Testing Numerical Transformer Differential Relays - IEEE

1y ago
3 Views
2 Downloads
1,023.89 KB
50 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Axel Lin
Transcription

Doble Life of a Transformer 2011 Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., Inc.

Doble Life of a Transformer 2011 Power Transformers Bushing LTC LTC Control Cabinet Cooler Main Tank Cooler

Testing Numerical Transformer Differential Relays INTRODUCTION Commissioning versus Maintenance Testing Main Transformer Protection: Restrained Phase Differential High Set Phase Differential Ground Differential

Testing Numerical Transformer Differential Relays INTRODUCTION Topics: Transformer Differential Boundary Test (Commissioning) Ground Differential Sensitivity Test (Commissioning/Maintenance) Secondary Transformer Protection Harmonic Restraint for Transformer Inrush (Maintenance)

Doble Life of a Transformer 2011 Failure Statistics of Transformers Failure Statistics of Transformers 1955- 1965 1975- 1982 1983- 1988 Number % of Total Number % of Total Number % of Total 134 51 615 55 144 37 Tap changer failures 49 19 231 21 85 22 Bushing failures 41 15 114 10 42 11 Terminal board failures 19 7 71 6 13 3 7 3 24 2 4 1 12 4 72 6 101 26 262 100 1127 100 389 100 Winding failures Core failures Miscellaneous Total Source: IEEE C37.91

Testing Numerical Transformer Differential Relays Commissioning Common Practice: Test all numerical relay settings – verify settings properly entered Easily facilitated using computer – automate test set & store results Hundreds of tests are possible – numerical relays have many settings

Testing Numerical Transformer Differential Relays Commissioning Final Goal Ensure the transformer is properly protected for the particular application

Testing Numerical Transformer Differential Relays Typical Distribution Transformer 46 RG 46: Negative-Sequence Overcurrent Element (sees ground faults through bank) RG: Grounding Resistor (Industrial Load)

Testing Numerical Transformer Differential Relays E 46 RG ZT I2 Sensitive setting for ground fault overreach for phase-to-phase fault 46 ZT ZT 3RG

Testing Numerical Transformer Differential Relays Transformer Differential Characteristic Boundary Test I2 I1 Y Y Y Y 87 * Simulate Through Current I1 Winding 1 per unit current (A, B or C-phase) I2 Winding 2 per unit current (A, B or C-phase) 3 elements per function (A, B & C-phase)

Testing Numerical Transformer Differential Relays Differential Characteristic Operating Equations Id I1 – I2 , Differential Current Ir I1 I2 , Restraint Current 2

Testing Numerical Transformer Differential Relays Differential Characteristic Id % Y *100% X Y Minimum Pickup (per unit) X Ir

Testing Numerical Transformer Differential Relays Differential Characteristic Id Minimum Pickup Ir

Testing Numerical Transformer Differential Relays Matrix [] Id Ir [ ][] 1 -1 * ½ ½ I1 I2

Testing Numerical Transformer Differential Relays Inverted Matrix [] I1 I2 [ ][] ½ 1 -½ 1 * Id Ir

Testing Numerical Transformer Differential Relays Differential Characteristic Test Current Equations I1 0.5*Id Ir, Winding 1 Test Current (per unit) I2 -0.5*Id Ir, Winding 2 Test Current (per unit)

Testing Numerical Transformer Differential Relays Differential Characteristic Test Points Minimum Pickup 0.2 per unit Id Slope 28.6% 4 3 1 2 Minimum Pickup Ir

Testing Numerical Transformer Differential Relays Differential Characteristic Test Points (Per Unit) Id Ir I1 I2 1 0.2 0.3 0.4 0.2 2 0.2 0.7 0.8 0.6 3 0.4 1.4 1.6 1.2 4 0.6 2.0 2.3 1.7 TABLE 1

Testing Numerical Transformer Differential Relays Delta-Wye Differential Characteristic DAB I2 I1 Y Y Y 87 * Simulate Through Current I1 Winding 1 per unit current (A, B or C-phase) I2 Winding 2 per unit current (A, B or C-phase) 3 elements per relay (A, B & C-phase)

Testing Numerical Transformer Differential Relays Delta-Wye Differential Characteristic (Relay Internally Compensates Test Currents) DAB WINDING IA1relay IA1/TAP1 WYE WINDING IB1relay IB1/TAP1 IA2relay (IA2- IB2)/(TAP2*SQRT(3)) IB2relay (IB2 - IC2)/(TAP2*SQRT(3)) IC1relay IB1/TAP1 IC2relay (IC2 - IA2)/(TAP2*SQRT(3)) MVA# TAP# kV#LL*CTR#*SQRT(3)

Testing Numerical Transformer Differential Relays Delta-Wye Differential Characteristic (Single-Phase Test for A-Phase Element) IA1 I1*TAP1 IA2 I2*TAP2*SQRT(3) From TABLE 1: 2 Id Ir I1 I2 0.2 0.7 0.8 0.6 IA1test 0.8*TAP1 IA2test 0.6*TAP2*SQRT(3)

y Testing Numerical Transformer Differential Relays g As an example, if we have a two winding transformer with Y/Delta-AC connection (or YD1) with Y-Y cts. This will be equivalent to case 2 with a 30o phase shift. A 1: 0O C B C A 3: 60O B C A B C 7: 180O A B 9: 240O A C A B 11: 300O C 0 1 0 I ' ABC 0 0 1 I ABC 1 0 0 A 2: 30O C B C 4: 90O A B 5: 120O B 1 0 0 I ' ABC 0 1 0 I ABC 0 0 1 0 0 1 I ' ABC 1 0 0 I ABC 0 1 0 1 0 0 I ' ABC 0 1 0 I ABC 0 0 1 0 1 0 I ' ABC 0 0 1 I ABC 1 0 0 0 0 1 I ' ABC 1 0 0 I ABC 0 1 0 C 6: 150O B 1 1 0 1 I ' ABC 0 1 1 I ABC 3 1 0 1 0 1 1 1 I ' ABC 1 0 1 I ABC 3 1 1 0 1 0 1 1 I ' ABC 1 1 0 I ABC 3 0 1 1 A B 8: 210O C A B 10: 270O A C A 12: 330O B C 1 1 0 1 I ' ABC 0 1 1 I ABC 3 1 0 1 0 1 1 1 I ' ABC 1 0 1 I ABC 3 1 1 0 1 0 1 1 I ' ABC 1 1 0 I ABC 3 0 1 1

Testing Numerical Transformer Differential Relays Ground Differential Element Sensitivity Test Directionality (I0 vs. IG) Ground Fault Location along Windings

Testing Numerical Transformer Differential Relays Ground Differential Element Directional Element 90o Internal External IG I0 -90o Disabled if 3I0 less than 140 mA (Improves Security for CT saturation during external faults)

Testing Numerical Transformer Differential Relays Ground Differential Element Pickup Operate When: 3I0 – IG Pickup

Testing Numerical Transformer Differential Relays Ground Differential Element Sensitivity Test Power System Parameters: Source Impedance (Varies) XT 10% RF (Varies) Ground Fault Location (5% from Transformer Neutral)

Testing Numerical Transformer Differential Relays Ground Differential Element RF Coverage vs. Source Strength 87GD Sensitivity 180 160 Fault Resistance 140 120 100 80 60 40 20 0 0 20 40 60 80 Source Impedance IG 200 mA IG 500 mA IG 1 Amp 100 120

Testing Numerical Transformer Differential Relays Ground Differential Element Pickup Setting R IG Cold Load Pickup Reclosing into Single-Phase Load Pickup Unbalance Directional Element Disabled if 3I0 Low

Testing Numerical Transformer Differential Relays IG2 0.3 Amps @ 177o 3I0(2) 0.136 Amps @ 58o (Threshold 0.14 Amps) CTCF*3I0(2) – IG2 0.75 Amps Original Pickup 0.3 Amps

Testing Numerical Transformer Differential Relays Directional Element INTERNAL EXTERNAL IG2 IOP CTCF*3I0(2) New Pickup 1.0 Amps

Doble Life of a Transformer 2011 Other Transformer Protection 24 – Overexcitation (V/Hz) 46 – Negative-Sequence Overcurrent 49 – Winding Overload 50 – Instantaneous Phase Overcurrent (per winding) 50G – Instantaneous Ground Overcurrent (per winding) 50N – Instantaneous Neutral Overcurrent (per winding) 51 – Inverse Time Phase Overcurrent (per winding) 51G – Inverse Time Ground Overcurrent (per winding) 51N – Inverse Time Neutral Overcurrent (per winding) 59G – Ground Overvoltage (Ungrounded Windings) 63 – Sudden Pressure

Doble Life of a Transformer 2011 Causes of Overexcitation Generating Plants Excitation system runaway Sudden loss of load Operational issues (reduced frequency) Static starts Pumped hydro starting Rotor warming Transmission Systems Voltage and Reactive Support Control Failures Capacitor banks ON when they should be OFF Shunt reactors OFF when they should be ON Near-end breaker failures resulting in voltage rise on line (Ferranti effect) Runaway LTCs

Doble Life of a Transformer 2011 System Control Issues: Overvoltage and Overexcitation 10-20 MVAR Ferranti Effect 10-20 MVAR 30-40 MVAR Reactors are off but should be on

Doble Life of a Transformer 2011 Overexcitation Curves

Doble Life of a Transformer 2011 Through Fault Monitoring

Doble Life of a Transformer 2011 Through Fault Monitoring

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush COMTRADE PLAYBACK Waveform Sources: Events from Numerical Relays Events from Digital Fault Recorders Simulate using Transient Software

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Traditional Approach 2nd Harmonic Restraint Cross Phase Blocking

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Auto-Transformer Model 13.2 kV W3 delta 230 kV 345 kV wye W1 wye W2 600 MVA Auto-Transformer (Tertiary Winding DAC)

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Auto-Transformer Model Auto-transform er Characteristics ZHM 0.01073 per unit ZHL 0.04777 per unit ZML 0.03123 per unit ZH Z HM Z HL Z ML 2 0.0140 per unit ZM Z HM Z ML Z HL 2 -0.0029 per unit ZL Z HL Z ML Z HM 2 0.0340 per unit CTRW1 1200:5 (wye connected) CTRW2 2000:5 (wye connected)

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Auto-Transformer Model 600 MVA TAP1 345 kV * 240 * SQRT(3) 600 MVA TAP2 230 kV * 400 * SQRT(3) 4.18 3.77 Minimum Pickup* 0.5 per unit Slope 25% *Original Pickup 0.45 per unit

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Energize Bank with Heavy A-Phase Residual Flux Total Phase Current

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Energize Bank with Heavy A-Phase Residual Flux 2nd Harmonic Phase Current

Testing Numerical Transformer Differential Relays Even Harmonic Restraint Ieven 2 (I2 2 1/2 I4 )

Testing Numerical Transformer Differential Relays Cross Phase Averaging Provides security if any phase has low harmonic content during inrush Cross phase averaging uses the sum of harmonics on all three phases as the restraint value

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush Energize Bank with Heavy A-Phase Residual Flux 4th Harmonic Phase Current

Testing Numerical Transformer Differential Relays Even Harmonic Restraint during Inrush A-Phase Current (Winding 2)

Testing Numerical Transformer Differential Relays CONCLUSIONS

Testing Numerical Transformer Differential Relays CONCLUSIONS Transformer Differential Boundary Test (Commissioning) Ground Differential Sensitivity Test (Commissioning/Maintenance) Harmonic Restraint for Transformer Inrush (Maintenance)

Testing Numerical Transformer Differential Relays QUESTIONS

Testing Numerical Transformer Differential Relays Commissioning . Common Practice: Test all numerical relay settings - verify settings properly entered Easily facilitated using computer - automate test set & store results Hundreds of tests are possible - numerical relays have many settings

Related Documents:

3.5 Phase-to-phase faults 4. PROTECTIVE RELA VS 4.1 General 4.2 Differential relays 4.2.1 General 4.2.2 Differential relays for fully insulated transformers 4.2.3 Differential relays for auto-transformers 4.3 Overcurrent protection and impedance relays 4.3.1 Time-overcurrent relays 4.3.2 Under-impedance relays 4.3.3 Distance relays 4.4 Grou d .

Directional Relays 4 Differential and Timing Relays 5 Auxiliary Relays 6 Reclosing Relays 7 Synchronizing Relays 8 Generator and Motor Protection Relays 9 Voltage and Frequency Relays 10 Test Equipment and Accessories 11 General Information, Dimensions and Data12 . GE Multilin Subject:

3. Instrument transformer: Used in relay and protection purpose in different instruments in industries . . Current transformer (CT) . Potential transformer (PT) . Open circuit and Short circuit Test on transformer . These two transformer tests are performed to find the parameters of equivalent circuit of transformer and losses of the transformer.

Motor Protection Relays - MM30, MM30W, MPR300, N-DIN-MA Generator Protection Relays -MG30, MG30I, MD32G Transformer Protection Relays - IM30T, MD32T, MD32TM Voltage and Frequency Relays - MC1V, MC3V, UFD34 Feeder Protection Relays- MC20, MC30, FMR Vector Surge Protection Relay -UM30A Neutral Displacement Relay -MND11 Reverse Power Relay -MRP11

Monitoring, Controlling and Switching with SIRIUS Relays One range for every application SIRIUS Monitor. 2 SIRIUS relays – . SIRIUS monitoring relays: Perfect protection of machines and systems Monitoring relays 3UG451 / 461 / 463 monitoring relays for line and single-phase

Introduction to Advanced Numerical Differential Equation Solving in Mathematica Overview The Mathematica function NDSolve is a general numerical differential equation solver. It can handle a wide range of ordinary differential equations (ODEs) as well as some partial differential equations (PDEs). In a system of ordinary differential equations there can be any number of

Transformer Design & Design Parameters - Ronnie Minhaz, P.Eng. Transformer Consulting Services Inc. Power Transmission Distribution Transformer Consulting Services Inc. Generator Step-Up Auto-transformer Step-down pads transformer transformer 115/10 or 20 kV 500/230 230/13.8 132 345/161 161 161 230/115 132 230 230/132 115 345 69 500 34 GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION .

Forex Trading Strategies Editor: Harry Turner www.ifcmarkets.com . One of the most powerful means of winning a trade is the portfolio of Forex trading strat-egies applied by traders in different situations. Following a single system all the time is not enough for a successful trade. Each trader should know how to face up to all market conditions, which, however, is not so easy, and requires a .