PV Grid Tie InverterSolis 4G Single Phase InverterInstallation and Operation ManualSolis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P2.5K-4G,Solis-1P3K-4G, Solis-1P3.6K-4G, 1P6K2-4GNingbo Ginlong Technologies Co., Ltd.No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,Zhejiang, 315712, P.R.China.Tel: 86 (0)574 6578 1806Fax: 86 (0)574 6578 1606If you encounter any problem on the inverter, please find out the inverter S/Nand contact us, we will try to respond to your question ASAP.CNingbo Ginlong Technologies Co., Ltd.Ver 1.8

Contents1. Introduction 1.1 Product Description 1.2 Packaging 2. Safety Instructions 2.1 Safety Symbols 2.2 General Safety Instructions 2.3 Notice For Use 3. Overview 3.1 Front Panel Display 3.2 LED Status Indicator Lights 3.3 Keypad 3.4 LCD 4. Installation 4.1 Select Location for the Inverter 4.2 Mounting the Inverter 4.3 Electrical Connections 4.3.1 Connect PV side of inverter 4.3.2 Connect grid side of inverter 4.3.3 External ground connection 4.3.4 Max. overcurrent protection device (OCPD) 4.3.5 Inverter monitoring connection 4.3.6 Electrical connection diagram 4.3.7 Meter Connection(optional) 4.3.8 CT connections(optional) 4.3.9 DRED port connections(Only for AUS.) 334555677788991113131618191920202121 5.1 Start the Inverter 5.2 Stop the Inverter 6. Operation 6.1 Main Menu 6.2 Information 6.2.1 Lock screen 232323242424265. Start & Stop

1. IntroductionContents 6.3.1 Set Time 6.3.2 Set Address 6.4 Advanced Info. 6.4.1 Alarm Message 6.4.2 Running Message 6.4.3 Version 6.4.4 Daily Energy 6.4.5 Monthly Energy and Yearly Energy 6.4.6 Daily Record 6.4.7 Communication Data 6.4.8 Warning Message 6.5 Advanced Settings 6.5.1 Select Standard 6.5.2 Grid ON/OFF 6.5.3 Clear Energy 6.5.4 Reset Password 6.5.5 Power Control 6.5.6 Calibrate Energy 6.5.7 Special Settings 6.5.8 STD. Mode Settings 6.5.9 Restore Settings 6.5.10 HMI Update 6.5.11 Export Power Set 6.5.12 Restart HMI 6.5.13 Debug Parameter 6.5.14 DSP Update 6.5.15 Power Parameter 7. Maintenance 8. Troubleshooting 9. Specifications 6.3 343434383838383939421.1 Product DescriptionSolis 4G single phase inverters integrate DRM and backflow power control function, thatcould suitable for smart grid requirement.Single phase 4G series inverter contain 10 models which are listed below:Solis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P2.5K-4G,Solis-1P3K-4G, Solis-1P3.6K-4G, Solis-1P4K-4G,Solis-1P4.6K-4G, Solis-1P5K-4G,Solis-1P6K2-4GLED lightsLCD display4 buttonsCT and Meter inputDC Switch(optional)DC inputFigure 1.1 Front side viewRS 485AC outputFigure 1.2 Bottom side view.3.

1. Introduction2.Safety InstructionsImproper use may result in potential electric shock hazards or burns. This manual1.2 Packagingcontains important instructions that should be followed during installation andWhen you receive the inverter, ensure that all the parts listed below are included:maintenance. Please read these instructions carefully before use and keep them forfuture reference.2.1 Safety SymbolsSafety symbols used in this manual, which highlight potential safety risks and importantsafety information, are listed as follows:WARNING:WARNING symbol indicates important safety instructions, which if notcorrectly followed, could result in serious injury or death.2NOTE:43NOTE symbol indicates important safety instructions, which if not correctlyfollowed, could result in some damage or the destruction of the inverter.1PV Grid Tie InverterSolis 4G Single Phase InverterInstallation and Operation ManualSolis-1P1K-4G, Solis-1P1.5K-4G, Solis-1P2K-4G, Solis-1P2.5K-4G,Solis-1P3K-4G, Solis-1P3.6K-4G, 1P6K2-4GCAUTION:CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safetyinstructions, which if not correctly followed, could result in electric shock.CAUTION:CNingbo Ginlong Technologies Co., Ltd.Ver 1.85Part #6Description7Number1PV grid tie inverter12Wall/pole bracket13Locking screwsGrounding screw( attached in g round point241at side of inverter ).4.2.2 General Safety InstructionsWARNING:Only devices in compliance with SELV (EN 69050) may be connected to theRS485 and USB interfaces.WARNING:Please don’t connect PV array positive( ) or negative(-) to ground, it couldcause serious damage to the inverter.5DC connector2 pairs6AC connector17Manual18CT with cable or Meter1Table 1.1 Parts listCAUTION, HOT SURFACE symbol indicates safety instructions, which if notcorrectly followed, could result in burns.WARNING:Electrical installations must be done in accordance with the local and nationalelectrical safety standards.WARNING:Do not touch any inner live parts until 5 minutes after disconnection fromthe utility grid and the PV input.5.

3. Overview2.Safety InstructionsWARNING:To reduce the risk of fire, over-current protective devices (OCPD) arerequired for circuits connected to the Inverter.The DC OCPD shall be installed per local requirements. All photovoltaic sourceand output circuit conductors shall have disconnects that comply with the NECArticle 690, Part II. All Solis single phase inverters feature an integratedDC switch.3.1 Front Panel DisplayCAUTION:Risk of electric shock. Do not remove cover. There is no user serviceableparts inside. Refer servicing to qualified and accredited service technicians.CAUTION:The PV array (Solar panels) supplies a DC voltage when they are exposed tosunlight.CAUTION:Risk of electric shock from energy stored in capacitors of the Inverter. Do notremove cover for 5 minutes after disconnecting all power sources(service technicianonly). Warranty may be voided if the cover is removed without unauthorized .CAUTION:The surface temperature of the inverter can reach up to 75 (167 F).To avoid risk of burns, do not touch the surface of the inverter while it’s operating.Inverter must be installed out of the reach of children.PV module used with inverter must have an IEC 61730 Class A rating.2.3 Notice For UseThe inverter has been constructed according to the applicable safety and technicalguidelines. Use the inverter in installations that meet the following specifications ONLY:Figure 3.1 Front Panel Display3.2 LED Status Indicator LightsThere are three LED status indicator lights in the front panel of the inverter. Left LED:POWER LED (red) indicates the power status of the inverter. Middle LED: OPERATIONLED (green) indicates the operation status. Right LED: ALARM LED (yellow) indicatesthe alarm status. Please see Table 3.1 for detailsLightOPERATIONThe inverter can detect DC powerOFFNo DC power or low DC powerONThe inverter is operating properly.OFFThe inverter has stopped to supply power.FLASHING3.The inverter must be installed according to the instructions stated in this manual.4.The inverter must be installed according to the correct technical specifications.5.To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, beforeONPOWER1.Permanent installation is required.2.The electrical installation must meet all the applicable regulations and standards.DescriptionStatusALARMThe inverter is initializing.ONAlarm or fault condition is detected.OFFThe inverter is operating properly.the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid SupplyMain Switch (AC) must be switched off before the solar panel's DC isolator shall beTable 3.1 Status Indicator Lightsswitched off.6.7.

4. Installation3. Overview3.3 KeypadThere are four keys in the front panel of the Inverter(from left to right):ESC, UP, DOWN and ENTER keys. The keypad is used for:4.1 Select a Location for the InverterTo select a location for the inverter, the following criteria should be considered:Do not install in small closed spaces where air can not circulate freely. To avoidoverheating, always make sure the flow of air around the inverter is not blocked.Scrolling through the displayed options (the UP and DOWN keys);Access to modify the adjustable settings (the ESC and ENTER keys).Exposure to direct sunlight will increase the operational temperature of the inverter andmay cause output power limiting. Ginlong recommends inverter installed to avoiddirect sunlight or raining.3.4 LCDThe two-line Liquid Crystal Display (LCD) is located on the front panel of the Inverter,To avoid over heating ambient air temperature must be considered when choosing theinverter installation location. Ginlong recommends using a sun shade minimizing directsunlight when the ambient air temperature around the unit exceeds 104 F/40 C.which shows the following information:Inverter operation status and data;Service messages for operator;Alarm messages and fault indications.Figure 4.1 Recommended Installation locations.8.9.

4. Installation4. Installation4.2 Mounting the InverterInstall vertically with a maximum incline of /- 5 .If the mounted inverter is tilted to anDimensions of wall bracket:angle greater than the maximum noted, heat dissipation can be inhibited, and may resultin less than expected output power.When 1 or more inverters are installed in one location, a minimum 12inchs clearanceshould be kept between each inverter or other object. The bottom of the inverter should300mm300mmbe 20inchs clearance to the ground.Figure 4.3 Inverter wall mounting300mm300mm300mmPlease see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter.The inverter shall be mounted vertically. The steps to mount the inverter are listed below:1. According to the figure 4.2, select the mounting height of the bracket and mark the300mm300mmmounting holes. For brick walls, the position of the holes should be suitable for theexpansion bolts.BracketFigure 4.2 Inverter Mounting clearanceVisibility of the LED status indicator lights and the LCD located at the front panel ofthe inverter should be considered.Adequate ventilation must be provided if the inverter is to be installed in a confined space.NOTE:Nothing should be stored on or placed against the inverter.Suitable fixing screwsFigure 4.4 Inverter wall mounting.10.11.

4. Installation4. Installation4.3 Electrical Connections2.Make sure the bracket is horizontal and the mounting holes (in Figure 4.4 )4.3.1 Connect PV side of inverterare marked correctly. Drill the holes into the wall or pillar at your marks.3.Use the suitable screws to fix the bracket to the wall.The electrical connection of the inverter must follow the steps listed below:1. Switch the Grid Supply Main Switch (AC) OFF.WARNING:The inverter must be mounted vertically.2. Switch the DC Isolator OFF.3. Assemble PV input connector to the Inverter.4.Lift up the inverter (be careful to avoid body strain), and align the back bracket on theinverter with the convex section of the mounting bracket. Hang the inverter on themounting bracket and make sure the inverter is secure (see Figure 4.5).Before connecting inverter, please make sure the PV array open circuit voltage iswithin the limit of the inverterMaximum 550Voc forSolis-1P1K-4G Solis-1P1.5K-4GSolis-1P2K-4G Solis-1P2.5K-4GMaximum 600Voc forLocking screwsSolis-1P3K-4G Solis-1P3.6K-4G Solis-1P4K-4GSolis-1P4.6K-4G Solis-1P5K-4G Solis-1P6K2-4GPlease don’t connect PV array positive or negative pole to the ground, it couldcause serious damages to the inverter.Before connection, please make sure the polarity of the output voltage of PV arraymatches the“DC ”and “DC-”symbols.Figure 4.5 Wall Mount Bracket5. Use M4*9 screws in accessory to lock the inverter to the mount bracket.Figure 4.6 DC Connector.12.Figure 4.7 DC- Connector.13.

4. Installation4. InstallationPlease use approved DC cable for PV system.Cable typeIndustry generic PV cable(model:PV1-F)iii) Crimp the contact pin to the wire using a proper wire crimper.Cross sectionRangeRecommendedvalue4.0 6.04.0(12AWG)(12 10AWG)Table 4.1 DC cableFigure 4.10 Crimp the contact pin to the wireThe steps to assemble the DC connectors are listed as follows:I) Strip off the DC wire for about 7mm, Disassemble the connector cap nut.iv) Insert the contact pin to the top part of the connector and screw up the cap nut tothe top part of the connector.Figure 4.8 Disassemble the Connector Cap nutFigure 4.11 Connector with Cap nut Screwed onii) Insert the wire into the connector cap nut and contact pin.v) Then connect the DC connectors to the inverter. Small click will confirm connection.Figure 4.12 Connect the DC Connectors to the InverterFigure 4.9 Insert the Wire into the Connector Cap nut and contact pin.14.15.

4. Installation4. Installation4.3.2 Connect grid side of inverterFor all AC connections, 2.5- 6mm 2 105 cable is required to be used. Please make surethe resistance of cable is lower than 1 ohm. If the wire is longer than 20m, it's recommendedto use 6mm 2 cable.The steps to assemble the AC grid terminal connectors are listed as follows:a) Disassemble the AC connector. Strip the AC wires about 6mm.WARNING:There aresymbols marked inside the connector , the Linewire of grid must be connected to“L”terminal; the Neutral wireof grid mustbe connected to“N”terminal; the Earth of grid must be connectedto“ ”(see Figure 4.13).Cable typeIndustry genericgrid cableCross sectionRangeRecommendedvalue2.5 6.0mm²6mm²Figure 4.15 Stripped AC Wiresb) Fix the green and yellow wire to the ground terminal. Fix the red(or brown) wire to LTable 4.2 Grid cable size(line) terminal. Fix the blue wire to N(Neutral). Tight the screws on the connector.Please try to pull out the wire to make sure the it’s well connected.Figure 4.13 AC Grid Terminal Connector InsideFigure 4.16 Connect Wires to the TerminalEach Solis Mini Single Phase Inverter is supplied with an AC grid terminal connector.c) Tighten up the cap on the terminal (see Figure 4.17).Figure 4.14 AC Grid Terminal Connector.16.Figure 4.17 Tighten up the Cap on the Terminal.17.

4. Installation4. Installation4.3.4 Max. over current protection device (OCPD)d) Connect the AC grid terminal connector to the inverter. Small click will confirmconnection.Figure 4.18 Connect the AC Connector to the InverterNote: Connection for Split phase grid.When connect to 208/220/240V split phase, please connect L1 to “L” terminal,L2 to “N” terminal. Also connect earth to ground terminal.4.3.3 External ground connectionAn external ground connection is provided at the right side of inverter.To protect the inverter's AC grid connection conductors, Solis recommends installingbreakers that will protect against overcurrent. The following table defines OCPDratings for the Solis 1-6kW single phase inverters.InverterRatedvoltage(V)Rated outputcurrent (A)Current for protectiondevice s-1P6K2-4G220V/230V27.340Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal.Connect the OT terminal with ground cable to the right side of inverter. The torque is20 in-lbs (2Nm).Table 4.3 Rating of grid OCPD4.3.5 Inverter monitoring connectionThe inverter can be monitored via Wi-Fi or GPRS. All Solis communicationdevices are optional (Figure 4.20). For connection instructions, please refer to theSolis Monitoring Device installation manuals.Smart phone monitoringGPRS monitoringInternetRouterWeb serverWi-Fi monitoringPC monitoringWi-Fi boxWi-Fi monitoringFigure4.19 Connect the external grounding conductor.18.Figure4.20 Wi-Fi or GPRS communication function.19.

4. Installation4. InstallationCommunication4.3.6 Electrical connection diagram5 6 7 8A BRefer to figure 4.21, which is a simple guidance for installing a solar system with PV inverter.A DC isolator is required to be installed in the system between PV panels with inverter.MAIN SWITCHBOARD1Isolation device1T1T2T31600 imp/kWhMENUL L N N Solar supplymain switchMainswitchConsumersmains(to grid)DDSD1352220V 10(60)A1Inverter withintegral gridProtection deviceLoadSolar(PV)arrayGrid2Figure 4.23 Meter in Grid4.3.8 CT connections(optional)Isolation switchThis inverter has integrated export limitation functionality. To use this function, a powermeter or a CT must be installed , if use the CT, please reference below picture. The CTshould be fitted around the live conductor on the grid side of the main incoming consumerunit. Use the directional flow indication arrow on the CT to ensure it is fitted in the correctorientation. The arrow should be pointing towards the grid, not the load. when the inverterpower on, please set the corresponding configuration as sections 6.5.11.1.4.1 and 6.5.11.1.4.2.Circuits not Circuits Protectedprotected byby RCDsRCDsFigure 4.21 Guidance for a Simple Installation of an Inverter Solar Energy SystemN1. The RCD should be in parallel connection between the consumers mains and the solar supply.2. More than one RCD may be used. Each RCD can protect one or more circuits.L4.3.7 Meter Connection(optional)CTThe inverter has intergrated export limitation functionality.To use this function , a power meter or a CT must be installed , if use the power meter, it shouldbe installed in the load side or in the grid side , see Figure 4.22 and 4.23. After the inverterpower on , please set the corresponding configuration as sections 6.5.11.1.2 and 6.5.11.1.3.Figure 4.24 Direction of CT4.3.9 DRED port connections(Only for Australia)CommunicationDRED means demand response enable device. The AS/NZS 4777.2 :2015 required inverterneed to support demand response mode(DRM). This function is for inverter that comply withAS/NZS 4777.2 :2015 standard. Solis 4G single phase inverter is fully comply with all DRM.A RJ45 terminal is used for DRM connection.5 6 7 8A BDDSD1352220V 10(60)A1T1T2T31600 imp/kWhMENUL L N N LoadFigure 4.22 Meter in Load.20.GridPinAssignment for inverters capableof both charging and dischargingPinAssignment for inverters capableof both charging and discharging1DRM 1/55RefGen2DRM 2/66Com/DRM03DRM 3/77V 4DRM 4/88V.21.

4. Installation5. Start & Stop5.1 Start the InverterNOTE:Solis 4G inverter is designed to provide 12V power for DRED.To start up the Inverter, it is important that the following steps are strictly followed:1. Switch the grid supply main Switch (AC) ON first.Please follow below steps to assemble RJ45 connector.1.Insert the network cable into the communication connection terminal of RJ45.(As shown in figure 4.25)2. Switch the DC switch ON. If the voltage of PV arrays are higher than start up voltage,the inverter will turn on. The red LED power will light.3. When both the DC and the AC sides supply to the inverter, it will be ready to generatepower. Initially, the inverter will check both its internal parameters and the parametersof the AC grid, to ensure that they are within the acceptable limits. At the same time,the green LED will flash and the LCD displays the information of INITIALIZING.Figure 4.25 RJ45 communication connection terminals4. After 30-300 seconds (depending on local requirement), the inverter will start togenerate power. The green LED will be on continually and the LCD displays2.Use the network wire stripper to strip the insulation layer of the communication cable.According to the standard line sequence of figure 4.26 connect the wire to the plug ofRJ45, and then use a network cable crimping tool to make it tight.GENERATING.WARNING:Do not touch the surface when the inverter is operating. It may behot and cause burns.5.1.1 Inverter working statusRj45 plug1--8Rj45terminal12345678Correspondence between thecable s and the stitch es of plugPin 1: white and orange ; Pin 2: orange12345678Pin 3: white and green; Pin 4: bluePin 5: white and blue; Pin 6: greenPin 7: white and brown; Pin 8: brownWhen inverter working normally,there would be 5 status :Generating:Inverter is working normallyLimByTemp: Inverter power limited by over ambient temperature.LimByFreq: Inverter power limited by over grid frequencyLimByVg: Inverter power limited by over grid voltageLimByVar: Inverter power limited by generating reactive power.5.2 Stop the InverterFigure 4.26 Strip the insulation layer and connect to RJ45 plug3.Connect RJ45 to DRM port.To stop the Inverter, the following steps must be strictly followed:1. Switch the Supply Main Switch (AC) OFF.2. Wait 30 seconds. Switch the DC Switch OFF. All the LEDs of the inverter will be off in oneminute.During normal operation, the display alternately shows the power and the operationstatus with each screen lasting for 10 seconds (see Figure 6.1). Screens can also bescrolled manually by pressing the UP and DOWN keys. Press the ENTER key toaccess to the Main Menu.22.23.

6. Operation6. OperationPressing theESC keycalls back theprevious menu.Power3424W01-01-2014 12:04Main MenuDisplayDurationV DC1 350.8VI DC15.1A10 secV DC2 350.8VI DC25.1A10 secDescriptionV DC1: Shows input 01 voltage value.I DC1: Shows input 01 current value.InformationUP/DOWNV DC2: Shows input 02 voltage value.I DC2: Shows input 02 current value.Settings5 secUP/DOWN orauto-scroll(10 sec)StartUP/DOWNAdvanced Info.Status: Generating01-01-2014 12:04Pressing theENTER keygives access tothe main menu.10 secStatus: GeneratingPower: 1488W10 secGrid FrequencyF Grid 60.06Hz10 secF Grid: Shows the grid's frequency value.Total Energy0258458 kwh10 secTotal generated energy valueThis Month: 0123kwhLast Month: 0123kwh10 secToday:15.1kwhYesterday: 13.5kwh10 secUP/DOWNAdvanced settingsFigure 6.1 Operation Overview6.1 Main MenuThere are four submenus in the Main Menu (see Figure 6.1):1. InformationInverter SN0000000000000010 secExport P:Export I: 0000W00.0A10 secWork Mode:NULLDRM Number:0810 sec2. Settings3. Advanced Info.4. Advanced Settings6.2 InformationMeter EnergyPThe Solis Single Phase 4G Inverter main menu provides access to operational data andV Grid: Shows the grid's voltage valueV Grid 230.4VI Grid8.1A0000000.00k Wh10 secI Grid: Shows the grid's current value.Status: Shows instant status of the Inverter.Power: Shows instant output power value.This Month: Total energy generated this month.Last Month: Total energy generated last month.Today: Total energy generated today.Yesterday: Total energy generated yesterday.Display series number of the inverter.Power of ERM.Current of EPM.Work Mode:The work mode of inverter.DRM Number:Show the number 01-08.Meter EnergyP:The active power.information. The information is displayed by selecting "Information" from the menuand then by scrolling up or down.24.Table 6.1 Information list.25.

6. Operation6. Operation6.2.1 Lock screenYES ENT NO ESC Set Address: 01Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks(Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen.Figure 6.4 Set AddressPress the UP/DOWN keys to set the address. Press the ENTER key to save the settings.Press the ESC key to cancel the change and return to the previous menu.5.2 Stop the Inverter (a)(b)Figure 6.2 Locks and Unlocks the Screen of LCD6.4 Advanced Info - Technicians OnlyNOTE:To access to this area is for fully qualified and accredited technicians only.Enter menu “Advanced Info.” and “Advanced settings” (need password).6.3 SettingsThe following submenus are displayed when the Settings menu is selected:1.Set TimeSelect “Advanced Info.” from the Main Menu. The screen will require the password as below2.Set AddressYES ENT NO ESC Password:00006.3.1 Set TimeFigure 6.5 Enter passwordThis function allows time and date setting. When this function is selected, the LCD willdisplay a screen as shown in Figure 6.3.The default password is “0010". Please press “down” to move the cursor, press “up” toselect the number.NEXT ENT OK ESC 01-01-2016 16:37After enter the correct password the Main Menu will display a screen and be able to accessto the following information.Figure 6.3 Set TimePress the UP/DOWN keys to set time and data. Press the ENTER key to move from onedigit to the next (from left to right). Press the ESC key to save the settings and return tothe previous menu.6.3.2 Set AddressThis function is used to set the address when muti inverters are connected to single monitor.1.Alarm Message 2. Running Message 3.Version 4. Daily Energy 5. Monthly Energy6. Yearly Energy 7. Daily Record 8.Communication Data 9.Warning MessageThe screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTERkey gives access to a submenu. Press the ESC key to return to the Main Menu.6.4.1 Alarm MessageThe display shows the 100 latest alarm messages (see Figure 6.6). Screens can be scrolledThe address number can be assigned from “01”to “99”(see Figure 6.4). The default addressmanually by pressing the UP/ DOWN keys. Press the ESC key to return to the previousnumber of Solis Single Phase Inverter is “01”.menu.Alarm001: OV-G-VTime: 27-11 Data: 7171Figure 6.6 Alarm Message.26.27.

6. Operation6. OperationPress DOWN key to move the cursor, press UP key to change the digit.6.4.2 Running MessageThis function is for maintaince person to get running message such as internal temperature,Press Enter after the month/year is fixed.2015-02: 0510kWh2015-01: 0610kWhStandard NO. etc.Screens can be scrolled manually by pressing the UP/DOWN keys.2015: 0017513kWh2014: 0165879kWhFigure 6.12 Month energy6.4.3 VersionFigure 6.13 Yearly energyPress UP/DOWN key to move one date from another.The screen shows the model version and the software version of the Inverter(see Figure 6.7).Model: 08Software Version: D200016.4.6 Daily recordThe screen shows history of changing settings. Only for maintance personel.6.4.7 Communication DataFigure 6.7 Model Version and Software VersionThe screen shows the internal data of the Inverter (see Figure 6.14), which is for servicetechnicians only.6.4.4 Daily Energy01-05: 01 25 E4 9D AA06-10: C2 B5 E4 9D 55The function is for checking the energy generation for selected day.YES ENT NO ESC Select: 2015-02-23Figure 6.14 Communication Data6.4.8 Warning MessageFigure 6.8 Select date for daily energyPress DOWN key to move the cursor to day, month and year, press UP key to change theThe display shows the 100 latest warn messages (see Figure 6.15). Screens can be scrolledmanually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.digit. Press Enter after the date is fixed.Msg000:T: 00-00 00:00 D:00002015-02-22: 051.3kWh2015-02-23: 061.5kWhFigure 6.15 Warning MessageFigure 6.9 Daily energy6.5 Advanced Settings - Technicians OnlyPress UP/DOWN key to move one date from another.6.4.5 Monthly Energy and Yearly EnergyNOTE:To access to this area is for fully qualified and accredited technicians only.Please follow 6.4 to enter password to access this menu.The two functions are for checking the energy generation for selected month and YearSelect Advanced Settings from the Main Menu to access the following options:YES ENT NO ESC Select: 2015-02Figure 6.10 Select month for monthly energyYES ENT NO ESC Select: 2015Figure 6.11 Select year for yearly energy1.Select Standard2.Grid ON/OFF3.Clear Energy4. Reset Password5. Power Control 6.Calibrate Energy 7.Special Settings8.STD. Mode Settings9.Restore Settings 10.HMI Update 11.Export Power Set 12.Restart HMI13.Debug Parameter 14.DSP Update 15.Power Parameter.28.29.

6. Operation6. Operation6.5.1 Selecting Standard6.5.2 Grid ON/OFFThis function is used to select the grid's reference standard (see Figure 6.16).YES ENT NO ESC Standard:AS4777-02This function is used to start up or stop the power generation of Solis Single PhaseInverter (see Figure 6.18).Grid ONGrid OFFFigure 6.16Press the UP/DOWN keys to select the standard (AS4777-02,AS4777-15, VDE4105, VDE0126,UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3(for 4-5kW models), EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function).Press the ENTER key to confirm the setting. Press the ESC key to cancel changes and returnsto previous menu.Figure 6.18 Set Grid ON/OFFScreens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER keyto save the setting. Press the ESC key to return to the previous menu.6.5.3 Clear EnergyNOTE:This function is for technicians use only.Clear Energy can reset the history yield of inverterThese two functions are applicable by maintenance personnel only, wrongSelecting the “User-Def” menu will access to the following submenu (see Figure 6.17),OV-G-V1: 260VOV-G-V1-T: 1SFigure 6.17NOTE:The " User-Def" function can be only used by the service engineer andmust be allowed by the local energy supplier.operation will prevent the inverter from working properly.6.5.4 Reset PasswordThis function is used to set the new password for menu “Advanced info.” and “Advancedinformation” (see Figure 6.19).YES ENT NO ESC Password: 0000Below is the setting range for “User-Def”. Using this function, the limits can be changedmanually.OV-G-V1: 240---270VOV-G-F1: 50.2-53Hz(60.2-64Hz)OV-G-V1-T: 0.1---9SOV-G-F1-T: 0.1---9SOV-G-V2: 240---300VOV-G-F2: 50.2-53Hz(60.2-64Hz)OV-G-V2-T: 0.1---1SOV-G-F2-T: 0.1---9SUN-G-V1: 170---210VUN-G-F1: 47-49.5Hz(56-59.8Hz)UN-G-V1-T: 0.1---9SUN-G-F1-T: 0.1---9SUN-G-V2: 110---210VUN-G

PV Grid Tie Inverter Installation and Operation Manual Solis 4G Single Phase Inverter Ver 1.8 Ningbo Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: 86 (0)574 6578 1806 Fax: 86 (0)574 6578 1606 If you encounter any problem on the inverter, please find out the .

Related Documents:

PV Grid Tie Inverter Installation and Operation Manual Solis 4G Single Phase Inverter Ver 1.0-US version Solis-1P6K-4G-US, Solis-1P7K-4G-US, Solis-1P7.6K-4G-US, . To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply

PV Grid Tie Inverter Installation and Operation Manual Solis 4G Single Phase Inverter 5 Ver 1.0 6 AC connector 1 6 7 Manual 1 DC connector 8 CT with cable (optional) 1 WARNING: Only devices in compliance with SELV (EN 69050) may be connected to the RS485 and USB interfaces. WARNING:

2. The electrical installation must meet all the applicable regulations and standards. 3. The inverter must be installed according to the instructions stated in this manual. 4. The inverter must be installed according to the correct technical specifications. 5. To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before

Xantrex Grid Tie Solar Inverter Owner's Manual GT2.5-DE GT3.8-DE GT2.8-SP GT3.8-SP GT5.0-SP www.xantrex.com.ua. www.xantrex.com.ua. . of the Xantrex Grid Tie Solar Inverter. Chapter 2, "Installation", provides information about planning for and installing the GT Inverter. It contains information to help you plan wire routes, ensure your

Switches the inverter ON or OFF, resets the inverter 5.2 Inverter Status LED's 5.2.1 Inverter Switched Off 5.2.2 Inverter Switched ON 5.2.3 Overload "STATUS LED" Blinking indicates that the inverter is switched off. "STATUS LED" steady ON and the other LEDS rotating in a clockwise direction indicates that the inverter is switched on a

Grid Tie Solar Inverter Xantrex Grid Tie Solar Inverter Owner's Manual GT5.-NA-240/208 UL-05 GT5.-NA-240/208-POS UL-05 GT4.0N-NA-240/208 UL-05 . information on determining a suitable location for installation, PV array requirements, and procedures for mounting the unit. Chapter 3 provides information about DC and AC wiring, and grounding .

the allocation Grid tie inverter, it is necessary to increase the cost of a grid tie inverter. 3. Combination of SGPV does not interact - The traditional solar grid tie system, they offer units ranging in high power output and these units are modular so you can have multiple units operating in parallel for large solar arrays.

transactions: (i) the exchange of the APX share for EPEX spot shares, which were then contributed by the Issuer to HGRT; (ii) the sale of 6.2% stake in HGRT to RTE and (iii) the sale of 1% to APG. The final result is that the Issuer has a participation in HGRT of 19%. For information regarding transactions (i) and (ii) please refer to the press release dated 28 August 2015 (in the note 4 pp .