INSTALLATION, OPERATION, AND MAINTENANCE GUIDE - InspectAPedia

1y ago
9 Views
2 Downloads
1.60 MB
52 Pages
Last View : 15d ago
Last Download : 3m ago
Upload by : Troy Oden
Transcription

41- 5016- 07INSTALLATION, OPERATION,AND MAINTENANCE GUIDEALL phases of this installation must comply with NATIONAL, STATE AND LOCAL ACDX1D120A9601AUpflow / Horizontal* andDownflow / Horizontal*,Single Stage Direct Vent GasFired Condensing FurnacesIMPORTANT — This Document is customer property and is to remain with this unit.Please return to service information pack upon completion of work.Downflow / Horizontal*Upflow / Horizontal** Models can ONLY be rotatedto LEFT Side for horizontal installationSince the manufacturer has a policy of continuous product and product dataimprovement, it reserves the right to change design and specifications without notice. 2008 American Standard Heating & Air ConditioningAll Rights ReservedA341624P07

Installation InstructionsSAFETY SECTIONThe following safety practices and precautions must be followedduring the installation, servicing, and operation of this furnace.1. Use only with the type of gas approved for this furnace. Referto the furnace rating plate.2. Install this furnace only in a location and position as specified in “Location and Clearances” (page 3), of these instructions.3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” (pages 7-8), of these instructions.4. Combustion products must be discharged outdoors. Connectthis furnace to an approved vent system only, as specified inthe “Venting” section (pages 11-21), of these instructions.5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in “GasPiping” (page 27), of these instructions.6. Always install the furnace to operate within the furnace’sintended temperature-rise range with a duct system whichhas an external static pressure within the allowable range, asspecified on the unit rating plate. Airflow with temperaturerise for cfm versus static is shown in the Service Factsaccompanying this furnace.7. When a furnace is installed so that supply ducts carry aircirculated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by aduct(s) sealed to the furnace casing and terminating outsidethe space containing the furnace.8. A gas-fired furnace for installation in a residential garagemust be installed as specified in “Location and Clearances”section (page 3), of these instructions.9. The furnace may be used for temporary heating of buildingsor structures under construction only when the followingconditions have been met:a. The furnace venting system must be complete and installed per manufacturer’s instructions.b. The furnace is controlled only by a room thermostat (nofield jumpers).c. The furnace return air duct must be complete and sealedto the furnace and clean air filters are in place.d. The furnace input rate and temperature rise must beverified to be within nameplate marking.e. 100% of the furnace combustion air requirement mustcome from outside the structure.f. The furnace return air temperature range is between55 and 80 degrees Fahrenheit.g. Clean the furnace, duct work, and components uponsubstantial completion of the construction process, andverify furnace operating conditions including ignition,input rate, temperature rise and venting, according to themanufacturer’s instructions.10.This product must be gas piped by a Licensed Plumber or GasFitter in the Commonwealth of Massachusetts.Safety signal words are used to designate a degree or level ofseriousness associated with a particular hazard. The signal wordsfor safety markings are WARNING and CAUTION.a. WARNING indicates a potentially hazardous situation which,if not avoided, could result in death or serious injury.b. CAUTION indicates a potentially hazardous situation which,if not avoided, may result in minor or moderate injury. It is alsoused to alert against unsafe practices and hazards involvingonly property damage.! WARNING CARBON MONOXIDE POISONING HAZARDFailure to follow the steps outlined below for eachappliance connected to the venting system beingplaced into operation could result in carbon monoxidepoisoning or death.The following steps shall be followed for each applianceconnected to the venting system being placed intooperation, while all other appliances connected to theventing system are not in operation:1. Seal any unused openings in the venting system.2. Inspect the venting system for proper size andhorizontal pitch, as required in the National Fuel GasCode, ANSI Z223.1/NFPA 54 or the CAN/CGA B149Installation Codes and these instructions. Determinethat there is no blockage or restriction, leakage,corrosion and other deficiencies which could cause anunsafe condition.3. As far as practical, close all building doors andwindows and all doors between the space in which theappliance(s) connected to the venting system arelocated and other deficiencies which could cause anunsafe condition.4. Close fireplace dampers.5. Turn on clothes dryers and any appliance notconnected to the venting system. Turn on any exhaustfans, such as range hoods and bathroom exhausts, sothey are operating at maximum speed. Do not operatea summer exhaust fan.6. Follow the lighting instructions. Place the appliancebeing inspected into operation. Adjust the thermostatso appliance is operating continuously.7. If improper venting is observed during any of the abovetests, the venting system must be corrected inaccordance with the National Fuel Gas Code,ANSI Z221.1/NFPA 54 and/or CAN/CGA B149Installation Codes.8. After it has been determined that each applianceconnected to the venting system properly vents wheretested as outlined above, return doors, windows,exhaust fans, fireplace dampers and any other gas-firedburning appliance to their previous conditions of use.! WARNING FIRE OR EXPLOSION HAZARDFailure to follow the safety warnings exactly could result inserious injury, death or property damage.Improper servicing could result in dangerous operation,serious injury, death, or property damage.Page 2Pub. No. 41-5016-07

INSTALLATION INSTRUCTIONSInstallation InstructionsGENERALThe manufacturer assumes no responsibility for equipment installed in violation of any code or regulation.It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimatingheating requirements. When estimating heating requirements forinstallation at altitudes above 2000 ft., remember the gas inputmay need to be reduced (See High Altitude Installation).Material in this shipment has been inspected at the factoryand released to the transportation agency without knowndamage. Inspect exterior of carton for evidence of roughhandling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents isfound, report the damage immediately to the deliveringagency.Codes and local utility requirements governing the installation ofgas fired equipment, wiring, plumbing, and flue connections mustbe adhered to. In the absence of local codes, the installation mustconform with latest edition of the National Fuel Gas Code ANSIZ223.1 National Installation Code, CAN/CGA B149.1. Thelatest code may be obtained from the American Gas AssociationLaboratories, 400 N. Capitol St. NW, Washington D.C. 20001.1-800-699-9277 or www.aga.orgThese furnaces have been classified as CATEGORY IV furnacesin accordance with latest edition of ANSI Z21.47 CAN/CGA 2.3standards. Category IV furnaces operate with positive vent staticpressure and with a flue loss less than 17 percent. These conditionsrequire special venting systems, which must be gas tight and watertight.LOCATION AND CLEARANCESThe location of the furnace is normally selected by the architect, thebuilder, or the installer. However, before the furnace is moved intoplace, be sure to consider the following requirements:1. Is the location selected as near the chimney or vent and ascentralized for heat distribution as practical?2. Do all clearances between the furnace and enclosure equal orexceed the minimums stated in Clearance Table on the OutlineDrawings?3. Is there sufficient space for servicing the furnace and otherequipment? A minimum of 24 inches front accessibility to thefurnace must be provided. Any access door or panel must permitremoval of the largest component.4. Are there at least 3 inches of clearance between the furnacecombustion air openings in the front panel and any closed panelor door provided?5. Are the ventilation and combustion air openings large enoughand will they remain unobstructed? If outside air is used, are theopenings set above the highest snow accumulation level? (See theAir for Combustion and Ventilation section.)6. Allow sufficient height in supply plenum above the furnace toprovide for cooling coil installation, if the cooling coil is notinstalled at the time of this furnace installation.7. A furnace shall be installed so electrical components areprotected from water.8. If the furnace is installed in a residential garage, it mustbe installed so that the burners, and the ignition source arelocated not less than 18 inches above the floor and the furnacemust be located or protected to avoid physical damage fromvehicles.Pub. No. 41-5016-07CONTENTSINSTALLATION INSTRUCTIONS .General Installation Instructions .Location and Clearances .Outline Drawings .Horizontal Installation .Air for Combustion and Ventilation .Duct Connections .Return Air Filters .General Venting Instructions .Venting Materials .Condensate Piping .Field Wiring Diagrams .Gas Piping .Combustion and Input Check .High Altitude Derate .START-UP AND ADJUSTMENT .Preliminary Inspections .Lighting Instructions .Sequence of Operation .Control and Safety Switch Adjustments .Airflow Adjustment .Abnormal Conditions .OWNER’S INFORMATION .Warranties .SERVICE INSTRUCTIONS .Product Specifications .Airflow .Periodic Servicing Requirements .IFC Fault Codes .Unit Wiring Diagram 03132-3850-5139-4940-4142-43444546-49! CAUTION To prevent shortening its service life, the furnace should notbe used as a “Construction Heater” during the finishingphases of construction until the requirements listed in item 9,a-g of the safety section of this publication have been met.Condensate in the presence of chlorides and fluorides frompaint, varnish, stains, adhesives, cleaning compounds, andcement create a corrosive condition which may cause rapiddeterioration of the heat exchanger.! CAUTION Do NOT install the furnace in a corrosive or contaminatedatmosphere.! CAUTION Disconnect all electric power including remote disconnectsbefore servicing, insure that all motor capacitors have discharged stored voltage.IMPORTANT:The furnace must be installed level. The only allowable variationwould be slightly to the left and/or forward in upflow installations orslightly toward the front in horizontal installations. This is necessaryfor proper condensate drainage.Page 3

Page 4(ALL DIMENSIONS ARE IN INCHES)OUTLINE DRAWING FOR CUX1 FURNACESInstallation InstructionsPub. No. 41-5016-07

(ALL DIMENSIONS ARE IN INCHES)OUTLINE DRAWING FOR CDX1 FURNACESInstallation InstructionsPub. No. 41-5016-07Page 5

Installation InstructionsTABLE 1UPFLOW INSTALLATIONStandoffs and screws (See Figure 1) are included with the casedcoils for attachment to the furnace. There are clearance alignmentholes near the bottom of the coil wrapper. Drill screws are used toengage the furnace top flanges. The standoff is inserted into thecabinet alignment hole. The drill screws are inserted through thestandoffs then screwed into the furnace flange. The coil is alwaysplaced downstream of the furnace airflow. The above instructionsonly apply if the coil is on top of an upflow furnace.DRILL SCREWS (4)STANDOFFS (4)CASECO DILFOR VERTICALINSTALLATIONS:FLOOR OPENING PLENUM OPENINGCABINETRETURNWIDTH DUCT WIDTH"A""B""C""D"14-1/2"13-1/4"13-5/8" 20-1/8"12-5/8"19-3/8"17-1/2"16-1/4"16-5/8" 20-1/8"15-5/8"19-3/8"21"19-3/4"20-1/8" 20-1/8"19-1/8"19-3/8"24-1/2"23-1/4"23-5/8" 20-1/8"22-5/8"19-3/8"HORIZONTAL INSTALLATIONThe coil and furnace must be fully supported when used in thehorizontal position. It is always recommended that an auxiliarydrain pan be installed under a horizontally installed evaporatorcoil or 90% gas furnace. Connect the auxiliary drain line to aseparate drain line (no trap is needed in this line).Three brackets (with screws) are included with downflow furnacesfor installation to stabilize and secure the furnace and TXC casedcoil in the horizontal position (See Figure 4).MPORTANT:The 2/4TXC cased coil must be placed downstream of thefurnace. In horizontal installations, the apex of the coil maypoint either toward or away from the furnace. See the2/4TXC coil Installer's Guide for more details.SCREWSUPFU FLORN WACE(BOTH SIDES)STANDOFFS(BOTH SIDES)FIGURE 1DOWNFLOW INSTALLATIONThe cased coil is secured to the furnace and both the furnace andthe cased coil must be properly supported. The brackets mountusing the rear screws on the coil case and use the screws providedto secure the bracket to the furnace. The remaining bracket isplaced as close to center as possible (horizontally) between the coilcase front and the furnace bottom channel (for downflow/horizontal furnace). Use four of the screws provided to secure the bracket.! WARNING Do not install the furnace directly on carpeting, tile or othercombustible material other than wood flooring. For verticaldownflow application, subbase (BAYBASE205) must be usedbetween the furnace and combustible flooring. When thedownflow furnace is installed vertically with a cased coil, asubbase is not required.CASED COIL CONNECTIONBRACKET FOR DOWNFLOWFIGURE 4The downflow furnace may be installed in an attic or crawl spacein the horizontal position by placing the furnace on the left side (asviewed from the front in the vertical position). The horizontalfurnace installation in an attic should be on a service platformlarge enough to allow for proper clearances on all sides and serviceaccess to the front of the furnace (See Outline Drawings). Linecontact is only permissible between lines formed by intersectionsof the top and two sides of the furnace casing and building joists,studs, or framing.FIGURE 2Required floor opening: (DOWNFLOW)See Figure 2 and Table 23456789A 123456789B 01234567890121234567890123456789FIGURE 3Page 6The furnace may be placed horizontally in a crawl space on a pador other noncombustible material which will raise the unit forsufficient protection from moisture. The furnace must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated approximately4-6 inches to allow clearance for the condensate drain toexit the cabinet in the horizontal position.The horizontal furnace may also be suspended from the joistsusing 3/8" all-thread rods with pieces of angle iron underneath thefurnace to form a hanging rack at both ends and the midpoint. Therods need to be of sufficient length to allow for proper clearancesfrom combustible materials. The angle iron needs to be at least 32"in length to allow for access to service panels.The upflow furnace, converted to horizontal, aligns and attachesthe TXC coil to the same flanges used in vertical. The coil needs tohave additional support.Pub. No. 41-5016-07

Installation InstructionsConfined spaces are installations with less than 50 cu. ft. of spaceper 1000 BTU/hr. input from all equipment installed. Air forcombustion and ventilation requirements can be supplied frominside the building as in Figure 8 or from the outdoors, as inFigure 9.UPFLOW/HORIZONTAL1. All air from inside the building as in Figure 8: The confinedspace shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume sothat the combined volume of all spaces meets the criteria for anunconfined space. The total input of all gas utilization equipmentinstalled in the combined space shall be considered in makingthis determination. Refer to Table 3, for minimum open areasrequired.FIGURE 5AIR FOR COMBUSTION AND VENTILATION2. All air from outdoors as in Figure 9: The confined space shallbe provided with two permanent openings, one commencingwithin 12 inches of the top and one commencing within 12 inchesof the bottom of the enclosure. The openings shall communicatedirectly, or by ducts, with the outdoors or spaces (crawl or attic)that freely communicate with the outdoors. Refer to Table 3, forminimum open areas required.Adequate flow of combustion and ventilating air must not beobstructed from reaching the furnace. Air openings provided in thefurnace casing must be kept free of obstructions which restrict theflow of air. Airflow restrictions affect the efficiency and safeoperation of the furnace. Keep this in mind should you choose toremodel or change the area which contains your furnace. Furnacesmust have a free flow of air for proper performance.3. The following types of installations will require use ofOUTDOOR AIR for combustion, due to chemical exposures:* Commercial buildings* Buildings with indoor pool* Furnaces installed in commercial laundry rooms* Furnaces installed in hobby or craft rooms* Furnaces installed near chemical storage areas.Provisions for combustion and ventilation air shall be made inaccordance with “latest edition” of Section 5.3, Air for Combustionand Ventilation, of the National Fuel Gas Code, ANSI Z223.1, orSections 7.2, 7.3 or 7.4 of CAN/CGA B149 Installation Codes, andapplicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces mustbe considered to avoid unsatisfactory furnace operation.Exposure to the following substances in the combustion airsupply will also require OUTDOOR AIR for combustion:* Permanent wave solutions* Chlorinated waxes and cleaners* Chlorine based swimming pool chemicals* Water softening chemicals* Deicing salts or chemicals* Carbon Tetrachloride* Halogen type refrigerants* Cleaning solvents (such as perchloroethylene)* Printing inks, paint removers, varnish, etc.* Hydrochloric acid* Cements and glues* Antistatic fabric softeners for clothes dryers* Masonry acid washing materialsFurnace locations may be in “confined space” or “unconfinedspace”. Unconfined space is defined in Table 2 and Figure 6. Thesespaces may have adequate air by infiltration to provide air forcombustion, ventilation, and dilution of flue gases. Buildings withtight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air provided as described for confined space.TABLE 250 CU. FT. OR MOREPER 1000 BTU/HR. INPUTALL EQUIP. INSTALLEDUNCONFINEDFIGURE 6CONFINEDLESS THAN 50 CU. FT.PER 1000 BTU/HR. INPUTALL EQUIP INSTALLEDFIGURE 7Pub. No. 41-5016-07MINIMUM AREA IN SQUARE FEETFOR UNCONFINED SPACE INSTALLATIONSFURNACEWITH 8 FT. CEILINGMAXIMUM BTUH MINIMUM AREA IN SQUAREINPUT RATING FEET OF UNCONFINED 75TABLE 3MINIMUM FREE AREA IN SQUARE INCHESEACH OPENING (FURNACE 20,00010010010010012010152025302030405060Air From OutsidePage 7

Installation InstructionsCentral furnaces, when used in connection with cooling units, shallbe installed in parallel or on the upstream side of the cooling unitsto avoid condensation in the heating element, unless the furnacehas been specifically approved for downstream installation. Witha parallel flow arrangement, the dampers or other means used tocontrol flow of air shall be adequate to prevent chilled air fromentering the furnace, and if manually operated, must be equippedwith means to prevent operation of either unit unless the damperis in full heat or cool position.FIGURE 8On any job, flexible connections of nonflammable material may beused for return air and discharge connections to prevent transmission of vibration. Though these units have been specificallydesigned for quiet, vibration free operation, air ducts can act assounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level.When the furnace is located in a utility room adjacent to the livingarea, the system should be carefully designed with returns whichminimize noise transmission through the return air grille.Although these winter air conditioners are designed with largeblowers operating at moderate speeds, any blower moving a highvolume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is oftenadvisable to route the return air ducts under the floor or throughthe attic. Such design permits the installation of air return remotefrom the living area (i.e. central hall).When the furnace is installed so that the supply ducts carry aircirculated by the furnace to areas outside the space containingthe furnace, the return air shall also be handled by a duct(s)sealed to the furnace and terminating outside the space containing the furnace.Minimum return air “entering temperature” for the furnace is 55 F.Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside theutility room, basement, attic, or crawl space.Do Not install return air through the back of the furnacecabinet.Do Not install return air through the side of the furnace cabineton horizontal applications.RETURN AIR DUCT CONNECTIONAll return air duct systems should provide for installation ofreturn air filters.1. Set the furnace in place.2. For side return installations on upflow models, remove theinsulation around the opening in the blower compartment.3. The side panels on upflow furnaces include locating notcheswhich may be used as guides for cutting an opening for return air.Refer to Figure 10 and the outline drawings on pages 4 and 5 forduct connection dimensions for various furnaces.FIGURE 9DUCT CONNECTIONSAir duct systems should be installed in accordance with standardsfor air conditioning systems, National Fire Protection AssociationPamphlet No. 90. They should be sized in accordance with ACCAManual D or whichever is applicable. Check on controls to makecertain they are correct for the electrical supply.4. If a 3/4" flange is to be used for attaching the air inlet duct,add to cut where indicated by solid lines in Figure 10. Cut cornersdiagonally and bend outward to form flange.5. If flanges are not required, and a filter frame is installed, cutalong knockout guidelines.6. Upflow furnaces: filter retainer brackets are factory supplied for bottom return. Use the filter retainer brackets on eitherside or on bottom if filter is to be used within the furnace cabinet.NOTE:On upflow 5 ton airflow models, if the airflow requirementexceeds 1800 CFM, these models will require filters on bothsides; OR 1 side and the bottom; OR just the bottom.Page 8Pub. No. 41-5016-07

Installation Instructions*LOCATINGNOTCHESPROVIDEDFOR SIDERETURNCUTOUTCUT OUTFORSIDEFILTERAirflow***FRONTof Furnace* SEE OUTLINE DRAWINGFIGURE 10Typical Bottom Return FilterDownflow Furnaces: Brackets are factory supplied to mount filtersin the return air duct work.7. Connect duct work to furnace. See Outline Drawing for supplyand return duct size and location. Flexible duct connectors arerecommended to connect both supply and return air ducts to thefurnace. If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable.Airflow8. When replacing a furnace, old duct work should be cleaned out.Thin cloths should be placed over the registers and the furnace fanshould be run for 10 minutes. Don’t forget to remove the clothsbefore you start the furnace.FIGURE 11RETURN AIR FILTERSFilters are not factory supplied for these furnaces. These furnacesrequire high velocity type air filters which may be located withinthe furnace blower compartment for UPFLOW furnaces in eithera BOTTOM or SIDE (left side or right side) return air inlet. SeeFigure 11. Some filters may need to be trimmed for side or bottomfilter use. Downflow furnaces must be located outside the furnacecabinet. Typical installations are shown in Figure 12. Table 5provides information for installation of the filter retaining bracketsshipped with downflow furnaces.NOTE:On upflow 5 ton airflow models, if the airflow requirementexceeds 1800 CFM, these models will require filters on bothsides; OR 1 side and the bottom; OR just the bottom.CABINETWIDTHFILTERQTY & SIZE17-1/2"1 - 17" X 25" X 1"21"1 - 20" X 25" X 1"CUX1D100A9601A#CUX1D120A9601A#24-1/2"1 - 24" X 25" X "2 - 14" X 20" X 1"CDX1C100A9481ACDX1D120A9601A21"24-1/2"2 - 16" X 20" X 1"2 - 16" X 20" X 1"# -NOTE - On the upflow 5 ton airflow models, if the airflowrequirement exceeds 1800 CFM, these models will require filters onboth sides; OR 1 side and the bottom; OR just the bottom.TYPICAL UPFLOW FURNACE RETURN AIR FILTERINSTALLATIONS FIGURE 11Pub. No. 41-5016-07FILTER RETAINER BRACKETS FORSIDE AIR RETURN ON UPFLOW FURNACESIf side air return is desired, it is necessary to move the 2 filterretainer brackets from the bottom of the furnace and reinstallthem on the side. The following instructions should be used:a. Remove the front doors.b. Remove the filter.c. Carefully place the unit on its back.d. Using a 5/16" nut driver, remove the 4 screws holding thefilter retainer brackets.e. Reinstall the filter retainer brackets on the desired side.TABLE A9421ACUX1C100A9481ATypical Side Return Filter(See Figure 11 “Typical Side Return Filter”).RETURN AIR FILTERS FOR UPFLOW FURNACE INHORIZONTAL CONFIGURATIONWhen the Upflow Furnace is installed in the horizontal configuration, the return air filters must be installed exterior to the cabinet.Remote filter grilles may be used for homeowner convenience or thefilters may be installed in the duct work upstream of the furnace.See Figure 11A.AirflowFIGURE 11APage 9

Installation Instructions! WARNING CARBON MONOXIDE POISONING HAZARDFailure to follow the steps outlined below for eachappliance connected to the venting system beingplaced into operation could result in carbon monoxidepoisoning or death.The following steps shall be followed for each applianceconnected to the venting system being placed intooperation, while all other appliances connected to theventing system are not in operation:1. Seal any unused openings in the venting system.AirflowDOWNFLOW2. Inspect the venting system for proper size andhorizontal pitch, as required in the National Fuel GasCode, ANSI Z223.1/NFPA 54 or the CAN/CGA B149Installation Codes and these instructions. Determinethat there is no blockage or restriction, leakage,corrosion and other deficiencies which could cause anunsafe condition.3. As far as practical, close all building doors andwindows and all doors between the space in which theappliance(s) connected to the venting system arelocated and other deficiencies which could cause anunsafe condition.4. Close fireplace dampers.5. Turn on clothes dryers and any appliance notconnected to the venting system. Turn on any exhaustfans, such as range hoods and bathroom exhausts, sothey are operating at maximum speed. Do not operatea summer exhaust fan.lowAirfDOWNFLOW / HORIZONTALFIGURE 12RETURN AIR FILTER FOR DOWNFLOW/HORIZONTALAfter the return air plenum has been connected to the downflowfurnace in either downflow or horizontal position the return airfilters may be installed in the plenum using the brackets (andscrews) supplied with the furnace. See Table 5. It is recommendedthat BAYFLTR206 be installed in the return air plenum. SeeFigure 12 and Table 5 for typical installation. The

7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain-ing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. 8. A gas-fired furnace for installation in a residential garage

Related Documents:

Installation, Operation, and Service Instructions Installation, Operation and Maintenance Instructions for your Cryo-Torr vacuum pump provides easily accessible information. All personnel with installation, operation, and servicing responsibilities should become familiar with the contents of these instructions to ensure safe, reliable

5.3. STAFInst Uninstall 6. Platform Installation Notes 6.1. Linux installation 6.2. AIX installation 6.3. HP-UX IA64 64-bit installation 6.4. IBM i 32-bit (previously known as i5/OS or OS/400) installation 6.5. z/OS installation 6.6. FreeBSD installation 6.7. Mac OS X installation 6.8. Solaris installation 7. Environment Variable Settings 7.1.

The Bobcat Filter Reference Guide is subject to change. Consult your Operation & Maintenance Manual for maintenance intervals and additional maintenance items. . Consult your Operation & Maintenance Manual for maintenance intervals and additional maintenance items. Skid-Steer Loader: Air Filter (Inner) . 843B: 6598362 6598492: 6659329 .

maintenance personnel. This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By care-fully reviewing the information within this manual and follow-ing the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be .

Forward this manual to the person responsible for Installation, Operation and Maintenance of the product described herein. Without access to this information, faulty Installation, Operation or Maintenance may result in personal injury or equipment damage. Installation, Operation and Maintenance of the Airflex Model CBC Clutch\Brake Combination

The following stormwater facility maintenance table (See ODOT Maintenance Guide) should be used to maintain the facility outlined in this Operation and Maintenance Manual or follow the Maintenance requirements outlined in Appendix C when proprietary structure is selected below: Table 1 (general maintenance) Table 2 (stormwater ponds)

8 Zenith ZTX Series ATS,OPERATION, MAINTENANCE, AND INSTALLATION GUIDE 1 3. General operation 27 3.1 Position indication 27 3.2 Operating and locking 28 3.3 Manual handle operation 29 3.4 Return to automatic mode, operating by HMI 30 3.5 LED functionality in HMI 31 3.6 Using Level 2 (DIP) control interface HMI 33 3.6.1 Keypad 33 4.

TRC500 ERV 1.800.961.7370 INSTALLATION, OPERATION AND MAINTENANCE MANUAL WWW.SOLERPALAU-USA.COM 5 PLANNING YOUR INSTALLATION INSTALLATION PLACEMENT OF THE TRC500 The TRC500 is designed for installation indoors. Select a location that is central to the inside duct runs,