Product DataWeatherMaker Single Packaged RooftopHeat Pump Units3 to 5 Nominal Tons50KCQ 04, 05, 06with Puron (R-410A) Refrigerant 2020 Carrier CorporationForm 50KCQ-4-6-03PD

Features/BenefitsYour Carrier Packaged HeatPump rooftop unit (RTU) wasdesigned by customers forcustomers. With no-stripscrew collars, handledaccess panels, and morewe’ve made your unit easy toinstall, easy to maintain andeasy to use.Easy to installAll WeatherMaker units are field-convertible to horizontal air flow whichmakes it easy to adjust to unexpected jobsite complications. Lighter units makeeasy replacement. Carrier 50KCQ rooftops fit on existing Carrier curbs datingback to 1989. Also, our large controlbox gives you room to work and room tomount Carrier accessory controls.Easy to maintainEasy access handles by Carrier providequick and easy access to all normallyserviced components. Our “no-strip”screw system has superior holdingpower and guides screws into positionwhile preventing the screw from stripping the unit’s metal. Take accuratepressure readings by reading condenserpressure with panels on. Simply removethe black, composite plug, route yourgage line(s) through the hole, and connect them to the refrigeration servicevalve(s). Now you can take refrigerationsystem pressure readings without affecting the condenser airflow.Easy to useThe newly designed, central terminalboard by Carrier puts all your connections and troubleshooting points in oneconvenient place, standard. Most lowvoltage connections are made to thesame board and make it easy to findwhat you’re looking for and easy toaccess it. Carrier rooftops have highand low pressure switches, a filter drier,and 2-in. (51 mm) filters standard. SEER up to 14.3 EER up to 12.2. HSPFs up to 8.2 Up to 28% lighter than similarindustry units. Lighter rooftopsmake easier replacement jobs. 3 to 5 ton units fit on existing Carrier rooftop curbs making the utilityconnections the same. This savestime and money on replacementjobs. Standardized components and layout. Standardized components andcontrols make service and stockingparts easier. Scroll compressors on all units. Thismakes service, stocking parts,replacement, and troubleshootingeasier. Crankcase heater on all models(except 04 size) provides added protection in all applications. Precision-sized suction line accumulator provides high reliability by preventing liquid from entering thecompressor during low ambient conditions and reverse cycle switch over. Field convertible from vertical tohorizontal airflow configuration onall models. No special kit required. 4-way reversing valve rapidlychanges the flow of refrigerant toquickly changeover from cooling toheating and heating to cooling. Easy-adjust, belt drive motor available on all sizes. There’s no need forfield-supplied drives or motors. Standard Direct Drive - ECM indoormotor with optional belt drive system to meet nearly all applications.Table of contentsFeatures and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Fan Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512 Provisions for bottom or side condensate drain. Capable of thru-the-base or thruthe-curb electrical routing. Dependable time / temperaturedefrost logic provides a defrostcycle, if needed, every 30, 60, 90,or 120 minutes and is adjustable. Single-point electrical connection. Sloped, composite drain pan shedswater; and won’t rust. Standardized controls and controlbox layout. Standardized components and controls make stockingparts and service easier. Clean, large, easy to use control box. Standard coils are copper round tube,aluminum plate fin with optional coilcoatings and copper fin design. Color-coded wiring. Large, laminated wiring and powerwiring drawings which are affixed tounit make troubleshooting easy. Single, central terminal board fortest and wiring connections. Fast-access, handled, panels foreasy access to the blower andblower motor, control box, andcompressors. “No-strip” screw system guidesscrews into the panel and capturesthem tightly without stripping thescrew, the panel, or the unit. Exclusive, newly-designed indoorrefrigerant header for easier maintenance and replacement. Mechanical cooling (115 F to 25 For 46 C to –4 C) on ElectroMechanical (E/M) and Direct DigitalController (DDC) (PremierLink orRTU Open controller). 2-in. (51 mm) disposable filters onall units. High capacity refrigerant filter drieron each circuit. High pressure switch, loss of chargeswitch and freeze protection addsgreater unit reliability.

Model number nomenclature50KCQ*04-06 MODEL NUMBER NOMENCLATURE1234567891050KCQA04A011 12 13A5-14015 16 17 18A0APackaging and Seismic Compliant0 Standard1 LTLUnit/Series Model50KC – Packaged 14 SEERRooftopElectrical OptionsA NoneC Non-Fused DisconnectD Thru-the-Base ConnectionsF Non-Fused Disconnect and Thru-the-Base ConnectionsQ Heat PumpService Options0 None1 Unpowered Convenience Outlet2 Powered Convenience Outlet3 Hinged Panels4 Hinged Panels, Unpowered Convenience Outlet5 Hinged Panels, Powered Convenience OutletRefrig. Systems OptionsA – Standard One-Stage Cooling ModelsCooling Tons04 – 3 ton05 – 4 ton06 – 5 tonSensor OptionsA NoneB RA Smoke DetectorC SA Smoke DetectorD RA SA Smoke DetectorE CO F RA Smoke Detector and CO G SA Smoke Detector and CO H RA SA Smoke Detector and CO J Condensate Overflow Switch (electromech controls only)K Condensate Overflow Switch and RA Smoke DetectorsL Condensate Overflow Switch and RA and SA SmokeDetectorsIndoor Fan Options0 Direct Drive X13 Motor2 Medium Static Option – Belt Drive3 High Static Option – Belt DriveNote: On single phase (-3 voltage code) models, the followingare not available as a factory installed option:- Coated Coils or Cu Fin Coils- Louvered Hail Guards- Economizer or 2 Position Damper- Powered 115 Volt Convenience Outlet0Intake / Exhaust OptionsA NoneB Temperature Economizer with Barometric ReliefF Enthalpy Economizer with Barometric ReliefK 2-Position DamperU Temp Ultra Low Leak Economizer with Baro ReliefW Enthalpy Ultra Low Leak Econo with Baro ReliefBase unit controls0 Electromechanical Controls can be used with W7212EconoMi er IV (Non-Fault Detection and Diagnostic)1 PremierLink Controller2 RTU Open Multi-Protocol Controller6 Electromechanical – can be used with W7220 EconoMi er X(with Fault Detection and Diagnostic)Design RevisionFactory AssignedVoltage1 575/3/603 208-230/1/605 208-230/3/606 460/3/60Coil Options (Outdoor – Indoor – Hailguard)A Al/Cu – Al/CuB Precoat Al/Cu – Al/CuC E-coat Al/Cu – Al/CuD E-coat Al/Cu – E-coat Al/CuE Cu/Cu – Al/CuF Cu/Cu – Cu/CuM Al/Cu – Al/Cu – Louvered Hail GuardsN Precoat Al/Cu – Al/Cu – Louvered Hail GuardsP E-coat Al/Cu – Al/Cu – Louvered Hail GuardsQ E-coat Al/Cu – E-coat Al/Cu – Louvered Hail GuardsR Cu/Cu – Al/Cu – Louvered Hail GuardsS Cu/Cu – Cu/Cu – Louvered Hail Guards3

Capacity ratingsAHRI RATINGSCOOLING MODENET COOLING CAPACITY(Btuh)35,60049,00058,000NOM. .008.20TOTAL POWER(kW)2.94.04.7HEATING MODEHEATING, LOWCAPACITY (Btuh)17,00027,40027,800LEGENDAHRI— Air Conditioning, Heating and Refrigeration InstituteASHRAE — American Society of Heating, Refrigerating and AirConditioningEER— Energy Efficiency RatioHSPF— Heating Seasonal Performance FactorSEER— Seasonal Energy Efficiency RatioSEEREER14.0014.0014.3012.1012.1012.20HEATING, HIGHCAPACITY (Btuh)34,20048,00053,500NOTES:1. Rated and certified under AHRI Standard 210/240.2. Ratings are based on:Cooling Standard: 80 F (27 C) db, 67 F (19 C) wb indoor air tempand 95 F (35 C) db outdoor air temp.3. All 50KCQ units comply with ASHRAE 90.1 Energy Standard forminimum SEER and EER requirements.MINIMUM — MAXIMUM AIRFLOWS (ELECTRIC 50020002500ELECTRIC HEATERSMINIMUMMAXIMUM90015001200200015002500SOUND 7.712569.069.666.6OUTDOOR SOUND LEGENDdB — DecibelNOTES:1. Outdoor sound data is measured in accordance with AHRI standard 270.2. Measurements are expressed in terms of sound power. Do notcompare these values to sound pressure values because 62.6pressure accounts for specific environmental factors which do notmatch individual applications. Sound power values are independent of the environment and therefore more accurate.3. A-weighted sound ratings filter out very high and very low frequencies, to better approximate the response of an “average” humanear. A-weighted measurements for Carrier units are taken inaccordance with AHRI standard 270.

Physical dataPHYSICAL DATA (COOLING) 3 TO 5 TONS50KCQA0450KCQA0550KCQA061 / 1 / Scroll14 - 8 / 25 / Accutrol Accurater630 / 50527 / 441 / 1 / Scroll18 - 0 / 42 / Accutrol Accurater630 / 50527 / 441 / 1 / Scroll19 - 8 / 42 / Accutrol Accurater630 / 50527 / 44REFRIGERATION SYSTEM# Circuits / # Comp. / TypeR-410A charge A/B (lbs - oz)oil A/B (oz)Metering deviceHigh-press. Trip / Reset (psig)Loss of charge press. Trip / Reset (psig)EVAP. COILMaterialCoil typeRows / FPITotal face area (ft2)Condensate drain conn. size3/Cu / AlRTPF3 / 155.53/ -in.48-in.3/Cu / AlRTPF3 / 157.33/ -in.48-in.3/Cu / AlRTPF4/ 157.33/ -in.48-in.EVAP. FAN AND MOTORSTANDARDSTATIC1 PHASESTANDARDSTATIC3 PHASEMEDIUMSTATIC3 PHASEHIGHSTATIC3 PHASEMotor qty / Drive typeMax BHPRPM rangeMotor frame sizeFan qty / TypeFan diameter x length (in.)Motor qty / Drive typeMax BHPRPM rangeMotor frame sizeFan qty / TypeFan diameter x length (in.)Motor qty / Drive typeMax BHPRPM rangeMotor frame sizeFan qty / TypeFan diameter x length (in.)Motor qty / Drive typeMax BHPRPM rangeMotor frame sizeFan qty / TypeFan diameter x length (in.)1 / Direct1600-1200481 / Centrifugal10 x 101 / Direct1600-1200481 / Centrifugal10 x 101 / Belt1.5819-1251561 / Centrifugal10 x 101 / Belt2.01035-1466561 / Centrifugal10 x 101 / Direct1600-1200481 / Centrifugal10 x 101 / Direct1600-1200481 / Centrifugal10 x 101 / Belt1.5920-1303561 / Centrifugal10 x 101 / Belt2.01035-1466561 / Centrifugal10 x 101 / Direct1600-1200481 / Centrifugal11 x 101 / Direct1600-1200481 / Centrifugal11 x 101 / Belt2.01066-1380561 / Centrifugal10 x 101 / Belt2.91208-1550561 / Centrifugal10 x 10COND. COILMaterialCoil typeRows / FPITotal face area (ft2)3/Cu / AlRTPF2 / 1716.58-in.3/Cu / AlRTPF2 / 1721.38-in.3/Cu / AlRTPF2 / 1721.38-in.COND. FAN / MOTORQty / Motor drive typeMotor HP / RPMFan diameter (in.)1 / direct1/ / 8258221 / direct4 / 1100221/1 / direct4 / 1100221/FILTERSRA Filter # / size (in.)OA inlet screen # / size (in.)2 / 16 x 25 x 21 / 20 x 24 x 14 / 16 x 16 x 21 / 20 x 24 x 14 / 16 x 16 x 21 / 20 x 24 x 15

Options and accessoriesFACTORY-INSTALLED OPTIONS AND FIELD-INSTALLED ACCESSORIESCATEGORYCabinetCoil OptionsCondenser ProtectionControlsEconomizersand Outdoor AirDampersEconomizerSensors andIAQ DevicesElectric HeatIndoor Motor and DriveLow AmbientControlPowerOptionsRoof CurbsITEMThru-the-base electrical connectionsHinged Access PanelsCu/Cu indoor and/or outdoor coils1Pre-coated outdoor coils1Premium, E-coated outdoor coils1Condenser coil hail guard (louvered design)1Thermostats, temperature sensors, and subbasesPremierLink DDC communicating controllerRTU Open protocol controllerSmoke detector (supply and/or return air)Time Guard II compressor delay control circuitPhase MonitorEconoMi er IV (for electro-mechanical controlled - Non FDD (Low Leak airdamper models)1,2EconoMi er2 for DDC controls, complies with FDD (Low Leak and Ultra LowLeak air damper models)1,3Motorized 2 position outdoor-air damper1Manual outdoor-air damper (25% and 50%)Barometric relief4Power exhaustEconoMi er X for electro-mechanical controls, complies with FDD (Low Leakand Ultra Low Leak air damper models)1,2Single dry bulb temperature sensors5Differential dry bulb temperature sensors5Single enthalpy sensors5Differential enthalpy sensors5CO2 sensor (wall, duct, or unit mounted)5Electric Resistance HeatersSingle Point KitMultiple motor and drive packagesWinter start kit6Motormaster head pressure controller6Convenience outlet (powered)1Convenience outlet (unpowered)Non-fused disconnect7Roof curb 14-in. (356 mm)Roof curb 24-in. (610 mm)FACTORYFIELDINSTALLED INSTALLEDOPTION XXXXNOTES:1. Not available as factory installed option on single phase (208/230/1/60) models. Use field-installed accessory where available.2. FDD (Fault Detection and Diagnostic) capability per California Title 24 section 120.2.3. Models with RTU Open DDC controls comply with California Title 24 Fault Detection and Diagnostic (FDD). PremierLink controls are non FDDcompatible.4. Included with economizer.5. Sensors for optimizing economizer.6. See application data for assistance.7. Available on units with MOCPs of 80 amps or less.6

Factory-installed optionsEconomizer (dry bulb or enthalpy)Economizers save money. They bring in fresh, outside airfor ventilation; and provide cool, outside air to cool yourbuilding. This is the preferred method of low ambient cooling. When coupled to CO2 sensors, Economizers can provide even more savings by coupling the ventilation air toonly that amount required.Economizers are available, installed and tested by the factory, with either enthalpy or dry bulb temperature inputs.There are also models for electromechanical as well asdirect digital controllers. Additional sensors are available asaccessories to optimize the economizers.Economizers include gravity-controlled barometric reliefwhich equalizes building pressure and ambient air pressures. This can be a cost effective solution to prevent building pressurization.CO2 SensorImproves productivity and saves money by working withthe economizer to intake only the correct amount of outside air for ventilation. As occupants fill your building, theCO2 sensor detects their presence through increasing CO2levels, and opens the economizer appropriately.When the occupants leave, the CO2 levels decrease, andthe sensor appropriately closes the economizer. This intelligent control of the ventilation air, called Demand Controlled Ventilation (DCV), reduces the overall load on therooftop, saving money.Smoke DetectorsTrust the experts. Smoke detectors make your applicationsafer and your job easier. Carrier smoke detectors immediately shut down the rooftop unit when smoke is detected.They are available, installed by the factory, for supply air,return air, or both.Louvered Hail GuardsSleek, louvered panels protect the condenser coil from haildamage, foreign objects, and incidental contact.Convenience Outlet (powered or un-powered)Lower service bills by including a convenience outlet inyour specification. Carrier will install this service feature atour factory, powered. Provides a convenient 15 amp,115V GFCI receptacle.Non-fused DisconnectThis OSHA-compliant, factory-installed, safety switchallows a service technician to locally secure power to therooftop.Motorized 2-Position DamperThe new Carrier 2-position, motorized outdoor air damperadmits up to 100% outside air. Using reliable, gear-driventechnology, the 2-position damper opens to allow ventilation air and closes when the rooftop stops, stoppingunwanted infiltration.PremierLink This CCN controller regulates your rooftop’s performanceto tighter tolerances and expanded limits, as well as facilitates zoning systems and digital accessories. It also unitesyour Carrier HVAC equipment together on one, coherentCCN network. The PremierLink can be factory-installed,or easily field-installed.RTU Open, Multi-protocol ControllerConnect the rooftop to an existing BAS without needingcomplicated translators or adapter modules using the RTUOpen controller. This new controller speaks the 4 mostcommon building automation system languages (BACnet1,Modbus2, N2, and Lonworks3). Use this controller whenyou have an existing BAS.Alternate Motors and DrivesSome applications need larger horsepower motors, someneed more airflow, and some need both. Regardless of thecase, your Carrier expert has a factory installed combination to meet your application. A wide selection of motorsand pulleys (drives) are available, factory installed, to handle nearly any application.Thru-the-Base ConnectionsThru-the-base connections, available as either an accessoryor as a factory option, are necessary to ensure proper connection and seal when routing wire and piping through therooftop’s basepan and curb. These couplings eliminateroof penetration and should be considered for gas lines,main power lines, as well as control power.Field-installed accessoriesPower Exhaust Pressure ReliefSuperior internal building pressure control. This fieldinstalled accessory may eliminate the need for costly, external pressure control fans.Time Guard II Control CircuitThis accessory protects your compressor by preventingshort-cycling in the event of some other failure, preventsthe compressor from restarting for 30 seconds after stopping. Not required with PremierLink, RTU Open, orauthorized commercial thermostats.Filter or Fan Status SwitchesUse these differential pressure switches to detect a filterclog or indoor fan motor failure. When used in conjunctionwith a compatible unit controller/thermostat, the switcheswill activate an alarm to warn the appropriate personnel.Manual OA DamperManual outdoor air dampers are an economical way tobring in ventilation air. The dampers are available in 25%and 50% versions.Motormaster Head Pressure ControllerThe Motormaster motor controller is a low ambient, headpressure controller kit that is designed to maintain theunit’s condenser head pressure during periods of low ambient cooling operation. This device should be used as analternative to economizer free cooling not when economizer usage is either not appropriate or desired. TheMotormaster will either cycle the outdoor fan motors oroperate them at reduced speed to maintain the unit operation, depending on the model.Electric HeatersCarrier offers a full line of field-installed accessory heaters.The heaters are very easy to use and install. All are preengineered and certified.1. BACnet is a registered trademark of ASHRAE (American Society ofHeating, Refrigerating, and Air-Conditioning Engineers).2. Modbus is a registered trademark of Schneider Electric.3. LonWorks is a registered trademark of Echelon Corporation.7

Options and accessoriesOPTION / ACCESSORY WEIGHTSOPTION / ACCESSORYPower Exhaust (vertical)Power Exhaust (horizontal)EconoMi er (IV, X or 2)Two Position DamperManual DampersHail Guard (louvered)Cu/Cu Condenser Coil1Cu/Cu Condenser and Evaporator Coils1Roof Curb (14-in. curb)Roof Curb (24-in. curb)CO2 sensorElectric HeaterSingle Point KitOptional Indoor Motor/DriveMotormaster ControllerReturn Smoke DetectorSupply Smoke DetectorNon-Fused DisconnectPowered Convenience OutletNon-Powered Convenience OutletEnthalpy SensorDifferential Enthalpy 552197892110510563351673731573616422131NOTE: Where multiple variations are available, the heaviest combination is listed.1Where available.8OPTION / ACCESSORY 15715736163616424221213131

50KCQ*04-06 UNITS BUILT ON AND AFTER 4/15/2019Dimensions9

50KCQ*04-06 UNITS BUILT PRIOR TO 4/15/2019Dimensions (cont)10

1150KCQ*04-06 CORNER WEIGHTS AND CLEARANCES

50KCQ*04-06 BASE RAIL DETAILSDimensions (cont)12

1350KCQ*04-06 THRU-THE-BASE CHARTS

144 355.6]15.19"[385.8]4.96"[126.0]21.74"[552.2]SUPPLY AIR20.41"[518.3]40.69"[1033.5]SUPPLY [356]ROOF CURBACCESSORY #RETURN AIR3.00"[76.2]13.78"[350.0]16.03"[407.2]ERETURN AIROPENINGE32.19"[817.6]70.87"[1800.2]REVAREVISION RECORD"A"DATE04/22/13BYMMCROOFING MATERIAL(FIELD SUPPLIED)CANT STRIP(FIELD SUPPLIED)ROOFING FELT(FIELD SUPPLIED)COUNTER FLASHING(FIELD SUPPLIED)TYPICAL (4) SIDESCHK'D-"A"APP'D-8 9/16"[217.5] WIDEINSULATED DECK PANELSUPPLY AIRECN NO.1067898-SURFACE FINISHPURCHMFG/PURCHT-005, Y-002WEIGHT:1-3/4"[44.5]RETURN AIR1' 4-13/16"[427] INSIDE3/4" [19] NPTPOWER WIRINGFITTING-3 DEC- --ANGMODEL (INTERNAL USE ONLY)CHECKER--CURB ASY, ROOF-N/ASCALEBREVMMCDISTRIBUTIONSHEET 5 OF 548TC4004271-3/4"[44.4]SEE NOTE #21/2" [12.7] NPTACCESSORY CONVENIENCEOUTLET WIRING CONNECTORDRAWING NUMBERNEXT DRAWINGDSIZETITLE5' 7-3/8"[1711.3]2-3/8"[61]1/2" [12.7] NPTCONTROL WIRINGFITTINGMANUFACTURING104173806/17/11 -DRAFTERMMC--2 DECAUTHORIZATION NUMBERENGINEERING-1 DECUNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHESTOLERANCES ON:PRODUCTIONCERTIFIED DRAWINGENGINEERING REQUIREMENTS-MATERIALTHIRD ANGLEPROJECTIONDRAWING RELEASE LEVEL:SEE VIEW "B"3'-1 3/16"[944.6]1/2" [12.7] NPT3/4" [19] NPTGAS FITTING11 3/4"[298.5] WIDEINSULATED DECK PANELSTHRU THE BOTTOMTHRU THE CURBGAS CONNECTION TYPEGAS SERVICE PLATETHRU THE CURBDRILL HOLE2" [50.8] @ASSEMBLY (IFREQUIRED)(SEE NOTE #8)1.00"[25.4]1-3/4"[44.4]E-ESECTIONSCALE CTOR PKG. ACC.NAIL (FIELD SUPPLIED)RIGID INSULATION(FIELD SUPPLIED)7/16"[11]UNITOVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GAMATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WASWITH CURBDUCT(FIELD SUPPLIED)GASKET(SUPPLIED WITH CURB)CORNER DETAILVIEW "B"NOTES:1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.4. ROOFCURB: 18 GAGE STEEL.5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.7.DIRECTION OF AIR FLOW.8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPEPACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.50KCQ*04-06 ROOF CURB DIMENSIONSDimensions (cont)

Performance data50KCQA04 1-STAGE COOLING CAPACITIES (3 .442.516.2——85EAT LEGEND—— Do not operate in this region (Points are outside SST andSDT permissible operating range)CFM— Cubic Feet Per Minute (supply air)EAT (db) — Entering Air Temperature (dry bulb)EAT (wb) — Entering Air Temperature (wet bulb)AMBIENT TEMPERATURE ( F)95105EAT (db)EAT ��115EAT 37.821.8— Sensible Heat Capacity (1000 Btuh)— Total Capacity (1000 Btuh)15

Performance data (cont)50KCQA05 1-STAGE COOLING CAPACITIES (4 0.953.121.0——85EAT LEGEND—— Do not operate in this region (Points are outside SST andSDT permissible operating range)CFM— Cubic Feet Per Minute (supply air)EAT (db) — Entering Air Temperature (dry bulb)EAT (wb) — Entering Air Temperature (wet bulb)16AMBIENT TEMPERATURE ( F)95105EAT (db)EAT ��— Sensible Heat Capacity (1000 Btuh)— Total Capacity (1000 Btuh)115EAT 51.030.4

50KCQA06 1-STAGE COOLING CAPACITIES (5 0.670.728.2——85EAT 69.938.873.529.560.66

heating and heating to cooling. † Easy-adjust, belt drive motor avail-able on all sizes. There's no need for field-supplied drives or motors. . Metering device Accutrol Accurater Accutrol Accurater Accutrol Accurater High-press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 Loss of charge press. Trip / Reset (psig) 27 / 44 27 / .

Related Documents:

Single circuit, 2-stage cooling mod-els are available from 7.5 to 10 ton. Dual circuit 2-stage cooling stage models are available from 7.5 to 15 ton. EERs up to 11.1 with IEERs up to 12.8 Staged Air Volume (SAV ) 2-speed indoor fan motor system automati-cally adjusts the indoor fan motor speed between cooling stages. Stan-

CA Packaged Metering Manhole, 2014-2015 ORD-167/1: South Placer PUD - CA Rocklin: CA Packaged Metering Manhole, 2014-2015 ORD-88/1: Sunset Avenue Reconstruction - CA Eureka: CA Packaged Metering Manhole, 2014-2015 ORD-1561/1: Eden Valley Institure WTF - Larimer County Loveland: CO Packaged

Single Packaged Heat Pump, Single Phase The Q6 Series single packaged heat pumps are high efficiency self contained cooling and heating units that can be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed. FEATURES and BENEFITS TECHNICAL SPECIFICATIONS

Packaged Rooftop Air Conditioners Voyager Cooling and Gas/Electric 12½–25 Tons, 60 Hz . Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro— . † Manual Outside Air Dampers .

Standard COOLER Air Cooled Packaged Liquid Chillers have the following characteristics: CAPC Models: from 30 up to 502 Ton (from 87,000 up to 1,500,000 Kcal) All Units can be custom tailored on request The COOLER Air Cooled Packaged Liquid Chillers is a packaged unit completely factory assembled on a stiff steel structure with

False Economy: An Analysis of Packaged Equipment Economizer Systems False Economy: An Analysis of Packaged Equipment Economizer Systems Summary Economizers don't work very well, especially in competitively-priced packaged HVAC units. This is important, because these types of units are applied in a majo

COMPARATIVE LIST OF REQUIREMENTS OF PDW AND PNMW 77 11. LIST OF TEST EQUIPMENTS 79 . 3 SECTION 1 FOREWORD BIS has published two Indian Standards for Packaged Drinking Water namely IS 13428 for Packaged Natural Mineral Water and IS 14543 for Packaged Drinking Water (Other Than Packaged Natural Mineral Water). .

However, the machining of these typically difficult-to-cut materials poses a challenge for conventional manufacturing technologies due to the high tool wear. Abrasive water jet (AWJ) machining is a promising alternative manufacturing technology for machining difficult-to-cut materials,