA03/AA, Deluxe Eave Flashing InstallationEA03A/AO, Deluxe Eave Flashing InstallationEA03/AO, Deluxe Eave Flashing Installation at Open SidewallEA03CA/AO, Deluxe Eave Flashing InstallationEA04A/SO, Section at EaveEA04CA/SO, Section at EaveEA04CF/SB, Cleated EaveEA04C/SB, Section at Eave with Thermal BlockEA04C/SD, Section at Eave with Thermal BlockEA04/SB, Section at Eave Without Thermal BlocksEA04/SD, Section at Eave Without Thermal BlocksEA04/SO, Section at EaveEA05A/SO, Highside Eave Flashing AttachmentEA05CA/SO, Highside Eave Flashing AttachmentEA05C/SB, Highside Eave Flashing Attachment with Thermal BlockEA05/SB, Highside Eave Flashing AttachmentEA05/SO, Highside Eave Flashing AttachmentEA06/SA, Roof to Wall Transition at Existing EaveEA10/AA, Eave Support Flashing AttachmentEA10/AD, Eave Support Flashing AttachmentEA10C/AA, Thermal Eave Support Flashing AttachmentEA10C/AD, Thermal Eave Support Flashing AttachmentEA11/AA, Roof Sheeting Prior to Wall Sheeting InstructionsEA11/SB, Roof to Wall Transition at High SideEA11/SD, Roof to Wall Transition at High SideEA11/SW, Roof to Wall Transition at High SideEA21A/SO, Ice & Snow Eave Detail w/ Deluxe Eave FlashingEA21CA/SO, Ice & Snow Eave Detail w/ Deluxe Eave FlashingEA21C/SB, Ice & Snow Eave Detail w/ Deluxe Eave Flashing & Thermal Block2/17/2021

EA21C/SD, Ice & Snow Eave Detail w/ Deluxe Eave Flashing & Thermal BlockEA21/SB, Ice & Snow Eave Detail w/ Deluxe Eave FlashingEA21/SD, Ice & Snow Eave Detail w/ Deluxe Eave FlashingEA22A/SO, Ice & Snow Eave DetailEA22CA/SO, Ice & Snow DetailEA22C/SB, Ice & Snow Eave Detail w/ Thermal Blocks (TB1T) at PurlinsEA22C/SD, Ice & Snow Detail w/ Thermal Blocks (TB1T) at PurlinsEA22/SB, Ice & Snow Eave DetailEA22/SD, Ice & Snow Eave DetailEA24A/SO, Ice & Snow Eave Detail w/ Standard GutterEA24CA/SO, Ice & Snow Eave Detail w/ Standard GutterEA24C/SA, Ice & Snow Eave Detail w/ Standard GutterEA24/SA, Ice & Snow Eave Detail w/ Standard GutterEA25A/SO, Ice & Snow Eave Detail w/ Oversize GutterEA25CA/SO, Ice & Snow Eave Detail w/ Oversize GutterEA25C/SA, Ice & Snow Eave Detail w/ Oversize GutterEA25/SA, Ice & Snow Eave Detail w/ Oversize GutterEA26C/SA, Fastener Installation at Eave Strut w/ Ice & SnowEA26/SA, Fastener Installation at Eave SupportEA27/SA, Low Eave Caulk DetailEA28/AB, Mastic and Insulation Application at EaveEA28C/AB, Mastic and Insulation Application at EaveEA28/SO, Mastic and Insulation at EaveEA36A/SO, Inside Metal Closure Installation at High Side EaveEA36/TA, Inside Metal Closure InstallationEA38/AA, Eave Member Type at Low SideEA38A/AA, Eave Member Type at Low SideEA38B/AA, Eave Member Type at High SideEA38BA/AA, Eave Member Type at High SideEO28C/SO, Mastic and Insulation Application at EaveEO28/SO, Mastic and Insulation Application at EaveWEA11/SB, Roof to Wall Transition at HighsideWEA11/SD, Roof to Wall Transition at HighsideWEA11/SW, Roof to Wall Transitions at Highside2/17/2021

PRODUCT MANUALSTANDING SEAM ROOF PANELHigh Side Eave DetailStanding Seam Roof with Rigid InsulationEA01A/SBSEE DETAILS: RC34SA AND RC35SAROOF TRIM FASTENER(S)H10301'-0" O.C.3"1"min.TAPE MASTIC3/4 TM(TOP & BOTTOM)PANEL CLIPSTANDING SEAM PANELOUTSIDE CLOSURESSMOCLAP STIFFENERSSLS-1HIGH SIDE FLASHINGTHSROOF TRIM FASTENER(S)H1030(7) PER CLOSUREMULTI-RIB PANEL (OPTIONAL)WALL TRIM FASTENER(S)#14X3/41'-0" O.C.RIGID INSULATIONSTRUCTURAL FASTENER(S)#12(2) PER CLIPOUTSIDE CLOSUREAVPO/LOAI/AOLIDECK ATTACHMENT ASSPECIFIED BY DESIGNWALL MAIN FASTENER(S)#12X1 1/41'-0" O.C.WALL PANELEAVE STRUTHIGH SIDE EAVE DETAILSTANDING SEAM ROOF WITH RIGID INSULATIONDownload the DWG file by clicking here.To Section IndexRevised: 02.23.21 (MR2021.03)EA01ASB

PRODUCT MANUALSTANDING SEAM ROOF PANELStandard Gutter Detail with Gutter Clip AttachmentEA01/AANOTE:SEE APPROPRIATE EAVE DETAILS FORMASTIC AND FASTENER LOCATIONROOF FASTENER(S)(B) SEE CHART BELOWENSURE ATTACHMENT OF SCREWTHROUGH EAVE SUPPORT TRIMTAPE MASTIC3/4 TM3" LENGTH(PLACE UNDER CLIP)GUTTER CLIP COVER TRIMTCGC(REQUIRED AT PAINTEDROOFS ONLY)* GUTTER CLIP(C) SEE CHART BELOW3'-0" O.C.PLACE IN FLAT OF PANELVARIESROOF PANELEAVE SUPPORT TRIMTFSEALIGN WITH OUTER FACEOF WALL PANELROOF FASTENER(S)(A) SEE CHART BELOWGUTTERTGT1GUTTER CLIPGC-A3'-0" O.C.OPTIONAL ROOF FASTENER(S)(A) SEE CHART BELOWMUST BE PRE-INSTALLEDFACE OF FLASHINGROOF PANELLOC SEAM (LOC)STANDING SEAM (S2P, S3P)ROOF FASTENER (A)(1) PER CLIP#14X3/4 SDRF#14X3/4 SDRFROOF FASTENER (B)(1) PER CLIPH1030H1030GUTTER CLIP (C)CGBCGBSTANDARD GUTTER DETAILEA01AADownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)

PRODUCT MANUALSTANDING SEAM ROOF PANELStandard Gutter Detail with Gutter Clip AttachmentWith Thermal BlocksEA01C/AAROOF MAIN FASTENER(S)H1030(2) PER GUTTER CLIPGUTTER CLIP COVER TRIMTCGC(REQUIRED AT PAINTEDROOFS ONLY)TAPE MASTIC3/4 TM3" LENGTH(PLACE UNDER CLIP)ROOF FASTENER(S)#14X3/4 SDRFGUTTER CLIPCGB3'-0" O.C.PLACE IN FLAT OF PANELROOF PANELEAVE SUPPORT TRIMTFSET w/ 1 1/4" wALLSTFSETIWP-10.2 w/ INSULATED WALLSTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSALIGN WITH OUTER FACEOF WALL PANELGUTTERTGT1STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.GUTTER CLIPGC-A3'-0" O.C.OPTIONAL H1030 FASTENERMUST BE PRE-INSTALLEDEAVE CLOSURE FLASHINGTFECWALL PANELSTANDARD GUTTER DETAIL WITH GUTTER CLIP ATTACHMENTWITH THERMAL BLOCKS AT PURLINSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA01CAA

PRODUCT MANUALSTANDING SEAM ROOF PANELStandard Gutter Detail at OverhangWith Thermal Blocks (TB1T, TB2T, & TB3T) at PurlinsEA01CA/AOROOF FASTENER(S)H1030ENSURE ATTACHMENT OF SCREWTHROUGH EAVE SUPPORT FLASHINGGUTTER CLIP COVER TRIMTCGC(REQUIRED AT PAINTED ROOFS ONLY)ROOF FASTENER(S)#14X3/4 SDRFROOF PANELGUTTER CLIPCGB3'-0" O.C.PLACE IN FLAT OF PANELEAVE SUPPORT TRIMTFSET w/ 1 1/4" wALLSTFSETIWP-10.2 w/ INSULATED WALLSTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSALIGN WITH OUTER FACEOF WALL PANELSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.VARIESGUTTER CLIPGC-A3'-0" O.C.GUTTERTGT1EAVE CLOSURE FLASHINGTFOS* EXTEND FLASHING ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSOPTIONAL FASTENERMUST BE PRE-INSTALLED(H1030)1'-0" O.C.BLIND RIVET1/8 RIVET1'-0" O.C."J" FLASHINGFJ2WALL TRIM FASTENER(S)#14X3/4 SDRF1'-0" O.C.1 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38AA, SF03AAWITHOUT SOFFIT EA38AAASTANDARD GUTTER DETAIL AT OVERHANG OR CANOPYWITH THERMAL BLOCKS (TB1T, TB2T & TB3T) AT PURLINSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)TAPE MASTIC3/4 TM3" LENGTH(PLACE UNDER CLIP)EA01CAAO

PRODUCT MANUALSTANDING SEAM ROOF PANELOversize Gutter Detail at OverhangWith Thermal Block at Roof Slopes Equal to or Less Than 6"1/2:12 - Standing Seam and Loc Seam Roof PanelsEA01CB/AOROOF FASTENER(S)#14X3/4 SDRFROOF FASTENER(S)H1030ENSURE ATTACHMENT OF SCREWTHROUGH EAVE SUPPORT TRIMGUTTER CLIP COVER TRIMTCGC(REQUIRED AT PAINTED ROOFS ONLY)TAPE MASTIC **3/4 TM3" LENGTH(PLACE UNDER CLIP)GUTTER CLIPCG3B2'-0" O.C.PLACE IN FLAT OF PANELEAVE SUPPORT FLASHINGTFSETTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSGUTTER CLIPCG3-A2'-0" O.C.STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.OVERSIZE GUTTERTG3BLIND RIVET1/8 RIVET1'-0" O.C.WALL TRIMFASTENER(S)#14X3/41'-0" O.C.TOP VIEWGUTTER CLIPCG3BEAVE CLOSURE FLASHINGTFOSSIDE VIEW"J" FLASHINGFJ2* EXTEND FLASHING ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSSEE APPROPRIATE DETAILWITH SOFFIT EA38AA, SF03AAWITHOUT SOFFIT EA38AAAOVERSIZE GUTTER DETAIL AT OVERHANG AND CANOPYLOC SEAM & STANDING SEAM w/THERMAL BLOCKS AT PURLINS & ROOF SLOPE EQUAL TO OR LESS THAN 6 1/2:12Download the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)** TAPE MASTIC3/4 TMINSTALLED UNDERGUTTER CLIPEA01CBAO

PRODUCT MANUALSTANDING SEAM ROOF PANELOversize Gutter DetailAll Slopes Equal to or Less Than 6 1/2:12EA01E/AANOTE:SEE APPROPRIATE EAVE DETAILS FORMASTIC AND FASTENER LOCATIONROOF FASTENER(S)(B) SEE CHART BELOWENSURE ATTACHMENT OF SCREWTHROUGH EAVE SUPPORT TRIMTAPE MASTIC3/4 TM3" LENGTH(PLACE UNDER CLIP)GUTTER CLIP COVER TRIMTCGC(REQUIRED AT PAINTEDROOFS ONLY)* GUTTER CLIP(C) SEE CHART BELOW2'-0" O.C.PLACE IN FLAT OF PANELVARIESROOF PANELEAVE SUPPORT TRIMROOF FASTENER(S)(A) SEE CHART BELOWGUTTER CLIPCG3-A2'-0" O.C.OPTIONAL ROOF FASTENER(S)(A) SEE CHART BELOWMUST BE PRE-INSTALLEDOVERSIZE GUTTERTG3FACE OF FLASHINGROOF PANELLOC SEAM (LOC)STANDING SEAM (S2P, S3P)ROOF FASTENER (A)(1) PER CLIP#14X3/4 SDRF#14X3/4 SDRFROOF FASTENER (B)(1) PER CLIPH1030H1030GUTTER CLIP (C)CG3BCG3BOVERSIZE GUTTER DETAILAT SLOPES EQUAL TO OR LESS THAN 6 1/2:12Download the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA01EAA

PRODUCT MANUALSTANDING SEAM ROOF PANELOversize Gutter Detail With Open SidewallAll Slopes Equal to or Less Than 6 1/2:12EA01E/AOROOF FASTENER(S), (B)(1) PER GUTTER CLIP, SEE CHART BELOWENSURE ATTACHMENT OF SCREWTHROUGH EAVE SUPPORT TRIMGUTTER CLIP COVER TRIMTCGC(REQUIRED AT PAINTEDROOFS ONLY)GUTTER CLIPCG3B2'-0" O.C.PLACE IN PANEL FLATTAPE MASTIC **(PLACE UNDER CLIP)3/4 TM3" LENGTHEAVE SUPPORT FLASHINGTFSEROOF FASTENER(S),(A)(1) PER GUTTER CLIPSEE CHART BELOWSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.TOP VIEWGUTTER CLIPCG3-A2'-0" O.C.WALL MAINFASTENER(S)#12X1 1/41'-0" O.C.GUTTERTG3BLIND RIVET1/8 RIVET1'-0" O.C.* EXTEND FLASHING ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSROOF PANELEAVE CLOSUREFLASHING* TFOSGUTTER CLIPCG3B"J" FLASHINGFJ2SIDE VIEWROOF FASTENER (A)ROOF FASTENER (B)LOC SEAM (LOC)#14X3/4 SDRFH1030STANDING SEAM (S2P, S3P)#14X3/4 SDRFH1030OVERSIZE GUTTER DETAIL WITH OPEN SIDEWALLAT ROOF SLOPES EQUAL TO OR LESS THAN 6 1/2:12Download the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)** TAPE MASTIC3/4 TMINSTALLED UNDERGUTTER CLIPEA01EAO

PRODUCT MANUALSTANDING SEAM ROOF PANELEave DetailStanding Seam Roof w/ Rigid Insulation - Architectural III, Architectural "V" Rib or Long Span II WallsEA01T/SBSTANDING SEAM INSIDEMETAL CLOSURE SSMC-I(3/4" X 3/16" MASTICTOP & BOTTOM OFCLOSURE AND ALONGEAVE TRIM)EAVE TRIMETXSEE RC91TSAEAVE TRIM SUPPORTETSXSEE NOTE 4 AT RC91TSAWALL TRIM FASTENER(S)#14X3/41'-0" O.C.OUTSIDE CLOSUREAVPI/LOAI/AOLIREQUIRED IF ORDEREDROOF TRIM FASTENER(S) (TYP.)EA26SASEE DETAILH1030STANDING SEAM PANELROOF TRIM FASTENER(S)H1030(2) PER CLOSURERIGID INSULATIONDECK ATTACHMENT ASSPECIFIED BY DESIGNSEE NOTE 3 AT RC91TSASTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.VAPORBARRIERMULTI-RIB PANEL(OPTIONAL)WALL MAIN FASTENER(S)#12X1 1/4 (SEE NOTE)1'-0" O.C.NOTE: #12X2 FASTENER(S) w/ 6" INSULATIONWALL PANELEAVE DETAILSTANDING SEAM ROOF W/ RIGID INSULATIONARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSDownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)EA01TSB

PRODUCT MANUALSTANDING SEAM ROOF PANELDeluxe Eave Flashing InstallationEA03/AANOTE: PANEL OVERHANG DIMENSION VARIESSEE PANEL SPECIFIC EAVE DETAILAND ROOF SHEETING LAYOUTAPPLY URETHANE CAULKGTSALL AROUND 1/4Ø BEADSEE FASTENER LAYOUT DETAILSAT EAVEROOF TRIM FASTENER(S)H1030 STANDING SEAM& LOC SEAM1'-0" O.C.DELUXE EAVEFLASHINGPEDEAVE SUPPORTFLASHINGTFSEEAVE CLOSURE FLASHINGTFECSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.BLIND RIVETS1/8 RIVET (TYP)WALL TRIM FASTENER(S)#14X3/41'-0" O.C.DELUXE EAVE ENDCAPTDEE(NOT REQ'D WITH CORNER BOX)OUTSIDE CLOSUREREQUIRED IF ORDEREDDELUXE EAVE FLASHING INSTALLATIONEA03AAREF. DETAIL EA04Download the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)

PRODUCT MANUALSTANDING SEAM ROOF PANELDeluxe Eave Flashing InstallationAt OverhangEA03A/AONOTE: PANEL OVERHANG DIMENSION VARIESSEE PANEL SPECIFIC EAVE DETAILAND ROOF SHEETING LAYOUTROOF FASTENER(S)H10301'-0" O.C.DELUXE EAVE FLASHINGPEDEAVE SUPPORT FLASHINGTFSE* EAVE CLOSURE FLASHINGTFOSSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.* EXTEND FLASHNG ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSWALL TRIM FASTENER(S)#14X3/41'-0" O.C.BLIND RIVET1/8 RIVET1'-0" O.C."J" FLASHINGFJ2ORFSJ2IF SLOPE 5:12 to 6:12WITHOUT SOFFIT1 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38AA, SF03AAWITHOUT SOFFIT EA38AAADELUXE EAVE FLASHING INSTALLATIONAT OVERHANG AND CANOPYDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA03AAO

PRODUCT MANUALSTANDING SEAM ROOF PANELDeluxe Eave Flashing Installation at Open SidewallEA03/AONOTE: PANEL OVERHANG DIMENSION VARIESSEE PANEL SPECIFIC EAVE DETAILAND ROOF SHEETING LAYOUTSEE FASTENER LAYOUT DETAILSAT EAVEROOF TRIM FASTENER(S)H10301'-0" O.C.DELUXE EAVE FLASHINGPEDEAVE SUPPORT FLASHINGTFSE* EAVE CLOSURE FLASHINGTFOS* EXTEND FLASHNG ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.BLIND RIVET1/8 RIVET1'-0" O.C.WALL MAIN FASTENER(S)#12X1 1/41'-0" O.C."J" FLASHINGFJ2ORFSJ2IF SLOPE 5:12 to 6:12WITHOUT SOFFIT1 5/16"NOTE: CORNER BOX REQUIRED AT OPEN WALLDELUXE EAVE FLASHING INSTALLATION AT OPEN SIDEWALLSTANDING SEAM & LOC SEAM ROOF PANELSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA03AO

PRODUCT MANUALSTANDING SEAM ROOF PANELDeluxe Eave Flashing InstallationAt Overhang w/ Thermal Blocks (TB1T, TB2T, OR TB3T) at PurlinsEA03CA/AONOTE: PANEL OVERHANG DIMENSION VARIESSEE PANEL SPECIFIC EAVE DETAILAND ROOF SHEETING LAYOUTROOF FASTENER(S)H1030SEE FASTENER LAYOUT AT EAVEROOF TRIM FASTENER(S)H10301'-0" O.C.EAVE SUPPORT FLASHINGTFSETTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSDELUXE EAVE FLASHINGPEDSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.EAVE CLOSURE FLASHINGTFOS* EXTEND FLASHNG ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSWALL TRIM FASTENER(S)#14X3/41'-0" O.C.BLIND RIVET1/8 RIVET1'-0" O.C."J" FLASHINGFJ21 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38AA, SF03AAWITHOUT SOFFIT EA38AAADELUXE EAVE FLASHING INSTALLATIONAT OVERHANG AND CANOPY w/ THERMAL BLOCKS (TB1T, TB2T OR TB3T) AT PURLINSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA03CAAO

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at EaveStanding Seam Roof at OverhangEA04A/SOSEE DETAIL EA26SAEA36TASAFETY PRECAUTION DO NOT STEPON PANEL NEAR THE EAVE UNTIL FULLYSECURED WITH FASTENERS.4"STANDING SEAM PANELROOF TRIM FASTENER(S)H1030METAL CLOSURESSMC-ITAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H1030EAVE SUPPORT FLASHINGTFSE* EAVE CLOSURE FLASHINGTFOSSTRUCTURAL FASTENER#12X1 1/41'-0" O.C.WALL TRIM FASTENER(S)#14X3/41'-0" O.C.* EXTEND FLASHING ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSBLIND RIVET1/8 RIVET1'-0" O.C."J" FLASHINGFJ21 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38AA, SF03AAWITHOUT SOFFIT EA38AAASECTION AT EAVESTANDING SEAM ROOF AT OVERHANG OR CANOPYDownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)EA04ASO

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at EaveStanding Seam Roof at Overhang w/ Themal Blocks (TBT1) at PurlinsEA04CA/SO4"STANDING SEAM PANELSAFETY PRECAUTIONDO NOT STEP ON PANEL NEARTHE EAVE UNTIL FULLY SECUREDWITH FASTENERS.ROOF TRIM FASTENER(S)H1030SEE FASTENER LAYOUT AT EAVEMETAL CLOSURESSMC-ITAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H1030(2) PER CLOSURE TO EAVE SUPPORT FLASHINGEAVE CLOSURE FLASHINGTFOS* EXTEND FLASHING ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSEAVE SUPPORT FLASHINGTFSETTFSEST-10.2 REQ'D w/S3PC-5T, SUPER TALL CLIPSWALL TRIM FASTENER(S)#14X3/41'-0" O.C.STRUCTURAL FASTENER#12X1 1/41'-0" O.C.BLIND RIVET1/8 RIVET1'-0" O.C."J" FLASHINGFJ21 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38AA, SF03AAWITHOUT SOFFIT EA38AAASECTION AT EAVESTANDING SEAM ROOF AT OVERHANG OR CANOPY w/ THERMAL BLOCKS (TB1T) AT PURLINSEA04CASOREFERENCE DETAILS: EA26SA, EA36TADownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)

PRODUCT MANUALSTANDING SEAM ROOF PANELCleated EaveStanding Seam Roof w/ Thermal Blocks (TBT1) / Arch. III, Arch. "V" Rib, or Long Span IIEA04CF/SB4"STANDING SEAM ROOF PANELROOF TRIM FASTENER(S)H1030SEE FASTENER LAYOUT AT EAVEMETAL CLOSURESSMC-ITAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H1030(2) PER CLOSURE TO EAVE SUPPORT FLASHINGCLEATED EAVE TRIMTCETEAVE SUPPORT FLASHINGTFSETTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSWALL MAIN FASTENER(S)#12X1 1/4 (SEE * NOTE)1'-0" O.C.ALIGN WITH OUTSIDE FACEOF WALL PANEL* NOTE: #12X2 FASTENER(S) w/ 6" INSULATIONWALL TRIM FASTENER(S)#14X3/41'-0" O.C.STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.CONTINUOUS CLEATSCCF1OUTSIDE CLOSUREAOLI / AVPO / LOAIREQUIRED IF ORDEREDWALL PANELCLEATED EAVE1 1/4"STANDING SEAM ROOF w/ THERMAL BLOCKS (TB1T) / ARCH. III, ARCH. "V" RIB or LONG SPAN III WALLSEA04CFSBREFERENCE DETAILS: EA26SA, EA36TADownload the DWG file by clicking here.To Section IndexRevised: 02.23.21 (MR2021.03)

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at Eave with Thermal BlockStanding Seam Roof / Architectural III, Architectural "V" Rib, or Long Span III WallsEA04C/SB4"ROOF TRIM FASTENER(S)H1030SEE FASTENER LAYOUT AT EAVESTANDING SEAM PANELSAFETY PRECAUTIONDO NOT STEP ON PANEL NEARTHE EAVE UNTIL FULLY SECUREDWITH FASTENERS.TAPE MASTIC3/4 TMMETAL CLOSURESSMC-IROOF TRIM FASTENER(S)H1030(2) PER CLOSURE TO EAVE SUPPORT FLASHINGTAPE MASTIC3/4 TMEAVE SUPPORT FLASHINGTFSETTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSEAVE CLOSURE FLASHINGTFECTFOS8 REQ'D w/S3PC-5T, SUPER TALL CLIPSWALL MAIN FASTENER(S)#12X1 1/4 (SEE * NOTE)1'-0" O.C.STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.* NOTE: #12X2 FASTENER(S) w/ 6" INSULATIONWALL TRIM FASTENER(S)#14X3/41'-0" O.C.OUTSIDE CLOSUREAOLI / AVPO / LOAIREQUIRED IF ORDEREDWALL PANELSECTION AT EAVE w/ THERMAL BLOCK (TB1T) AT PURLINS (NOT AT EAVE STRUT) EA04CSTANDING SEAM ROOF / ARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSSBREFERENCE DETAILS: EA26SA, EA36TADownload the DWG file by clicking here.To Section IndexRevised: 06.23.21 (MR2021.08)

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at Eave with Thermal BlockStanding Seam Roof / Shadow Panel WallsEA04C/SDROOF TRIM FASTENER(S)H1030SEE FASTENER LAYOUT AT EAVEENSURE ATTACHMENT OF SCREWTHROUGH EAVE SUPPORT FLASHINGSTANDING SEAM PANELSAFETY PRECAUTIONDO NOT STEP ON PANEL NEARTHE EAVE UNTIL FULLY SECUREDWITH FASTENERS.METAL CLOSURESSMC-IROOF TRIM FASTENER(S)H1030(2) PER CLOSURE TO EAVE SUPPORT FLASHINGTAPE MASTIC3/4 TMEAVE SUPPORT FLASHINGTFSETTFSEST-10.2, REQ'D w/S3PC-5T, SUPER TALL CLIPSEAVE CLOSURE FLASHINGTFECCLOSURESHPI/OREQUIRED IF ORDEREDSTRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.WALL TRIM FASTENER(S)#14X3/41'-4" O.C.WALL MAIN FASTENER(S)#12X1 SDYC W/NUTBLK1'-4" O.C.WALL PANELSECTION AT EAVE w/ THERMAL BLOCK (TB1T) AT PURLINSSTANDING SEAM ROOF / SHADOW PANEL WALLSEA04CSDREFERENCE DETAILS: EA26CSA, EA36TADownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at Eave Without Thermal BlocksStanding Seam Roof / Architectural III, Architectural "V" Rib or Long Span III WallsEA04/SB4"STANDING SEAM PANELSAFETY PRECAUTIONDO NOT STEP ON PANEL NEARTHE EAVE UNTIL FULLY SECUREDWITH FASTENERS.ROOF TRIM FASTENER(S)H1030SEE DETAILS: EA26SA AND EA36TASTANDING SEAMMETAL CLOSURESSMC-ITAPE MASTIC3/4 TMTAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H1030(2) PER CLOSUREEAVE SUPPORT FLASHINGTFSEEAVE CLOSURE FLASHINGTFECWALL MAIN FASTENER(S)#12X1 1/4 (SEE * NOTE)1'-0" O.C.STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.* NOTE: #12X2 FASTENER(S) w/ 6" INSULATIONWALL TRIM FASTENER(S)#14X3/41'-0" O.C.WALL PANELOUTSIDE CLOSUREREQUIRED IF ORDEREDSECTION AT EAVE WITHOUT THERMAL BLOCKSSTANDING SEAM ROOF / ARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSDownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)EA04SB

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at Eave Without Thermal BlocksStanding Seam Roof / Shadow Panel WallsEA04/SDSAFETY PRECAUTIONDO NOT STEP ON PANEL NEARTHE EAVE UNTIL FULLY SECUREDWITH FASTENERS.STANDING SEAM PANELROOF TRIM FASTENER(S)H1030METAL CLOSURESSMC-ITAPE MASTIC3/4 TMTAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H1030(2) PER CLOSUREEAVE SUPPORT FLASHINGTFSEEAVE CLOSURE FLASHINGTFECCLOSURESHPI/OREQUIRED IF ORDEREDSTRUCTURAL FASTENER#12X1 1/41'-0" O.C.WALL FASTENER#14X3/41'-4" O.C.WALL FASTENER#12X1 SDYC W/NUTBLK1'-4" O.C.SEE DETAILS: EA26SA AND EA36TAWALL PANELSECTION AT EAVE WITHOUT THERMAL BLOCKSSTANDING SEAM ROOF / SHADOW PANEL WALLSDownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)EA04SD

PRODUCT MANUALSTANDING SEAM ROOF PANELSection at EaveStanding Seam Roof / Open SidewallEA04/SOSEE DETAILS: EA26SA AND EA36TASTANDING SEAM PANEL4"SAFETY PRECAUTIONDO NOT STEP ON PANEL NEARTHE EAVE UNTIL FULLY SECUREDWITH FASTENERS.ROOF TRIM FASTENER(S)H1030STANDING SEAMMETAL CLOSURESSMC-ITAPE MASTIC3/4 TMTAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H1030* EAVE CLOSURE FLASHINGTFOSEAVE SUPPORT FLASHINGTFSE* EXTEND FLASHING ANDFIELD WORK AS REQUIREDTO CREATE ENDCAPSWALL MAIN FASTENER(S)#12X1 1/41'-0" O.C.STRUCTURAL FASTENER#12X1 1/41'-0" O.C.BLIND RIVET1/8 RIVET1'-0" O.C."J" FLASHINGFJ21 5/16"SECTION AT EAVEEA04SOSTANDING SEAM ROOF / OPEN SIDEWALLDownload the DWG file by clicking here.To Section IndexRevised: 02.19.21 (MR2021.03)

PRODUCT MANUALSTANDING SEAM ROOF PANELHighside Eave Flashing AttachmentStanding Seam Roof at OverhangEA05A/SOROOF TRIM FASTENER(S)H10306" O.C.NOTE:SEE DETAILS RC34SA AND RC35SATAPE MASTIC 3/4 TM (TOP ANDBOTTOM OF METAL CLOSURE)1"min.***STANDING SEAMPANEL CLIPSTANDING SEAM PANELMETAL CLOSURESSMOCHIGH SIDE FLASHINGTHS OR WTHSLAP STIFFENERSSLS-1ROOF FASTENERH1030(7) PER CLOSUREWALL TRIM FASTENER(S)#14X3/41'-0" O.C.STRUCTURAL FASTENER(S), MK. H1020(H1025 w/INSULATION OVER 6")(2) PER CLIP TYP U.N.BLIND RIVET1/8 RIVET1'-0" O.C.*** - PANEL CUTBACK/EXTENSION VARIES.SEE ROOF PANEL LAYOUT."J" FLASHINGFJ21 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38BAA, SF03BAAWITHOUT SOFFIT EA38BAAAHIGHSIDE EAVE FLASHING ATTACHMENTSTANDING SEAM ROOF AT OVERHANG OR CANOPYDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA05ASO

PRODUCT MANUALSTANDING SEAM ROOF PANELHighside Eave Flashing AttachmentStanding Seam Roof at Overhang with Thermal BlocksEA05CA/SOROOF TRIM FASTENER(S)H10306" O.C.SEE DETAIL: RC34SA AND RC35SATAPE MASTIC 3/4 TM (TOP ANDBOTTOM OF METAL CLOSURE)1"min.***PANEL CLIPSTANDING SEAM PANELMETAL CLOSURESSMOCHIGH SIDE FLASHINGTHS OR WTHSLAP STIFFENERSSLS-1ROOF FASTENERH1030(7) PER CLOSUREWALL TRIM FASTENER(S)#14X3/41'-0" O.C.THERMAL BLOCKTB1TSTRUCTURAL FASTENER(S), MK. H1020(H1025 w/INSULATION OVER 6")(2) PER CLIP TYP U.N.BLIND RIVET1/8 RIVET1'-0" O.C.*** - PANEL CUTBACK/EXTENSION VARIES.SEE ROOF PANEL LAYOUT."J" FLASHINGFJ21 5/16"SEE APPROPRIATE DETAILWITH SOFFIT EA38BAA, SF03BAAWITHOUT SOFFIT EA38BAAAHIGHSIDE EAVE FLASHING ATTACHMENTSTANDING SEAM ROOF AT OVERHANG OR CANOPY WITH THERMAL BLOCKSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA05CASO

PRODUCT MANUALSTANDING SEAM ROOF PANELHighside Eave Flashing Attachment with Thermal BlockStanding Seam Roof / Architectural III, Architectural "V" Rib, or Long Span III WallsEA05C/SB*** - PANEL CUTBACK/EXTENSION VARIES.SEE ROOF PANEL LAYOUT.ROOF TRIM FASTENER(S)H10306" O.C.SEE DETAILS: RC34SARC35SATAPE MASTIC 3/4 TM (TOP ANDBOTTOM OF METAL CLOSURE)1" min.***HIGH SIDE FLASHINGTHS OR WTHSSTANDING SEAM PANELPANEL CLIPLAP STIFFENERSSLS-1METAL CLOSURESSMOCTHERMAL BLOCKTB-1 OR TB1TWALL MAIN FASTENER(S)#12X1 1/4 (SEE NOTE)1'-0" O.C.NOTE: #12X2 FASTENER(S) w/ 6" INSULATIONWALL TRIM FASTENER(S)#14X3/41'-0" O.C.OUTSIDE CLOSUREREQUIRED IF ORDEREDROOF FASTENERH1030(7) PER CLOSURESTRUCTURAL FASTENER(S), MK. H1020(H1025 w/INSULATION OVER 6")(2) PER CLIP TYP U.N.WALL PANELHIGHSIDE EAVE FLASHING ATTACHMENT WITH THERMAL BLOCKSTANDING SEAM ROOF / ARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA05CSB

PRODUCT MANUALSTANDING SEAM ROOF PANELHighside Eave Flashing AttachmentStanding Seam Roof / Architectural III, Architectural "V" Rib or Long Span III WallsEA05/SBROOF TRIM FASTENER(S)H10306" O.C.TAPE MASTIC 3/4 TM (TOP ANDBOTTOM OF METAL CLOSURE)1" min.***HIGH SIDE FLASHINGTHS OR WTHSSTANDING SEAM PANELPANEL CLIPMETAL CLOSURESSMOCLAP STIFFENERSSLS-1WALL MAIN FASTENER(S)#12X1 1/4 (SEE NOTE)1'-0" O.C.NOTE: #12X2 FASTENER(S) w/ 6" INSULATIONROOF FASTENERH1030(7) PER CLOSURESTRUCTURAL FASTENER(S), MK. H1020(H1025 w/INSULATION OVER 6")(2) PER CLIP TYP U.N.WALL TRIM FASTENER(S)#14X3/41'-0" O.C.*** - PANEL CUTBACK/EXTENSION VARIES.SEE ROOF PANEL LAYOUT.OUTSIDE CLOSUREREQUIRED IF ORDEREDWALL PANELSEE DETAILS: RC34SARC35SAHIGHSIDE EAVE FLASHING ATTACHMENTSTANDING SEAM ROOF / ARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA05SB

PRODUCT MANUALSTANDING SEAM ROOF PANELHighside Eave Flashing AttachmentStanding Seam Roof / at Open SidewallEA05/SOROOF TRIM FASTENER(S)H10306" O.C.TAPE MASTIC 3/4 TM (TOP ANDBOTTOM OF METAL CLOSURE)HIGH SIDE FLASHINGTHS OR WTHS1"min.***STANDING SEAM PANELPANEL CLIPMETAL CLOSURESSMOCLAP STIFFENERSSLS-1WALL MAIN FASTENER(S)#12X1 1/41'-0" O.C.ROOF TRIM FASTENER(S)H1030(7) PER CLOSUREBLIND RIVET1/8 RIVET1'-0" O.C.STRUCTURAL FASTENER(S), MK. H1020(H1025 w/INSULATION OVER 6")(2) PER CLIP TYP U.N."J" FLASHINGFJ2EAVE CLOSURE FLASHINGMEC21 5/16"*** - PANEL CUTBACK/EXTENSION VARIES.SEE ROOF PANEL LAYOUT.SEE DETAILS: RC34SARC35SAHIGHSIDE EAVE FLASHING ATTACHMENTSTANDING SEAM ROOF / AT OPEN SIDEWALLDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA05SO

PRODUCT MANUALSTANDING SEAM II/360Roof to Wall Transition at Existing EaveStanding Seam Roof/Architectural III, Architectural "V" Rib or Long Span III WallsEA06/SAINSIDE METAL CLOSURESSMC-IEXISTING ROOFPANELROOF TRIM FASTENER(S)H1030(SEE FASTENER INSTALLATIONAT EAVE FOR LAYOUT)TAPE MASTIC3/4 TMROOF TRIM FASTENER(S)H10306" O.C.ROOF TO WALL FLASHINGTHS1SXEAVE SUPPORT FLASHINGEAVE CLOSURE FLASHINGSTANDING SEAMPANELWP AT STEEL LINESEE DETAIL RC34SA AND* NOTE:RC35SA FOR CLOSURE*LAP STIFFENERSSLS* OUTSIDE CLOSURESSMOC**4"SEE ROOFPANEL LAYOUT** : IF LAP STIFFENER, SSLS-1, DOESN'T REACH THE TOP LEG OF PURLIN, USE (1) H1030ON THE UPHILL SIDE OF THE METAL CLOSURE LOCATION TO PROVIDE A SUPPORT FORTHE LAP STIFFENER FOR THE ATTACHMENT OF THE METAL CLOSUREROOF TO WALL TRANSITION AT EXISTING EAVESTANDING SEAM ROOF / ARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)INSTALLATIONSEE DETAIL RC32SA FOR RIDGE SUPPORTFLASHING INSTALLATIONEA06SA

PRODUCT MANUALSTANDING SEAM ROOF PANELRoof Sheeting Prior to Wall Sheeting InstructionsEA11/AADownload the DWG file by clicking here.To Section IndexRevised 04.01.2018

PRODUCT MANUALSTANDING SEAM II/360Roof to Wall Transition at High SideStanding Seam Roof/Architectural III, Architectural "V" Rib or Long Span III WallsEA11/SB* NOTE: SEE DETAIL RC34SA ANDRC35SA FOR CLOSUREINSTALLATIONSEE DETAIL RC32SA FOR RIDGE INSTALLATIONSEAL WALL PANEL SIDELAPS WITH 3/4"TAPE MASTIC DURING INSTALLATION. STARTMASTIC AT CLOSURE AND CONTINUE UPSIDELAP 36". STITCH SCREWS 6" O.C. FOR 36"AOLI/LOAI/AVPI CLOSURE WITH 3/4" TAPEMASTIC APPLIED TO BOTH SIDES. CAULKJOINTS (SEE EA01BA)REQUIREDSTOP INSULATIONABOVE CLOSUREGIRTROOF TO WALL FLASHINGTHS1S* LAP STIFFENERSSLS-1H1030ROOF FASTENER(GIRT TOED DOWNSHOWN, TOED UPSIMILAR)STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C., 305 mm O.C.* OUTSIDE CLOSURESSMOCSTANDING SEAMPANELGABLE ANGLEGA-4WALL MAIN FASTENER(S) TYP#12X1 1/41'-0" O.C. , 305 mm O.C.NOTE: #12X2 FASTENER(S)w/ 6" INSULATIONWP AT STEEL LINEH1030ROOF FASTENER** : IF LAP STIFFENER, SSLS-1, DOESN'TREACH THE TOP LEG OF PURLIN, USE(1)H1030 ON THE UPHILL SIDE OF THEMETAL CLOSURE LOCATION TO PROVIDE ASUPPORT FOR THE LAP STIFFENER FOR THEATTACHMENT OF THE METAL CLOSURE**INSIDE CLOSUREREQUIRED IF ORDEREDFLASHINGPF95-4"102 mmSEE ROOFTPANEL LAYOUWALL TRIM FASTENER(S)#14X3/41'-0" O.C., 305 mm O.C.WALL PANELROOF TO WALL TRANSITION AT HIGH SIDESTANDING SEAM ROOF / ARCHITECTURAL III, ARCHITECTURAL "V" RIB OR LONG SPAN III WALLSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)EA11SB

PRODUCT MANUALSTANDING SEAM II/360Roof to Wall Transition at High SideStanding Seam Roof/Shadow Panel WallsEA11/SDNOTE: SEE DETAIL RC34SA AND RC35SA FOR CLOSURE* INSTALLATIONSEE DETAIL RC32SA FOR RIDGE INSTALLATIONSEAL WALL PANEL SIDELAPS WITH 3/4"TAPE MASTIC DURING INSTALLATION. STARTMASTIC AT CLOSURE AND CONTINUE UPSIDELAP 36". STITCH SCREWS 6" O.C. FOR 36"WALL MAIN FASTENER(S) TYP#12X1 SDYC W/NUTBLK1'-4" O.C.SHP-IO CLOSURE WITH 3/4" TAPEMASTIC APPLIED TO ALL SIDES OF CLOSURE.REQUIREDROOF TO WALL FLASHINGTHS2SLAP STIFFENERSSLS-1FLASHINGROOF FASTENER H1030PF95-STRUCTURAL FASTENER(S)#12X1 1/41'-0" O.C.*** OUTSIDE CLOSURESSMOCGABLE ANGLEGA-3STANDING SEAMPANELCLOSURESHPI/OREQUIRED IF ORDEREDGIRT(GIRT TOED UPSHOWN, TOEDDOWN SIMILAR)WP AT STEEL LINE**** : IF LAP STIFFENER, SSLS-1, DOESN'TREACH THE TOP LEG OF PURLIN, USE(1)H1030 ON THE UPHILL SIDE OF THE METALCLOSURE LOCATION TO PROVIDE ASUPPORT FOR THE LAP STIFFENER FOR THEATTACHMENT OF THE METAL CLOSUREWALL TRIM FASTENER(S)#14X3/41'-0" O.C.4"SEE ROOFPANEL LAYOUTROOF TO WALL TRANSITION AT HIGH SIDESTANDING SEAM ROOF / SHADOW PANEL WALLSDownload the DWG file by clicking here.To Section IndexRevised: 03.05.21 (MR2021.03)WALL PANELEA11SD

PRODUCT MANUALSTANDING SEAM II/360Roof to Wall Transition at High SideStanding Seam Roof/Insulated Wall PanelsEA11/SWPANELTHICKNESSPANEL CLIP WC-O1SEE CHART FORHIDDEN JOINT FASTENERHIDDEN JOINT FASTENER QTY.FASTENERPER WC-01 CLIP2"#1/4-14X2 SDHH(2)2 1/2"#1/4-14X3 SDHH(2)3"#1/4-14X3 SDHH(2)4"#1/4-14X4 SDHH(

Product Manual - Standing Seam Panels - Eave EA01A/SB, High Side Eave Detail . EA03/AA, Deluxe Eave Flashing Installation EA03A/AO, Deluxe Eave Flashing Installation EA03/AO, Deluxe Eave Flashing Installation at Open Sidewall . MULTI-RIB PANEL (OPTIONAL) DECK ATTACHMENT AS SPECIFIED BY DESIGN AVPO/LOAI/AOLI min. 3" 1"

Related Documents:

this installation guide. Substrates: Select Seam roofing panels can be used over solid substrates only. Slope Requirements: Panels should be used on slopes of 3:12 or greater. Select Seam Narrow Batten panels can be used for curved applications. Inquire with your AEP Span Representative for details. Condensation, Insulation, & Ventilation:

400ml Static Mixing Tips - 3/8′′ x 11′′ x 24 EL Finishing Kit - Inline Seam and Radial Seam Finishers for seam smoothing (R50SEAM-KIT) Solvent for clean-up (IPA, acetone) Protective gloves needed when using seam sealant Sealant an

Color Construction Dimples Country Manufacturer Effective -10/6/2021 Thru 11/2/2021 Pole /Seam Marking Rating Spin Pole 1: B logo pink 2P-1c L-L 330 USA Bridgestone Golf, Inc. Seam 1: (long arrow) e6 Lady Pole 1: B logo white 2P-1c L-L 330 USA Bridgestone Golf, Inc. Seam 1: (long arrow) e6 Lady Pole 1: B logo yellow 3P-2c L-L 326 USA Bridgestone Golf, Inc. Seam 1: (symbol) e6 Soft (symbol)File Size: 333KBPage Count: 40

Apr 06, 2016 · Tuck the seam edges together and wipe off excess bond/sealer with a clean, damp cloth. 6. Use a resilient flooring type hand roller (or wallpaper seam roller) to squeeze out any remaining bond/sealer from the seam. Immediately clean seam with a damp cloth followed by a clean, dry cloth. 7. Protect the

the primary-secondary backing. The two seam edges should be butted together to assure even placement and complete seam sealing. The seam sealer can prevent tuft loss, raveling, and even waterproof the Activ Turf seam edges. 10. After Installation: Restrict foot traffic and moving of heavy

Joint & Seam Filler PROSOCO R-Guard Joint & Seam Filler is a gun-grade, crack and joint filler, adhesive and detailing compound that combines the best of silicone and polyurethane properties. This single-component, fiber-reinforced, Silyl-Terminated-Polymer (STP) is easy to gun, spread and tool. Use Joint & Seam Filler to fill openings and create

D4884 "Standard Test Method for Seam Strength of Sewn Geotextiles". Figure 2 shows a wide width seam test per ASTM D4884. Although some promising techniques are being researched to provide very high seam efficiencies, seam strengths can often be achieved up to 60% or more of the ultimate wide width tensile strength in the cross- machine direction.

ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC) ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods. Test Procedure. All testing was conducted in the VT test chambers at Intertek-ATI located in York, Pennsylvania. The microphones were calibrated before conducting the tests. The airborne .