Air-CooledLiquid Chillers10 to 60TonsApril 2004CG-PRC007-EN

IntroductionAir-CooledLiquid ChillersDesign and manufacturing excellencemakesTrane a leader in the air-cooledchiller marketplace. For over 40 years,Trane has been using the bestengineering available in development,manufacturing, and marketing toproduce quality products. This traditionof using excellence to meet marketdemands is illustrated with theTrane 10to 60-ton air-cooled chillers.10, 15 Tons20–60 Tons 2003 American Standard Inc. All rights reservedCG-PRC007-EN

ContentsIntroductionFeatures and Benefits2Application Considerations94Selection Procedure14Model Number DescriptionGeneral Data1516Performance Data21Performance Adjustment FactorsCG-PRC001-ENControls1730Electric Power37Dimension and Weights39Mechanical Specifications483

Features andBenefitsInstallationSmall size, complete factory wiring, easylifting provisions, factory installedoptions and start-up control provide fast,easy installation. A complete factory runtest is performed on each unit,eliminating potential start-up problems.Integrated Comfort SystemsAllTrane chillers are ICS compatible. Asimple twisted wire pair is all it takes tohook an air-cooled chiller into aTracersystem. An ICS system provides themost advanced diagnostics, monitoring,and control that the industry can offer.OnlyTrane can supply the entire package.ICS provides comfort with one word —Trane.4(10–60 Ton)Packed Stock IncreasesProject FlexibilityTrane 10 to 60-ton air-cooled chillersare available through the most flexiblepacked stock program in the industry.Trane knows you want your units onthe jobsite, on time, when you needthem. To help meet this demand,Tranekeeps a multitude of unit sizes andvoltages in packed stock. Many ofthese include optional features such asisolators, low ambient head pressurecontrols and refrigerant gauge piping.You no longer have to settle for ascaled-down, basic unit to meet yourjob schedule. In many cases, units canbe shipped directly to the jobsite frompacked stock!CG-PRC007-EN

The 10 and 15-ton air-cooled ColdGenerator chillers, withTrane directdrive hermetic scroll compressors, hasoutstanding standard features andadditional benefits that make selection,installation, and servicing easy.FlexibilityFootprintCentral to the design of any project is theoperating envelope of the air-cooledpackaged chiller. With this in mind,Tranebuilds the chillers to make the mostefficient use of the available installationspace.The Trane CGA model chillers areextremely compact. They have thelightest weight, the smallest footprint,and the lowest silhouette of any chiller inthe industry.Features andBenefits(10–15 Ton)Optional Features Elapsed Time Meter/Number StartsCounter — Records number ofcompressor starts and operatinghours. Flow Switch — Required as a safetyinterlock to prevent operation of unitwithout evaporator flow (availableoption for field installation only). Integrated Comfort Systems (ICS)Interface — Provides the ability tocommunicate withTrane Tracer orTracker building management systemsvia aThermostat Control Module —(TCM). Gauges — Monitor suction anddischarge pressures. Hot Gas Bypass — Allows unitoperation below the minimum step ofunloading. Low Ambient Head Pressure Control— Modulates the rpm of the fan motorin response to outdoor ambienttemperature and unit head pressure.Provides unit cooling operation downto outdoor temperatures of 0 F. Coil Guard — Metal grille with PVCcoating to protect the condenser coil. Isolation — Neoprene in shear orspring flex isolators. Power Supply Monitor — Providesprotection against phase loss, phasereversal, phase imbalance, incorrectphase sequence and low line voltage.Less WeightThese lightweight models afford lessstress on building supports and greaterhandling ease.InstallationInstallation time and effort are reducedwhen dealing with a significantly smallerand lighter unit. In addition, havingelectrical and water connections on thesame side of the unit and a single-pointmain power connection serves to makeinstallation easier. The unit arrives at thejobsite fully assembled, tested, chargedand ready to provide chilled water.Ease of ServiceThe control panel and unit panels arecompletely removable for serviceaccessibility and convenience.ICS InterfaceCommunication withTraneTracer orTracker is possible through the ICSInterface on the 10 and 15 ton ColdGenerator chiller.CG-PRC007-EN5

Trane’s 20-60 ton chillers offer the sametime-tested and proven controltechnology that is applied to theIntelliPak Air Cooled rooftops.Superior control makes the IntelliPak atruly advanced chiller.Standard FeaturesMicroprocessor ControlThe IntelliPak chiller’s Unit ControlModule (UCM) is an innovative,modular microprocessor controldesign. It coordinates the actions of thechiller in an efficient manner andprovides stand-alone operation of theunit. A Human Interface (HI) Panel is astandard component of the IntelliPakChiller. Access to all unit controls is viathe Human Interface Panel.Factory Run TestingIn addition to outstanding efficientperformance, IntelliPak Chillers haveestablished a reputation for reliableoperation. Aside from the individualcomponent tests, allTrane 20 to 60-tonchillers are factory run tested withwater running through the evaporatorto confirm proper operation. Controloperation and current draw are bothmonitored to assure safe, reliableoperation.6Features andBenefits(20–60 Ton)Other Standard FeaturesOptional Features Trane 3-D Scroll compressors Advanced motor protection 300 psi waterside evaporator Evaporator insulation (¾-inchArmaflex II or equivalent) Evaporator heat tape (thermostatcontrolled) Condenser coil guards Operation down to 30 F withoutadditional wind baffles or headpressure control Loss of flow protection UL and CSA approval available Packed stock availability Control PowerTransformer Low ambient lockout Plain English (Spanish/French)Human Interface display Smart Lead/Lag operation Integrated chilled solution pumpcontrol Selectable process or comfort controlalgorithm External auto/stop Electronic low ambient dampercontrol integrated into UCM Flow switch Strainer/connection kit Controls for ice making operationMiscellaneous Options Trane Communications InterfaceModule (TCI) Unit Mounted Disconnect Isolators Superheat/Sub-Cooling Module Hot Gas Bypass Generic B A S Modules with 0-10 vanalog input/output, 0-5 v analoginput/binary output Remote Human Interface Panel(RHI) Remote Set point Potentiometer Zone Sensor (Chilled SolutionReset) Copper Fin Condenser Coils Electronic Low Ambient Damper(s) Inter-Processor CommunicationBridge (IPCB) Ice building control Other optionsIn addition to all of these options,Tranecan offer in-house design for manyapplications, including special coilcoating.CG-PRC007-EN

Features andBenefits(20–60 Ton)Enhanced ControlsIntelliPak Chiller Unit Control Module(UCM)Microprocessor ControlThe brain of the 20 to 60 ton air-cooledchiller is its Unit Control Module (UCM).The UCM is an innovative, modularmicroprocessor control design, whichcoordinates the actions of the chiller inan efficient manner, providing standalone operation of the unit.Access to the unit controls is via aHuman Interface (HI) Panel, a standardcomponent of the IntelliPak chiller. Thispanel provides a high degree of control.Superior monitoring capability andunmatched diagnostic information isprovided through a 2 line 40 characterper line, English language display.There are no diagnostic “codes”requiring a translation key forinterpretation. All system statusinformation and control adjustmentscan be made from the onboard HumanInterface Panel.Remote Human Interface (RHI) —The optional Remote Human Interface (RHI)performs the same functions as the Human Interface, with the exception of theservice mode. The RHI can be used with up to 4 air-cooled chillers from a singlepanel.The Integrated Comfort System — The Industry’s Most Advanced Comfort SystemThe UCM allows the 20 to 60-tonIntelliPak chiller to be part of the factoryinstalled Integrated Comfort System(ICS). ICS joins theTraneTracer buildingmanagement systems andTrane HVACequipment by a single twisted wirepair. This allows bidirectionalcommunication between theTracersystem and the unit mounted controls.Connected to the chiller’s UCM, thissimple pair allows you to control,monitor, and diagnose your building’scomfort system.The UCM is linked totheTracer system and theyelectronically “talk” to one another.Since ICS is factory-packaged, there isno need to install separate sensors tomonitor your chiller’s operation. All ofthe control points are on the controllerand ready to go when the unit ships.Simply hookup theTracer system to theIntelliPak chiller with the twisted wirepair.This feature means lower installedcost, less chance for jobsite errors, lessdesign time on the front end of yourproject, and fewer callbacks.CG-PRC007-ENICS gives you the most powerfulmonitoring and diagnostic systemavailable. Monitoring up to 30 individualpoints, the ICS can detect and correctproblems before a comfort level changeis even noticed. Advanced monitoringand diagnostics can help buildingowners to more effectively market theirbuildings to prospective tenants.An ICS system is the most advancedcomfort system in the industry. BecauseTrane has more experience with ICSthan all other equipment manufacturerscombined, you can feel secure knowingthat you are dealing with a proven trackrecord in building management. Trane isthe only brand that supplies the entirepackage.Tracer control points forIntelliPak Chillers Chilled solution set point Default chilled solution set point Ice set point Default ice set point Chiller enable point Failure mode Ice making enable point KW limit enable point Demand limiting cooling stages Default number of compressors Design delta temperature Control response set point Reset option7

Trane 3-D Scroll CompressorSimple Design with 70% Fewer PartsFewer parts than an equal capacityreciprocating compressor meanssignificant reliability and efficiencybenefits. The single orbiting scrolleliminates the need for pistons,connecting rods, wrist pins and valves.Fewer parts lead to increased reliability.Fewer moving parts, less rotating massand less internal friction means greaterefficiency than reciprocatingcompressors.Features andBenefits(20–60 Ton)Proven Design Through Testing andResearchWith over twenty years of developmentand testing,Trane 3-D Scrollcompressors have undergone morethan 400,000 hours of laboratory testingand field operation.This work combinedwith over 25 patents makesTrane theworldwide leader in air conditioningscroll compressor technology.One of two matched scroll plates —the distinguishing feature of the scrollcompressor.Chart illustrates low torque variation of3-D Scroll compressor vs.reciprocating compressor.TheTrane 3-D Scroll provides importantreliability and efficiency benefits.The 3-DScroll allows the orbiting scrolls to touchin all three dimensions, forming acompletely enclosed compressionchamber which leads to increasedefficiency. In addition, the orbiting scrollsonly touch with enough force to create aseal; there is no wear between the scrollplates.The fixed and orbiting scrolls aremade of high strength cast iron whichresults in less thermal distortion, lessleakage, and higher efficiencies. Themost outstanding feature of the 3-DScroll compressor is that slugging willnot cause failure. In a reciprocatingcompressor, however, the liquid or dirtcan cause serious damage.Low Torque VariationThe 3-D Scroll compressor has a verysmooth compression cycle; torquevariations are only 30 percent of thatproduced by a reciprocating compressor.This means that the scroll compressorimposes very little stress on the motorresulting in greater reliability. Low torquevariation reduces noise and vibration.Suction Gas Cooled MotorCompressor motor efficiency andreliability is further optimized with thelatest scroll design. Cool suction gaskeeps the motor cooler for longer life andbetter efficiency.8CG-PRC007-EN

ApplicationConsiderationsCertain application constraints should beconsidered when sizing, selecting andinstallingTrane air-cooled chillers. Unitand system reliability is often dependentupon proper and complete compliancewith these considerations. Where theapplication varies from the guidelinespresented, it should be reviewed withyour localTrane sales engineer.Note: The terms water and solution areused interchangeably in the followingparagraphs.UNIT SIZINGUnit capacities are listed in the“Performance Data” section.Intentionally oversizing a unit to assureadequate capacity is not recommended.Erratic system operation and excessivecompressor cycling are often a directresult of an oversized chiller. In addition,an oversized unit is usually moreexpensive to purchase, install, andoperate. If oversizing is desired, considerusing two units.UNIT PLACEMENT1Setting The UnitA base or foundation is not required ifthe selected unit location is level andstrong enough to support the unit’soperating weight (see “Weights” sectionof this catalog).For a detailed discussion of base andfoundation construction, refer to theTrane Reciprocating RefrigerationManual. Manuals are available throughthe localTrane office.2Isolation and Sound EmissionThe most effective form of isolation is tolocate the unit away from any soundsensitive area. Structurally transmittedsound can be reduced by using springisolators. Spring isolators are generallyeffective in reducing vibratory noisegenerated by compressors, andtherefore, are recommended for soundsensitive installations. An acousticalengineer should always be consulted oncritical applications.CG-PRC007-ENFor maximum isolation effect, water linesand electrical conduit should also beisolated. Wall sleeves and rubber isolatedpiping hangers can be used to reduce thesound transmitted through water piping.To reduce the sound transmitted throughelectrical conduit, use flexible electricalconduit.State and local codes on soundemissions should always be considered.Since the environment in which a soundsource is located affects sound pressure,unit placement must be carefullyevaluated. Sound pressure and soundpower levels for chillers are available onrequest.3ServicingAdequate clearance for evaporator andcompressor servicing should beprovided. Recommended minimumspace envelopes for servicing are locatedin the dimensional data section and canserve as a guideline for providingadequate clearance.The minimum spaceenvelopes also allow for control paneldoor swing and routing maintenancerequirements. Local code requirementsmay take precedence.4Unit LocationaGeneralUnobstructed flow of condenser air isessential to maintain chiller capacity andoperating efficiency. When determiningunit placement, careful considerationmust be given to assure a sufficient flowof air across the condenser heat transfersurface.Two detrimental conditions arepossible and must be avoided: warm airrecirculation and coil starvation.Debris, trash, supplies, etc., should notbe allowed to accumulate in the vicinityof the air-cooled chiller. Supply airmovement may draw debris into thecondenser coil, blocking spaces betweencoil fins and causing coil starvation.Both warm air recirculation and coilstarvation cause reductions in unitefficiency and capacity because of thehigher head pressures associated withthem. In addition, in more severe cases,nuisance unit shutdowns will result fromexcessive head pressures. Estimates ofthe degree of efficiency and capacityreduction in such situations can bedetermined. Consult your localTranesales engineer.Cross winds, those perpendicular to thecondenser, tend to aid efficient operationin warmer ambient conditions, however,they tend to be detrimental to operationin lower ambients or when hot gasbypass is used due to the accompanyingloss of adequate head pressure. As aresult, it is advisable to protect air-cooledchillers from continuous direct windsexceeding 10 miles per hour in lowambient conditions.Low Ambient Operation — 20-60 Tonmodels — Human InterfaceRecommendationsWhen the temperature outside issubzero, who wants to be out theremonitoring or troubleshootingdiagnostics? Because we understand aservice technician’s reluctance to do this,we recommend using a Remote HumanInterface (RHI) panel. The servicetechnician can troubleshoot anddiagnose in the comfort of a mechanicalroom.Warm air recirculation occurs whendischarge air from the condenser fans isrecycled back to the condenser coil inlet.Coil starvation occurs when free airflowto the condenser is restricted.Condenser coils and fan discharge mustbe kept free of snow or otherobstructions to permit adequate airflowfor satisfactory unit operation.9

ApplicationConsiderationsbdWATER TREATMENTProvide Vertical ClearanceProvide Sufficient Unit-to-Unit ClearanceVertical condenser air discharge must beunobstructed. While it is difficult topredict the degree of warm airrecirculation, a unit installed as shownbelow would have its capacity andefficiency significantly reduced —possibly to the degree of nuisance highhead pressure trip outs. Performancedata is based on free air discharge.Units should be separated from eachother by sufficient distance to preventwarm air recirculation or coil starvation.Doubling the recommended single unitair-cooled chiller clearances willgenerally prove to be adequate.Dirt, scale, products of corrosion, andother foreign material in the water willadversely affect heat transfer betweenthe water and system components.Foreign matter in the chilled watersystem can also increase pressure dropand, consequently, reduce waterflow.Proper water treatment must bedetermined locally and depends on thetype of system and local watercharacteristics.eWalled Enclosure InstallationsWhen the unit is placed in an enclosureor small depression, the top of the fansshould be no lower than the top of theenclosure or depression. If they are,consideration should be given to ductingthe top of the unit. Ducting individualfans, however, is not recommended.Such applications should always bereviewed with the localTrane salesengineer.cProvide Lateral ClearanceThe condenser coil inlet must not beobstructed. A unit installed closer thanthe minimum recommended distance toa wall or other vertical riser mayexperience a combination of coilstarvation and warm air recirculation,resulting in unit capacity and efficiencyreductions and possible excessive headpressures.The recommended lateral clearances aredepicted in the dimensional data section.These are estimates and should bereviewed with the localTrane salesengineer at the jobsite.10Do not use salt or brackish water inTranechillers. Use of either will lead to ashortened life.Trane encourages theemployment of a reputable watertreatment specialist, familiar with localwater conditions, to assist in theestablishment of a proper watertreatment program.The capacities given in the “PerformanceData” section of this catalog are basedon water with a fouling factor of 0.0001(in accordance with ARI 550/590-98). Forcapacities at other fouling factors, see“Performance Adjustment Factors”section of this catalog.EFFECT OF ALTITUDE ONCAPACITYVOLTAGENominal voltage is the nameplate ratingvoltage.The actual range of line voltagesat which the equipment can satisfactorilyoperate are given -440374-456414-508520-635Chiller capacities given in the“Performance Data” section are basedupon application at sea level. Atelevations substantially above sea level,the decreased air density will decreasecondenser capacity and, therefore, unitcapacity and efficiency. The adjustmentfactors in the “Performance AdjustmentFactors” section of this catalog can beapplied directly to the performance datato determine the unit’s adjustedperformance.CG-PRC007-EN

ApplicationConsiderationsAMBIENT

Air-Cooled Liquid Chillers 10, 15 Tons 20–60 Tons Design and manufacturing excellence makes Trane a leader in the air-cooled chiller marketplace. For over 40 years, Trane has been using the best engineering available in development, manufacturing, and marketing to produce quality products. This tradition of using excellence to meet market

Related Documents:

cause water-cooled chillers can take advantage of lower condensing temperatures than air-cooled chillers. Air-cooled chillers have a full load kW/ton of approxi-mately 1.25 while water-cooled chillers have a full load kW/ton of between 0.55 and 0.8 kW/ton. The kW draw of the cooling tower fans and con-denser water pump should be

Air Cooled Chiller Air Air 2 Air Air 6 AIR COOLED CHILLERS Air-cooled chillers are refrigeration machines that remove heat from cooling loads using chilled water and reject this heat into the atmosphere using refrigerant. THEY ALL HAVE fans, condenser coils, and compressors. Air-cooled chillers are used to provide cooling for human comfort and electronic equipment as well as industrial process .

Air-Cooled Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Nominal Capacities: 50 to 410 Tons 179 to 1445 kW Product Data Features/Benefits ComfortLink control Your link to a world of simple and easy to use air-cooled chillers that offer out-standing performance and value. The 30GTN,GTR liquid chillers employ more than the .

Air-Cooled Liquid Chillers The 30XAS Aquaforce liquid chillers are the premium solution for industrial and commercial applications where installers, consultants and building owners require optimal performances and maximum quality. The Aquaforce liquid chillers are designed to meet current and future requirements in terms of energy efficiency and

AIR-COOLED LIQUID CHILLERS Liquid chillers with partial heat recovery Liquid chillers with total heat recovery FOCS FOCS-D FOCS-R I dati contenuti possono essere variati senza obbligo di preavviso All specification and data are subject to change without notice CLIMAVENETA S.p.A. Via Sarson, 57/C Tel. ( 39) 0424 509 500 Fax ( 39) 0424 509 509

Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 80 F chilled water. MAXIMUM SERIES † Air & Water-Cooled † 1/4 to 40 Tons † 20 F to 80 F † Using Non-Ozone Depleting Refrigerants 10 ton air-cooled model 10 ton water-cooled model 2 ton water-cooled model 1 ton air-cooled model

8 to 12 F for water-cooled chillers and 10 to 15 F for air-cooled chillers. ENSURE PROPER SUPERHEAT For air-cooled chillers, make sure fans work properly and coils are clean on the condenser side of the system. For water-cooled chillers, ensure that all flow rates and pressure drops on th

air-cooled screw liquid chillers e/v high efficiency and s/p standard efficiency air-cooled screw liquid chillers installation, operation, maintenance supersedes: 201.23-nm2 (610) form 201.23-nm2 (315) 035-21506-101 issue date: march 9, 2015. 2 johnson controls form 201.23-nm2