Square D EX Low Voltage Distribution Transformers

1y ago
13 Views
2 Downloads
3.80 MB
24 Pages
Last View : 11d ago
Last Download : 3m ago
Upload by : Raelyn Goode
Transcription

Square D EX Low VoltageDistribution TransformersOne product in the distribution systemCatalog7400CT15012015Class 7400CONTENTSDescription . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PageGeneral Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Department of Energy (DOE) Compliance . . . . . . . . . . . . . . . . . . . . . . . 3Product Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4New Energy Efficient Transformer Family – EX . . . . . . . . . . . . . . . . . . . 4Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Mounting Bracket Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Wall and Ceiling Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Weather Shields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Terminal Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Mechanical Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Square D EX Low Voltage Distribution TransformersProduct DescriptionProduct DescriptionGeneral InformationThe Square D Distribution Transformer is designed to supply power throughout the building. Thetransformer permits multiple voltages to be leveraged in the design of the system.Advantages to designing a system with low voltage transformers: Distributes a voltage higher than required by the load to limit wire losses and voltage drop.Adds source impedance to the system, reducing common overcurrent at normal voltages.Mitigates harmonics through an internal magnetic circuit.Allows system grounding closer to the load which reduces capacitive noise.Utilizes multiple voltage equipment since transformers can be designed for any output voltage thatis required.Disadvantages to designing a system with low voltage distribution transformers: Slightly reduces overall efficiency of the system due to internal losses within the transformer.Adds heat to the building if installed indoors (and in the HVAC system).The impact on the efficiency of the system and the concerns for improvements in the market for energyconsumption are why low voltage distribution transformers have been regulated through the EnergyPolicy and Conservation Act.The first improvement to transformer efficiency was the development of NEMA TP1 – 1996 (updated2002). This was a volunteer standard to increase the efficiency of transformers. The second was the2005 Energy Act which mandated the NEMA TP1 – 2002 levels for all units manufactured afterJanuary 1, 2007. EPAct2005 also authorized the Department of Energy to evaluate whether or notmore stringent levels should be mandated.The Department of Energy evaluated low voltage transformers as part of an overall DistributionTransformer analysis in 2010 and 2011. They published their advanced rule in 2012 increasing thelevels slightly, but chose to increase to the maximum improvement in energy efficiency that wastechnologically feasible. This increase occurred after multiple comments from stake holders requestingthat the levels be increased beyond the levels published in 2012. The final levels which were publishedin April 2013 affect all transformers manufactured after January 1, 2016. The increase in efficiencyonly affects three-phase units.212/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersProduct DescriptionDepartment of Energy (DOE) Compliance10 CFR 431 – Energy Conservation standards431.196 (a) Low Voltage Transformers(2) The efficiency of low voltage dry-type distribution transformers manufactured on or afterJanuary 1, 2016 shall be no less than that required for their kVA rating in the Table 1.Table 1:Efficiency Ratings of Low Voltage Dry-type Distribution TransformersSingle-phaseThree-phasekVAEfficiency (%)kVAEfficiency 099.23——100099.28All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring theEnergy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431.Low-voltage, dry-type distribution transformers with kVA ratings not appearing in Table 1 have theirminimum efficiency level determined by linear interpolation of the kVA and efficiency valuesimmediately above and below that kVA rating.The new Type EX Energy Efficient Low Voltage Dry-Type Distribution Transformers comply with thenew levels of efficiency.Figure 1:Type EX Energy Efficient Low Voltage Dry-Type Distribution Transformer3 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersProduct FeaturesProduct FeaturesNew Energy Efficient Transformer Family – EXThe efficiency levels set by the U.S. Department of Energy necessitated completely new transformerdesigns. Components used within Schneider Electric transformers were optimized for performance,including: Coil—Computer designed to reduce the losses with customized wire configurations usedexclusively by Schneider Electric. Computer winding equipment to minimize variability during thewinding process. Available as standard with Aluminum Conductor, but also available with copper. Insulation System—The system consists of a conductor wrap or coating, layer insulation, air gapspacing, and varnish material. The system is UL listed for a specific maximum temperature foraverage temperature rise, hot spot, and ambient temperature. Schneider Electric’s EX family oftransformers have a 428 F (220 C) insulation system, with an average temperature rise maximumof 302 F (150 C). The design also allows further reduction in conductor losses, while also offeringthe product with an average temperature rise of 239 F (115 C) or 176 F (80 C).Figure 2:Insulation System Core—Transformers are designed with high grade grain oriented, non-aging silicon steellaminations with high magnetic permeability and low hysteresis and eddy current losses. Thecomputer design program allows the design to keep the magnetic flux densities well below thesaturation point. The laminations are carefully and evenly stacked in one of two coreconfigurations: distributive gap or full step mitre. Then they are clamped together to ensure themost efficient magnetic circuit while providing a quiet quality offering of low voltage transformers. Terminals—Sized to allow the lugs to align with all corresponding Schneider Electric equipment(such as: breakers, switches, panels, switchboards, and so forth). Layout separates the Primaryand Secondary terminals and meet the NEC minimum bending requirements. Lugs are not shippedwith the transformers to give the installer the flexibility to meet any distribution system conductorsrequested. All incoming terminals are sized for 125% or 250% lug landing.NOTE: Both mechanical and compression lug kits are available from Schneider Electric.412/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersProduct Features Enclosure—Two new enclosure styles: K and J. See Figure 3.— Style K units are designed with no top or rear ventilation and alcove tested with ½ in.(12.7 mm)clearance from the rear and sides. The front and rear panels are designed to attach to thecover, increasing the support strength of the tops. The base is vented and designed with aconduit entry and three (3) locations for mounting a ground terminal bar.— Style J units are designed with no rear ventilation and alcove tested at ½ in.(12.7 mm)clearance from the rear and sides. The front and rear panels are designed to attach to thecover, increasing the support strength of the tops. The open design of the enclosure baseincludes two (2) locations for mounting a ground terminal bar and conduit entry area for ease ofinstallation.Both enclosures have mounting holes on the side to easily bolt the transformer enclosure to thefloor using a floor mounting kit.Figure 3: Figure 4:Style K and J EnclosureNameplate—Two nameplates are attached to each unit. See Figure 4. One on the front coverwhich is required by standards, the second nameplate is attached to the core and coil, providinginstallation information inside the unit. The second nameplate also carries a UR listing for the coreand coil, allowing the enclosure to be removed and the device installed in the equipment.Sample NameplatesNameplate Core and CoilAttached to the Front CoverAttached to the Core and Coil5 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersProduct Features Testing—All designs are tested at state of the art test labs, including:— UL certified as part of the Test Program.— UL 1561 and NEMA ST-20.— DOE Product verification testing is completed yearly in compliance with 10 CFR 429.Routine Testing is performed on all units shipped. Packaging--Shipping materials are updated to insure the new designs arrive undamaged fromhandling and logistics. Pallets are designed to increase clearances between units, and spacers areadded underneath the box to prevent small dings in the enclosure. The enclosure design is alsoenhanced to prevent damage during shipments. Quiet Quality—All units are designed and guaranteed to have sound levels 3 dB below the NEMAST-20 tables with most units designed 6 dB below the NEMA ST-20 tables. Since each 3 dB cutsthe audible sound in half, new units produce 25% less noise than the EE product offering. Manufacturing—All units are built in two ISO registered facilities. One location is designed tomanufacture the high volume products and populate our two distribution centers. The other isdesigned to manufacture lower volume units which are shipped directly to our customers. Product Environmental Profile:— RoHS compliant— REACH compliant— Eco-Passport612/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersElectrical DataElectrical DataTable 2:kVAProduct Specifications including Catalog ondary Efficiency @ 35% Temp. RiseInc ClassLevelWinding167 F / 75 C( F/ C)Catalog No.Weight(lbs)Enclosure1598.17%39 dBEX15T3H24517K3098.38%39 dBEX30T3H40018K4598.60%39 dBEX45T3H49018K7598.69%44 dBEX75T3H71020K98.83%44 dBEX112T3H92021K47 dBEX150T3H117022K112.51506–2.5% 2 4–480208Y/12099.00%15022022599.06%49 dBEX225T3H182525J30099.13%49 dBEX300T3H197525J50099.24%56 dBEX500T68H310030J99.34%58 dBEX750T68H412531J7504–2.5% 2 2–Figure 5:TAPS 6 — 2.5% 2 FCAB, 4 FCBNTAPS 5-2.5% 2 FCAN, 2 FCBN7 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersElectrical DataThe transformer source impedance limits the overcurrent on the secondary terminals. Table 3 providesthe maximum amount of overcurrent available:Table 3:Technical data: IZ, IX, X/R, and Let Through CurrentSecondary NPCurrentSecondaryNEC 125%IZ%%IXX/RInfinite Primary BusLet ndaryWinding208Y/120Calculation of regulation voltage drop on a transformer is complex, requiring information about loadpower factor as well as amperage. Since complete information is often lacking, a worse casecalculation as shown below is often used to provide conservative results:Maximum load currentVoltage drop (%) x Impedance (%)Transformer secondary full load rating812/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersElectrical DataWhen voltage is applied to the input winding of a transformer there can be a brief period of inrushcurrent until the transformer core is stabilized. Inrush lasts approximately 6 power cycles, or about0.1 seconds. The magnitude of the inrush varies depending on when the switch closes on the powerwave, so that inrush can be anywhere from zero to greater than the full load current rating of thetransformer. In addition, the impedance of the supply system can influence the amount of inrushcurrent the transformer can draw. To avoid tripping breakers, or blowing fuses on the primary side ofthe transformer during energizing, careful coordination of fuse sizes or breaker handle ratings andmagnetic trip settings is essential. This coordination requires information about maximum possibleinrush to be expected from the particular transformer in question.Schneider Electric has taken the inrush data for our units and plotted this data on our breakers’ tripcurves. As a result of this data, it has been determined that breakers sized at either the NEC 125% or250% levels will energize the product without tripping.Table 4 permits completion of the analysis by supplying the maximum inrush times rated, but alsoincludes the type of breaker at the NEC level listed for a quick guide to choosing the propertransformer breaker.Table 4:Breaker SelectionCatalogNumberRMS InrushPrimary Winding NP(x Rated Pri Current) (Delta)AmpsNEC125%NEC250%SE Breakers@125%EX15T3H8.118.02545ED, EG, EJ, HD, HG, HJ, HL, HR ED, EG, EJ, HD, HG, HJ, HL, HREX30T3H9.336.15090ED, EG, EJ, HD, HG, HJ, HL, HR ED, EG, EJ, HD, HG, HJ, HL, HREX45T3H7.854.170125ED, EG, EJ, HD, HG, HJ, HL, HR ED, EG, EJ, HD, HG, HJ, HL, HREX75T3H7.690.2125225ED, EG, EJ, HD, HG, HJ, HL, HR JD, JG, JJ, JL, JREX112T3H5.7135.3175330JD, JG, JJ, JL, JD, JG, JJ, JL, JRSE Breakers@ 250%LD, LG, LJ, LL, LR180.42504504.4270.6350600LD, LG, LJ, LL, LRLD, LG, LJ, LL, LR, MG, MJ5.5360.8500800LD, LG, LJ, LL, LR, MG, MJMG, MJ PG, PJ, PK, PL2.1601.48001200MG, MJ PG, PJ, PK, PL4.3902.1Figure 6:12002000LD, LG, LJ, LL, LRPG, PJ, PK, PL, RG, RJ, RK, RLLD, LG, LJ, LL, LRPG, PJ, PK, PL, RG, RJ, RK, RLRG, RJ, RK, RL,NW-N, NW-H, NW-L, NW-LFPrimary and Secondary Protection9 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersElectrical DataTransformer efficiency can be defined as the percentage of power out compared to the percentage ofpower in. A perfect zero loss transformer would have the same power in as out, and would be 100%efficient. With the implementation of EPACT2005 Final Rule 10 CFR 431 Subpart K, most low voltagetransformers exceed 98% at 35% load.For compliance with the 2005 Energy Act, manufacturers must measure and calculate the efficiencylevels using the following formula:% Efficiency 100 X P X VA(P X VA) Core Loss (P2 X Coil Loss X T)Where:P per unit load (EPACT2005 0.35)T correction factor for winding material and temperature correction (convert to 167 F (75 C))(302 F (150 C) Rise AL 0.8152; CU 0.8193)Correction factors are used because resistance losses vary by temperature and winding material.See 10 CFR 431.193 for more details on formula.Table 5:Transformer EfficiencykVAPart NumberNOLOADCOILLOSSPower OutTotal Loss35% Load35% 167 F (75 C)Power In35% LoadEfficiency35% LoadMinimum EfficiencyEPACT 2005167 F (75 C) 167 F (75 C) 167 F (75 C) 10 CFR 37.9262500264237.9499.34%99.23%Manufacturers are required to use sampling plans for Distribution Transformers under Department ofEnergy 10 CFR 429.47.Manufactures can use actual test results in accordance with 10 CFR 431.193, to certify:a. Basic Modelsb. kVA GroupsManufacturers may also use Alternative Methods for Determining Efficiency (AEDM) per10 CFR 429.70.1012/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersElectrical DataCore loss (No-Load Loss): When a transformer is energized on the primary side, the laminated steelcore carries a magnetic field, or flux. This magnetic field causes certain losses in the core, generatingheat and dissipating real power from the primary source even when no load is on the secondary side ofthe transformer.Coil Loss (Load Loss): Under load, a transformer looses energy in the form of heat within the windingconductors. That’s because these conductors have a certain amount of resistance. Nearly all of thecoil loss can be accounted for by the simple I2R (current in amperes squared times resistance in ohms)formula for watts. There is a small amount of stray losses, and the sum of these and I2R watts equaltotal coil loss.These losses are typically reported by engineering in watts. Many contractors interested in airconditioning requirements of a building will request the BTU/HR (British Thermal Units per hour)equivalent, which can be determined as follows: BTU/HR 3.414 x Losses in WattsTable 6:Transformer Core and Coil LosskVAPart ed Load per ST-20, 338 F (170 11 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersDimensional DrawingsDimensional DrawingsFigure 7:Enclosure 17K1212/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 8:Enclosure 18K13 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 9:Enclosure 20K1412/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 10:Enclosure 21K15 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 11:Enclosure 22K1612/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 12:Enclosure 25J17 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 13:Enclosure 30J1812/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersDimensional DrawingsFigure 14:Enclosure 31J19 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersAccessoriesAccessoriesMounting Bracket OptionsMounting brackets are available for each unit to provide multiple options for attaching the unitsto the floor.Figure 15:Style K EnclosureFigure 16:Style J Enclosure2012/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersAccessoriesWall and Ceiling Mounting BracketsNOTE: Wall mounting brackets are used with units weighing no more than 800 lbs.Ceiling mounting brackets are used with units weighing no more than 1300 lbs.Table 7:Figure 17:Mounting Bracket Enclosure Styles and Part NumberEnclosure StyleWall Mount Bracket PartNumberCeiling Mount Bracket 0K21K—7400CMB21K22K—7400CMB22KWall Mounted TransformerWall mounting bracketsWall mountingbracketsFront ViewFigure 18:Side ViewCeiling Mounted TransformerCeiling mountingbracketsFront ViewSide View21 2015 Schneider ElectricAll Rights Reserved12/2015

Square D EX Low Voltage Distribution TransformersAccessoriesWeather ShieldsTable 8:Weather Shield—Enclosure Style and Part NumberEnclosure StylePart S20K21K7400WS21K22K7400WS22KFigure 19:Weather Shield EnclosuresWeather shieldsFront ViewSide ViewWeather shieldsWeather shieldsFront ViewSide View2212/2015 2015 Schneider ElectricAll Rights Reserved

Square D EX Low Voltage Distribution TransformersAccessoriesTerminal LugsTable 9 includes terminal sizes to handle lugs for the following wire range.(All terminals allow for NEMA two hole lugs.)Table 9:Terminal Sizes and Wire Ranges300 V and AbovekVABelow 300 VTerminalMechanical LugsTerminalCompression LugsTerminalMechanical LugsTerminalCompression Lugs15(1) 2/0–14 AWG(1) #12–10 AWG(1) #8–#1/0 AWG(1) 2/0–14 AWG(1) #8–#1/0 AWG30(1) 2/0–14 AWG(1) #8–#1/0 AWG(1) 350 kcmil–6 AWG(1) #8–#1/0 AWG(1) #4–300 kcmil(1) 250 kcmil–350 kcmil45(1) 2/0–14 AWG(1) 350 kcmil–6 AWG(1) #8–#1/0 AWG(1) #4–300 kcmil350 kcmil–6 AWG(1) 600 kcmil–4 AWGor(2) Equal 250 kcmil–1/0 AWG(1) 250 kcmil–350 kcmil(1) #2/0–500 kcmil(2) #4–300 kcmil75(1) 2/0–14 AWG(1) 350 kcmil–6 AWG(1) #8–#1/0 AWG(1) #4–300 kcmil(1) 250 kcmil–350 kcmil(1) 600 kcmil–4 AWGor(2) Equal 250 kcmil–1/0 AWG(2) #2/0–500 kcmil(1) 400 kcmil–600 kcmil (AL)(2) #4–300 kcmil(2) 250 kcmil–350 kcmil112.5(1) 350 kcmil–6 AWG(1) 600 kcmil–4 AWGor(2) Equal 250 kcmil–1/0 AWG(1) 250 kcmil–350 kcmil(1) #2/0–500 kcmil(2) #4–300 kcmil(2) 350 kcmil–6 AWG(2) 600 kcmil–2 AWG(3) 250 kcmil–350 kcmil(3) #4–300 kcmil(2) 400 kcmil–600 kcmil (AL)150(1) 600 kcmil–4 AWGor(2) Equal 250 kcmil–1/0 AWG(1) 250 kcmil–350 kcmil(2) #4–300 kcmil(3) 350 kcmil–6 AWG(2) 600 kcmil–2 AWG(3) #2/0–500 kcmil(3) #4–300 kcmil(3) 400 kcmil–600 kcmil (AL)(4) 250 kcmil–350 kcmil225(1) 600 kcmil–2 AWG(2) 600 kcmil–2 AWG(2) #2/0–500 kcmil(2) 400 kcmil–600 kcmil (AL)(2) #4–300 kcmil(3) 600 kcmil–2 AWG(4) #4–300 kcmil(4) #2/0–500 kcmil300(2) 600 kcmil–2 AWG(3) 250 kcmil–350 kcmil(3) #2/0–500 kcmil(3) 400 kcmil–600 kcmil (AL)(4) 600 kcmil–2 AWG(6) #2/0–500 kcmil(6) 400 kcmil–600 kcmil (AL)500(3) 600 kcmil–2 AWG(4) #4–300 kcmil(4) #2/0–500 kcmil(6) 600 kcmil–2 AWG(9) #2/0–500 kcmil(9) 400 kcmil–600 kcmil (AL)750(4) 600 kcmil–2 AWG(6) #2/0–500 kcmil(6) 400 kcmil–600 kcmil (AL)(9) 600 kcmil–2 AWG(15) #2/0–500 kcmil(15) 400 kcmil–600 kcmil (AL)23 2015 Schneider ElectricAll Rights Reserved12/2015

Mechanical Lug KitsTable 10:CatalogNumberSquare D Lug Kits for Dry-type TransformersLugsperKitWire RangeCapScrewsCurrentRangeGroundingLugsper KitWire RangeBondingLugsper KitWire RangeNotApplicableNotApplicableSingle-phase Primary, Single-phase Secondary, Three-phase Delta Primary, Three-phase SecondaryDASKP10031/0–14 STR.1/4 in. x 1 in.Up to 100 ADASKP2503350 kcmil–6 STR.3/8 in. x 2 in.101–250 A3600 kcmil–4 STR.(2) 250 kcmil–1/0 STR.3/8 in. x 2 in.201–400 A6600 kcmil–4 STR.(2) 250 kcmil–1/0 STR.3/8 in. x 2 in.601–800 ADASKP400DASKP600DASKP10009600 kcmil–2 STR.3/8 in. x 2 in.601–800 ADASKP120012600 kcmil–2 STR.3/8 in. x 2 in.801–1200 ANotApplicableNotApplicableSingle-phase Primary and Secondary, Three-phase Wye Secondary, Three-phase Delta with Center TapDASKGS10051/0–14 STR.1/4 in. x 1 in.Up to 100 A1(4) 2/0–14 STR.12–14 STR.DASKGS2505350 kcmil–6 STR.3/8 in. x 2 in.101–250 A1(4) 2/0–14 STR.12–14 STR.DASKGS4005600 kcmil–4 STR.(2) 250 kcmil–1/0 STR.3/8 in. x 2 in.201–400 A1(4) 2/0–14 STR.11/0–14 STR.DASKGS60010600 kcmil–4 STR.(2) 250 kcmil–1/0 STR.3/8 in. x 2 in.601–800 A1(4) 350 kcmil–6 STR.1250 kcmil–6 STR.DASKGS100015600 kcmil–2 STR.3/8 in. x 2 in.601–800 A1(4) 350 kcmil–6 STR.1250 kcmil–6 STR.DASKGS120020600 kcmil–2 STR.3/8 in. x 2 in.801–1200 A1(4) 350 kcmil–6 STR.1250 kcmil–6 STR.DASKGS200025600 kcmil–2 STR.3/8 in. x 2 in.1201–2000 A1(4) 350 kcmil–6 STR.1250 kcmil–6 STR.NOTE: Lugs are not supplied with transformer units. They must be purchased separately.Schneider Electric USA, Inc.800 Federal StreetAndover, MA 01810 USA888-778-2733www.schneider-electric.usSchneider Electric and Square D are trademarks and the property of Schneider Electric SE, itssubsidiaries and affiliated companies. All other trademarks are the property of their respective owners.7400CT150112/2015

431.196 (a) Low Voltage Transformers (2) The efficiency of low voltage dry-type distribution transformers manufactured on or after January 1, 2016 shall be no less than that required for their kVA rating in the Table 1. Low-voltage, dry-type distribution transformers with kVA ratings not appearing in Table 1 have their

Related Documents:

ft feet 0.305 Meters m yd yards 0.914 Meters m mi miles 1.61 Kilometers km AREA in2 square inches 645.2 square millimeters mm2 ft2 square feet 0.093 square meters m2 yd2 2 square yard 0.836 square meters m ac acres 0.405 hectares ha mi2 square miles 2.59 square kilometers km2 VOLUME

specifically designed for the low-voltage, structured cabling market. The floor bracket is industry-standard orange to identify low-voltage applications, the open design provides the space needed for low-voltage bend radius requirements, and the Leviton QuickPort Quad 106 insert provides up to four low-voltage outlet ports.

Amplifier Configurations . Voltage Amplifier: Voltage input and Voltage output The controlled source is a Voltage -controlled-Voltage Source A. v Open Circuit Voltage Gain can be found by applying a voltage source with R. s 0, and measuring the open circuit output voltage(no load or R. L infinity) Source Amplifier Load . Amplifier Input .

NS (5kV) Medium Voltage Network Switch IS (5kV) Isolation Switch (Fused or Non-Fused) . (Low Voltage) Power Panel in Vault HDP 600V (High Voltage) Distribution Panel LDP 208V (Low Voltage) Distribution Panel HP 600V (High Voltage) Panelboard LP 208V (Low Voltage) Panelboard . 16.6. Acceptable products: Master Padlock catalogue numbers .

square root of 144? 12 6 What is the value of (-11) squared? 121 7 What is the positive square root of 81? 9 8 What is the value of (-4) squared? 16 9 What is the positive square root of 225? 15 10 What is the positive square root of 121? 11 Day 8 Q Question Answer 1 What is the positive square root of 16? 4 2 What is the value of (-6) squared? 36

3. The maximum voltage is the highest voltage that can be imposed on the relay coil. Contact form Rated voltage Rated current (mA) Coil resistance ( ) Must operate voltage (V) Must release voltage (V) Max. voltage (V) Power consumption (mW) % of rated voltage DPDT (2c) 3 VDC 66.7 45 70% max. 10% min. 200% (at 23 C) Approx. 200 4.5 VDC 44.6 101 .

Jul 24, 2000 · 6 beeps every 3 sec. Low Voltage. Voltage is 92 Vac or less. 7 beeps every 3 sec. High Voltage. Control voltage 147 Vac 5%. The red LED will de-energize if voltage protection operates. The voltage safety automatically resets when voltage is corrected. The Output Test switch “S3” provides a relay sequence test. With power OFF, place S3File Size: 1MBPage Count: 51

output voltage to input voltage depending on number of stages is called Cockcroft-Walton Voltage multiplier circuit which is used to develop high voltages in order of several kV. An output voltage, from any stage, can be taken out through tapings. In this work, the input voltage, for Cockcroft-Walton voltage multiplier, has been taken