Operating Instructions – Description of Instrument FunctionsCerabar S PMC71, PMP71/75Deltabar S FMD77, FMD78, PMD75Deltapilot S FMB70Process pressure / Differential pressure, Flow / HydrostaticBA00274P/00/EN/17.1471270402valid from Software version:02.20.zz

Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTOrder code 00X00-XXXX0XX0XXXSer. No.:X000X000000TAG No.: XXX000Serial numberwww.endress.com/deviceviewerEndress Hauser Operations AppA00235552Endress Hauser

Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTTable of contentsTable of contents1Notes on use . . . . . . . . . . . . . . . . . . . . 41.11.21.3Finding parameter description using ID numbers . . . 4Finding function group using graphic representation 4Finding parameter description using parameter names(index) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Finding parameter description usingID numbers . . . . . . . . . . . . . . . . . . . . . 53Graphic representation of function groups104Pressure measurement. . . . . . . . . . . . 114.14.2Calibration with reference pressure . . . . . . . . . . . . 11Calibration without reference pressure . . . . . . . . . 125Level measurement . . . . . . . . . . . . . . 145.15.25.35.4Overview of level measurement . . . . . . . . . . . . . ."Level Easy Pressure" level selection . . . . . . . . . . ."Level Easy Height" level selection . . . . . . . . . . . . ."Level Standard" level selection,"Linear" level type . . . . . . . . . . . . . . . . . . . . . . . ."Level Standard" level selection,"Pressure Linearized" level type . . . . . . . . . . . . . ."Level Standard" level selection,"Height Linearized" level type . . . . . . . . . . . . . . . .5.55.61415192428336Flow measurement. . . . . . . . . . . . . . . 406.16.2Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Totalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437Description of parameters . . . . . . . . . 448Trouble-shooting . . . . . . . . . . . . . . . 1328.18.28.3Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132Response of outputs to errors . . . . . . . . . . . . . . . . 141Confirming messages . . . . . . . . . . . . . . . . . . . . . . 1429Appendix . . . . . . . . . . . . . . . . . . . . . 1429.1Operating menu for on-site display, Digitalcommunication . . . . . . . . . . . . . . . . . . . . . . . . . . 142Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151Endress Hauser3

Notes on useCerabar S/Deltabar S/Deltapilot S 4.20mA HART1Notes on useSection 7 describes all the parameters in order of how they appear in the menu. Sections 4 to 6provide typical examples of configuration.Sections 1.1 to 1.3 describe ways of finding a certain parameter description more easily.1.1Finding parameter description using ID numbersEach parameter is shown on the on-site display with a unique identification number (ID). Section 2lists all the parameters in numerical order. The page reference/link takes you to the parameter inquestion.In the Operating program, additional parameters and, to an extent, other parameters are displayed.These parameters are not listed in Section 2. You can find these parameters by means of the index. See also Section 1.3.1.2Finding function group using graphic representationAll the function groups are shown in table form in Section 3. The page reference/link takes you tothe function group in question. In Section 7, all the parameters of a function group are compiled ina table.1.3Finding parameter description using parameter names(index)The index lists all the parameters in alphabetical order. The page reference/link takes you to theparameter in question.4Endress Hauser

Cerabar S/Deltabar S/Deltapilot S 4.20mA HART2Finding parameter description usingID numbersID numberParameter nameDescription, see 2254264266270271272301DENSITY UNIT – Level Selection "Level Easy Pressure"HEIGHT UNITFULL CALIB. – QUICK SETUPFULL CALIB. – Level Selection "Level Easy Pressure"FULL CALIB. – Level Selection "Level Easy Height"FULL PRESSUREFULL HEIGHTADJUST DENSITY – Level Selection "Level Easy Height"CALIBRATION MODE – Level Selection "Level Easy Pressure"CALIBRATION MODE – Level Selection "Level Easy Height"EMPTY HEIGHTEMPTY CALIB. – QUICK SETUPEMPTY CALIB. – Level Selection "Level Easy Pressure"EMPTY CALIB. – Level Selection "Level Easy Height"EMPTY PRESSURESET URV – Level Selection "Level Easy Pressure"SET URV – Level Selection "Level Easy Height"SET LRV – Level Selection "Level Easy Pressure"SET LRV – Level Selection "Level Easy Height"DOWNLOAD SELECTFULL PRESSUREEMPTY PRESSUREFULL CALIB.EMPTY CALIB.LEVEL SELECTIONSET LRVSET URVOUTPUT UNIT – Level Selection "Level Easy Pressure"OUTPUT UNIT – Level Selection "Level Easy Height"PROCESS DENSITY – Level Selection "Level Easy Pressure"PREAMBLE NUMBERCURR. TRIM 20mAOFFSET 4mA TRIMOFFSET 20mA TRIMCURR. TRIM 4mAALARM STATUSENTER RESET CODEINSERT PIN NoLEVEL BEFORE LINCUST. TAG NUMBERPRESS. ENG. UNITCUSTOMER UNIT PLANGUAGESET LRV – "Pressure" measuring modeSET URV – "Pressure" measuring modeDAMPING VALUESENSOR SER. No.Pmin SENS. DAMAGEPmax SENS. DAMAGEOUTPUT CURRENTSOFTWARE VERSIONHARDWARE REV.SIM. CURRENTHART MESSAGEADDITIONAL INFO.PRESSURE – "Pressure" measuring modePRESSURE – "Level" measuring modePRESSURE – "Flow" measuring modeLONG TAG NUMBER64 or 9764516165616664 or 976064655060 or 61656161666166126See 1)See 1See 1See 146See 1See 160649711513113113113112812612612311756, 59, 63, 67 or 9256, 59, 63, 68 or 924448 or 5648 or 5748, 51, 53, 57, 61, 66, 77, 81, 90 or ess HauserFinding parameter description using ID numbersSee Safety Manual SD00189P for Deltabar S, SD00190P for Cerabar S and SD00213P for Deltapilot S.5

Finding parameter description using ID numbersID numberParameter nameDescription, see page309310311313GET LRVGET URVMAX. FLOWUNIT VOLUME – "Linear" level typeUNIT VOLUME – "Pressure Linearized" level typeUNIT VOLUME – "Height Linearized" level typeEMPTY CALIB. – QUICK SETUPEMPTY CALIB. – "Linear" level typeEMPTY CALIB. – "Height Linearized" level typeFULL CALIB. – QUICK SETUPFULL CALIB. – "Pressure Linearized" level typeFULL CALIB. – "Height Linearized" level typeADJUST DENSITY – "Linear" level typeADJUST DENSITY – "Height Linearized" level typeADJUST DENSITY– "Level" extended setupCUST. UNIT FACT. PTEMP. ENG. UNIT – "Pressure" measuring modeTEMP. ENG. UNIT – "Level" measuring modeTEMP. ENG. UNIT – "Flow" measuring modeCALIB. OFFSETSET. L. FL. CUT-OFFFACT. U. U. TOTAL. 1FACT. U. U. TOTAL. 2RESET TOTALIZER1Pmin ALARM WINDOWPmax ALARM WINDOWTmin ALARM WINDOWTmax ALARM WINDOWALARM DELAYDISPLAY CONTRASTSET MAX. ALARMSET MIN. CURRENTBUS ADDRESSDEVICE DESIGN.DEVICE TYPE, Deltabar SCONFIG RECORDERDEVICE SERIAL NoPCB TEMPERATUREALLOWED MIN. TEMPALLOWED MAX. TEMPMAT. PROC. CONN. MAT. PROC. CONN. SEAL TYPEDIP STATUSMAT. MEMBRANEFILLING FLUIDSENSOR TEMP.Tmin SENSORTmax SENSORTANK CONTENTSUPPRESSED FLOWMEAS. VAL. TRENDCOUNTER:P PmaxRESET PEAKHOLDMAX. MEAS. PRESS.ELECTR. SERIAL NoOUTPUT FAIL MODEMEASURING MODELINEAR/SQROOTUNIT FLOWCALIBRATION MODE – "Linear" level typeCALIBRATION MODE – "Height Linearized" level typeLIN. EDIT MODETOTALIZER 1 UNIT – "Volume p. cond." flow typeTOTALIZER 2 UNIT – "Volume p. cond." flow typeNEG. FLOW TOT. 1ACK. ALARM MODE575752 or 9571 or 75798450738751748774889756, 68 or 7115117117117117117118118118117120120122 or 123120120123123122 or 6Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTEndress Hauser

Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTID numberParameter nameDescription, see page404409413414416419423432434COUNTER:T TmaxOPERATING HOURSSIMULATION MODESIM. PRESSURENEG. FLOW TOT. 2MENU DESCRIPTORALTERNATE DATAMANUFACTOR IDCORRECTED PRESS. – "Pressure" measuring modeCORRECTED PRESS. – "Level" measuring modeCORRECTED PRESS. – "Flow" measuring modeLOW FLOW CUT-OFFCOUNTER:P PminMIN. MEAS. PRESS.MAX. MEAS. TEMP.COUNTER:T TminMIN. MEAS. TEMP.SIM. ERROR NO.ALARM DISPL. TIMEHART DATEPROC. CONN. TYPEPRESS. SENS LOLIMPRESS. SENS HILIMSENS H/WARE REVPCB COUNT:T TmaxPCB MAX. TEMP.PCB COUNT:T TminPCB MIN. TEMP.ACK. ALARMCURRENT MODEMEASURING TABLE (display)EDITOR TABLE, LINE-NUMB (enter values)EDITOR TABLE, X-VAL. (enter values)EDITOR TABLE, Y-VAL. (enter values)POS. INPUT VALUELAST DIAG. CODEPmax PROC. CONN.MASS FLOW UNITSENSOR MEAS.TYPESENSOR PRESSURE – "Pressure" measuring modeSENSOR PRESSURE – "Level" measuring modeSENSOR PRESSURE – "Flow" measuring modeHART VERSIONMINIMUM SPANSELECT ALARMTYPEALT. CURR. OUTPUTSELECT ALARMTYPERESET ALL ALARMSCUST. UNIT FACT. V – "Linear" level typeCUST. UNIT FACT. V – "Pressure Linearized" level typeCUST. UNIT FACT. V – "Height Linearized" level typeCUSTOMER UNIT V – "Linear" level typeCUSTOMER UNIT V – "Pressure Linearized" level typeCUSTOMER UNIT V – "Height Linearized" level typeCUST. UNIT FACT. FCUSTOMER UNIT FTOT. 1 USER UNITTOT. 2 USER UNITMAX PRESS. FLOWSET LRV – "Flow" extended setupSET URV – "Flow" extended setupSIM.FLOW VALUEFLOW-MEAS. TYPETOTALIZER 1TOTAL. 1 OVERFLOWTOTALIZER 2TOTAL. 2 OVERFLOWSTD. FLOW 02102, 10248, 50 or 85959410810953 or 34637638639640652655657658660Endress HauserFinding parameter description using ID numbers7

Finding parameter description using ID numbers661NORM FLOW UNIT93ID numberParameter nameDescription, see page662663664665666667679TOTALIZER 1 UNIT – "Mass" flow typeTOTALIZER 2 UNIT – "Mass" flow typeTOTALIZER 1 UNIT – "Gas. std. conditions" flow typeTOTALIZER 2 UNIT – "Gas. std. conditions" flow typeTOTALIZER 1 UNIT – "Gas. norm conditions" flow typeTOTALIZER 2 UNIT – "Gas. norm conditions" flow typeMEASURED VALUE – "Pressure"MEASURED VALUE – "Level"MEASURED VALUE – "Flow"POS. ZERO ADJUSTMAIN DATA FORMATCURR. CHARACT. – "Pressure"CURR. CHARACT. – "Flow"CURR. CHARACT. – "Height"DEVICE REVISIONCUST. UNIT FACT. M – "Linear" level typeCUST. UNIT FACT. M – "Pressure Linearized" level typeCUST. UNIT FACT. M – "Height Linearized" level typeCUSTOMER UNIT M – "Linear" level typeCUSTOMER UNIT M – "Pressure Linearized" level typeCUSTOMER UNIT M – "Height Linearized" level typeCUST. UNIT FACT. H – "Linear" level typeCUST. UNIT FACT. H – "Height Linearized" level typeCUSTOMER UNIT H – "Linear" level typeCUSTOMER UNIT H – "Height Linearized" level typeHEIGHT UNIT – "Linear" level typeHEIGHT UNIT – "Height Linearized" level typeMASS UNIT – "Linear" level typeMASS UNIT – "Pressure Linearized" level typeMASS UNIT – "Height Linearized" level typeEMPTY PRESSURE – "Linear" level typeEMPTY PRESSURE – "Height Linearized" level typeFULL PRESSURE – "Linear" level typeFULL PRESSURE – "Height Linearized" level typeLEVEL MAXTANK CONTENT MAXSIM. LEVELSIM. TANK CONT.MEASURING TABLE (selection)LEVEL MODESET LRV – "Level" basic setupSET URV – "Level" basic setupLEVEL MINTANK CONTENT MINASSIGN CURRENTHYDR. PRESS MAX.SET LRV – "Level" extended setupSET URV – "Level" extended setupCURR. CHARACT. – "Tank content"EDITOR TABLE (continue entry)HYDR. PRESS MIN.DEVICE TYPE, Cerabar SLIN. MEASURANDLINd. MEASURANDCOMB. MEASURANDTABLE SELECTIONEDITOR TABLE (select table)ADJUSTED DENSITY – "Linear" level typeADJUSTED DENSITY – "Height Linearized" level typePROCESS DENSITYDENSITY UNIT – "Linear" level typeDENSITY UNIT – "Height Linearized" level type100 % POINT – "Linear" level type100 % POINT – "Height Linearized" level type10810910810910810912112212348, 50, 52 or 5411011211211211573808672808671 or 7684 or 8970 or 7684 or 8970 or 7683 or 08118128138Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTEndress Hauser

Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTID numberParameter nameDescription, see page814ZERO POSITION – "Linear" level typeZERO POSITION – "Height Linearized" level typeTANK DESCRIPTIONHistoROM AVAIL.HistoROM CONTROLSAFETY LOCKSTATESAFETY LOCKSAFETY PASSWORDDIGIT SETSDIGIT SETSACK. ALARM MODEMEASURING MODECALIB. OFFSETMAX. FLOWMAX PRESS. FLOWLOW FLOW CUT-OFFSET. L. FL. CUT-OFFSET LRVSET URVLINEAR/SQROOT.DAMPING VALUECONF. PASSWORDTANK VOLUMETANK HEIGHTCURRENT OUTPUT7790103126127See 8548558568588598751)Endress HauserFinding parameter description using ID numbersSee 1111See 1See 1See 1See 1See 1See 1See 1See 1See 1See 1See 1See 1See 17576See 1See Safety Manual SD00189P for Deltabar S, SD00190P for Cerabar S and SD00213P for Deltapilot S.9

Graphic representation of function groups3!Cerabar S/Deltabar S/Deltapilot S 4.20mA HARTGraphic representation of function groupsNote!The "Flow" measuring mode is only available for the Deltabar S differential pressure transmitter. Thegroups marked with "*" are only displayed for Deltabar S.1st selection level2nd selection level (groups)LANGUAGELANGUAGE (079) 44MEASURING MODEMEASURING MODE (389) 45QUICK SETUP pressure 47QUICK SETUP level 49QUICK SETUP flow* 52 POSITION ADJUSTMENT 53 BASIC SETUP pressure 55 BASIC SETUP level,"Level Easy Pressure" 58 BASIC SETUP level,"Level Easy Height" 62 BASIC SETUP level,"Level Easy Standard" 67 BASIC SETUP flow* 91 EXTENDED SETUP pressure 96 EXTENDED SETUP level 96 EXTENDED SETUPflow* 98 LINEARISATION –on-site display 100 LINEARISATION –Digital communication 104 TOTALIZER SETUP * 107 SAFETY CONFIRM. See 1) DISPLAY (558) 110 OUTPUT (559) 111 HART DATA 114 TRANSMITTER DATA 117 PROCESS CONNECTION 117 SENSOR DATA 119 PROCESS VALUES pressure 121 PROCESS VALUES level 122 PROCESS VALUES flow* 123 PEAK HOLD INDICATOR 124 126 SIMULATION 127 MESSAGES 128 USER LIMITS 130 SYSTEM 2 131OPERATING MENU (555) SETTINGS (557) TRANSMITTER INFO (560) PROCESSINFO (561)Function groups OPERATING DIAGNOSTICS (562) SERVICE (561)1)10Description,see pageSee Safety Manual SD00189P for Deltabar S, SD00190P for Cerabar S and for SD00213P Deltapilot S.Endress Hauser

Cerabar S/Deltabar S/Deltapilot S 4.20mA HART4Pressure measurement4.1Calibration with reference pressurePressure measurementExample:In this example, a device with a 500 mbar (7.5 psi) sensor is configured for the 0. 300 mbar (4.5psi)measuring range, i.e. 0 mbar and 300 mbar (4.5 psi) are assigned to the 4 mA value and 20 mAvalue respectively.Prerequisite: The pressure values 0 mbar and 300 mbar (4.5 psi) can be specified. The device is alreadyinstalled, for example.!#Endress HauserNote! See also Operating Instructions Deltabar S (BA00270P), Section 6.6 "Differential pressuremeasurement", Cerabar S (BA00271P), Section 6.4 "Pressure measurement" or Deltapilot S(BA00332P), Section 6.5 "Pressure measurement". For a description of the parameters mentioned, see– Page 45, Table 2: MEASURING MODE– Page 53, Table 6: POSITION ADJUSTMENT– Page 55, Table 7: BASIC SETUP. For a description of further relevant parameters, see– Page 96, Table 15: EXTENDED SETUP– Page 121, Table 25: PROCESS VALUES.Warning!If the measuring mode is changed, the span setting (URV) must be verified in the "Calibration" "Basic Setup" operating menu and, if necessary, reconfigured.11

Pressure measurementCerabar S/Deltabar S/Deltapilot S 4.20mA HARTDescription1Deltabar S: before configuring the device for yourapplication, the pressure piping must be cleaned andfilled with fluid. See Operating Instructions BA00270P,Section 6.6.2Carry out position adjustment if necessary. See Page 53,Table 6: POSITION ADJUSTMENT.3If necessary, select the "Pressure" measuring mode viathe MEASURING MODE parameter. –On-site display:Menu path: GROUP SELECTION MEASURINGMODEDigital communication:Menu path: OPERATING MENU SETTINGS BASIC SETUP MEASURING MODE4On-site display:Select BASIC SETUP function group.Menu path: GROUP SELECTION OPERATINGMENU SETTINGS BASIC SETUP5Select a pressure unit via the PRESS. ENG. UNITparameter, here mbar for example.6The pressure for the lower range value (4 mA value) ispresent at the device, here 0 mbar for example.P01-PMD75xxx-19-xx-xx-xx-000I[mA]➁ 20Select GET LRV parameter.➀Confirm value present. The pressure value present isassigned to the lower current value (4 mA).40300p[mbar]P01-xxxxxxxx-05-xx-xx-xx-010Fig. 1:127Calibration with reference pressureSee table, step 6.See table, step 7.The pressure for the upper range value (20 mA value) ispresent at the device, here 300 mbar (4.5 psi) forexample.Select GET URV parameter.Confirm value present. The pressure value present isassigned to the upper current value (20 mA).8!Result:The measuring range is set for 0. 300 mbar (4.5 psi).Note! You can also specify a customer-specific unit. See parameter description for PRESS. ENG. UNIT( Page 56).4.2Calibration without reference pressureExample:In this example, a device with a 400 mbar (6 psi) sensor is configured for the 0. 300 mbar (4.5psi) measuring range, i.e. 0 mbar and 300 mbar (4.5 psi) are assigned to the 4 mA value and 20 mAvalue respectively.Prerequisite: This is a theoretical calibration, i.e. the pressure values for thelower range and upper range value are known.12Endress Hauser

Cerabar S/Deltabar S/Deltapilot S 4.20mA HART!#Pressure measurementNote! See also Operating Instructions Deltabar S (BA00270P), Section 6.6 "Differential pressuremeasurement", Cerabar S (BA00271P), Section 6.4 "Pressure measurement" or Deltapilot S(BA00332P), Section 6.5 "Pressure measurement". Due to the orientation of the device, there may be a shift in the measured value, i.e. when thecontainer is empty or partly filled, the MEASURED VALUE parameter does not display zero. To perform a position adjustment see also Page 53, Table 6: Position adjustment. For a description of the parameters mentioned, see– Page 45, Table 2: MEASURING MODE– Page 53, Table 6: POSITION ADJUSTMENT– Page 55, Table 7: BASIC SETUP. For a description of further relevant parameters, see– Page 96, Table 15: EXTENDED SETUP– Page 121, Table 27: PROCESS VALUES.Warning!If the measuring mode is changed, the span setting (URV) must be verified in the "Calibration" "Basic Setup" operating menu and, if necessary, reconfigured.Description1If necessary, select the "Pressure" measuring mode viathe MEASURING MODE parameter.On-site display:Menu path: GROUP SELECTION MEASURINGMODEDigital communication:Menu path: OPERATING MENU SETTINGS BASIC SETUP MEASURING MODE2On-site display:Select BASIC SETUP function group.Menu path: GROUP SELECTION OPERATINGMENU SETTINGS BASIC SETUP3Select a pressure unit via the PRESS. ENG. UNITparameter, here mbar for example.4Select SET LRV parameter.P01-PMP71xxx-19-xx-xx-xx-000I[mA]➁ 20Enter value, here 0 mbar, for the SET LRV parameterand confirm. This pressure value is assigned to the lowercurrent value (4 mA).5Select SET URV parameter.Enter value, here 300 mbar (4.5 psi), for the SET URVparameter and confirm. This pressure value is assigned tothe upper current value (20 mA).6➀Result:The measuring range is set for 0. 300 mbar (4.5 psi).40300p[mbar]P01-xxxxxxxx-05-xx-xx-xx-010Fig. 2:12!Endress HauserCalibration without reference pressureSee table, step 4.See table, step 5.Note! You can also perform calibration without reference pressure by means of the QUICK SETUPmenu. See Page 47 ff, Table 3: QUICK S

334 tmin alarm window 130 335 tmax alarm window 130 336 alarm delay 129 339 display contrast 111 342 set max. alarm 113 343 set min. current 113 345 bus address 115 350 device design. 117 351 device type, deltabar s 115 352 config recorder 117 354 device serial no 117 357 pcb temperatur

Related Documents:

Prosonic S FMU90 Prosonic S FDU90 Cerabar M PMP51 Cerabar M PMP51 Cerabar M PMP51 Cerabar M PMP51 Cerabar M PMP51 Cerabar M PMP51 Cerabar M PMP51 Cerabar M PMP51 Condensate trap Particle filter Filter Filter Gas motor Boiler Digester Gas flare Gas tank

Safety Manual SD 172P/00/en 71036063 Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal 4.20 mA/HART Functional Safety Manual Application Pressure measurement (e.g. limit pressure monitoring) to satisfy particular safety systems requirements as per IEC 61508/ IEC 61511-1. The measuring device fulfils the

Endress Hauser AT 70 Mass Flowmeter CERABAR M Analog or Digital Level Transmitter Pressure Transmitter Cerabar M 5x Absolute Level Transmitter . ProMass 63 Coriolis Flowmeter ProMass 80 Coriolis Flowmeter ProMass 83 Coriolis Flowmeter PROMASS 84 Coriolis Flowmeter Promass TB2 Coriol

Independent Personal Pronouns Personal Pronouns in Hebrew Person, Gender, Number Singular Person, Gender, Number Plural 3ms (he, it) א ִוה 3mp (they) Sֵה ,הַָּ֫ ֵה 3fs (she, it) א O ה 3fp (they) Uֵה , הַָּ֫ ֵה 2ms (you) הָּ תַא2mp (you all) Sֶּ תַא 2fs (you) ְ תַא 2fp (you

– PMP71, PMP75: NACE-compliant materials – PMC71, PMP71, PMP75: inspection certificate 3.1 –HistoROM /M-DAT memory module – Separate housing Specialities – Metal-free measurement with PVDF connection – Cleaning of the transmitter for the use in paint shops – Oil volume

Measuring system P01-PMx13xxx-14-xx-xx-xx-002 1 PMP131, PMP135: current output with transmitter power supply unit, e.g. RN 221N from Endress Hauser 2 PMP131, PMP135: switch output with load, e.g. PLC, DCS, relay 3 PMC

HART I/O module The ControlLogix HART analog I/O module converts to or from 4.20 mA analog signals and the digital values used in the ControlLogix controller. The I/O module automatically collects dynamic process data from the HART field instrument. The I/O module also bridges HART messages from CIP clients to HART field instruments.

Albert Woodfox, myself and all political prisoners over the years. Thank you for helping to bring these injustices to the forefront. If I omitted anyone it was an honest mistake, my apologies and sincere thanks for everything you have done too!! Free The Angola 3! Free ALL political prisoners and prisoners of conscience! All Power to the People! ROBERT KING AKA Robert King Wilkerson 2008. 15 .