TECHNICAL BULLETINLogix 500si Series Digital PositionerFCD LGENTB0056-02 – 09/13Experience In Motion

Logix 500si Series FCD LGENTB0056-02 09/13500si Series Digital PositionersFigure 1: Logix 500si SeriesOptional semi-integratedmounting manifold4-20 mAOptional gaugeblock moduleOptionaldouble-actingmoduleThe Flowserve Logix 500si is the next generation of intrinsicallysafe digital positioners, which builds on the success of the Logix500 design. The Logix 510si series serves the analog (4–20 mA) market, whileoffering all of the benefits of digital technology, such as simple,push-button calibration, diagnostics, etc. The Logix 520si is a “smart” positioner, which can communicatevia the HART communications protocol.The Logix 500si series is built with the needs of the customer inmind, and offers several benefits and features, including:Simple Calibration/Configuration – Status information, configuration, and diagnostic options are easy and convenient to access. TheLogix 500si can be configured and calibrated without the use of anyadditional handheld device or configuration/calibration tool.Semi-Integrated (SI) Mounting – The Logix 500si mountingdesign is simple, easy to install and maintain, and reduces thechance of injury.Low Price – Logix 500si customers benefit from Flowserve’s globalsourcing capabilities, and receive a robust digital positioner at anexceptional price.2Compact, lightweight, modular design – The Logix 510si and520si use the same lightweight, compact housings and mountinghardware. All optional accessories, such as limit switches and sidemounted double-acting modules can be used on all models of theLogix 500si family. Modularity is our strength.

Logix 500si Seires FCD LGENTB0056-02 09/13510si and 520si Digital PositionersFeatures and AdvantagesLogix510siLogix520siCommissioning is performed by simply setting a few switches and pressing the QUICK-CALbutton. The Direct User Interface provides local access to positioner control without requiringmulti-level menus, a handheld communicator or laptop computer. Local Status LEDsLEDs, visible from a distance, indicate the positioner’s current status without removing thecover. Internal Diagnostic CodesLEDs provide instant information relating to internal diagnostic codes. These codes indicateto the user positioner status and alarms without the need for a handheld communicator orlaptop computer. Fast and Simple ConfigurationWith its unique Direct User Interface, the Logix 500si positioner provides fast and easyconfiguration. Local configuration switches allow the user to set all basic parameters forpositioner operation, such as output characteristic (e.g. equal percent, linear or custom), airaction, signal direction, gain, tuning, etc. Calibration typically takes less than one minute. Jog CalibrateThe jog calibrate function allows the user to easily and quickly calibrate the positioner on allactuators without physical stroke stops. Auto TuneAdapting the response of the Logix 500 series positioner to a particular valve configurationis as simple as pressing a button. The Logix 500 positioner has a built-in auto-tuning function that, when enabled, quickly adjusts the response to match the valve and actuator. If theautomatic tuning does not match the needs of the process, it can be modified in seconds byselecting a less aggressive auto-tune (gain) setting from the local user interface. Once set,the tuning is fixed until the next time an auto-tune is performed. HART CommunicationUsing industry standard HART protocol, the Logix 500si positioner can use existing handheld communicators and supply extensive information to maintenance database softwarepackages.Low Air ConsumptionState-of-the-art piezo technology combined with inner-loop feedback produces high-performance control with minimal air consumption.21-Point CharacterizationWith SoftTools software or a handheld communicator, a custom 21-point characterizationcurve can be generated that can be used to change the response of the positioner to meetthe process requirements. DiagnosticsSoftTools allows the user to gather detailed diagnostic information regarding valve performance and positioner condition, in addition to the LED status codes. Two-Stage Control DesignPositioner uses two-stage control to provide faster response and tightercontrol.Configuration LockoutConfiguration lockout option in SoftTools permits users to perform automatic calibrationprocedures without modifying existing configuration and tuning settings.NAMUR and VDI/VDENAMUR and VDI/VDE mounting interfaces provide direct standardized mounting to variouslinear or rotary actuators. Brackets are available for non-NAMUR actuators. Compact and LightweightThe positioner’s compact design allows it to be installed on smaller actuators.Multiple Limit Switch OptionsModular design allows reliable, inexpensive, non-contact, high resolution limit switches. Self-Adjusting LinkageConnecting the position feedback linkage of the Logix 500 series positioner to an actuatoris simplified by the ability of the feedback arm to rotate 360 and adapt to any shaft rotationangle between 15 and 100 at any orientation. FeaturesAdvantagesEasy Commissioning 3flowserve.com

Logix 500si Series FCD LGENTB0056-02 09/13510si Series Digital PositionersIntroductionFigure 2: Logix 510si Digital PositionerLED StatusLightsConfigurationDIP SwitchesQUICK-CALButtonJogCalibrateButtonsGain Selector4-20 mA InputThe Flowserve Logix 510si series are single-acting, user-friendlydigital positioners. As with all positioners in the Logix 500si family,the Logix 510si uses the latest piezo-technology with inner-loopfeedback to produce an improved dynamic behavior. The completeconfiguration can be made by DIP switches on the device. Differentgain values allow the best setup for each individual actuator size.4Optional 4-20 mAFeedbackThree colored LED indicators continuously indicate the positionerstatus. Fast calibration and setup can be achieved by simplypressing the QUICK-CAL button. Interchangeable components suchas circuit board, piezo-drivers, etc., allow an easy and economicalupgrade or repair. Optional 4–20 mA analog feedback circuit andproximity limit switches complete the Logix 510si.

Logix 500si Seires FCD LGENTB0056-02 09/13510si Series Digital PositionersPrinciple of OperationFigure 3: Logix 510si Digital Positioner Schematic2) Electro-pneumatic Converter ModuleFilter / Regulatorfor Supply Air22–87 psi (1.5–6.0 bar)Air SupplyPressure RegulatorInner LoopPiezo Control - 4–20 mAInput4–20 mAOutputInner LoopPosition FeedbackMicroprocessor(0ptional)Piezo eControl Valve1) Digital Control CircuitThe Flowserve Logix 510si positioner is a digital positioner operated with an analog 4–20 mA input signal. The positioner consistsof three main modules: 1) the microprocessor-based electroniccontrol module with optional analog feedback and direct local userinterface switches; 2) the piezo-valve-based electro-pneumaticconverter module; and 3) the infinite resolution valve positionsensor.Figure 3 shows the principle of operation of the Logix 510si. Theanalog 4–20 mA command signal is passed to the microprocessor,where it is compared to the measured valve stem position. Thecontrol algorithm in the processor performs dual gain calculationsand produces an output command to the analog piezo valve, whichdrives the pneumatic amplifier. The pilot valve position in the pneumatic amplifier is measured and relayed to the inner loop control3) Valve Position Sensorcircuit. This two-stage control provides for a more responsiveand tighter control than is possible with a single-stage controlalgorithm.The pneumatic amplifier controls the airflow to the actuator. Thechange of pressure and volume of the air in the actuator causesthe valve to stroke. As the valve approaches the desired position,the difference between the commanded position and the measuredposition becomes smaller and the output to the piezo is decreased.This, in turn, causes the pilot valve to close and the resultingairflow to decrease, which slows the actuator movement as itapproaches the new command position. When the actuator hasreached the desired position, the pneumatic amplifier output is heldat zero, which holds the valve in a constant position.5flowserve.com

Logix 500si Series FCD LGENTB0056-02 09/13510si Series Digital PositionersSelf Diagnostic FeaturesThe Flowserve Logix 510si digital positioner automatically providesusers with comprehensive, detailed diagnostic information. ColoredLEDs continuously indicate positioner status or health duringnormal operation or calibration. This information can be used todetermine whether a valve is functioning properly or needs service.In total, 28 different status situations can be displayed, e.g.: Normal operation, no internal problems Device is undergoing calibration Calibration error detected Deviation error detected Internal electronic board errorSpecificationsTable 6: Performance Characteristics (typical)Table 1: Input SignalInput Signal Range4–20 mALinearity 1.0%Compliance Voltage6.0 VDCResolution 0.3%Voltage Supply (maximum)30 VDCRepeatability 0.5%Minimum Required Operating Current3.6 mADeadband 0.5%Table 2: Stroke OutputFeedback Shaft RotationTable 7: Environmental ConditionsMinimum 15 , Maximum 90 ,40 recommended for linearapplicationsTable 3: Supply AirSupply Air QualityFree from moisture, oil and dust perIEC 770 and ISA-7.0.01Input Pressure Range22–87 psi (1.5 to 6.0 bar)Air Consumption(steady state)0.047 SCFM @ 22 psi0.08 Nm3/h @ 1.5 bar0.071 SCFM @ 87 psi0.120 Nm3/h @ 6.0 barTable 4: Output SignalOutput Pressure Range0–100% of supply air pressureOutput Flow Capacity(@ input pressure)1.41 SCFM @ 22 psi2.4 Nm3/h @ 1.5 bar4.12 SCFM @ 87 psi7.0 Nm3/h @ 6.0 barTable 5: Shipping Weights (includes mounting kit)6With Pressure Gauges3.5 lb. (1.6 kg)Without Pressure Gauges2.7 lb. (1.2 kg)Operating TemperatureStandard-4–176 F-20–80 CLow-40–176 F-40–80 CTransport and Storage Temperature-40–176 F-40–80 COperating Humidity0–100% non-condensingTypeNEMA 4, NEMA 4X, IP65Table 8: Hazardous Area SpecificationsATEXII 1G EEx ia II C T6Certificate No. Sira03ATEX2243Non-incendiveFMClass 1, Division 2Groups A, B, C, DTemp. Class. T4 Ta 85 CIntrinsic SafetyFMClass 1, Division 1Groups A, B, C, DTemp. Class. T4 Ta 85 CTable 9: Physical SpecificationsHousing MaterialCast aluminum,powder-paintedSoft GoodsNitrileWeight2.7 lb. (1.2 kg)

Logix 500si Seires FCD LGENTB0056-02 09/13520si Series Digital (HART) PositionersIntroductionFigure 4: Logix 520si Digital D Status LightsAuto TuneSwitchJog Button4–20 mA inputwith HART CommunicationsThe Flowserve Logix 520si series digital positioners with HARTcommunications capability are simple-to-use single-acting digitalpositioners. They combine state-of-the-art piezo valve technologywith inner-loop feedback that provides high-performance controlwith minimal air consumption. The Logix 520si positioner is quicklyand easily configured at the valve. The essential configurationsettings do not require a hand-held device or a host system. Highlyvisible LED status lights allow the user to diagnose the conditionof the valve at a glance. The Logix 520si positioner can be easilyconfigured at the valve via the push-buttons and DIP switches,using a HART 275/375 handheld communicator, or with SoftTools software for diagnostics, alarms and communications.Similar in cost to an analog I/P positioner, the Logix 520si seriesdigital positioners provide quick setup and calibration, as wellas high-performance digital communications. With its versatilemounting options, the Logix 520si digital positioner offers a costeffective retrofit solution for applications requiring communication(HART protocol) and diagnostics for single-acting actuators fromany manufacturer.When used with Flowserve’s SoftTools software, the Logix 520sipositioner provides a wealth of information and functionality tothe user, including 21-point characterization, dual-gain tuning,signatures for diagnostic purposes, and performance and accuracymeasurements.7flowserve.com

Logix 500si Series FCD LGENTB0056-02 09/13520si Series Digital PositionersPrinciple of OperationFigure 5: Logix 520si Digital Positioner Schematic2) Electro-pneumatic Converter ModuleFilter / Regulatorfor Supply Air22–87 psi (1.5 – 6.0 bar)Supply AirPressure RegulatorInner LoopPiezo Control - 4–20 mA HARTHARTInner LoopPosition FeedbackMicroprocessorPiezo ValveGainLocalUserInterface1) Digital Control CircuitThe Flowserve Logix 520si positioner is a digital positioner thatincorporates the HART protocol for communication. The positionerconsists of three main modules: 1) the microprocessor-basedelectronic control module includes HART communications anddirect local user interface switches; 2) the piezo-valve-basedelectro-pneumatic converter module; and 3) the infinite resolutionvalve position sensor.The basic positioner operation is best understood by referring toFigure 5. The complete control circuit is powered by the two-wire,4–20 mA command signal. The HART module sends and receivesthe Frequency Shift Key (FSK) HART digital communications superimposed over the 4–20 mA signal wires, providing two-way digitalcommunications to the microprocessor.8PneumaticAmplifierThe analog 4–20 mA command is passed to the microprocessor,where it is compared to the measured valve stem position. Thecontrol algorithm in the processor performs dual gain controlStrokeControlValve3) Valve Position Sensorcalculations and produces an output command to the analog piezovalve, which drives the pneumatic amplifier. The pilot valve positionin the pneumatic amplifier is measured and relayed to the innerloop control circuit. This two-stage control provides for moreresponsive and tighter control than is possible with a single-stagecontrol algorithm.The pneumatic amplifier controls the airflow to the actuator. Thechange of pressure and volume of the air in the actuator causesthe valve to stroke. As the valve approaches the desired position,the difference between the commanded position and the measuredposition becomes smaller and the output to the piezo is decreased.This, in turn, causes the pilot valve to close and the resulting flowto decrease, which slows the actuator movement as it approachesthe new command position. When the valve actuator is at thedesired position, the pneumatic amplifier output is held at zero,which holds the valve in a constant position.

Logix 500si Seires FCD LGENTB0056-02 09/13520si Series Digital PositionersSelf Diagnostic FeaturesThe Flowserve Logix 520si digital positioner automatically providesusers with comprehensive, detailed diagnostic information. ColoredLEDs continuously indicate positioner status or health duringnormal operation or calibration. This information can be used todetermine whether a valve is functioning properly or needs service. Travel limit is exceededSome of the conditions detected include: Manual override in progress Device has exceeded upper or lower travel limits Device is undergoing calibration Calibration error detected Board current too high Normal operation, no internal problems Internal temperature limit exceeded Cycle limit is exceededSpecificationsTable 15: Performance Characteristics (typical)Table 10: Input SignalInput Signal Range (with HART)4–20 mALinearity 1.0%Compliance Voltage (with HART signal)9.5 VDCResolution 0.1%Voltage Supply (maximum)30 VDCRepeatability 0.2%Minimum Required Operating Current3.6 mADeadband 0.2%Table 11: Stroke OutputFeedback Shaft RotationTable 16: Environmental ConditionsMinimum 15 Maximum 90 40 recommended for linearapplicationsTable 12: Supply AirSupply Air QualityFree from moisture, oil and dust perIEC 770 and ISA-7.0.01Input Pressure Range22–87 psi (1.5 to 6.0 bar)Air Consumption(steady state)0.047 SCFM @ 22 psi0.08 Nm3/h @ 1.5 bar0.071 SCFM @ 87 psi0.120 Nm3/h @ 6.0 barOperating TemperatureTransport and StorageTemperature0–100% of supply air pressureOutput Flow Capacity(@ input pressure)1.41 SCFM @ 22 psi2.4 Nm3/h @ 1.5 bar4.12 SCFM @ 87 psi7.0 Nm3/h @ 6.0 barTable 14: Shipping Weights (includes mounting kit)With Pressure GaugesWithout Pressure Gauges-40–176 F-40–80 C-40–176 F-40–80 COperating Humidity0–100% non-condensingTypeNEMA 4, NEMA 4X, IP65Table 17: Hazardous Area SpecificationsATEXII 1G EEx ia II C T6Certificate No. Sira03ATEX2243Non-incendiveFMClass 1, Division 2Groups A, B, C, DTemp. Class. T4 Ta 85 CIntrinsic SafetyFMClass 1, Division 1Groups A, B, C, DTemp. Class. T4 Ta 85 CTable 13: Output SignalOutput Pressure RangeStandardTable 18: Physical SpecificationsHousing MaterialCast aluminum, powder-painted3.5 lb. (1.6 kg)Soft GoodsNitrile2.7 lb. (1.2 kg)Weight2.7 lb. (1.2 kg)9flowserve.com

Logix 500si Series FCD LGENTB0056-02 09/13520si Series Digital PositionersSoftTools InterfaceIntroduction to SoftTools SoftwareFlowserve’s SoftTools Suite software helps manage field devicesby combining features of field network hardware and a variety ofcommunication protocols with the performance of Flowserve Logix520si digital positioners. SoftTools Suite is a complete softwarepackage, featuring device status, configuration and calibrationscreens. Additionally, the user can access customized reports forall configuration, calibration and event data. SoftTools softwareopens the ‘window’ to the device and allows immediate views withlive feedback on all active device sensors including valve stem position, control signal, and other important process metrics. Multipleinstances of the software can be run simultaneously, addressingunique positioners. Up to 33 field devices can be viewed simultaneously, allowing the control professional to study cause and effectscenarios.Note: SoftTools is available for download from www.flowserve.com.ConfiguratorLogix 520si configurations can be savedsecurely in a database file. By uploading apositioner configuration, the informationis automatically saved and written to diskon the workstation. SoftTools softwareallows the user to selectively query thedatabase to isolate or identify specificconfigurations. Therefore, the user can sortby any number of parameters including tagnumber, valve size or type, trim type, flowdirection, and liquid or gas application.SoftTools software also allows the user toeasily upload a configuration from the positioner. This means that a new replacementpositioner can be identically configuredwith the simple click of a mouse once thecorrect configuration has been identified.The configurator enables users to editindividual configurations, export to wordprocessors and spreadsheets and importfrom other files. It also allows the user toformat and print a positioner configurationreport (Figure 6).10Figure 6: ConfiguratorSoftTools software enables communication between the softwaresuite of tools and field device networks using the HART protocoland provides access to the diagnostic information from fielddevices. Using the MTL or ELCON brand HART multiplexer, userscan access more than 63,000 Logix HART positioners from a singleworkstation. Additionally, the software includes an active databaseto capture configuration, calibration history and event logging foreach digital positioner addressed through the software.Users can now obtain a new level of detailed diagnostic informationwith SoftTools software. Diagnostic tests and functions (formallyavailable only in strap-on diagnostic testers) are now part of thefunctionality. The software retains the traditional signature andlogging features made popular in previous Flowserve software andadds scheduled polling for device alarms, critical diagnostic testsfor friction, and performance analysis of positioners.

Logix 500si Seires FCD LGENTB0056-02 09/13520si Series Digital PositionersSoftTools Interface21-point Characterization CurveFigure 7: 21-point Characterization CurveWith SoftTools software, the user canadjust a 21-point characterization curve(Figure 7) to change the response of thepositioner in order to meet the processrequirements. The output of each controlpoint is independent, allowing the user tocreate a custom curve with very high resolution. This customized curve can be savedin the memory of the Flowserve Logix520si, and either activated or overriddenwith a simple on-board selector switch.TuningUnlike other positioners that offer only onegain setting, the Logix 520si positionerprovides dual-gain tuning. This allows theuser to tune the positioner to make largestep changes with minimal overshoot,while achieving the resolution to respond tovery small step changes. The Logix 520sipositioner not only provides several presetgain settings, it also allows the user todevelop custom settings for a wide rangeof actuator sizes and types. Tuning sets canbe configured, or selected with the HART275/375 hand-held, SoftTools, or directlyfrom the user interface on the positioner.Figure 8: Manual Tuning with User InterfaceBy setting the Auto Tune on/off DIP switch,the tuning mode can be changed frommanual to auto. The Auto Tune procedurecycles the actuator (Figure 8) to produce ameasured response and selects those gainvalues that provide appropriate actuatorperformance. The Auto Tune functionincludes a gain modifier selector thatcan be used to increase or decrease thecalculated gain in order to achieve optimalperformance.11flowserve.com

Logix 500si Series FCD LGENTB0056-02 09/13Figure 9: Ramp Open Test520si Series Digital PositionersSoftTools, Signatures and Performance TestingSignaturesThe Flowserve Logix 520si positioner is designed to assure thatdata is easily gathered, stored and compared to historical valvedata so the user can determine the performance of critical valves.Figure 10: Signature ComparisonWith SoftTools software a user-defined signature ramp (Figure 9)or step response test can be generated with a Logix 520si positioner. Signatures can be saved and cataloged (and later retrieved)for comparison (Figure 10) with a more recent signature.SoftTools software allows a user to easily overlay valve signaturesand compare current performance with past performance over aparticular time period. This allows the user to determine if degradation has occurred over time on critical valves. It also allows theuser to compare historical data and determine if a valve needs tobe pulled for maintenance. User-defined steps (large or small) canbe tested and stored—large steps for speed and small steps forresolution and precision. Internal sensors allow the user to test theresponse and health of the valve at any time.Figure 11: Performance TestPositioner PerformanceStatic performance and accuracy measures such as hysteresis,deadband, linearity, and repeatability can be obtained with theLogix 520si positioner. These values can be graphically depicted,stored and later retrieved for comparative analysis (Figure 11).500si Series Digital PositionersLimit Switches and Position TransmitterLimit Switches (Optional)Position TransmitterThe modular design of the FlowserveLogix 500si allows the use of two optionalinternal limit switches. This innovative,robust package provides the followingfeatures:The analog position transmitter (optional)provides an infinite-resolution 4–20 mAfeedback signal proportional to the valveposition throughout the complete strokelength. Innovative, reliable technology Automatically calibrated for 0% to 100%. Several limit switch options available: Easy to calibrate for other configurations.- Mechanical SPDT switches- Proximity (reed)- Namur slotted sensors Wide range of adjustment12Figure 12: Optional Internal Limit SwitchesLimit Switches on Circuit BoardThis option is currently only available for theLogix 510si series.Analog Output Board(4–20 mA Transmitter) Option Intrinsically safe switches availableSupply9–20 VDC High resistance to shock and vibrationOutput4–20 mA Limit sensing using two-wire sensor inaccordance with NAMUR standardsResolution0.1%Linearity full span 0.5% Infinite resolution of trip pointOutput current limit30 mA DCThis option is available for the Logix 510siand the Logix 520si series.Load impedance800 Ω @ 24 VDCFigure 13: Position Transmitter ConnectionOptional 4-20 mA Feedback

Logix 500si Seires FCD LGENTB0056-02 09/13Logix 500si Limit Switch OptionsModelOptionTemperatureRatingSwitch TypeContactsRatings1Mechanical LimitSwitchSPDT3 A/125 VAC, 2 A/30 VDC2Reed SwitchSPST3NAMUR V3 TypeProximity Switch,P F NJ2-V3-NSolid StateSlot-type NAMURsensor, P F SJ2S1NSolid StateSlot-type NAMURsensor, P F SJ2 SNSolid State-13ºF to 185ºF(-25ºC to 85ºC)Current: 0.5 A Switching/1.2 A Carrying456Slot-type NAMURsensor, P F SJ2NVoltage: 200 VDC maximumSwitching/250 VDC minimum BreakdownLoad Current Target Present: 1 mALoad Current Target Absent: 3 mA (15 mA max.)Supply Voltage: 5–25 VDCLoad Current Target Present: 1 mALoad Current Target Absent: 3 mASupply Voltage: 5–25 VDCLoad Current Target Present: 1 mALoad Current Target Absent: 3 mASupply Voltage: 5–25 VDCLoad Current Target Present: 1 mASolid StateLoad Current Target Absent: 3 mASupply Voltage: 5–25 VDCSpecial Notes-40ºF to 221ºF(-40ºC to 105ºC)-14ºF to 212ºF(-26ºC to 100ºC)-13ºF to 212ºF(-25ºC to 100ºC)-40ºF to 212ºF(-40ºC to 100ºC)-13ºF to 212ºF(-25ºC to 100ºC)Normally Open. For usein “Control Safe” I.S.installations.Normally Closed. Foruse in “Control Safe” I.S.installations.Standard Switch. For usein standard I.S. installations.Certifications: Limit switches are intrinsically safe when installed per appropriate Logix 500si IOM instructions and device entity parameters.U.S. Switch Option Certifications are pending.500si Series Digital PositionersMounting OptionsThe Flowserve Logix 500si series digitalpositioners feature a versatile mountingsystem. Mounting kits are available forNAMUR standard on linear actuatorsand VDI/VDE 3845 for rotary actuators(Figure 14).Logix 500si positioners are also availablewith a semi-integrated mounting systemin accordance with the new VDI/VDE3847 standard (Figure 18). This eliminatesexposed linkages while allowing easyaccess to mounting screws from theexterior for fast and easy service.Figure 14: Logix 500si Series Positioner mountedon Valtek MaxFlo 3 Eccentric Rotary PlugControl Valve.Figure 15: Logix 500si Series Positioner mountingon a Kammer Control Valve Acc. to VDI/VDE 3847.Figure 16: Logix 500si Series Positioner withDouble-Acting Module mounted on a Mark OneValve Assembly.The unique mounting of the positioner tothe FlowTop actuators (Figure 18) meansthat the positioner can be fitted to theactuator yoke for fail-closed operation withno exposed linkages, and without the needfor external piping.The Logix 500si digital positioner alsolends itself for mounting to any type ofdiaphragm actuator. Brackets are availablefor the most popular brands and sizes ofactuator.13Figure 17: Logix 500si Series Positioner Acc.Industry-standard VDI/VDE 3845 (DIN ISO 5211)Mounting.Figure 18: Logix 500si Series Positioner MountedDirectly on a FlowTop Valve Assembly.flowserve.com

Logix 500si Series FCD LGENTB0056-02 09/13Ordering GuideOptionChoiceCodeExample5No Remote Communications2HART0Standard diagnostics0Electronic Hardware Options12Communicationssi14ACCORD, Aluminum, Black11/2” NPT Conduit, 1/4” Pneumatic2M20 Conduit, 1/4” NPT Pnuematic31/2” NPT Conduit, 1/4” NPT Pnuemaitc, 1/4” NPT Aux Vent4M20 Conduit, 1/4” NPT Pnuematic, 1/4” Aux VentDStandard Linear - D ShaftRStandard VDI/VDE 3845 Rotary Shaft (NAMUR)SStandard -4 F to 185 C (-20 C to 85 C) (Available on 510 model only)EExtended -40 F to 185 F (-40 C to 85 C)EEnglish-0No Indicator-FFlat Indicator-DDome Indicator0None0No Add-In CircuitsF4-20mA Position Feedback (available on 510 model only)0No Switches1Mechanical Limit Switches2Reed Switches3NAMUR V3 Type Proximity Switch, P&F NJ2-V3-N4Slot Type NAMUR Sensor, P&F SJ2-S1N5Slot Type NAMUR Sensor, P&F SJ2-SN6Slot Type NAMUR Sensor, P&F SJ2-N0Limit Switches-A0Add-In ElectronicsFlowserve, Aluminum, Black0Special OptionsFlowserve, Aluminum, Black with Yellow Cover-0Rotary Indicator-Y-BELanguageFlowserve, Aluminum, Black with White CoverEOperating TemperatureATEX II 1 G Ex ia IIC-WDFeedback ShaftGeneral Purpose-151Threaded Connections-14-WHousing and Brand LabelFM/CSA Intrinsically Safe Class I Div 1 Groups A,B,C,DFM/CSA Non-Incendive, Class I Div 2 Groups A,B,C,D-14Certifications-02-08

Manifold and Gauge OptionsOrdering InformationGauge OptionsManifold OptionsLogix 500si Seires FCD LGENTB0056-02 09/13XXXMMNManifold Options (MM)No Manifold00Double ActingDAGauge AdapterGAGauge Manifold - NPT ThreadsGMGauge Manifold - G ThreadsGCVDI/VDE 3847 Semi-Integrated ManifoldVEGauge Options (N)No GaugesOutput, PSI/BAR/KPA Stainless Steel with Brass Internals(qty. 1)Output Supply, PSI/BAR/KPA Stainless Steel with Brass Internals(qty. 2)Output Output PSI/BAR/KPA Stainless Steel with Brass Internals(qty. 2)Output, PSI/BAR/KPA Stainless Steel with Stainless Steel Internals(qty. 1)Output Supply, PSI/BAR/KPA Stainless Steel with Stainless Steel Internals(qty. 2)Output Output PSI/BAR/KPA Stainless Steel with Stainless Steel Internals(qty. 2)Output, Kg/Cm /PSI/Stainless Steel with Brass Internals(qty. 1)Output Supply Kg/Cm2/PSI Stainless Steel with Brass Internals(qty. 2)2Output Output, Kg/Cm /PSI Stainless Steel with Brass Internals(qty. 2)Output, KG/CM2/PSI Stainless Steel with Stainless Steel Internals(qty. 1)Output Supply, Kg/Cm2/PSI Stainless Steel with Stainless Steel Internals(qty. 2)Output Output, Kg/Cm /PSI Stainless Steel with Stainless Steel Internals(qty. 2)22Any KPA XXXAXXXBXXXDX6XX9XXXCXOutput Output Supply, PSI/BAR/KPA Stainless Steel with Brass Internals(qty. 3)XEOutput Output Supply, PSI/BAR/KPA Stainless Steel with Stainles

Auto Tune Adapting the response of the Logix 500 series positioner to a particular valve configuration is as simple as pressing a button. The Logix 500 positioner has a built-in auto-tuning func-tion that, when enabled, quickly adj

Related Documents:

Figure 1. Principle of Operation 5. Principle of operation The Logix 500si positioner is a digital positioner with various options. The positioner consists of three main modules: 1. The microprocessor-based electronic control module includes direct local user interface switches 2. The piezo valve-based electro-pneumatic converter module 3.

element is the Studio 5000 Logix Designer application. The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix 5000 controllers for discrete, process, batch, motion, safety, and drive-based solutions. The Studio 5000 environment is the foundation for the future ofFile Size: 1MBPage Count: 71Explore furtherEmulate a Studio 5000 Controller and Connect to a .www.dmcinfo.comStudio 5000 Logix Emulate (Virtual PLC) - PLC Programmin www.plctr.comDownload Center Rockwell Automation United Stateswww.rockwellautomation.comStudio 5000 Logix Emulate FactoryTalk United Stateswww.rockwellautomation.comStudio 5000 Design Software FactoryTalk United Stateswww.rockwellautomation.comRecommended to you based on what's popular Feedback

Valtek XL Series Positioner Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611 Figure 2: XL Series Positioner Mounted on Valtek Linear Actuator Figure 3: XL Series Positioner Mounted on Fisher 657 Actuator Calibration is easy using the XL positioner due to minimal interaction between zero and span. Also, the

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20 flowserve.com 10 2 SAFETY INFORMATION 2.1 Using This Document Product users and maintenance personnel should thoroughly review this manual before installing, operating, or performing any maintenance on the positioner. The following instructions are designed to assist in unpacking,

element is the Studio 5000 Logix Designer application. The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix 5000 controllers for discrete, process, batch, motion, safety, and drive -based solutions. The Stu

Programming Manual Original Instructions Logix 5000 Controllers EDS AOP Guidelines for Logix Designer . 1756

Any previous installation of RSLogix Emulate 5000 or Studio 5000 Logix Emulate upgrades when you install Studio 5000 Logix Emulate. Installing Studio 5000 Logix Emulate on a computer that has a SoftLogix 5800 controller installed is not allowed. Before you begin

Algae: Lectures -15 Unit 1: Classification of algae- comparative survey of important system : Fritsch- Smith-Round Ultrastructure of algal cells: cell wall, flagella, chloroplast, pyrenoid, eye-spot and their importance in classification. Structure and function of heterocysts, pigments in algae and Economic importance of algae. Unit 2: General account of thallus structure, reproduction .