Water And Remote Air Cooled Liquid Chillers With Screw Compressors Style B

1y ago
6 Views
2 Downloads
2.84 MB
68 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Ryan Jay
Transcription

YCSE040-YCSE100 & YCRE040-YCRE100INSTALLATION, COMMISSIONING,OPERATION & MAINTENANCERevision 1Form 035-21786-100 (0909)WATER AND REMOTE AIRCOOLED LIQUID CHILLERSWITH SCREW COMPRESSORSSTYLE B(YCSE 134-320KW)(YCRE 127-307KW)AspakR407C

035-21786-100 Rev. 1 (0909)TABLE OF CONTENTS12SUPPLIER INFORMATION41.1Introduction1.14.1Location Requirements4.11.2Warranty1.14.2Installation of Vibration Isolators4.11.3Safety1.14.3Pipework Connection4.11.4Responsibility for Safety1.24.4Water Treatment4.21.5About this Manual1.24.5Pipework Arrangement4.31.6Misuse of Equipment1.24.6Connection Types & Sizes4.31.7Emergency Shutdown1.34.7Condenser Cooling Liquid Systems 4.41.8Safety Labels1.34.8Electrical Connection4.51.9Material Safety Data1.44.9Remote Refrigerant CondenserSystems (YCRE models only)4.5PRODUCT frigerant Circuits2.12.4Evaporator2.12.5Condenser2.12.6Power and Control Panels2.22.7Accessories and Options2.22.8Nomenclature2.32.9Refrigerant Flow Diagram2.453INSTALLATION64.10 Power Wiring4.84.11 Control Wiring4.84.12 Connection Diagram4.9COMMISSIONING5.1Preparation5.15.2First Time Start-up5.2UNIT OPERATION6.1General Description6.16.2Operation6.16.3Normal Running and Cycling6.1TRANSPORTATION, HANDLING ANDSTORAGE6.4Shutdown6.13.1Delivery and Storage3.16.5Control System6.13.2Inspection3.13.3Moving the Unit3.17.1General Requirements7.13.4Lifting Weights3.27.2Daily Maintenance7.13.5Weight Distribution & Centreof Gravity7.3Scheduled Maintenance7.13.27.4Pressure Vessel In-ServiceInspection7.27MAINTENANCEI-i

035-21786-100 Rev. 1 (0909)8TROUBLE SHOOTING8.19Competent Persons TroubleShooting Guide8.1TECHNICAL DATA9.1Flow Rate and Pressure DropGraphs9.19.2Performance Graphs9.29.3Operating Limitations9.49.4Physical Data9.59.5Electrical Data9.69.6Sound Data9.79.7Clearances and Foundations9.89.8Dimensions9.910 SPARE PARTS10.1 Renewal Parts List10.110.2 Recommended Compressor Oils10.110.3 Associated Drawings10.111 DECOMMISSIONING. DISMANTLING ANDDISPOSAL11.1 GeneralI-ii11.1

035-21786-100 Rev. 1 (0909)1SUPPLIER INFORMATION1.1IntroductionYork YCSE/YCRE chillers are manufactured to thehighest design and construction standards to ensurehigh performance, reliability and adaptability to all typesof air conditioning installations.For warranty purposes, the following conditions must besatisfied:The initial start of the unit must be carried out by trainedpersonnel from an Authorised York Service Centre.Only genuine York approved spare parts, oils andrefrigerants must be used.The units are intended for cooling water or glycolsolutions and are not suitable for purposes other thanthose specified in this manual.All the scheduled maintenance operations detailed inthis manual must be performed at the specified times bysuitably trained and qualified personnel.This manual contains all the information required forcorrect installation and commissioning of the unit,together with operating and maintenance instructions.The manuals should be read thoroughly beforeattempting to operate or service the unit.Failure to satisfy any of these conditions willautomatically void the warranty.All procedures detailed in the manuals, includinginstallation, commissioning and maintenance tasksmust only be performed by suitably trained and qualifiedpersonnel.The manufacturer will not be liable for any injury ordamage caused by incorrect installation,commissioning, operation or maintenance resultingfrom a failure to follow the procedures and instructionsdetailed in the manuals.1.2WarrantyJohnson Controls warrants all equipment and materialsagainst defects in workmanship and materials for oneyear from initial start-up, or eighteen months fromdelivery (whichever occurs first) unless extendedwarranty has been agreed as part of the contract.The warranty is limited to free replacement and shippingof any faulty part, or sub-assembly which has failed dueto poor quality or manufacturing errors. All claims mustbe supported by evidence that the failure has occurredwithin the warranty period, and that the unit has beenoperated within the designed parameters specified.All warranty claims must specify the unit model, serialnumber and order number. These details are printed onthe unit identification plate, fitted on the outer edge of theoptions panel.The unit warranty will be void if any modification to theunit is carried out without prior written approval fromJohnson Controls.1.3SafetyStandards for SafetyYCSE/YCRE chillers are designed and built within anEN ISO 9001 accredited design and manufacturingorganisation and, within the limits specified in thismanual, are in conformity with the essential health andsafety requirements of the following European UnionDirectives:Machinery Directive (98/37/EC)Low Voltage Directive (2006/95/EC)EMC Directive (2004/108/EC)They conform to the applicable and essential safetyrequirements of Pressure Equipment Directive97/23/EC and bear CE marking.Fluorinated Greenhouse GasesnThis equipment contains fluorinated greenhousegases covered by the Kyoto Protocol.nThe global warming potential of the refrigerant(R407C) used in this unit is 1520.nThe refrigerant quantity is stated in the PhysicalData table in Section 9 of this document.nThe fluorinated greenhouse gases in thisequipment may not be vented to the atmosphere.nThis equipment should only be serviced byqualified technicians.1-1

035-21786-100 Rev. 1 (0909)1.4Responsibility for SafetyEvery care has been taken in the design andmanufacture of the units to ensure that they meet thesafety requirements listed in the previous paragraph.However, the individual operating or working on anymachinery is primarily responsible for:Personal safety, safety of other personnel, and themachinery.Correct utilisation of the machinery in accordance withthe procedures detailed in the manuals.1.51.6Misuse of EquipmentSuitability for ApplicationThe unit is intended for cooling water or glycol solutionsand is not suitable for purposes other than thosespecified in these instructions. Any use of the equipmentother than its intended use, or operation of theequipment contrary to the relevant procedures mayresult in injury to the operator, or damage to theequipment.The unit must not be operated outside the design limitsspecified in this manual.About this ManualStructural SupportThe following symbols are used in this document to alertthe reader to areas of potential hazard.A Warning is given in this document toidentify a hazard which could lead topersonal injury. Usually an instruction willbe given, together with a brief explanationand the possible result of ignoring theinstruction.A Caution identifies a hazard which couldlead to damage to the machine, damage toother equipment and/or environmentalpollution. Usually an instruction will be given,together with a brief explanation and thepossible result of ignoring the instruction.A Note is used to highlight additionalinformation which may be helpful to you butw h e r e th e r e a r e n o s p e c i a l s a f e t yimplications.The contents of this manual include suggested bestworking practices and procedures. These are issued forguidance only, they do not take precedence over theabove stated individual responsibility and/or local safetyregulations.This manual and any other document supplied with theunit, are the property of Johnson Controls whichreserves all rights. They may not be reproduced, inwhole or in part, without prior written authorisation froman Authorised Johnson Controls representative.1-2Structural support of the unit must be provided asindicated in these instructions. Failure to provide propersupport may result in injury to the operator, or damage tothe equipment.Mechanical StrengthThe unit is not designed to withstand loads or stressesfrom adjacent equipment, pipework or structures.Additional components must not be mounted on theunit. Any such extraneous loads may cause structuralfailure and may result in injury to the operator, ordamage to the equipment.General AccessThere are a number of areas and features which may bea hazard and potentially cause injury when working withthe unit unless suitable safety precautions are taken. Itis important to ensure access to the unit is restricted tosuitably qualified persons who are familiar with thepotential hazards and precautions necessary for safeoperation and maintenance of equipment containinghigh temperatures, pressures and voltages.Pressure SystemsThe unit contains refrigerant vapour and liquid underpressure, release of which can be a danger and causeinjury. The user should ensure that care is taken duringinstallation, operation and maintenance to avoiddamage to the pressure system. No attempt should bemade to gain access to the component parts of thepressure system other than by suitably trained andqualified personnel.

035-21786-100 Rev. 1 (0909)Electrical1.8The unit must be earthed. No installation ormaintenance work should be attempted on electricalequipment without first switching off, isolating andlocking-off the power supplies. Work on live equipmentmust only be carried-out by suitably trained andqualified personnel. No attempt should be made to gainaccess to inside of the control panel, wiring or otherelectrical enclosures during normal operation of the unit.The following labels are fixed to each unit to giveinstruction, or to indicate potential hazards which mayexist.Refrigerants and OilsRefrigerants and oils used in the unit are generallynon-toxic, non-flammable and non-corrosive, and poseno special safety hazards. Use of gloves and safetyglasses are, however, recommended when working onthe unit. Build up of refrigerant vapour, from a leak forexample, does pose a risk of asphyxiation in confined orenclosed spaces and attention should be given to goodventilation. For more comprehensive information onsafety precautions for use of refrigerants and oils, referto the Materials Safety Data tables provided.High Temperature and Pressure CleaningHigh temperature and pressure cleaning methods (e.g.steam cleaning) should not be used on any part of thepressure system as this may cause operation of thepressure relief device(s). Detergents and solventswhich may cause corrosion should also be avoided.1.7Emergency ShutdownIn case of emergency the unit can be shut down byoperating the main power switch on the control panel.Safety LabelsWhite symbol on blue backgroundFor safe operation, read theInstructions firstBlack symbol on yellow backgroundWarning: This machine may startautomatically without prior warningBlack symbol on yellow backgroundWarning: Hot surfaceBlack symbol on yellow backgroundWarning: Safety relief valve maydischarge gas or liquid without priorwarningBlack symbol on yellow backgroundWarning: Isolate all electrical sourcesof supply before opening or removingthe cover, as lethal voltages may existBlack symbol on yellow backgroundGeneral attention symbol1-3

035-21786-100 Rev. 1 (0909)1.9Material Safety DataRefrigerant Data:Safety DataToxicityIn contact with skinR407CLow.Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous by skin absorption.Thaw affected areas with water. Remove contaminated clothing carefully — may adhere to skin incase of freeze burns. Wash affected areas with plenty of warm water. If symptoms occur (irritationor blistering) obtain medical attention.In contact with eyesVapour has no effect. Liquid splashes or spray may cause freeze burns. Immediately irrigate witheyewash solution or clean water for at least 10 minutes. Obtain immediate medical attention.IngestedHighly unlikely to occur — but should this occur freeze burn will occur. Do not induce vomiting.Provided patient is conscious, wash mouth with water and give about 250 ml (0.5 pint) to drink.Obtain immediate medical attention.InhalationHigh atmospheric concentrations may have an anaesthetic effect, including loss of consciousness.Very high exposures may cause an abnormal heart rhythm and prove suddenly fatal.At higher concentration there is a danger from asphyxiation due to reduced oxygen content ofatmosphere. Remove patient to fresh air, keep warm and at rest. Administer oxygen if necessary.Apply artificial respiration if breathing has ceased or shows signs of failing. In event of cardiacarrest apply external cardiac massage. Obtain immediate medical attention.Further medical advice Symptomatic and supportive therapy is indicated. Cardiac sensitisation has been described whichmay, in the presence of circulating catecholamines such as adrenalin, give rise to cardiacarrhythmia’s and subsequent arrest following exposure to high concentrations.Long term exposureA lifetime inhalation study in rats has shown that exposure to 50,000 ppm resulted in benigntumours of the testis. This is not considered to be of relevance to humans exposed toconcentrations at or below the occupational exposure limit.Occupational exposure Recommended limit: 1000 ppm v/v - 8 hr TWA.limitsStabilityNot specified.Conditions to avoidUse in presence of naked flames, red hot surfaces and high moisture levels.May react violently with sodium, potassium, barium and other alkali and alkaline earth metals.Hazardous reactionsIncompatible materials: Magnesium and alloys containing more then 2% magnesium.HazardousHalogen acids by thermal decomposition and hydrolysis.decompositionproductsGeneral precautionsAvoid inhalation of high concentrations of vapours. Atmospheric concentrations should beminimised and kept as low as reasonably practicable below the occupational exposure limit. Thevapour is heavier than air and collects at low level and in confined areas. Ventilate by extraction atlowest levels.Respiratory protection Where doubt exists on atmospheric concentration, HSE approved breathing apparatus should beworn. This should be self contained or of the long breather type.StorageKeep containers dry and in a cool place away from fire risk, direct sunlight, and all sources of heatsuch as radiators. Keep at temperatures not exceeding 45 C.Protective clothingWear overalls, impervious gloves and goggles/face protection.Spill/leak procedureEnsure suitable personal protective clothing and respiratory protection is worn. Provided it is safeto do so, isolate the source of the leak. Allow small spillage’s to evaporate provided there issuitable ventilation.Large spillage’s: Ventilate area. Contain spillage’s with sand, earth or any suitable absorbentmaterial. Prevent liquid from entering drains, sewers, basements and work pits since vapour maycreate a suffocating atmosphere.DisposalBest to recover and recycle. If this is not possible, destruction is to be in an approved facility whichis equipped to absorb and neutralise acids and other toxic processing products.Fire extinguishing data Non-flammable at atmospheric conditions.ContainersFire exposed containers should be kept cool with water sprays. Containers may burst ifoverheated.Fire fighting protective Self contained breathing apparatus and protective clothing must be worn in fire conditions.equipment1-4

035-21786-100 Rev. 1 (0909)Thermal and Acoustic Materials DataHealth Hazard & FirstAidStability / ReactivityHandling / Use /DisposalFire & ExplosionToxicity Index 10 to NES713 Issue 3 (1991): Non-hazardous, non-toxic. No first aid necessary.Stable.No special handling precautions required. Dispose of according to local laws and regulationsgoverning non-biodegradable non-hazardous solid wastes.Flammability rating Class 1 to BS 476 pt 7: Non-flammable. If forced to burn, combustion productsare typically over 95% carbon dioxide and carbon monoxide.Refrigerant Oil Data:Safety DataYork "Y" OilHazardous Ingredients / Identity InformationHazardous Components (Specific ChemicalIdentity, Common Name)No hazardous materials present.CHEMICAL NAME:Polyole ester and Lubricating oil additiveCOMPONENT :Polyole ester 99mass%Lubricating oil additive 1mass%OSHA PELACGIH TLVPhysical CharacteristicsBoiling PointNot applicableVapor Pressure (mmHg)Not applicableVapor Density (AIR 1)Not applicableAppearance and OdorLight yellow, clear mobile liquidSpecific Gravity (H.0 1)1.0230g/cm³(15)Melting Point (Pour point)-27.5Evaporation RateNot applicableFire and Explosion Hazard DataFlash Point (Method Used)250 (COC)Flammable limitsNo informationExtinguishing MediaFoam, dry chemical, carbon dioxideSpecial Fire Fighting ProceduresNoUnusual Fire and Explosion HazardsNot in particular. Normal protective measures for organic chemical productswith flash points of above 100LELUELReactivity DataStabilityStableIncompatibility (Materials to Avoid)NoHazardous Decomposition or By-productsNoHazardous PolymerizationWill not occur1-5

035-21786-100 Rev. 1 (0909)Health Hazard DataRoute(s) of EntryNo significant health hazards are identified. Prolonged repeated skincontact may cause irritation and dermatitisHealth Hazards (Acute and Chronic)No significant health hazards are identified. Prolonged repeated skincontact may cause irritation and dermatitisCarcinogenicityNTP: NoSigns and Symptoms of ExposureNo information is availableMedical Conditions Generally Aggravatedby ExposureNo information is availableSkin ContactWash material off the skin with copious amounts of water and soapEyes ContactImmediately flush with plenty of water for at least 15 minutesInhalationRemove exposed person to fresh airIngestionDo not induce vomiting. Call a physician immediatelyIARC Monographs: NoOSHA Regulated: NoPrecautions for Safe Handling and UseSteps to be Taken In Case Material isReleased or SpilledPrevent spillage from spreading by using sand and absorb the liquidsubstance using a suitable inert material. Transfer to a suitably labelledsealable container. Do not allow liquid to enter open waters or groundwater.Waste Disposal MethodWaste material may be incinerated under conditions which meet all Federal,state and local environmental control regulations.Precautions to be Taken in Handling andStoringStore in cool, dark and low humidity place.Other PrecautionsAvoid repeated skin contact and breathing of mist or vapour.Control MeasuresRespiratory ProtectionUnder normal conditions, respirator is not usually required.VentilationLocal ExhaustMechanical (General)SpecialProtective GlovesRubber glovesEye ProtectionGlasses or gogglesOther Protective Clothing or EquipmentNot requiredWork/Hygienic PracticesNot requiredNot requiredNot requiredAdequate ventilation should be maintainedwhen handling heated productsAdditional InformationThe information contained herein has been compiled from data published in the literature. This data is believed to bereliable, but certain values may vary from source to source.This data is not to be construed as absolutely complete. It is the responsibility of the user to determine the bestprecautions necessary for his/her application.This data only refers to the specific material designated and not to any combinations.1-6

035-21786-100 Rev. 1 (0909)451212345CompressorEvaporatorCondenser (YCSE only)Power SectionControl Panel2PRODUCT DESCRIPTION2.1Introduction3YORK YCSE/YCRE R407C chillers are designed forwater or water-glycol cooling. It is designed for indoorinstallation in a plant room. Units are available with oneor two independent refrigerant circuits with a singleevaporator and, on YCSE models, a single condenser.Units are completely factory assembled with allinterconnecting refrigerant piping and wiring ready forfield installation. The units are pressure tested,evacuated, and fully factory charged with refrigerantR407C and oil in each of the independent refrigerantcircuits. After assembly, an operational test isperformed with water flowing through the evaporatorand condenser (YCSE) to ensure that each refrigerantcircuit operates correctly.2.2CompressorThe unit has suction cooled, semi-hermetic screwcompressors. The compressors incorporate twin-screwrotors and solenoid valves for continuous capacitycontrol. The compressors are equipped with a built-in oilseparator, an oil sight glass, a crankcase oil heater anda suction filter. The compressors have a 2-pole motorwith over current and thermostat protection. Start / Deltastarting is provided as standard. All compressors aremounted on isolator pads to reduce transmission ofvibration to the rest of the unit.Capacity ControlFor YCSE/YCRE units, the compressors will start at theminimum load position and provide a capacity controlrange from 15% to 100 % per compressor using acontinuous function slide valve.2.3Refrigerant CircuitsDepending on model size, one or two independentrefrigerant circuits are provided on each unit. Eachcircuit uses copper refrigerant pipe formed on computercontrolled bending machines to reduce the number ofbrazed joints resulting in a reliable and leak resistantsystem.Liquid line components include a service valve, a highabsorption filter dryer, a sight glass with moistureindicator and an electronic expansion valve.Suction line components include an optional serviceand isolation valve.Discharge line components include a check valve, anoptional service and isolation valve and a pressure reliefvalve.2.4EvaporatorThe evaporator is a stainless steel brazed type plateheat exchanger. The waterside design workingpressure is 10 barg. The refrigerant side design workingpressure is 18 bar g. The cooler is thermally insulatedwith flexible closed cell foam. Water connection to theevaporator is via victaulic-grooved connections. Flangeconnections are available as an option.2.5Condenser (YCSE Only)The condenser is a stainless steel brazed type plateheat exchanger. The waterside design workingpressure is 10 barg. The refrigerant side design workingpressure is 30 bar g. Water connection to the condenseris via victaulic-grooved connections. Flangeconnections are available as an option.2-1

035-21786-100 Rev. 1 (0909)2.7Accessories and OptionsModbus1234562-Pole MotorBuilt-in Oil SeparatorTwin Screw RotorsOil Sight GlassOil HeaterSuction FilterTo integrate the unit into the building managementsystem. The interface permits the connection of up to 8units using the Modbus communications protocol. Referto HARC Modbus data sheet (035-22384-000).Lonworks2To integrate the unit into the building managementsystem. The interface permits the connection of up to 8units using the Lon communications protocol. Refer toHARC Lonworks data sheet (035-22383-000).1Multi Unit Sequencer - CSC-5S3645Provides individual control and monitoring for up to 8units within the air conditioning system. This allows theunits to be managed remotely from the plant room.Compressor Circuit BreakersCircuit breakers to replace the standard fuses forprotection against over current. The breakers providemore precise monitoring than fuses and easy reset afterfault.2.6Power and Control PanelsAll power and controls are contained in an IP2X cabinetwith hinged and gasket sealed outer doors.The power section includesA factory mounted non-fused disconnect switch withexternal handle to enable connection of the unit powersupply. The disconnect switch can be used to isolate thepower for servicing.Factory mounted compressor contactors, fuses andover current relays to provide overload and short circuitprotection.Differential Water Pressure Switch (es)Differential pressure switches between the water inletand outlets to ensure liquid flow during operation.Flow Switch (es)Field installed flow switches to ensure liquid flow duringoperation.Glycol CoolingFour 7-segment LED displayFactory set-up for applications requiring water outlettemperatures below 5 C: Category 1: Outlettemperature 0 to 4 C; Category 2: Outlet temperature -1to - 5 C and Category 3: Outlet temperature - 6 to - 10 C.The system must have the correct percentage of glycoladded. (Refer to glycol application factors)Four push button switchesDischarge and/or Suction Stop ValvesLED indicators for power, operation and alarm statusFactory fitted valve(s) to allow refrigerant isolationduring servicing.Customer terminal block for control inputs and liquidflow switch connectionCompressor Safety Valve(s)The control section includesMicroprocessor boards to provide automatic operationand accurate temperature control.2-2Factory fitted single or dual compressor safety valve(s).

035-21786-100 Rev. 1 (0909)Dual Pressure Relief ValvesAVM (Spring Isolators)Two safety valves in parallel of which one is operationalto assist in valve replacement during maintenance.Spring and cage type isolators for mounting under theunit base rails to avoid transmission of vibration to theplant room structure (supplied loose with unit for fieldassembly)Suction Pressure Relief ValvesAdditional pressure relief valve on suction side ofcompressor when required.Water FilterPN16 FlangesField installed water filter at the cooler inlet to protect theexchanger from excessive fouling.Wooden CrateWelded PN16 flanges and companion flanges on thewater connections with gasket seals.Special packing in a wooden crate to protect the chillerfrom damages during transportationAVM (Resilient Pads)Heat Pump Kit (YCSE only)Rubber anti-vibration pads underneath the unit to avoidtransmission of vibration to the plant room structure.Capability to control the chiller based on the condenserleaving water temperature.2.8NomenclatureYCSE100SB50B12345BASE PRODUCT TYPEY: YorkC: ChillerS: S Screw: R Remote AirCooled ScrewE677NOMINAL CAPACITY###Standard Units:040:050 :060:080:100kW89UNIT DESIGNATOR / REFRIGERANTS: Standard UnitB: R407C Refrigerant10 11VOLTAGE5DESIGN SERIES: 380-415 / 3 / 50 N0B: Design Level: EuropeanRefigerant Flow DiagramYCSELow-pressure liquid refrigerant enters the cooler and is evaporated and superheated by the heat energy absorbedfrom the chilled liquid passing through the cooler plates. Low-pressure vapour enters the compressors wherepressure and superheat are increased. High pressure superheated refrigerant enters the condenser where heat isrejected to the condenser water passing through the plates. The fully condensed and subcooled liquid leaves thecondenser and enters the expansion valve, where pressure reduction and further cooling takes place. Thelow-pressure liquid refrigerant then returns to the cooler.YCRELow pressure liquid refrigerant enters the cooler and is evaporated and superheated by the heat energy absorbedfrom the chilled water passing through the cooler plates. Low pressure vapour enters the compressor wherepressure and superheat are increased. Heat is rejected by the remote condenser. The fully condensed andsubcooled liquid refrigerant then enters the expansion valve where pressure reduction and further cooling takesplace before returning to the cooler.2-3

035-21786-100 Rev. 1 (0909)2.9Refrigerant Flow DiagramYCSE 040, 050, 060, 100 Models1234567891011121314152-4CompressorCheck ValvePressure Relief ValveStop Valve (Option)CondenserStop Valve - Refrigerant Charge PointStop ValveDrierSight GlassElectronic Expansion ValveEvaporatorStop Valve (Option)Low Pressure SensorHigh Pressure SwitchHigh Pressure Sensor1617181920212223242526272829Compressor Safety Valve (Option)Compressor Dual Safety Valve (Option)Thermistor - SuctionThermistor - DischargeThermistor - EvaporatorThermistor - Evaporator Water InletThermistor - Evaporator Water OuletThermistor - Evaporator Water OuletThermistor - Condenser Water Inlet (Option)Thermistor - Condenser Water Outlet (Option)Condenser Water OutletCondenser Water InletEvaporator Water InletEvaporator Water Outlet

035-21786-100 Rev. 1 (0909)YCSE 080 Models1234567891011121314151617CompressorCheck ValvePressure Relief ValveStop Valve (Option)CondenserStop Valve - Refrigerant Charge PointStop ValveDrierSight GlassElectronic Expansion ValveEvaporatorStop Valve (Option)Low Pressure SensorHigh Pressure SwitchHigh Pressure SensorCompressor Safety Valve (Option)Compressor Dual Safety Valve (Option)1819202122232425262728293031323334Pressure SwitchSolenoid ValveCapillary TubeEconomiserStrainerThermistor - SuctionThermistor - DischargeThermistor - EvaporatorThermistor - Evaporator Water InletThermistor - Evaporator Water OuletThermistor - Evaporator Water OuletThermistor - Condenser Water Inlet (Option)Thermistor - Condenser Water Outlet (Option)Condenser Water OutletCondenser Water InletEvaporator Water InletEvaporator Water Outlet2-5

035-21786-100 Rev. 1 (0909)YCRE 040, 050, 060, 080, 100 Models12345678910111213142-6CompressorStop ValveCheck ValvePressure Relief Valve (Field Supplied)Remote Condenser (Field Supplied)Stop ValveDrierSolenoid ValveSight GlassExpansion ValveEvaporatorStop Valve (Option)Low Pressure SensorHigh Pressure Switch15161718192021222324252627High Pressure SensorCompressor Safety Valve (Option)Compressor Dual Safety Valve (Option)Thermistor - SuctionThermistor - DischargeThermistor - EvaporatorThermistor - Evaporator Water InletThermistor - Evaporator Water OuletThermistor - Evaporator Water OuletEvaporator Water InletEvaporator Water OutletYCREField Supplied

035-21786-100 Rev. 1 (0909)3TRANSPORTATION, HANDLING ANDSTORAGE3.1Delivery and StorageTo ensure consistent quality and maximum reliability, allunits are tested and inspected before leaving thefactory. Units are shipped completely assembled andcontaining refrigerant under pressure. Units areshipped without export crating unless this has beenspecified on the Sales Order.If the unit is to be put into storage, before installation, thefollowing precautions should be observed:3.2InspectionRemove any transit packing and inspect the unit toensure that all components have been delivered andthat no damage has occurred during transit. If anydamage is evident, it should be noted on the shipmentdocumentation and a claim entered according to theinstructions given.Major damage must be reported immediately to yourlocal Johnson Controls representative.3.3Moving the UnitEnsure that all openings, such as water connections,are securely capped.Before moving the unit, ensure that the installation site issuitable for installing the unit and is capable ofsupporting

WATER AND REMOTE AIR COOLED LIQUID CHILLERS WITH SCREW COMPRESSORS STYLE B (YCSE 134-320KW) (YCRE 127-307KW) TABLE OF CONTENTS 1 SUPPLIER INFORMATION 1.1 Introduction 1.1 1.2 Warranty 1.1 . YCSE/YCRE chillers are designed and built within an EN ISO 9001 accredited design and manufacturing organisation and, within the limits specified in this

Related Documents:

Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 80 F chilled water. MAXIMUM SERIES † Air & Water-Cooled † 1/4 to 40 Tons † 20 F to 80 F † Using Non-Ozone Depleting Refrigerants 10 ton air-cooled model 10 ton water-cooled model 2 ton water-cooled model 1 ton air-cooled model

Air Cooled Chiller Air Air 2 Air Air 6 AIR COOLED CHILLERS Air-cooled chillers are refrigeration machines that remove heat from cooling loads using chilled water and reject this heat into the atmosphere using refrigerant. THEY ALL HAVE fans, condenser coils, and compressors. Air-cooled chillers are used to provide cooling for human comfort and electronic equipment as well as industrial process .

ACH Air-Cooled, Horizontal Air Flow ACV Air-Cooled, Vertical Air Flow ACR Air-Cooled Remote Condenser WCC Water-Cooled Condenser Digit 6 — Chilled Water System P Recirculating System, Tank and Pump M Single Pass Chiller Unit (no tank and pump) Digit 7 — Cabinet Type H Horizontal Low Profile V Vertical Upright

AIR-COOLED Air-Cooled chillers utilize plant ambient air to extract heat from the refrigeration circuit. Fan or blowers move the plant air across generously sized finned condenser coils to permit full rated capacity at design conditions. WATER-COOLED Water-Cooled chillers utilize a secondary plant water source such as cooling tower or city .

EWY Air-cooled chiller, heat pump EWL Remote condenser chiller ERA Air cooled condensing unit EWW Water-cooled chiller, cooling only EWC Air-cooled chiller, cooling only with centrifugal fan EWT Air-cooled chiller, cooling only with heat recovery Refrigerant D R-134a P R-407c Q R-410a Capacity class in kW (Cooling) Always 3 .

A wide range of indoor-duty air-cooled, water-cooled, or remote air-cooled condensers as well as outdoor air-cooled chillers fit a variety of applications. . Air-Cooled Condenser Chillers Model NQA04 NQA05 NQA08 NQA10 NQA13 NQA15 NQA20 NQA25 NQA30 Cooling Capacity (tons)1 4 5 8 11 13 15 21 26 31 Set Point Range ( F) 20 to 80 20 to 80 20 to .

Air-cooled chillers are used to produce chilled water to air-side systems such as primary air fan coil systems, constant air volume systems and variable air volume systems in different zones of the building. An air-cooled screw chiller generally comprises a shell and tube evaporator, an air-cooled condenser with

cause water-cooled chillers can take advantage of lower condensing temperatures than air-cooled chillers. Air-cooled chillers have a full load kW/ton of approxi-mately 1.25 while water-cooled chillers have a full load kW/ton of between 0.55 and 0.8 kW/ton. The kW draw of the cooling tower fans and con-denser water pump should be