4-20mA Input Programming - Advantage Controls

1y ago
4 Views
2 Downloads
534.38 KB
5 Pages
Last View : 12d ago
Last Download : 3m ago
Upload by : Adalynn Cowell
Transcription

MegaTron Quick Steps 4-20mA Input Programming Step 1: Push the SET UP RUN button to get this screen. From here push CUSTOMIZE (Button 4) to go to the next screen Step 5: Set the value of mA INPUT 1 NAME by using the arrow keys. Then press ENTER to confirm and go to the previous screen HOME SETUP SETPOINTS CALIBRATION TIMERS CUSTOMIZE ALARMS CUSTOMIZE mA INPUT 1 DATE/TIME CONFIGURE HISTORY TOTALIZERS RELAYS Step 2: This is the Customize Screen. From here push mA IN (Button 9) on a MegaTron SS or select the appropriate SYSTEM number on a multi-system MegaTron. mA INPUT 1 NAME NAME mAIN1 [mAIN1 ] UNITS % USE UP/DOWNxxxxx KEYS TO CHANGE NUMBER PRESS ENTER TO ACCEPT Step 6: Set the value of TYPE OF UNITS by using the arrow keys. Then press ENTER to confirm and go to the previous screen CUSTOMIZE mA INPUT 1 TYPE OF UNITS NAME mAIN1 -- % UNITS % USE UP/DOWN KEYS TO CHANGE NUMBER xxxxx CUSTOMIZE UNIT NAME RELAY NAMES SYS NAME INPUT NAMES FLOW METERS NOTEPAD mA IN RUN SCREEN Step 3: PRESS ENTER TO ACCEPT Step 7: Set the value of NUMBER FORMAT by using the arrow keys. Then press ENTER to confirm and go to the previous screen This is the Customize mA Screen. From here push INPUT 1 (Button 1) to go to the next screen CUSTOMIZE mA INPUT 1 NUMBER FORMAT NAME mAIN1 -- % xxxxx UNITS USE UP/DOWN KEYS TO CHANGE NUMBER xxxxx CUSTOMIZE mA INPUTS PRESS ENTER TO ACCEPT INPUT 1 Step 8: Step 4: This is the Customize mA Input 1 Screen. From here you can set a NAME (Button 1), UNITS (Button 2) and NUMBER range (Button 3). Press desired button to go to the next screen CUSTOMIZE mA INPUT 1 NAME UNITS NUMBER mAIN1 % xxxxx Push the HOME button to get this screen. From here push CALIBRATION (Button 2) to go to the next screen. HOME SETUP SETPOINTS CALIBRATION TIMERS CUSTOMIZE ALARMS DATE/TIME CONFIGURE HISTORY TOTALIZERS RELAYS

MegaTron Quick Steps 4-20mA Input Programming Step 9: Select the mA Inputs (Button 7) to go to mA Input calibration. Then select the mA input to calibrate. CURRENT LOOP CALIBRATION INPUT 1 INPUT 2 INPUT 3 If these are improperly set by entering an A/D value for the settings while the input is not seeing the correct signal a signal generator will be required to reset the calibration. Step 12: Push the HOME button to leave Calibration and go back to the HOME menu screen. From here push SETPOINTS (Button 1) to go to the next screen HOME SETUP Step 10: This will be the mA INPUT CALIBRATION screen. From here select MAX (Button 3) to set what the controller needs to display when it is receiving a 20mA signal. Use number keys to select and ENTER to set value. mA INPUT 1 CALIBRATION 20mA 4mA MAX MIN OFFSET 14500 2900 200 PPM 0 PPM From the mA INPUT CALIBRATION screen select MIN (Button 4) to set what the controller needs to display when receiving a 4mA signal. Use number keys to select and ENTER to set value. mA INPUT 1 CALIBRATION WARNING: 14500 2900 200 PPM 0 PPM DISABLED The 20mA and 4mA calibration selections (Buttons 1 & 2) should only be selected if a 4-20mA signal generator is connected to the input. DATE/TIME CONFIGURE HISTORY TOTALIZERS RELAYS Step 13: This is the Setpoints Setup Screen. From here push mA IN (Button 7) to go to the next screen SENSORS DISABLED Step 11: 20mA 4mA MAX MIN OFFSET SETPOINTS CALIBRATION TIMERS CUSTOMIZE ALARMS SETPOINTS SETUP mA IN Step 14: This is the mA Inputs Screen. From here push INPUT 1 (Button 1) to go to the next screen INPUT 1 mA INPUTS Step 15: This is the mA Input 1 Setpoint Review Screen. From here push SETPOINTS (Button 5) to go to the next screen mA INPUT 1 SETPOINT mAIN1 SET POINT: DIFFERENTIAL: HIGH ALARM AT: LOW ALARM AT: LIMIT TIME: SETPOINTS 500% RISING CONTROL 20 1000(OFF ) 0(OFF ) 00:01 HH:MM

MegaTron Quick Steps 4-20mA Input Programming Step 16: This is the mA Input 1 Setpoint Change Screen. From here you can set SET POINT (Button 1), DIFFERENTIAL (Button 2), HIGH ALARM (Button 3), LOW ALARM (Button 4) and LIMIT TIME (Button 5). Press the desired button to go to the next screen Step 19: Set the HIGH ALARM settings for VALUE (the reading that will give a High Alarm) and NOTIFICATION. Press ENTER to confirm and go to the previous page mA INPUT 1 HIGH ALARM High Alarm 00020 %) VALUE ALARM NOTIFY [ ] % USE NUMBER KEYS TO CHANGE, PRESS ENTER TO ACCEPT OR BACK TO ERASE mA INPUT 1 SETPOINT CHANGE SET POINT DIFFERENTIAL HIGH ALARM LOW ALARM LIMIT TIME Step 20: Step 17: Set the value of SET POINT by using the number keys. Use the left arrow to set the reaction direction of the set point between RISING or FALLING. Then press ENTER to confirm and go to the previous screen mA INPUT 1 SETPOINT CHANGE SET POINT (RISES TO 00500 %) SET POINT [RISES][ ] % DIFFERENTIAL HIGH ALARM KEYS TO CHANGE, PRESS USE NUMBER ENTER TO ACCEPT OR BACK TO ERASE LOW ALARM LIMIT TIME Step 18: Set the value of DIFFERENTIAL by using the number keys. Then press ENTER to confirm and go to the previous screen mA INPUT 1 SETPOINT CHANGE DIFFERENTIAL 00020 %) SET POINT ] % DIFFERENTIAL[ HIGH ALARM KEYS TO CHANGE, PRESS USE NUMBER ENTER TO ACCEPT OR BACK TO ERASE LOW ALARM LIMIT TIME Set the value of the ALARM NOTIFY by using the arrow keys. Then press ENTER to confirm and go to the previous screen. Note: Display - will appear on controller display only, Remote - appears through email if controller is online, or both Dis/Remote mA INPUT 1 HIGH ALARM VALUE ALARM NOTIFY (OFF ) ALARM NOTIFY -- OFF USE UP/DOWN KEYS TO CHANGE PRESS ENTER TO ACCEPT Step 21: Repeat Steps 19 and 20 for the LOW ALARM. Press BACK to return the mA Input 1 Set Points mA INPUT 1 SETPOINT CHANGE SET POINT DIFFERENTIAL HIGH ALARM LOW ALARM LIMIT TIME

MegaTron Quick Steps 4-20mA Input Programming Step 22: Set the value of LIMIT TIME by using the number keys. Then press ENTER to confirm and go to the previous screen. The Limit Time and the Alarm Notification will need to be set. Press HOME when finished to return to the HOME menu Step 25: This is the Configure Relays screen. From here push the RELAY desired then go to the next screen CONFIG RELAYS RELAY RELAY RELAY RELAY RELAY mA INPUT 1 SETPOINT CHANGE SET POINT DIFFERENTIAL HIGH ALARM LOW ALARM LIMIT TIME This is the Relay Setup Screen. From here push the MAIN ACTION (Button 1) to go to the next screen RELAY 5 SETUP MAIN ACTION - OFF ACTIVATOR 2 ACTIVATOR 3 ACTIVATOR 4 Step 23: From the HOME menu select the CONFIGURE (Button 7) to go to the next screen HOME SETUP DATE/TIME CONFIGURE HISTORY WATER METER RELAYS Step 24: This is the Configure Screen. From here push the RELAYS (Button 2) to go to the next screen CONFIGURE PASSWORD RELAYS HISTORY 6 TO 10 Step 26: Note: If the Limit Time is met a relay activated by the 4-20mA input will be forced off until the Set Point has been satisfied and reset. SETPOINTS CALIBRATION TIMERS CUSTOMIZE ALARMS 1 2 3 4 5 CONTRAST TEMP SCALE SYS INFO FACTORY DISABLE 1 DISABLE 2 DISABLE 3 DISABLE 4 00 - DAILY MAX Step 27: This is the Relay Setup screen. From here select the Main Action that is going the drive your relay by using the Arrow buttons. Then press ENTER and then HOME to go to the next screen. Note: You may need to repeat this for each Relay to ensure that each one has the correct action assigned to it for your application RELAY 5 SETUP MAIN ACTION - OFF ACTIVAT5 2 ACTIVATOR 3 ACTIVATOR 4 DISABLE 1 DISABLE 2 DISABLE 3 DISABLE 4 00 - DAILY MAX

MegaTron Quick Steps 4-20mA Input Programming Step 28: Next you may need to assign additional Activators or Disablers for a relay. For example a relay with a Main Action of a mA INPUT set point may need to have a Disabler for a no flow alarm since this is not an automatic action for mA inputs. From the Relay Setup screen select Disabler 1 (Button 6) to go to the next screen RELAY 5 SETUP MAIN ACTION - OFF ACTIVATOR 2 ACTIVATOR 3 ACTIVATOR 4 DISABLE 1 DISABLE 2 DISABLE 3 DISABLE 4 00 - DAILY MAX Step 29: Select the action to disable relay using the Arrow buttons. Then press ENTER and BACK to select more Disablers or HOME if finished RELAY 5 SETUP MAIN ACTION - OFF ACTIVATOR 2 ACTIVATOR 3 ACTIVATOR 4 DISABLE 1 DISABLE 2 DISABLE 3 DISABLE 4 00 - DAILY MAX Step 30: Select DAILY MAX to set a maximum accumulated number of hours that the relay can be on for a 24 hour period the using the Arrow buttons. Then press ENTER then set the ALARM notification desired, press ENTER and HOME if finished RELAY 5 SETUP MAIN ACTION - OFF ACTIVATOR 2 ACTIVATOR 3 ACTIVATOR 4 DISABLE 1 DISABLE 2 DISABLE 3 DISABLE 4 00 - DAILY MAX NOTE: If the maximum number of hours that a relay can be on is met the relay will be forced off and an alarm sent. The Daily Max time and alarm are automatically reset at midnight allow the relay to run if called to do so for another Daily Max amount.

receiving a 20mA signal. Use number keys to select and ENTER to set value. mA INPUT 1 CALIBRATION 20mA 14500 4mA 2900 MAX 200 PPM MIN 0 PPM OFFSET DISABLED Step 11: From the mA INPUT CALIBRATION screen select MIN (Button 4) to set what the controller needs to display when receiving a 4mA signal.

Related Documents:

4-20mA/0-20mA Output Three Channels, 4-20mA/0-20mA Output. 3 Power On Light Indicates that the RIK is powered up. 4 CT Configurator Seven individual field configurable CT ratios for each channel 5 Power Supply RIK integrated power supply. 6 Power Supply Input Power supply input (100-240Vac). 7 Flxible Rogowski Coil Current Transfomer

PF2100 4-20mA Input Card Instruction Manual v1.0 2011 Profire Energy Inc Nov 2, 2011 Page 1 Description The 4-20mA Input Card is an Expansion Card designed for use with PF2100 Burner Management Systems. It provides three separate 4-20mA Analog Current Loop Receivers - each of which can be enabled or disabled using a DIP switch on the card: 1.

HART Communicator can be connected anywhere along the 4-20mA loop (HART Secondary Master) 60.278 0 DEG C ADDR 4-20mA Proportional to 2nd Variable (Process Temperature) 4-20mA Proportional to 3rd Variable (Flow Rate) 4-20mA Proportional to 4th

4-20mA output (sometimes called 4-20mA analog output since the output current is an "analog" of the measurement), then the transmitter is built into the sensor or meter. If it doesn't, you will need to add an external transmitter (such as Seametrics AO55) to convert the flow sensor pulse output to a 4-20mA current.

750-454 2 AI 4-20 mA, Differential Inputs 750-454/000-001 2 AI (4-20mA) Differential Inputs, RC low pass 5 Hz 750-454/000-002 2 AI (4-20mA) Differential Inputs, special data format 750-454/000-003 2 AI (4-20mA) Differential Inputs, Diagnosis for extended measuring range 750-454/000-200 2 AI (4-20mA) Differential Inputs with Siemens (S5-FB

COOLING TOWER CONDUCTIVITY, PH, PTSA & ORP CONTROLLER. Large LCD screen for programming simplicity Maintenance free toroidal conductivity Bleed, pH & ORP control PTSA on a 4-20mA input Up to Six programmable timers Two 4-20mA inputs Four 4-20mA outputs USB data logging and cloning Alarm dry contact

series or parallel, and the value of the resistor changes like this: Series circuit: LED1 LED2 LED3 1.7V, 20mA (E – (number of LEDs x 1.7)) x 1000 R (9V – (3 x 1.7)) x 1000 R 195Ω 20 mA 20 mA The red, green and yellow LEDs in the holiday kit are 1.7V@20mA The blue LED is 3.4V@20mA

Academic writing is cautious, because many things are uncertain. When we put forward an argument, point of view or claim, we know that it can probably be contested and that not everybody would necessarily agree with it. We use words and phrases that express lack of certainty, such as: Appears to Tends to Seems to May indicate Might In some .