Adjustable Frequency AC Drive - Powerflex.su

2y ago
9 Views
2 Downloads
5.06 MB
118 Pages
Last View : 26d ago
Last Download : 3m ago
Upload by : Alexia Money
Transcription

AdjustableFrequency ACDriveFRN 1.xx - 2.xxUser Manualwww.abpowerflex.com

Important User InformationSolid state equipment has operational characteristics differing from those ofelectromechanical equipment. Safety Guidelines for the Application, Installationand Maintenance of Solid State Controls (Publication SGI-1.1 available from yourlocal Rockwell Automation sales office or online athttp://www.rockwellautomation.com/literature) describes some importantdifferences between solid state equipment and hard-wired electromechanicaldevices. Because of this difference, and also because of the wide variety of uses forsolid state equipment, all persons responsible for applying this equipment mustsatisfy themselves that each intended application of this equipment is acceptable.In no event will Rockwell Automation, Inc. be responsible or liable for indirect orconsequential damages resulting from the use or application of this equipment.The examples and diagrams in this manual are included solely for illustrativepurposes. Because of the many variables and requirements associated with anyparticular installation, Rockwell Automation, Inc. cannot assume responsibility orliability for actual use based on the examples and diagrams.No patent liability is assumed by Rockwell Automation, Inc. with respect to use ofinformation, circuits, equipment, or software described in this manual.Reproduction of the contents of this manual, in whole or in part, without writtenpermission of Rockwell Automation, Inc. is prohibited.Throughout this manual, when necessary we use notes to make you aware of safetyconsiderations.WARNING: Identifies information about practices or circumstancesthat can cause an explosion in a hazardous environment, which maylead to personal injury or death, property damage, or economic loss.Important: Identifies information that is critical for successful application andunderstanding of the product.ATTENTION: Identifies information about practices or circumstancesthat can lead to personal injury or death, property damage, or economicloss. Attentions help you: identify a hazard avoid the hazard recognize the consequencesShock Hazard labels may be located on or inside the equipment (e.g.,drive or motor) to alert people that dangerous voltage may be present.Burn Hazard labels may be located on or inside the equipment (e.g.,drive or motor) to alert people that surfaces may be at dangeroustemperatures.Allen-Bradley, Rockwell Automation, and PowerFlex are registered trademarks of Rockwell Automation, Inc.DriveExplorer, DriveExecutive, and SCANport are trademarks of Rockwell Automation, Inc.PLC is a registered trademark of Rockwell Automation, Inc.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Summary of ChangesThe information below summarizes the changes to the PowerFlex 4MUser Manual since the August 2007 release.Manual UpdatesDescription of New or Updated InformationFootnote (2) deleted from “EN61800-3 Second Environment” in Table 1.I.Note to stop drive before changing parameter t211 [Anlg In 0-10V Lo]removed.New option 13, I/O Control, for parameter t221 [Relay Out Sel] added.Fault description for F3 corrected.Corrected Table B.F by adding the 0.75 kW (1.0 HP) and 1.5 kW (2.0 HP)ratings for the 22F-RF025-BL EMC line filter.Description for bits 14, 13, and 12 of register address 8192 corrected.Information on reading register address 8192 clarified.Description for bits 6, 7, and 15 of register address 8192 updated.Information on reading register address 8193 clarified.Figure C.1, Network Wiring Diagram, updated.Guidelines on standard RS485 wiring practices owerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

soc-2The information below summarizes the changes to the PowerFlex 4MUser Manual since the February 2007 release.Manual UpdatesDescription of New or Updated InformationInput description and attention text for Multiple Digital Input Connectionexample corrected.Description for option 21 of parameter t221 [Relay Out Sel] corrected.Invalid catalog number for L Type Filter deleted.Graphic for the “Connecting an RS-485 Network” section correctedPowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-EPage(s)1-183-15B-4, B-10D-3

Table of ContentsPrefaceOverviewWho Should Use this Manual? . . . . . . . . .Reference Materials . . . . . . . . . . . . . . . . .Manual Conventions . . . . . . . . . . . . . . . . .Drive Frame Sizes . . . . . . . . . . . . . . . . . . .General Precautions . . . . . . . . . . . . . . . . .Catalog Number Explanation . . . . . . . . . .Chapter 1P-1P-1P-2P-2P-3P-4Installation/WiringOpening the Cover . . . . . . . . . . . . . . . . . . 1-1Mounting Considerations . . . . . . . . . . . . . 1-2AC Supply Source Considerations . . . . . . 1-3General Grounding Requirements . . . . . . 1-5Fuses and Circuit Breakers . . . . . . . . . . . . 1-7Power Wiring . . . . . . . . . . . . . . . . . . . . . . 1-9I/O Wiring Recommendations . . . . . . . . 1-13Start and Speed Reference Control . . . . . 1-19EMC Instructions . . . . . . . . . . . . . . . . . . 1-21Chapter 2Start UpPrepare For Drive Start-Up . . . . . . . . . . . . 2-1Integral Keypad . . . . . . . . . . . . . . . . . . . . . 2-3Viewing and Editing Parameters . . . . . . . . 2-4Chapter 3Programming and ParametersAbout Parameters . . . . . . . . . . . . . . . . . . . 3-1Parameter Organization. . . . . . . . . . . . . . . 3-2Display Group . . . . . . . . . . . . . . . . . . . . . . 3-3Basic Program Group . . . . . . . . . . . . . . . . 3-8Terminal Block Group. . . . . . . . . . . . . . . 3-13Communications Group . . . . . . . . . . . . . 3-17Advanced Program Group. . . . . . . . . . . . 3-19Parameter Cross Reference – by Name. . 3-31Chapter 4TroubleshootingDrive Status . . . . . . . . . . . . . . . . . . . . . . . .Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Fault Descriptions . . . . . . . . . . . . . . . . . . .Common Symptoms and CorrectiveActions . . . . . . . . . . . . . . . . . . . . . . . . .Appendix A4-14-14-34-5Supplemental Drive InformationDrive, Fuse & Circuit Breaker Ratings . . . A-1Specifications . . . . . . . . . . . . . . . . . . . . . . A-2Appendix BAccessories and DimensionsProduct Selection . . . . . . . . . . . . . . . . . . . B-1Product Dimensions . . . . . . . . . . . . . . . . . B-6PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

iiTable of ContentsAppendix CRS485 (DSI) ProtocolNetwork Wiring . . . . . . . . . . . . . . . . . . . . .Parameter Configuration . . . . . . . . . . . . . .Supported Modbus Function Codes . . . . .Writing (06) Logic Command Data. . . . . .Writing (06) Reference . . . . . . . . . . . . . . .Reading (03) Logic Status Data. . . . . . . . .Reading (03) Feedback . . . . . . . . . . . . . . .Reading (03) Drive Error Codes . . . . . . . .Reading (03) and Writing (06) DriveParameters . . . . . . . . . . . . . . . . . . . . . .Additional Information . . . . . . . . . . . . . . .Appendix DC-1C-3C-3C-4C-5C-5C-6C-6C-7C-7RJ45 DSI Splitter CableConnectivity Guidelines . . . . . . . . . . . . . . D-1DSI Cable Accessories . . . . . . . . . . . . . . . D-2Connecting an RS-485 Network . . . . . . . . D-3IndexPowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

PrefaceOverviewThe purpose of this manual is to provide you with the basic informationneeded to install, start-up and troubleshoot the PowerFlex 4MAdjustable Frequency AC Drive.For information on Who Should Use this Manual?Reference MaterialsManual ConventionsDrive Frame SizesGeneral PrecautionsCatalog Number ExplanationSee page P-1P-1P-2P-2P-3P-4Who Should Use this Manual?This manual is intended for qualified personnel. You must be able toprogram and operate Adjustable Frequency AC Drive devices. Inaddition, you must have an understanding of the parameter settings andfunctions.Reference MaterialsThe following manuals are recommended for general drive information:TitleWiring and GroundingGuidelines for Pulse WidthModulated (PWM) AC DrivesPreventive Maintenance ofIndustrial Control and DriveSystem EquipmentSafety Guidelines for theApplication, Installation andMaintenance of Solid StateControlA Global Reference Guide forReading Schematic DiagramsGuarding Against ElectrostaticDamagePublicationAvailable Online at DRIVES-IN001 DRIVES-SB001 .108000-4.5.2PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

P-2OverviewManual Conventions In this manual we refer to the PowerFlex 4M Adjustable FrequencyAC Drive as: drive, PowerFlex 4M or PowerFlex 4M Drive. Parameter numbers and names are shown in this format:P101 [Motor NP Volts]NameNumberGroupd Display GroupP Basic Program Groupt Terminal Block GroupC Communications GroupA Advanced Program Group The following words are used throughout the manual to describe anaction:WordCanCannotMayMustShallShouldShould NotMeaningPossible, able to do somethingNot possible, not able to do somethingPermitted, allowedUnavoidable, you must do thisRequired and necessaryRecommendedNot RecommendedDrive Frame SizesSimilar PowerFlex 4M drive sizes are grouped into frame sizes tosimplify spare parts ordering, dimensioning, etc. A cross-reference ofdrive catalog numbers and their respective frame sizes is provided inAppendix B.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

OverviewP-3General Precautions!ATTENTION: To avoid an electric shock hazard, verify that thevoltage on the bus capacitors has discharged before performing anywork on the drive. Measure the DC bus voltage at the –DC and DCterminals on the Power Terminal Block (refer to Chapter 1 PowerTerminal descriptions). The voltage must be zero.Darkened LEDs or a darkened LCD display is not an indication thatcapacitors have discharged to safe voltage levels.!!!!ATTENTION: Only qualified personnel familiar with adjustablefrequency AC drives and associated machinery should plan orimplement the installation, start-up and subsequent maintenance of thesystem. Failure to comply may result in personal injury and/orequipment damage.ATTENTION: This drive contains ESD (Electrostatic Discharge)sensitive parts and assemblies. Static control precautions are requiredwhen installing, testing, servicing or repairing this assembly.Component damage may result if ESD control procedures are notfollowed. If you are not familiar with static control procedures,reference A-B publication 8000-4.5.2, “Guarding Against ElectrostaticDamage” or any other applicable ESD protection handbook.ATTENTION: An incorrectly applied or installed drive can result incomponent damage or a reduction in product life. Wiring or applicationerrors, such as, undersizing the motor, incorrect or inadequate ACsupply, or excessive ambient temperatures may result in malfunction ofthe system.ATTENTION: The bus regulator function is extremely useful forpreventing nuisance overvoltage faults resulting from aggressivedecelerations, overhauling loads, and eccentric loads. However, it canalso cause either of the following two conditions to occur.1. Fast positive changes in input voltage or imbalanced input voltagescan cause uncommanded positive speed changes;2. Actual deceleration times can be longer than commandeddeceleration times.However, a “Stall Fault” is generated if the drive remains in this statefor 1 minute. If this condition is unacceptable, the bus regulator must bedisabled (see parameter A441). In addition, installing a properly sizeddynamic brake resistor will provide equal or better performance in mostcases.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

P-4OverviewCatalog Number Explanation1-3456-822F -D8P7DriveDash Voltage RatingRating91011N11Enclosure HIM Emission ClassCode22F PowerFlex 4MCodeVABDVoltage120V AC240V AC240V AC480V AC1213-143AATypeOptionalCode Version3No Brake IGBT4StandardPh.1133Code Rating0Not Filtered1FilteredCode Interface Module1Fixed KeypadCode PurposeAA Reserved forthru custom firmwareZZCode EnclosureNPanel Mount - IP 20 (NEMA Type Open)Output Current @ 100-120V InputOutput Current @ 200-240V InputOutput Current @ 380-480V 33Code1P52P54P26P08P7013018024Amps1.62.54.56.0kW (HP)0.2 (0.25)0.4 (0.5)0.75 (1.0)1.1 (1.5)Amps1.62.54.28.011.012.017.525.033.0kW (HP)0.2 (0.25)0.4 (0.5)0.75 (1.0)1.5 (2.0)2.2 (3.0)2.2 (3.0)3.7 (5.0)5.5 (7.5)7.5 (10.0)Amps1.52.54.26.08.713.018.024.0kW (HP)0.4 (0.5)0.75 (1.0)1.5 (2.0)2.2 (3.0)3.7 (5.0)5.5 (7.5)7.5 (10.0)10.0 (15.0)Additional accessories, options and adapters are available. See Appendix B for details.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Chapter 1Installation/WiringThis chapter provides information on mounting and wiring thePowerFlex 4M Drive.For information on Opening the CoverMounting ConsiderationsAC Supply Source ConsiderationsSee page1-11-21-3General Grounding Requirements 1-5For information on Fuses and Circuit BreakersPower WiringI/O WiringRecommendationsEMC InstructionsSee page1-71-91-131-21Most start-up difficulties are the result of incorrect wiring. Everyprecaution must be taken to assure that the wiring is done as instructed.All items must be read and understood before the actual installationbegins.!ATTENTION: The following information is merely a guide for properinstallation. Rockwell Automation, Inc. cannot assume responsibilityfor the compliance or the noncompliance to any code, national, local orotherwise for the proper installation of this drive or associatedequipment. A hazard of personal injury and/or equipment damageexists if codes are ignored during installation.Opening the Cover1. Press and hold in the tabs on each side of the cover.2. Pull the cover out and up to release.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

1-2Installation/WiringMounting Considerations Mount the drive upright on a flat, vertical and level surface.– Install on 35 mm DIN Rail (for frames A and B).or– Install with screws.Table 1.A Screw Mounting Recommendations Minimum Panel Thickness Screw SizeMounting Torque1.9 mm (0.0747 in.)1.56-1.96 N-m (14-17 lb.-in.)M4 (#8-32)Protect the cooling fan by avoiding dust or metallic particles.Do not expose to a corrosive atmosphere.Protect from moisture and direct sunlight.Minimum Mounting ClearancesRefer to Appendix B for mounting dimensions.See Table 1.B76.2 mm (3.0 in.)76.2 mm (3.0 in.)Closest object thatmay obstruct air flowthrough the driveheat sink and chassis76.2 mm (3.0 in.)76.2 mm (3.0 in.)AirflowAmbient Operating TemperaturesTable 1.B Enclosure and Clearance RequirementsHorizontal Clearance between drives0 mm and greater25 mm and greaterAmbient TemperatureMinimumMaximum-10 C (14 F)40 C (104 F)-10 C (14 F)50 C (122 F)Drive enclosure is rated IP20, NEMA/UL Type Open.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Installation/Wiring1-3Storage Store within an ambient temperature range of -40 to 85 C.Store within a relative humidity range of 0% to 95%,non-condensing.Do not expose to a corrosive atmosphere.AC Supply Source ConsiderationsUngrounded Distribution Systems!ATTENTION: PowerFlex 4M drives contain protective MOVs thatare referenced to ground. These devices must be disconnected if thedrive is installed on an ungrounded or resistive grounded distributionsystem.Disconnecting MOVsTo prevent drive damage, the MOVs connected to ground shall bedisconnected if the drive is installed on an ungrounded distributionsystem where the line-to-ground voltages on any phase could exceed125% of the nominal line-to-line voltage. To disconnect these devices,remove the jumper shown in the Figures 1.1 and 1.2.1. Turn the screw counterclockwise to loosen.2. Pull the jumper completely out of the drive chassis.3. Tighten the screw to keep it in place.Figure 1.1 Jumper Location (Frame A shown)Important:Tighten screw afterjumper removal.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

1-4Installation/WiringFigure 1.2 Phase to Ground MOV RemovalR/L1Three-PhaseAC Input S/L2T/L3Jumper1234Input Power ConditioningThe drive is suitable for direct connection to input power within the ratedvoltage of the drive (see Appendix A). Listed in Table 1.C are certaininput power conditions which may cause component damage orreduction in product life. If any of the conditions exist, as described inTable 1.C, install one of the devices listed under the heading CorrectiveAction on the line side of the drive.Important: Only one device per branch circuit is required. It should bemounted closest to the branch and sized to handle the totalcurrent of the branch circuit.Table 1.C Input Power ConditionsInput Power ConditionCorrective ActionLow Line Impedance (less than 1% line reactance) Install Line Reactor(1) or Isolation TransformerGreater than 120 kVA supply transformerLine has power factor correction capacitorsLine has frequent power interruptionsLine has intermittent noise spikes in excess of6000V (lightning)Phase to ground voltage exceeds 125% of normalline to line voltageUngrounded distribution system(1) Remove MOV jumper to ground. or Install Isolation Transformerwith grounded secondary ifnecessary.Refer to Appendix B for accessory ordering information.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Installation/Wiring1-5General Grounding RequirementsThe drive Safety Ground (PE) must be connected to system ground.Ground impedance must conform to the requirements of national andlocal industrial safety regulations and/or electrical codes. The integrityof all ground connections should be periodically checked.Figure 1.3 Typical GroundingR/L1S/L2T/L3U/T1V/T2W/T3SHLDGround Fault MonitoringIf a system ground fault monitor (RCD) is to be used, only Type B(adjustable) devices should be used to avoid nuisance tripping.Safety Ground -(PE)This is the safety ground for the drive that is required by code. One ofthese points must be connected to adjacent building steel (girder, joist), afloor ground rod or bus bar. Grounding points must comply withnational and local industrial safety regulations and/or electrical codes.Motor GroundThe motor ground must be connected to one of the ground terminals onthe drive.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

1-6Installation/WiringShield Termination - SHLDEither of the safety ground terminals located on the power terminalblock provides a grounding point for the motor cable shield. The motorcable shield connected to one of these terminals (drive end) should alsobe connected to the motor frame (motor end). Use a shield terminating orEMI clamp to connect the shield to the safety ground terminal. Theconduit box option may be used with a cable clamp for a grounding pointfor the cable shield.When shielded cable is used for control and signal wiring, the shieldshould be grounded at the source end only, not at the drive end.RFI Filter GroundingUsing single phase drives with integral filter, or an external filter withany drive rating, may result in relatively high ground leakage currents.Therefore, the filter must only be used in installations with groundedAC supply systems and be permanently installed and solidlygrounded (bonded) to the building power distribution ground. Ensurethat the incoming supply neutral is solidly connected (bonded) to thesame building power distribution ground. Grounding must not rely onflexible cables and should not include any form of plug or socket thatwould permit inadvertent disconnection. Some local codes may requireredundant ground connections. The integrity of all connections shouldbe periodically checked.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Installation/Wiring1-7Fuses and Circuit BreakersThe PowerFlex 4M does not provide branch short circuit protection. Thisproduct should be installed with either input fuses or an input circuitbreaker. National and local industrial safety regulations and/or electricalcodes may determine additional requirements for these installations.!ATTENTION: To guard against personal injury and/or equipmentdamage caused by improper fusing or circuit breaker selection, use onlythe recommended line fuses/circuit breakers specified in this section.FusingThe PowerFlex 4M has been UL tested and approved for use with inputfuses. The ratings in the table that follows are the maximumrecommended values for use with each drive rating. The devices listed inthis table are provided to serve as a guide.Bulletin 140M (Self-Protected Combination Controller)/UL489Circuit BreakersWhen using Bulletin 140M or UL489 rated circuit breakers, theguidelines listed below must be followed in order to meet the NECrequirements for branch circuit protection. Bulletin 140M can be used in single and group motor applications.Bulletin 140M can be used up stream from the drive without theneed for fuses.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

1-8Installation/WiringTable 1.D Minimum Recommended Branch Circuit Protective DevicesVoltageRatingDrive RatingkW (HP)Fuse Rating(1)Amps140M(2)Catalog No.RecommendedMCS ContactorsCatalog No.120V AC –1-Phase0.2 (0.25)0.4 (0.5)0.75 (1.0)1.1 40M-F8E-C32100-C09100-C12100-C23100-C30240V AC –1-Phase0.2 (0.25)0.4 (0.5)0.75 (1.0)1.5 (2.0)2.2 C23100-C30240V AC –3-Phase0.2 (0.25)0.4 (0.5)0.75 (1.0)1.5 (2.0)2.2 (3.0)3.7 (5.0)5.5 (7.5)7.5 3100-C23100-C37100-C60480V AC –3-Phase0.4 (0.5)0.75 (1.0)1.5 (2.0)2.2 (3.0)3.7 (5.0)5.5 (7.5)7.5 (10.0)11.0 2100-C23100-C23100-C30(1)(2)Recommended Fuse Type: UL Class J, RK1, T or Type BS88; 600V (550V) orequivalent.Refer to the selection guide for Bulletin 140M motor protectors for AIC ratings suitablefor your particular application.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Installation/Wiring1-9Power Wiring!!ATTENTION: National Codes and standards (NEC, VDE, BSI, etc.)and local codes outline provisions for safely installing electricalequipment. Installation must comply with specifications regarding wiretypes, conductor sizes, branch circuit protection and disconnectdevices. Failure to do so may result in personal injury and/or equipmentdamage.ATTENTION: To avoid a possible shock hazard caused by inducedvoltages, unused wires in the conduit must be grounded at both ends.For the same reason, if a drive sharing a conduit is being serviced orinstalled, all drives using this conduit should be disabled. This will helpminimize the possible shock hazard from “cross coupled” power leads.Motor Cable Types Acceptable for 200-600 Volt InstallationsGeneralA variety of cable types are acceptable for drive installations. For manyinstallations, unshielded cable is adequate, provided it can be separatedfrom sensitive circuits. As an approximate guide, allow a spacing of 0.3meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases,long parallel runs must be avoided. Do not use cable with an insulationthickness less than 15 mils (0.4 mm/0.015 in.). Do not route more thanthree sets of motor leads in a single conduit to minimize “cross talk”. Ifmore than three drive/motor connections per conduit are required,shielded cable must be used.UL installations in 50 C ambient must use 600V, 75 C or 90 C wire.UL installations in 40 C ambient should use 600V, 75 C or 90 C wire.Use copper wire only. Wire gauge requirements and recommendationsare based on 75 degree C. Do not reduce wire gauge when using highertemperature wire.UnshieldedTHHN, THWN or similar wire is acceptable for drive installation in dryenvironments provided adequate free air space and/or conduit fill rateslimits are provided. Do not use THHN or similarly coated wire in wetareas. Any wire chosen must have a minimum insulation thickness of15 mils and should not have large variations in insulation concentricity.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

tion 1)Rating/Type600V, 75 C or 90 C (167 For 194 F) RHH/RHW-2Belden 29501-29507 orequivalentStandard(Option 2)Tray rated 600V, 75 C or90 C (167 F or 194 F)RHH/RHW-2Shawflex 2ACD/3ACD orequivalentClass I & II; Tray rated 600V, 75 C orDivision I & II 90 C (167 F or 194 F)RHH/RHW-2Description Four tinned copper conductors with XLPE insulation Foil shield and tinned copper drain wire with 85% braidcoverage PVC jacket Three tinned copper conductors with XLPE insulation 5 mil single helical copper tape (25% overlap min.)with three bare copper grounds in contact with shield PVC jacket Three tinned copper conductors with XLPE insulation 5 mil single helical copper tape (25% overlap min.)with three bare copper grounds in contact with shield PVC copper grounds on #10 AWG and smallerReflected Wave ProtectionThe drive should be installed as close to the motor as possible.Installations with long motor cables may require the addition of externaldevices to limit voltage reflections at the motor (reflected wavephenomena). See Table 1.E for recommendations.The reflected wave data applies to all frequencies 2 to 10 kHz.For 240V ratings, reflected wave effects do not need to be considered.Table 1.E Maximum Cable Length RecommendationsReflected Wave380-480V Ratings(1)Motor Insulation RatingMotor Cable Only(1)1000 Vp-p15 meters (49 feet)1200 Vp-p40 meters (131 feet)1600 Vp-p170 meters (558 feet)Longer cable lengths can be achieved by installing devices on the output of the drive.Consult factory for recommendations.Output DisconnectThe drive is intended to be commanded by control input signals that willstart and stop the motor. A device that routinely disconnects thenreapplies output power to the motor for the purpose of starting andstopping the motor should not be used. If it is necessary to disconnectpower to the motor with the drive outputting power, an auxiliary contactshould be used to simultaneously disable drive control run commands.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Installation/Wiring1-11Power Terminal BlockThe drive utilizes a finger guard over the power wiring terminals.To remove:1. Press in and hold the locking tab.2. For the finger guard on the top of the drive, slide it down and out.For the finger guard at the bottom of the drive, slide it up and out.Replace the finger guard when wiring is complete.Figure 1.4 Power Terminal BlockFrame A and BR/L1 S/L2 T/L3Frame CR/L1 S/L2 T/L3P1P2Frame A and BU/T1 V/T2 W/T3 DC DC-Frame CBR U/T1 V/T2 W/T3 DC BR-DC-TerminalDescriptionR/L1, S/L21-Phase InputR/L1, S/L2, T/L3 3-Phase InputDC Bus Inductor Connection (Frame C drives only.)P1(1), P2(1)U/T1V/T2W/T3The Frame C drive is shipped with a jumper between Terminals P1and P2. Remove this jumper only when a DC Bus Inductor will beconnected. Drive will not power up without a jumper or inductorconnected.To Motor U/T1Switch any two motorleads to change forwardTo Motor V/T2 direction.To Motor W/T3PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

1-12Installation/WiringTerminalDC (2), DC-(2)BR (1), BR-(1)(1)(2)DescriptionDC Bus ConnectionDynamic Brake Resistor ConnectionSafety Ground - PEFor Frame C only [5.5 kW (7.5 HP) ratings and higher].Not applicable to 120 V, 1-Phase drives.Table 1.F Power Terminal Block SpecificationsFrameMaximum Wire Size (1) Minimum Wire Size (1) TorqueA3.3 mm2 (12 AWG)0.8 mm2 (18 AWG)1.4-1.6 N-m (12-14 lb.-in.)B8.4 mm2 (8 AWG)0.8 mm2 (18 AWG)1.6-1.9 N-m (14-17 lb.-in.)C13.3 mm2 (6 AWG)3.3 mm2 (12 AWG)2.7-3.2 N-m (24-28 lb.-in.)(1)Maximum/minimum sizes that the terminal block will accept - these are notrecommendations.Motor Start/Stop Precautions!!ATTENTION: A contactor or other device that routinely disconnectsand reapplies the AC line to the drive to start and stop the motor cancause drive hardware damage. The drive is designed to use control inputsignals that will start and stop the motor. If used, the input device mustnot exceed one operation per minute or drive damage can occur.ATTENTION: The drive start/stop control circuitry includessolid-state components. If hazards due to accidental contact withmoving machinery or unintentional flow of liquid, gas or solids exist,an additional hardwired stop circuit may be required to remove the ACline to the drive. When the AC line is removed, there will be a loss ofany inherent regenerative braking effect that might be present - themotor will coast to a stop. An auxiliary braking method may berequired.PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User ManualPublication 22F-UM001C-EN-E

Installation/Wiring1-13I/O Wiring RecommendationsImportant points to remember about I/O wiring: Always use copper wire.Wire with an insulation rating of 600V or greater is recommended.Control and signal wires should be separated from power wires by atleast 0.3 meters (1 foot).Important: I/O terminals labeled “Common” are not referenced to thesafety gro

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual Publication 22F-UM001C-EN-E In this manual we refer to the PowerFlex 4M Adjustable Frequency AC Drive as: drive, PowerFlex 4M or PowerFlex 4M Drive. Parameter numbers and names are shown in this format: The following words are used throughout the manual to describe an

Related Documents:

20D PowerFlex 700S 22A PowerFlex 4 22F PowerFlex 4M 22B PowerFlex 40 22D PowerFlex 40P 22C PowerFlex 400 25A PowerFlex 523 25B PowerFlex 525 25C PowerFlex 527 Reliance Electric A

PowerFlex 70 Drive PowerFlex 70 User Manual PowerFlex 70/700 Reference Manual 20A-UM001 PFLEX-RM001 PowerFlex 700 Drive PowerFlex 700 User Manual PowerFlex 70/700 Reference Manual 20B-UM001 PFLEX-RM001 PowerFlex 700S Drive PowerFlex 700S High Performance AC User Manual 20D-

PowerFlex 4 Adjustable Frequency AC Drive FRN 6.xx This Quick Start guide summarizes the basic steps needed to install, start-up and program the PowerFlex 4 Adjustable Frequency AC Drive. The information provided Does Not replace the User Manual and is intended for qualified drive service personnel only.

Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage PowerFlex 700, 700VC, and 750-Series AC Drives About This Document This information applies to PowerFlex 700, PowerFlex 700VC, and PowerFlex 750-Series AC Drives. This document pro

Manual Conventions In this manual we refer to the PowerFlex 70 Adjustable Frequency AC Drive as; drive, PowerFlex 70, or PowerFlex 70 Drive. To help differentiate parameter names and Liquid Crystal Display (LCD) text from other text, the following conventions are used: Parameter N

The information below summarizes the changes to the PowerFlex 70/700 Reference Manual, publication PFLEX-RM001 since the last release. Change Page PowerFlex 700 60 HP, 600V Derate added 1-6 PowerFlex 70 dimensions updated 1-7 PowerFlex 700 Frame 4 dimensio

PowerFlex 4 and PowerFlex 40 AC Drives Technical Data Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley PowerFlex 4 and 40 AC drives are the smallest and most cost-effective members of the PowerFlex family of drives. Available in power ratings from 0.2 to 11 kW (0.25 to 15 HP) and in voltage

Botany-B.P. Pandey 3. A Textbook of Algae – B.R. Vashishtha 4. Introductory Mycology- Alexopoulos and Mims 5. The Fungi-H.C. Dube . B.Sc. –I BOTANY : PAPER –II (Bryophytes, Pteridophytes, Gymnosperms and Palaeobotany) Maximum marks- 50 Duration - 3 hrs. UNIT -1 General classification of Bryophytes as Proposed by ICBN. Classification of Pteridophytes upto the rank of classes as proposed .