Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20USER Logix 3800Digital PositionerFCD LGENIM0112-06 01/20flowserve.com1

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20This page intentionally left blank.

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20CONTENTS11QUICK START GUIDE . 42SAFETY INFORMATION . 103PRE-INSTALLATION . 124INSTALLATION – MOUNTING . 1745INSTALLATION - TUBING . 2356INSTALLATION – ELECTRICAL CONNECTIONS (HART). 2567INSTALLATION – ELECTRICAL CONNECTIONS (FF) . 3078OPERATION - HOW IT WORKS . 3289OPERATION – DIP SWITCH CONFIGURATION . 34910OPERATION – CALIBRATION AND CONTROL . 361011OPERATION – USER INTERFACE . 371112OPERATION – DIAGNOSTIC LEVELS . 411213MAINTENANCE – TROUBLESHOOTING . 421314MAINTENCANCE - REPAIR . 451415MAINTENANCE - HELP FROM FLOWSERVE . 491516POSITIONER SPECIFICATIONS. 501617HAZARDOUS LOCATION SPECIFICATIONS . 541718SIL 3 REQUIREMENTS FOR SAFETY INTEGRITY . 6418APPENDIX A – LCD MENU TREE OVERVIEW . 66AAPPENDIX B – LCD MENU TREE DESCRIPTIONS . 67BAPPENDIX C – PROGRAMMED FLOW CHARACTERIZATION OPTIONS . 74CAPPENDIX D – 4-BLINK STATUS CODES . 76DAPPENDIX E – STATUS CODE DESCRIPTIONS . 79EAPPENDIX F – HOT KEYS . 94APPENDIX G - HOW TO ORDER . 96flowserve.com323FG

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/2011.1QUICK START GUIDELogix 3800 Positioner FeaturesConduit(3x)Control ButtonsPressureGauges(3x)Grounding LugMain Cover Bolts(6x)ViewingWindowVentMounting BoltPatternsPort AContactlessFeedback ShaftSupplyPort BFigure 1: Logix 3800 External Positioner Features (EX and SS)flowserve.com4

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/201Main CoverBolts 011GroundingLug12131415Direct Mount BoltPattern1617Vent18Mounting BoltPatternsABPort ACDEFSupplyContactlessFeedback ShaftPort BFigure 2: Logix 3800 External Positioner Features (IS)flowserve.com5G

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20Menu Control Buttons(3x)Quick- CalibrationButtonGainSwitchConfigurationDIP Switches(8x)LCDDisplayLED Indicators(5x)HARTConnectorsDiscreteOutput (2)Analog InputDiscreteOutput (1)Analog Output4 – 20 mACommandDiscrete InputInternalRemote MountGrounding LugFigure 3: Logix 3820 (HART) Internal Positioner Featuresflowserve.com6

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/201234Quick- CalibrationButton5Menu Control Buttons(3x)678910GainSwitch1112ConfigurationDIP Switches(8x)131415LCDDisplay1617LED Indicators(5x)FFConnectors18ABCDEFGFF TerminalsFigure 4: Logix 3840 (Foundation Fieldbus) Internal Positioner Featuresflowserve.com7

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/201.2Safety1.4Set the configuration dip switches. See section 9, Operation –Dip Switch Configuration, for more detail.CAUTION: Before installation, read all safety relatedinformation in section 2 Safety Information.1.3ConfigurationAIR ACTION DIP SWITCH (ATO ATC)For increasing pressure in port A to open the valve (air toopen) select “ATO.” For increasing pressure in port A to closethe valve (air to close) select “ATC.”InstallationMOUNTINGSecurely mount the positioner to the actuator using the boltpattern on the back of the positioner or use the direct mountblock option. See section 4, Installation – Mounting, for moredetail.ACTUATOR SWITCH (DOUBLE SINGLE)For double-acting actuators select “DOUBLE.” For singleacting actuators, select “SINGLE.”FEEDBACKConnect feedback linkage. Align the follower arm to movefreely within the expected range of valve travel. Over-rotatingthe feedback shaft will not damage the unit.CHARACTERIZATION SWITCH (LINEAR OTHER)For a linear relationship between the command signal and theposition of the valve, select” LINEAR.” To customize thecharacterization curve, select “OTHER.” Other curves can bechosen using the LCD menu, a handheld device, or DTM. SeeAppendix C – Programmed Flow Characterization Options fora table and graph describing the “OTHER” options.PNEUMATIC CONNECTIONSConnect pneumatic ports A and B to the actuator. Port Ashould typically be connected to the side of the actuatoropposing the actuator spring. With air supplied, but noelectrical power to the system, port A will vent, and leave portB pressurized. For single acting actuators, connect to port Aand plug port B. See section 5, Installation - Tubing, for moredetail.AUTO TUNE SWITCH (TUNE ON TUNE OFF)For the QUICK-CAL calibration to automatically select customtuning parameters, select TUNE ON (preferred). For defaulttuning parameters, select TUNE OFF.JOG CALIBRATION SWITCH (CAL AUTO CAL JOG)For valves with a mechanical stop at the fully opened position(most valves), select CAL AUTO. For valves with nomechanical stop, select CAL JOG. This allows the user to setthe upper limit of travel by jogging the position manually.CAUTION: Connecting the supply air may cause the valveto move. Before connecting supply air, ensure the valve isisolated.Connect port S to a clean, filtered air supply. See section 16,Positioner Specifications, for air cleanliness specifications.ELECTRICAL CONNECTIONS (HART)VALVE STABILITY SWITCH (LO FRIC HI FRIC)For valves with normal friction, select LO FRIC. For valves withvery high friction, select HI FRIC.CAUTION: Connecting the 4-20 mA signal may cause thevalve to move. Before connecting electrical signal, ensure thevalve is isolated.SIGNAL AT CLOSED SWITCH (HART) (4mA 20mA)For a 4mA signal to move the valve to a closed position, select4mA. For a 20mA signal to move the valve to closed, select20mA.Connect a 4-20 mA signal to the terminals labeled “4-20” orthe tabs labeled “HART.” The tabs should only be used fortemporary testing and are not meant as a permanentconnection. A signal above 3.8 mA will activate the positioner.LEDs on the positioner will light up indicating power isconnected. SILHART SWITCH (HART) (HART 6 HART 7)For HART 6 protocol, select HART6. For HART 7 protocol,select HART7.FF WRITE PROTECT SWITCH (FOUNDATION FIELDBUS)(FF WP OFF ON)To write protect variables and inputs, select ON. To leavevariables writeable, select OFF. For more information, see theLogix 3800 FF Reference Guide, LGENIM3840.ELECTRICAL CONNECTIONS (FF)CAUTION: After connecting the FF signal, the valve maymove. Before connecting electrical signal, ensure the valve isisolated.FF SIMULATION SWITCH (FOUNDATION FIELDBUS) (FFSIM OFF ON)For normal operation, select OFF. To place in simulationmode, select ON. For more information, see the Logix 3800FF Reference Guide, LGENIM3840.Connect the FF signal to the terminals labeled “FF” or thecorresponding tabs. LEDs on the positioner will light upindicating power is connected.flowserve.com8

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/201.5Calibration1CAUTION: During the QUICK-CAL operation the valvemay stroke unexpectedly. Notify proper personnel that thevalve will stroke, and make sure the valve is properly isolated.2QUICK-CAL4The QUICK-CALbutton is used to initiate an automaticstroke calibration. This stroke calibration determines theclosed (0%) and open (100%) positions of the valve andgathers information about the response of the valve todetermine the control gains. The gains are automatically set.After a QUICK-CAL calibration, the positioner is ready tocontrol.536789To perform a QUICK-CAL, press and hold the QUICK-CAL10button for approximately 3 seconds, then release.11During the calibration, the LED lights will flash Yellow-RedYellow-Green indicating the calibration is in progress. Afterthe calibration is complete, the LED lights should flashGreen-Green-Green-Green indicating a successfulcalibration.121314 NOTE: This first time the QUICK-CAL is performed, thepositioner will also complete a Full Calibration. This willextend the time required for the calibration. This happenswith Standard and Pro diagnostic levels.15161718GAIN SWITCHAfter the calibration, (and at any time during operation), finetune the gains by adjusting the Selectable GAIN Switch.Selecting “A” through “D” will provide a more stable or slowerresponse. Selecting “F” through “J” will provide a more activeor quicker response. The “E” position is the default and istypically more stable.ABCDEFG--- END OF QUICK START GUIDE --flowserve.com9

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/202 SAFETY INFORMATION2.32.1FLOWSERVE positioners use high-pressure gas to operate.Use eye protection when working around pressurizedequipment. Follow proper procedures for working with naturalgas.Using This DocumentProduct users and maintenance personnel should thoroughlyreview this manual before installing, operating, or performingany maintenance on the positioner. DANGER: Standard industry safety practices must beadhered to when working on this or any process controlproduct. Specifically, use personal protective equipment aswarranted.The following instructions are designed to assist in unpacking,installing and performing maintenance as required on Logix 3800 positioners. Logix 3800 is the term used for all thepositioners herein; however, specific numbers indicatefeatures specific to model (i.e., Logix 3820 indicates that thepositioner has HART protocol and 3840 indicatesFoundation Fieldbus).2.4Qualified PersonnelQualified personnel are people who, on account of theirtraining, experience, instruction and their knowledge ofrelevant standards, specifications, accident preventionregulations and operating conditions, have been authorized bythose responsible for the safety of the plant to perform thenecessary work and who can recognize and avoid possibledangers.Separate Flow Control Products User Instructions cover thevalve, actuator, or other portions of the system and otheraccessories. Refer to the appropriate instructions when thisinformation is needed. The design of FLOWSERVE valves,actuators, and accessories are for specific applicationsconsidering medium, pressure, and temperature in mostcases. For this reason, do not use them in other applicationswithout first contacting the manufacturer.2.2Protective ClothingIn unpacking, installing and performing maintenance asrequired on FLOWSERVE products, product users andmaintenance personnel should thoroughly review this manualbefore installing, operating, or performing any maintenance.Terms Concerning Safety2.5The safety terms NOTE,CAUTION , and DANGERare used in these instructions to highlight particular hazardsand to provide additional information on aspects that may notbe readily apparent. DANGER andCAUTION notesmust be strictly followed to avoid possible injury to personnelor damage to equipment or property.Valve and Actuator VariationsThese instructions cannot claim to cover all details of allpossible product variations, nor can they provide informationfor every possible example of installation, operation scenario,or maintenance requirement. Qualified personnel shouldfollow the instructions provided and only use the product for itsdefined purpose. If clarification is needed or there are anyuncertainties in this respect, particularly in the event of missingproduct-related information, immediately contact theappropriate Flowserve sales office. Contact information islisted at the back of this manual. NOTE: Indicates and provides additional technicalinformation, which may not be obvious.CAUTION: Proper precautions must be observed to avoidminor personal injury and property damage.2.6Spare PartsUse only FLOWSERVE original components. FLOWSERVEcannot accept responsibility for any damages that occur fromusing components or fastening materials from othermanufacturers. If FLOWSERVE products (especially sealingmaterials) have been in storage for longer periods, check themfor corrosion or deterioration before using these products. SeeAppendix G - How To Order for more information. DANGER: Indicates that death, severe personal injuryand/or substantial property damage can occur if properprecautions are not taken.Compliance with notes about installation, operation,maintenance and technical documentation (e.g. in theoperating instruction, product documentation or on thepositioner) is essential to avoid faults, which in themselvesmight directly or indirectly cause severe personal injury orproperty damage.2.7Service / RepairCAUTION: Proper precautions must be strictly observedto avoid possible personal injury and property damage.Modifying this product, substituting non-factory parts, or usingmaintenance procedures other than outlined in this instructioncould drastically affect performance and be hazardous topersonnel and equipment, and may void existing warranties.flowserve.com10

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20There are moving parts between the actuator and the valve.To avoid injury FLOWSERVE provides pinch-point-protectionin the form of cover plates, especially with side-mountedpositioners. Special attention is required when removing theseplates for inspection, service or repair. Refit the cover platesafter completing work.1Logix 3800 positioner repair is limited to the replacement ofsub-assemblies and circuit boards with FLOWSERVEmanufactured replacements as outlined in this manual.5 7DANGER: Substitution with non-factorycomponents may impair intrinsic safety.2346positioner89CAUTION: Before returning products to FLOWSERVE forrepair or service, provide a certificate to FLOWSERVE whichconfirms that the product has been decontaminated and isclean; FLOWSERVE will not accept deliveries if a certificate isnot provided (a form is available from FLOWSERVE).101112Apart from the operating instructions and the necessaryaccident prevention directives valid in the country of use,follow all recognized regulations for safety and goodengineering practices.132.8 Natural Gas Service16If a natural gas model positioner is ordered, then the use ofnatural gas as an actuation medium with a FLOWSERVELogix 3800 positioner is acceptable.17141518ACAUTION: The natural gas used must be sweet naturalgas. Use of sour natural gas may cause positioner to failprematurely.B DANGER: The Logix 3800 is vented directly to atmosphere.DCThe substitution of sweet natural gas as the air supply requirespiping to route the exhausted natural gas to a safeenvironment. Refer to section 5.4, Venting, for venting details.EFGflowserve.com11

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/2033.1PRE-INSTALLATIONStorageIt is mandatory to store FLOWSERVE control valves andinstruments in a clean, dry environment. Prevent flooding ofthe equipment, including rainwater, that can pool in packagingmaterials. Prevent dirt or sand accumulation in the pneumaticand valve ports. Plastic caps are fitted to protect positionerports from ingress of foreign materials. These caps should beremoved before fitting with conduit or air supply lines.If FLOWSERVE products have been in storage for longerperiods, check them for corrosion or deterioration before usingthese products. The end user must provide fire protection forFLOWSERVE products. NOTE: The positioner is not IP66/NEMA 4X certified untilinstalled and temporary plugs have been fitted with tubing,conduit or permanent plugs.3.2UnpackingWhile unpacking the valve and Logix 3800 positioner, checkthe packing list against the materials received. Each shippingcontainer includes a list describing the system andaccessories included.In the event of shipping damage, contact the shipperimmediately. Should any problems arise, please contact aFLOWSERVE Flow Control Division representative. Phonenumbers are at the back of the manual.Remove the plastic plugs (blue color) from the conduit andpneumatic ports before installing. Replace with plugs that willseal the opening using either ¼” NPT, ½” NPT or M20threaded plug, depending on the housing, which is clearlymarked.CAUTION: The plastic plugs in the conduit and pneumaticports are intended only to protect the threads during shipment.Failure to replace these with a sealing plug may result in liquidand debris ingress and damage to the positioner. DANGER: When lifting a valve/actuator assembly withlifting straps, be aware that the center of gravity may be abovethe lifting point. Therefore, support must be given to preventthe valve/actuator from rotating and falling. Failure to do socan cause serious injury to personnel or damage to nearbyequipment.3.3Pre-installation InspectionWhen installing a positioner, check the feedback shaft fordamage and that the plugs and cover are in place. If there iscontamination in the positioner, clean the positionercomponents gently with a soft damp cloth. One may removesome parts for better access. Do not get water on theelectronics assembly.flowserve.com12

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/203.4Label Verification1Verify that the labels match the intended application. See section 17, Hazardous Location Specifications, for more details. NOTE: The installer should mark the checkbox on the label that is appropriate for the intended use of the Logix 3800.23456789101112131415161718ABCDEFGFigure 5: Certification Labels (Explosion Proof Housing)flowserve.com13

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20Figure 6: Certification Labels (Explosion Proof Housing)flowserve.com14

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/201234567891011Figure 7: Certification Labels (Explosion Proof Housing)12131415161718ABCDEFFigure 8: Model Code Labelflowserve.com15G

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20Figure 9: Certification Labels (Intrinsically Safe Housing)flowserve.com16

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/204INSTALLATION – MOUNTING4 NOTE: The Logix 3800 positioner can be mounted in anyorientation - with gauges on the left or right.4.15Mounting to Mark One Linear ValvesTo attach a Logix 3800 positioner to a Valtek linear Mark Ivalve, refer to Figure 10: Mounting to Mark I Linear Valve andproceed as outlined below. Refer to Figure 11: MountingNamur to Linear Valve if using a Namur shaft. Refer to,APPENDIX G - HOW TO ORDER, for complete linear actuatormounting kit listings.12Remove washer and nut from follower pin assembly.Insert pin into the appropriate hole in follower arm, orlocate the pin along the slot in the follower arm based onstroke length. The stroke lengths are located on thefollower arm. Make sure the stamped side of the arm istoward the unthreaded end of the pin. Reinstall the lockwasher and tighten the nut to complete follower armassembly.Slide the slot in the follower arm assembly over the flatson the position feedback shaft on the back of thepositioner. The follower arm will be specific to a D shaftor a Namur shaft. Rotate the arm until the arm is pointingtoward the side of the positioner with ports A, B, andSupply. Slide the lock washer over the threads on theshaft and tighten down the nut. NOTE: The feedback shaft has a clutch mechanism thatScrew one mounting bolt into the hole on the yokemounting pad nearest the cylinder. Stop when the bolt isapproximately 3 16" from being flush with the mountingpad.Slip the large end of the slotted mounting hole in the backof the positioner/bracket assembly over the mountingbolt. Slide the small end of the teardrop under themounting bolt and align the lower mounting hole.6Insert the lower mounting bolt and tighten the bolting.7Position the take-off arm mounting slot against the stemclamp mounting pad. Apply Loctite 222 to the take-offarm bolting and insert through washers into stem clamp.Leave bolts loose.1234567898Center the take-off arm on the follower pin.109Align the take-off arm with the top surface of the stemclamp and tighten bolt. Torque to 120 in-lb.11 NOTE: If mounted correctly, the follower arm should be12horizontal when the valve is at 50% stroke and should moveapproximately 30 from horizontal over the full stroke of thevalve. A stroke calibration error will occur if the positioner ismounted incorrectly, and the indicator lights will blink a RedRed-Yellow-Green code indicating the position sensor hasgone out of range on one end of travel, or the travel is toosmall. Reposition the feedback linkage or the positioner tocorrect the error.13 NOTE: To virtually eliminate non-linearity, use the18Linearization feature in the Custom Characterization page ofthe DTM.A14151617allows for over-rotation of the shaft for easy adjustments.B3CAlign the bracket with the three outer mounting holes onthe positioner. Fasten with 5/16-18 UNC bolts.DBracketEFGPositioner Feedback ShaftFollower ArmFollower PinTake-Off Arm Pin SlotFigure 10: Mounting to Mark I Linear Valveflowserve.com17Take-Off ArmStem Clamp

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20SplineLeverAdapterTake-OffArmAssemblyFigure 11: Mounting Namur to Linear Valve4.2Mounting to Standard Valtek RotaryValvesThe standard rotary mounting applies to Valtek valve/actuatorassemblies that do not have mounted volume tanks or handwheels. The standard mounting uses a linkage directlycoupled to the valve shaft. This linkage has been designed toallow for minimal misalignment between the positioner and theactuator. Refer to Figure 12: Valtek Rotary Follower Armthrough Figure 15: Valtek Rotary Final Orientation.Figure 13: Valtek Rotary Take Off ArmFigure 14: Valtek Rotary MountingUniversal BracketFollowerArmFeedbackShaftFigure 12: Valtek Rotary Follower Armflowserve.com18

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/209If calibration fails, retry the calibration. Exceeding thefeedback values will cause it to continue to fail, and thearm must be adjusted away from the positioner’s limits.Rotate the feedback shaft so that the full free travel ofthe feedback shaft is in the range of the actuatormovement. Optionally, continue to attempt thecalibration. Each calibration attempt adjusts theacceptable limits, and it should eventually pass.12345CAUTION: Remember to remove the air supply before readjusting take-off arm. NOTE: If mounted correctly to a standard valve, thefollower arm should be horizontal when the valve is at 50%stroke and should move approximately 30 from horizontalover the full stroke of the valve. NOTE: To improve linearity of feedback, use theFigure 15: Valtek Rotary Final OrientationFasten the spline lever adapter to the splined lever usingtwo 4-40 screws.2Slide the take-off arm onto the spline lever adapter shaft,orienting the arm to the current valve position. Insert thescrew with star washer through the take-off arm and addthe second star washer and nut and tighten.3Attach follower arm to positioner feedback shaft usingthe 10-32 nut.4Rotate the follower arm so that the follower pin will slideinto the slot on the take-off arm. Adjust the bracketposition as needed noting the engagement of thefollower pin and the take-off arm slot. The pin shouldextend approximately 2 mm past the take-off arm. Whenproperly adjusted, securely tighten the bracket bolts.5Using three 5/16-18 UNC x 1/2" bolts, fasten positionerto the universal bracket.6Using a ½” end wrench and two 5/16-18 UNC X ½” bolts,attach the bracket to actuator transfer case pad. Leavingthese bolts slightly loose will aid in final adjustments.7Rotate follower arm so the follower pin will slide into theslot on the take-off arm. Over-rotate the follower arm ifneeded, so the arm moves freely through the intendedtravel.9104.313Mounting to MaxFlo Rotary ValvesSlide the take-off arm onto the shaft. Insert the screwwith the star washer through the take-off arm and addthe second star washer and nut. Tighten the nut with asocket, so the arm is just snug on the shaft but still ableto rotate. Tightening will occur after linkage is correctlyoriented. Refer to Figure 16: MaxFlo Take Off Arm.121415161718ABCDEFGFigure 16: MaxFlo Take Off ArmAdjust the bracket position as needed noting theengagement of the follower pin and the take-off arm slot.The pin should extend approximately 1 16" past the takeoff arm. When properly adjusted, securely tighten thebracket bolts.flowserve.com811 NOTE: The feedback shaft has a clutch mechanism thatallows for over-rotation of the shaft for easy adjustments.87Linearization feature on the Custom Characterization page ofthe DTM.11619

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/202Attach the mounting plate to the positioner using fourscrews and attach follower arm to positioner feedbackshaft. See Figure 17: MaxFlo Follower Arm and Figure18: MaxFlo Connection.MountingPlateFeedbackShaftFollower ArmFigure 19: MaxFlo AssemblyFigure 17: MaxFlo Follower Arm NOTE: The feedback shaft has a clutch mechanism thatallows for over-rotation of the shaft for easy adjustments.4Figure 18: MaxFlo Connection3Rotate the follower arm so that the take-off pin will slideinto the slot on the follower arm. Adjust the bracketposition as needed noting the engagement of thefollower pin and the take-off arm slot. The pin shouldextend approximately 2 mm past the take-off arm.When properly adjusted, securely tighten thebracketing bolts. See Figure 19: MaxFlo Assembly.flowserve.com20If calibration fails, retry the calibration. If it still fails,remove power from the positioner, disconnect the air,and then reconnect the positioner and continue toattempt the calibration. Each calibration attempt adjuststhe acceptable limits, and it should pass eventually.

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/204.4Mounting to Rotary NAMUR Valves11Attach the mounting plate to the positioner using fourscrews. See Figure 20: AutoMax Bracket.23456789101112Figure 21: AutoMax Assembly1314151617Figure 20: AutoMax Bracket18A2Rotate the feedback shaft to match the orientation of thereceiver on the actuator.B NOTE: The feedback shaft has a clutch mechanism thatCallows for over-rotation of the shaft for easy adjustments.34DMount the positioner onto the actuator using thewashers and nuts as shown in Figure 21: AutoMaxAssembly and Figure 22: MaxFlo 4 Assembly.EIf calibration fails, retry the calibration. If it still fails,remove power from the positioner, disconnect the air,and then reconnect the positioner and continue toattempt the calibration. Each calibration attempt adjuststhe acceptable limits, and it should eventually pass.GFFigure 22: MaxFlo 4 AssemblyCAUTION: Remember to remove the air supply before readjusting take-off arm.flowserve.com21

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/204.5Direct MountDirect mount allows the positioner to be mounted directly tothe actuator without tubing. See your Flowserve salesrepresentative for actuator options.1Assemble the direct mount block onto the positioner.See figure 23.2Ensure the feedback shaft and take-off arm are properlyaligned.3If the actuator is designed as an ATO system, removethe plug from the positioner’s direct air port, and insert a1/4" plug into positioner ports A and B.4Mount the positioner assembly to the actuator that iscompatible with Flowserve direct mount devices.Figure 23: Direct Mount on IS Housingflowserve.com22

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20INSTALLATION - TUBING5After mounting to the actuator, tube the positioner using theappropriate compression fitting connectors. For bestperformance, use 10 mm (3/8 inch) tubing for 645 square cm(100 square inches) actuators or larger.5.1Determine Air ActionExample: Rotary Double-Acting Actuators1For a rotary actuator, rout tubing from Port “A” to the far sideof the actuator and tubing from port “B” to the side of theactuator closer to the transfer case. Follow this tubingconvention regardless of air action. On rotary actuators, thetransfer case orientation determines the air action. See Figure25: Rotary, Double Acting, Air to Open.23456When an air supply is present, and the relay is energized, port“A” delivers air. Typically, the tubing from port “A” is connectedto side of the actuator that results in the air compressing theactuator spring. When tubed this way, the spring is designedto return the valve to the fail-safe state should supply air orpower to the unit fail or be turned off.789ASBTube the port labeled “A” to the side of the actuator that mustreceive air to begin moving away from the fail-safe state.1112If air from “A” should open the valve, set the Air Actionconfiguration DIP switch on the positioner to Air-to-Open,otherwise set it to Air-to-Close. The Air-to-Open and Air-toClose selection is only a reflection of the tubing. Whenselecting air action during configuration, the selection tells thecontrol which way the actuator was tubed.Figure 25: Rotary, Double Acting, Air to Open1314Example: Tubing Single-Acting Actuators15For single-acting actuators, tubing for port “A” is always to thepneumatic side of the actuator regardless of air action. Port Bis plugged. See Figur

Logix 3800 Digital Positioner FCD LGENIM0112-06 01/20 flowserve.com 10 2 SAFETY INFORMATION 2.1 Using This Document Product users and maintenance personnel should thoroughly review this manual before installing, operating, or performing any maintenance on the positioner. The following instructions are designed to assist in unpacking,

Related Documents:

6.175 deutz bf6l913c turbo wr-200/9 wo-630 fcd-2083 ó fcd-740 6.190 deutz bf6l913c wr-200/9 wo-630 fcd-2083 ó fcd-740 6.220 deutz bf6l913c wr-200/9 wo-630 fcd-3026 optima 440 agco allis 914 wap-165 wo-480 fcd-2083 wap-106-s fcd-740 optima 550 bf6 m 1013 ec wo-480 fcd-2083 woh-200 optima 660 deutz wo-480 fcd-2083 modelo 600 case jfa-514 fcd-710

Auto Tune Adapting the response of the Logix 500 series positioner to a particular valve configuration is as simple as pressing a button. The Logix 500 positioner has a built-in auto-tuning func-tion that, when enabled, quickly adj

element is the Studio 5000 Logix Designer application. The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix 5000 controllers for discrete, process, batch, motion, safety, and drive-based solutions. The Studio 5000 environment is the foundation for the future ofFile Size: 1MBPage Count: 71Explore furtherEmulate a Studio 5000 Controller and Connect to a .www.dmcinfo.comStudio 5000 Logix Emulate (Virtual PLC) - PLC Programmin www.plctr.comDownload Center Rockwell Automation United Stateswww.rockwellautomation.comStudio 5000 Logix Emulate FactoryTalk United Stateswww.rockwellautomation.comStudio 5000 Design Software FactoryTalk United Stateswww.rockwellautomation.comRecommended to you based on what's popular Feedback

Figure 1. Principle of Operation 5. Principle of operation The Logix 500si positioner is a digital positioner with various options. The positioner consists of three main modules: 1. The microprocessor-based electronic control module includes direct local user interface switches 2. The piezo valve-based electro-pneumatic converter module 3.

The Graco 3800 ProComp is a three-stage turbine sprayer. The Graco 4900 ProComp is a four-stage turbine sprayer. 3800 ProComp Turbine Component Table System Model 2-qt Remote Pressure Pot 30-ft (9 m) Turbine Air Hose 30-ft (9 m) Compressor Air Hose Gun/Fluid Set Extra Fluid Sets HVLP 3800 Pro-Comp Nippon 3800 246857 249590 287819 241413 240071 .

Valtek XL Series Positioner Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611 Figure 2: XL Series Positioner Mounted on Valtek Linear Actuator Figure 3: XL Series Positioner Mounted on Fisher 657 Actuator Calibration is easy using the XL positioner due to minimal interaction between zero and span. Also, the

The Varian CP-3800 GC for any application The Varian CP-3800 GC meets all your analytical requirements with practical solutions for simple and complex applications. In a standard configuration, the CP-3800 accommodates up to three injectors and three detectors, all operating simultaneously. In addition, the CP-3800 is easily configured toFile Size: 1012KBPage Count: 18

Refer to API RP 500 and NFPA 70 for guidance. When loading liquids that can accumulate static charges, refer to the precautions described in the International Safety Guide for Oil Tankers and Terminals, Safety of Life at Sea, API MPMS Ch. 3, and API RP 2003. Care must be taken with all liquid-in-glass thermometers to prevent breakage, which will result in a safety hazard. If the liquid in the .