INSTALLATION INSTRUCTIONS Fan Coils FVM4X “B” Series

2y ago
32 Views
2 Downloads
364.01 KB
23 Pages
Last View : 16d ago
Last Download : 3m ago
Upload by : Javier Atchley
Transcription

INSTALLATION INSTRUCTIONSFan CoilsFVM4X “B” SeriesThese instructions must be read and understood completely before attempting installation.Safety Labeling and Signal WordsDANGER, WARNING, CAUTION, andNOTEThe signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is onlyused on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, andNOTE will be used on product labels and throughout this manual and other manuals that may applyto the product.DANGER Immediate hazards which will result insevere personal injury or death.WARNING Hazards or unsafe practices whichcould result in severe personal injury or death.CAUTION Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.Signal Words in ManualsThe signal word WARNING is used throughout thismanual in the following manner:!WARNINGWARNINGThe signal word CAUTION is used throughout thismanual in the following manner:!CAUTIONSignal Words on Product LabelingSignal words are used in combination with colorsand/or pictures on product labels.NOTE Used to highlight suggestions which willresult in enhanced installation, reliability, or operation.TABLE OF CONTENTSIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Heater Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Position Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 7Air Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Electrical Connections . . . . . . . . . . . . . . . . . . . . . . 8 10Refrigerant Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Refrigerant Metering Device . . . . . . . . . . . . . . . . . . . . 10Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Blower Motor CFM . . . . . . . . . . . . . . . . . . . . . . . 12 13Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 15Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Fan Coil Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 19ECM Motor and Control . . . . . . . . . . . . . . . . . . . . . . . . 19Troubleshooting ECM Motor and Controls . . . . 19 21Start up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 22R 410A Quick Reference Guide . . . . . . . . . . . . . . . . . 23Specifications are subject to change without notice!WARNINGDEATH, PERSONAL INJURY, AND/OR PROPERTYDAMAGE HAZARDFailure to carefully read and follow this warningcould result in equipment malfunction, propertydamage, personal injury and/or death.Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death.The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped withthe proper tools and test instruments.Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenchingcloth for brazing operations. Have fire extinguisher available.Installation must conform with local buildingcodes and with the National Electrical CodeNFPA70 current edition.In Canada, refer to current editions of the Canadian electrical code CSA22.1.496 01 5002 00 July 2012

INSTALLATION INSTRUCTIONSFan Coils: FVM4XINTRODUCTIONModels FVM4X are designed for maximum flexibility andcan be used for upflow, horizontal left or right, anddownflow applications (accessory kit required fordownflow or horizontal right).These units are designed to meet the low air leakrequirements currently in effect. Because of this, the unitsneed special attention in the condensate pan and drainconnection area and when brazing tubing.Four fan coil sizes will combine with various outdoor unitsizes to offer systems ranging from 1½ 5 tons (18,000 60,000 BTUH) nominal cooling capacity.All models have a factory installed and appropriatelysized hard shut off TXV metering device.Factory authorized, field installed electric heaterpackages are available in sizes 5 kW through 30 kW. SeeProduct Specification literature for available accessorykits.LOCATIONSelect the best position which suits the installation siteconditions. The location should provide adequatestructural support, space in the front of the unit for serviceaccess, clearance for return air and supply ductconnections, space for refrigerant piping connections andcondensate drain line connections. If heaters are beinginstalled make sure adequate clearance is maintainedfrom supply duct work. Refer to Clearances in Figure 1.If the unit is located in an area of high humidity, nuisancesweating of casing may occur. On these installations awrap of 2” fiberglass insulation with a vapor barrier isrecommended.Clearances and Unit DimensionsFigure 1( OPENING)FABNOTE: Internal filter can be accessed from separate filterdoor. If the filter can NOT be easily accessed, a remotefilter is recommended. Refer to ACCA Manual D forremote filter sizing.WARNING!FIRE HAZARDFailure to maintain proper clearances could resultin personal injury, death, and/or property damage.When heaters are installed, maintain clearancesfrom combustible materials as specified on unitrating plate. Do not use plastic lined or combustible flexible ducting within 36” (914.4) of the supply end of the fan coil.REQUIRED CLEARANCES ALL MODELS (inches)All SidesNoHeatersFrom Supply DuctAll SidesWithFrom First 3 feet of Supply Duct to CombustiblesHeatersFrom Supply Duct to Combustibles after 3 feetEUnit Size2400360048006000Unit Size2400360048006000HA15w19419422wB11111111FVM Dimensions x 22n 22z 24n00010G21212124FVMH (inches)42n53v53v59xGCD( OPENING)2(SERVICE ACCESS)38 11 82496 01 5002 00

INSTALLATION INSTRUCTIONSFan Coils: FVM4XHEATER PACKAGESFactory approved, field installed, UL listed heaterpackages are available from the equipment supplier. Seeunit rating plate for a list of factory approved heaters.Heaters that are not factory approved could causedamage which would not be covered under theequipment warranty.POSITION UNITUnit can stand or lie on floor, or hang from ceiling or wall.Allow space for wiring, piping, and servicing unit.CAUTION!If return air is to be ducted through a floor, install duct flushwith floor. Set unit on floor over opening.Side return is a field option on slope coil models. Cutopening per dimensions shown in Figure 2. Afield supplied bottom closure is required.PROPERTY DAMAGE HAZARDFailure to follow this caution may result in property damage.A field fabricated auxiliary drain pan, with a separate drain is REQUIRED for all installations over afinished living space or in any area that may bedamaged by overflow from a restricted main drainpan. In some localities, local codes require an auxiliary drain pan for ANY horizontal installation.Figure 2A. UPFLOW INSTALLATION!CAUTIONFailure to follow this caution may result in personalinjury.Sheet metal parts may have sharp edges or burrs.Use care and wear appropriate protective clothingand gloves when handling parts.Slope Coil Unit in Upflow ApplicationPOWER ENTRYOPTIONSFIELD SUPPLIEDSUPPLY DUCTLOW VOLTENTRYOPTIONSFRONT SERVICE CLEARANCE24 48 models 21”(533.4)60 model 24”(609.6)SLOPE COIL UNITMODEL SIZEAA COILUNITSUPFLOW/DOWNFLOWSECONDARY DRAINUPFLOW/DOWNFLOWPRIMARY DRAIN36” (914.4)19" (482.6)1½”(38.1)19”(482.6)2½”(63.5)AFIELD MODIFIEDSIDE RETURNLOCATION FORSLOPE COILUNITS ONLYUPFLOW/DOWNFLOWSECONDARY DRAINUPFLOW/DOWNFLOWPRIMARY DRAIN496 01 5002 00FIELD SUPPLIEDRETURN PLENUM3

INSTALLATION INSTRUCTIONSFigure 3Fan Coils: FVM4XModular Unit AssemblyB. MODULAR UNITSFVM fan coil sizes 4800 and 6000 are two piece modularunits. This allows for modular units to be disassembledand components moved separately to installation area forreassembly. This process accommodates small scuttleholes and limiting entrances to installation sites (refer toFigure 3).C. HORIZONTAL INSTALLATIONBLOWER BOXUnit must NOT be installed with access panels facing upor down. Access panels must only face to the side.2 SCREWSFVM models are factory built for horizontal left installation(refer to Figure 4 and Figure 5). They can be fieldconverted to horizontal right (accessory Gasket Kitrequired EBAC01GSK).2 SCREWSNOTE: When suspending unit from ceiling, dimples incasing indicate suitable location of screws for mountingmetal support straps (refer to Figure 4).REAR CORNERBRACKET2 SCREWSCOIL BOXFigure 4NOTE: For optimum condensate drainage performancein horizontal installations, unit should be leveled along itslength and width.Slope Coil In Horizontal Left Application (FVM factory configuration)A COILHORIZONTAL YDRAINFRONT SERVICE CLEARANCE(FULL FACE OF UNIT)24 48 models 21” (533.4)60 model 24”(609.6)SECONDARYDRAINLOW VOLTENTRYOPTIONS1¾” (44.45)FILTER ACCESSCLEARANCEPOWERENTRYOPTIONS4PRIMARYDRAIN496 01 5002 00

INSTALLATION INSTRUCTIONSFigure 5Fan Coils: FVM4XA Coil in Horizontal Left Application (FVM factory configuration)ACOILBRACKETFACTORY SHIPPEDHORIZONTAL LEFTAPPLICATIONCOILSUPPORTRAILBCDRAIN PANSUPPORTBRACKETCOILBRACKETHORIZONTALDRAIN PANPRIMARY DRAINHORIZONTAL LEFTAIR SEALASSEMBLYREFRIGERANTCONNECTIONSHorizontal Right Conversion of Units With SlopeCoils1. Remove blower and coil access panel and fittingpanel (refer to Figure 6).2. Remove coil mounting screw securing coilassembly to right side casing flange.3. Remove coil assembly.SECONDARY DRAINHORIZONTAL LEFT4. Lay fan coil unit on its right side and reinstall coilassembly with condensate pan down (refer toFigure 6).5. Attach coil to casing flange using coil mountingscrew previously removed.6. Make sure the pan cap in the fitting door is properlyseated on the fitting door to retain the low air leakrating of the unit.Horizontal Right Conversion Applications Slope CoilFigure 6COIL MOUNTINGSCREWBLOWERASSEMBLYCOIL SUPPORT RAILSLOPE COILDRAINPANREFRIGERANTCONNECTIONSPRIMARY DRAINSECONDARY DRAIN496 01 5002 005

INSTALLATION INSTRUCTIONSFan Coils: FVM4X7. Add gaskets from the Gasket Accessory Kit EBAC01GSK.Figure 78. Align holes with tubing connections andcondensate pan connections, and reinstall accesspanels and fitting panel. Make sure liquid andsuction tube grommets are in place to prevent airleaks and cabinet sweating.Conversion for Horizontal Right Applications A CoilAREFRIGERANTCONNECTIONSAIR AILCOILBRACKETBCDRAIN TALDRAIN PANPRIAMRY DRAINHORIZONTAL RIGHTSECONDARY DRAINHORIZONTAL RIGHTHorizontal Right Conversion of Units With A Coils1. Remove blower and coil access panel and fittingpanel (refer to Figure 7).2. Remove metal clip securing fitting panel tocondensate pan. Remove fitting panel.3. Remove two (2) snap in clips securing A coil inunit.4. Slide coil and pan assembly out of unit.5. Remove horizontal drain pan support bracket fromcoil support rail on left side of unit and reinstall oncoil support rail on right side of unit.6. Convert air seal assembly for horizontal right.a. Remove air seal assembly from coil by removingfour (4) screws (refer to Figure 7).b. Remove air splitter (B) from coil seal assembly byremoving three (3) screws. (factory shippedinset.)c. Remove filler plate (A) and install air splitter (B)in place of filler plate.d. Install filler plate (A) as shown in horizontal rightapplication.e. Remove condensate troughs (C) and install onopposite tube sheets.f. Install hose onto plastic spout.67. Install horizontal pan on right side of coil assembly.8. Slide coil assembly into casing. Be sure coilbracket on each corner of vertical pan engages coilsupport rails.9. Reinstall two (2) snap in clips to correctly positionand secure coil assembly in unit. Be sure clip withlarge offsets is used on right side of unit to securehorizontal pan.10. Remove two (2) oval fitting caps from left side ofthe coil, access panel, and fitting panel.11. Remove insulation knockouts on right side of coilaccess panel12. Remove two (2) oval coil access panel plugs andreinstall into holes on left side of coil access paneland fitting panel.13. Install condensate pan fitting caps (from Step 10)in the right side of the coil door making sure that thecap snaps and seats cleanly on the back side of thecoil door. Make sure no insulation interferes withseating of the cap.14. Reinstall access fitting panels, aligning holes withtubing connections and condensate panconnections. Be sure to reinstall metal clipbetween fitting panel and vertical condensate pan.15. After brazing, make sure liquid and suction tubegrommets are in place to prevent air leaks andcabinet sweating.496 01 5002 00

INSTALLATION INSTRUCTIONSF. DOWNFLOW INSTALLATION!CAUTIONPRODUCT OR PROPERTY DAMAGE HAZARDFailure to follow this caution may result in productor property damageThe conversion of the fan coil to downflow requires special procedures for the condensatedrains on both A coil and Slope coil units. Thevertical drains have an overflow hole between theprimary and secondary drain holes. This hole isplugged for all applications except downflow, andmust be used for downflow.Failure to follow instructions could result in personal injury or product and property damage.In this application, field conversion of the evaporator coilis required using accessory Downflow Kit along with anaccessory Base Kit. Set unit on floor over opening anduse 1/8” (3.175) to 1/4” (6.35) thick fireproof resilient gasketbetween duct, unit, and floor. Refer to installationinstructions packaged with accessory kit. See ProductSpecification literature for kit part numbers.Fan Coils: FVM4X3. Recommended method of securing for typicalapplications:a. If fan coil is away from wall, attach pipe strap totop of fan coil using No. 10 self tapping screws.Angle strap down and away from back of fan coil,remove all slack, and fasten to wall stud ofstructure using 5/16” (7.9375) lag screws. Typicalboth sides of fan coil.b. If fan coil is against wall, secure fan coil to wallstud using 1/8” (3.175) wide right angle brackets.Attach brackets to fan coil using No. 10 selftapping screws and to wall stud using 5/16” (7.9375)lag screws (refer to Figure 8).Figure 8Mobile Home or ManufacturedHousing Applications4” MAX(101.6)SECURE FAN COIL TO STRUCTUREUNIT AWAY FROM WALLPIPE STRAP(TYPICAL BOTH SIDES)ORUNIT AGAINST WALL1/8” (3.175) THICKANGLE MOUNTINGBRACKET(TYPICAL BOTH SIDES)During the conversion process, removed the plastic capcovering the vertical drains only and discard.Remove the plug from the overflow hole and discard.At completion of the downflow installation, caulk aroundthe vertical pan fitting to door joint to retain low air leakperformance of the unit.NOTE: Gasket kit number (EBAC01GSK) is alsorequired for all downflow applications to maintain low airleak/low sweat performance.G. MANUFACTURED HOUSING AND MOBILE HOMEAPPLICATIONS1. Fan coil unit must be secured to the structureusing field supplied hardware.2. Allow a minimum of 24” (609.6) clearance fromaccess panels.DOWN FLOWBASE KITSECURE UNIT TO FLOORANGLE BRACKET OR PIPE STRAP4” MAX(101.6)AIR DUCTSConnect supply air duct over the outside of ¾” (19.05 )flanges provided on supply air opening. Secure duct toflange using proper fasteners for type of duct used, andseal duct to unit joint.Duct connections flanges are provided on unit airdischarge connection.When using FVM units with 20kW, 24kW, and 30kWelectric heaters, maintain a 1” (25.4) clearance fromcombustible materials to discharge plenum and ductworkfor a distance of 36” (914.4) from unit. Use accessorydownflow base to maintain proper clearance on downflowinstallations.connection. Duct work passing through unconditionedspace must be insulated and covered with vapor barrier.Duct work Acoustical TreatmentMetal duct systems that do not have a 90 degree elbowand 10 feet of main duct before first branch takeoff mayrequire internal acoustical insulation lining. As analternative, fibrous duct work may be used if constructedand installed in accordance with the latest edition ofSMACNA construction standard on fibrous glass ducts.Both acoustical lining and fibrous duct work shall complywith National Fire Protection Association as tested by ULStandard 181 for Class 1 air ducts.Use flexible connectors between duct work and unit toprevent transmission of vibration. When electric heater isinstalled, use heat resistant material for flexibleconnector between duct work and unit at discharge496 01 5002 007

INSTALLATION INSTRUCTIONSFan Coils: FVM4XELECTRICAL CONNECTIONSOn units with a factory installed disconnect with pull outremoved, service and maintenance can be safelyperformed on only the load side of the control package.NOTE: Before proceeding with electrical connections,make certain that supply voltage, frequency, phase, andcircuit ampacity are as specified on the unit rating plate.See unit wiring label for proper field high and low voltagewiring. Make all electrical connections in accordance withthe NEC and any local codes or ordinances that mayapply. Use copper wire only. The unit must have aseparate branch electric circuit with a field supplieddisconnect switch located within sight from, and readilyaccessible from the unit.!WARNINGB. 24V CONTROL SYSTEMControl System Connections to Fan Control BoardRefer to unit wiring instructions for recommended wiringprocedures. Use 18 AWG color coded, insulated (35 Cminimum) wires to make the low voltage connectionsbetween the thermostat, the unit, and the outdoorequipment. If the thermostat is located more than 100 feetfrom the unit (as measured along the low voltage wire),use 16 AWG color coded, insulated (35 C minimum)wire. Fan Control Board is circuited for single stageheater operation. When additional heater staging isdesired using outdoor thermostats of Heat Staging,remove Jumper J2 on Fan Control Board to enablestaging.ELECTRICAL SHOCK or UNIT DAMAGE HAZARDAll wiring must be NEC Class 1 and must be separatedfrom incoming power leads. Refer to outdoor unit wiringinstructions for additional wiring recommendations.Failure to follow this warning could result in personal injury or death.Connect low voltage leads to thermostat and outdoorunit (refer to Figure 9, Figure 10, Figure 11, Figure 12).Turn off the main (remote) disconnect device before working on incoming (field) wiring .Incoming (field) wires on the line side of the disconnect found in the fan coil unit remain live, evenwhen the pull out is removed. Service and maintenance to incoming (field) wiring cannot be performed until the main disconnect switch (remoteto the unit) is turned off.C. HEAT STAGING!WARNINGELECTRICAL SHOCK or UNIT DAMAGE HAZARDFailure to follow this warning could result in personal injury, death, and/or unit damage.If a disconnect switch is to be mounted on unit, select a location where drill and fasteners will notcontact electrical or refrigeration components.A. LINE VOLTAGE CONNECTIONSIf unit contains an electric heater, remove and discardpower plug from fan coil and connect male plug fromheater to female plug from unit wiring harness. (Refer toElectric Heater Installation Instructions.) For units withoutelectric heat:1. Connect 208/230V power leads from fielddisconnect to yellow and black stripped leads.2. Connect ground wire to unit ground lug.Check all factory wiring per unit wiring diagram andinspect factory wiring connections to be sure none wereloosened in transit or installation.8Heat Staging OptionHeat Staging of the electric heat package is possiblewhen the FVM is installed as a part of a s

INSTALLATION INSTRUCTIONS Fan Coils FVM4X “B” Series These instructions must be read and understood completely before attempting installation. DANGER, WARNING, CAUTION, and . 2400 15 11 19 15 22 17 21 3600 19 11 19 19 22 21 21 4800 19 11 19 19 22 21 21

Related Documents:

calculation. FAN SPEED 0000 RPM Displays fan real time speed based on the fan frequency reading. FAN OUTPUT FREQUENCY 000.0 Hz Displays the output frequency of the fan inverter. FAN OUTPUT CURRENT 000.0 A Displays the output current of the fan inverter. FAN OUTPUT VOLTAGE 000.0 V Displays output voltage of the fan inverter. FAN OUTPUT POWER

These units are designed to meet the low air leak ts need special attention in the condensate pan and drain connection area and when brazing tubing. Four fan coil sizes will combine with various outdoor unit sizes to offer systems ranging from 1½ -- 5 tons (18,000

3.2.4. Cooling Coils 6 3.2.5. Refrigerant Coils 6 3.2.6. Enclosed Style Casing 6 4. Operation 7 4.1. Water Coils 7 4.2. Steam Coils 7 5. Maintenance 8 5.1. Maintenance Schedule 8 . Heating and cooling coils comprise a matrix of copper tubes supported in tube end plates and associated casing work. The tube matrix carries thin continuous fins .

b. "High": Fan operates continuously at high speed. Heat strip cycles On and Off. c. "Auto": Fan operates in low speed and will cycle On and Off with thermostat. F. "Fan" - Fan Mode 1. There are 3 fan speeds in Fan mode. a. "Low": Fan operates continuously at low speed. b. "High": Fan operates continuously at high speed.

standard steam coils. Steam distributing coils are tube within a tube design and are often referred to as “non-freeze” coils. This really is a misnomer, because under the right conditions, you can freeze any type of coil. Steam distributing coils are generally used when

MSD IGNITION www.msdignition.com (915) 857-5200 FAX (915) 857-3344 COIls The MSD 6M-2 Ignition can be used with most stock coils and aftermarket coils designed to replace the stock coils. There are some "race only" coils such as the MSD Pro Power Coil, PN 8201, that cannot be used with a 6 Series MSD Ignition Control. For more .

common coil shapes are pancake coils and racetrack coils. Pancake coils are circular bifilar coils that contain two closely spaced, parallel windings. The name” racetrack" coil arises because at each end the superconductor loops around 180 like the end of a race track. Pancake coils wound using HTS are a viable design option for spatially

start again from scratch the next Weak processing speed Poor short-term memory Emotional impacts Difficulties processing visual material. 01/04/2016 14 How can dyslexia affect music? Commonly reported difficulties with music Reading musical notation (especially sight reading and singing) Learning new music quickly Rhythmical difficulties especially from notation .