Testing Substation Yardstone-Lessons Learned - University Of Minnesota

1y ago
4 Views
1 Downloads
4.68 MB
17 Pages
Last View : 5m ago
Last Download : 3m ago
Upload by : Sabrina Baez
Transcription

Testing Substation Yardstone-Lessons Learned FIVE YEARS OF NATIONWIDE TESTING SUMMARIZED JOHN EDLEBECK COLEMAN ENGINEERING COMPANY

IEEE Standard 80–2000, Section 12.5 suggests that the resistivity of the surface materials used in grounding systems should be tested. IEEE 80-2000, Section 17.3 includes a sample calculation using a value of 3,000 Ωm for the resistivity of surfacing material. Mistakenly, this value is often utilized as a typical value for surfacing material when values are unknown. 3,000 Ωm is often cited in specifications as a minimum resistivity for surfacing material. Table D.1 presents a range of resistivity for a variety of surfacing materials. The information lacks standard terminology for describing the materials and too general to assign values.

Brief Background and History 2012 to 2013 ATC inquired about possibility of testing yardstone surfacing. 2014 “Napkin” sketches of test apparatus and “garage” bench scale tests. Started testing surfacing material at substations throughout the ATC footprint. Coleman retained to develop standard apparatus and test procedure. Presented the proposed test procedure and data at professional conferences. Published findings in IEEE Transactions October 2013. Acquired significant data on various surfacing materials. Started noticing that 3,000 Ω m was elusive and not easily achieved. 2015 to Present PES IEEE Working Group G6 Task Force 1 formed to address standardized testing and prepare technical report. Trafficability over surfacing material prompts a look at composite surfacing sections. Continued testing is being completed to gather more information about surfacing materials.

Existing Recognized Standard Resistivity Test Procedures ASTM G57 – Discusses the 4 pin Wenner array for field determination of soil resistivity. The procedure extends to laboratory testing using a small test box with 4 pin measurement. ASTM G187 – Discusses a 2 pin method in a small test box. Generally utilized to evaluate soils for corrosion potential for embedded steel construction components (culverts, guy anchors, steel pile, etc.). AASHTO T288 – Presents 2 pin and 4 pin methods referring to ASTM methods. Other standard test methods, developed by various electrical utilities, are not universally recognized. Some of these methods were discussed in an informational report published in IEEE 80-2012.

ASTM G57/AASHTO T288 Revisited G57 and T288 provide a reasonable approach to measuring electrical resistivity in soils. The approach does not consider coarse materials such as yardstone surfacing materials. The standards do not address variables that affect resistivity other than indicating the minimum resistivity is considered when sample is saturated. Conventional test apparatus does not accommodate coarse size particles generally included in surfacing material. Test procedure does not include discussion on variables that will affect resistivity such as particle geology, grading, compactness and moisture. The test could easily be modified to include documentation and control of variables as well as accommodate larger particles. Agencies are reluctant to change test procedures.

Examples of ASTM/AASHTO Test Boxes

What’s Wrong with this Picture? Rather than modify the test box, laboratories have modified the samples or used existing equipment. Top example shows removing or crushing larger particles to prepare a sample that can accommodate the test box. Bottom example tries to utilize a test box that is much too small to accommodate the maximum particle size.

Make the Box Fit the Material Larger dimensions allow representing coarse particles in the test procedure. Non conductive materials. Rigid construction to allow rough service. Easily modified to incorporate 2 pin and 4 pin test methods. Meets the intent of ASTM and AASHTO.

Gradation alone is not enough ASTM Size 57 (Granitic Particles) ASTM Size 57 (Limestone/Dolomite Particles) Resistivity – 2,000 to 3,500 Ω m Resistivity 1,000 to 2,000 Ω m Saturated Moisture - 0.5 to 1.5% Saturated Moisture 2.0 to 3.5 %

Geology plays an important role The geologic origin of surfacing materials contribute to the resistive properties of the particles in surfacing materials. Granites, basalts and other metavolcanic rock are dense and less likely to absorb water contributing to high resistivity. Limestone, dolomite, shale, sandstone, and other sedimentary or metasedimentary rock generally absorb more water contributing to low resistivity. Have also tested caliche, coral and coconut straw.

Geographic Limitations Bedrock Geology of North America Red oldest; yellow youngest. Reds generally very dense volcanic and meta volcanic granite and basalt, very dense (Canadian Shield). Blues and purples are moderately dense and consist of meta volcanics and metamorphic rock created from sediments (shales, dolomites, slates). Yellows are sedimentary rock very soft and absorptive(limestone, sandstone). Map courtesy of Kate E. Barton, David G. Howell, José F. Vigil on behalf of the U.S. Geological Survey in collaboration with the Geological Survey of Canada and the Mexican Consejo Recursos de Minerales.

What Does 3,000 Ω m Material Look Like? Maximum Density: 101.6 pcf Saturated Moisture: 1.1% Test Compaction: 100% Test Method: Moisture Condition Wenner 4 Pin and Modified Test Box 1/3 Saturated 2/3 Saturated Saturated Voltage (V) 13.84 15.44 14.90 Current (A) 0.000148 0.00026 0.00048 Resistance (Ω) 93,514 59,385 31,042 Box Factor 0.131 0.131 0.131 Resistivity (Ω m) 12,250 7,779 3,104

Trafficability Particle shape and range of sizes affect the support of traffic. Rounded particles all of uniform shape and size reduce trafficability. Angular particles with range of sizes improve trafficability. Some designers are considering composite layers to maintain resistivity and improve trafficability.

What we are seeing to improve trafficability Dense graded aggregate placed to enhance traffic support. Saturated resistivity 150 to 300 Ω m

Current Movements in Testing IEEE Working Group G6 Task Force 1 is currently preparing a technical report to discuss electrical resistivity of surfacing material and considers standardized test methods currently being developed. ASTM Standard Guide being considered which will provide guidance to designer and testing agencies to consider variables when measuring the resistive properties of soil and construction materials. Vertical oriented test to allow composite layers of surfacing material being considered to evaluate resistivity.

Design and Construction Consider a resistivity value that is achievable given local constraints of materials available. Consider regional limitations of available surface materials. Establish submittal process to test surfacing materials to confirm that minimum resistivity criteria is met or achievable. Do not rely on gradation alone. Gradation is only one variable. Consider geologic composition and shape of particles and absorption characteristics. Consider trafficability of surfacing material. Include a minimum crushed particle content. Consider constructing traffic lanes which can accommodate lower resistivity materials which will support traffic.

Questions? THANK YOU

Resistivity Test Procedures ASTM G57 - Discusses the 4 pin Wenner array for field determination of soil resistivity. The procedure extends to laboratory testing using a small test box with 4 pin measurement. ASTM G187 - Discusses a 2 pin method in a small test box. Generally utilized to

Related Documents:

Electrical Substation Configuration Effect on Substation Reliability . Courtney Otania and Kurt Vedros a. a Idaho National Laboratory, Idaho Falls, ID, USA . . Substation Level, Generic 4.931E-05 Busbar, Substation [7] 132 kV Busbars 1.507E-05 Control Panel Switchgear [2] C4-300 2.845E-06 .

- NJT01113, ROC Unit Substation: This project includes construction of a replacement Substation to be built above Design Flood Elevation and integration of emergency power equipment to service the Rail Operations Center (ROC). 8. Contract/Program Location Henderson Street Substation, Bay Head Yard Substation, Depot Substation, Rail Operations .

The new substation will sit on the footprint of the oldest structure and extend a little beyond. The second substation will be demolished. At completion of the project there will be only one substation. In answer to the survey posted on the internet concerning the project we have prepared a sheet answering those questions they are as follows:

LESSONS_LEARNED_REPORT BI Project Page 1 PROJECT LESSONS LEARNED REPORT Project Name: Business Intelligence (BI) Prepared by: Diane Kleinman Date: June 15, 2009 Project Close-Out Discussion A Lessons Learned meeting was held on 6/12/09. The summarized lessons learned survey results are attached to this document. Attendees: Janet Heller Vel Angamthu

As the centralized lessons learned capability for the Army, CALL synthesizes input from across the ALLP community and disseminates pertinent lessons learned information to units to help plan, prepare, and execute mission requirements. This collaboration allows TRADOC, as the lead for Army lessons learned, to provide

Apr 19, 1995 · Lessons Learned Major Lessons Learned Lessons Learned through Response/Recovery Operations Lessons Learned from Other Agencies Statistics Introduction, Summary of Fatalities and Injuries Exhibits Exhibit A - Murrah Building Floor Plan Image of Floors 1 and 2 (73Kb) Imag

11.2.3 Electrical Conduits, Cable Ducts and Earthing 34 . This document is a reference for the Designers of Ergon Energy substations and it covers all aspects of substation design for both Greenfield and Brownfield substation projects to meet the performance expected by Ergon Energy. The manual is applicable for all substation projects

Welcome to the ASME/Bath 2019 Symposium on Fluid Power and Motion Control (FPMC 2019) held at the Zota Beach Resort, on the powdery white sands and brilliant turquoise waters of Sarasota’s Longboat Key, Florida. I hope you will find the technical program of the symposium engaging. I also hope that you will enjoy the social events and further develop your network with colleagues. The .