Hilti Cfs-pl Firestop Plug Kit

1y ago
18 Views
2 Downloads
1.49 MB
12 Pages
Last View : 12d ago
Last Download : 3m ago
Upload by : Nixon Dill
Transcription

HILTI CFS-PL FIRESTOP PLUG KIT HILTI FIRESTOP PLUG CFS-PL HILTI FIRESTOP FILLER CFS-FIL HILTI FIRESTOP PUTTY BANDAGE CFS-P BA European Technical Approval ETA N 13/0125

FIRESTOP PLUG CFS-PL Technical data CFS-PL Cable Yes Max. cable bundle diameter 100 mm Cable tray No Plastic conduits Yes Steel conduits Yes Temporary closing Yes Mixed penetration seals No Fire resistance in concrete EI60/90/120 Fire resistance in masonry EI60/90/120 Fire resistance in drywalls EI60/90/120 APPLICATIONS ADVANTAGES Temporary or permanent sealing around cables, cable bundles and conduits in wall and floor openings Cables and cable bundles Conduits and conduit bundles Possible with a PVC sleeve for a cast-in concrete process Optimal for rooms with dust and fiber-free requirements and areas that often change services, such as server rooms, laboratories and hospitals For round holes between 107 and 202 mm in diameter Easy to install, no electric tools required Simple maintenance and re-penetration of cables Economical installation as the plug is pre-cured and ready-touse Painting of cables with firestop coating is not required Ideal for the temporary closing of empty core holes Easiest and fastest firestop system Order designation Package content Discount group Minimum order quantity Item number Firestop plug CFS-PL 107 max. opening size Ø 107 mm 1 pc 02059530 Firestop plug CFS-PL 132 max. opening size Ø 132 mm 4 pc 02059531 Firestop plug CFS-PL 158 max. opening size Ø 158 mm 2 pc 02059532 Firestop plug CFS-PL 202 max. opening size Ø 202 mm 2 pc 02059533 FIRESTOP FILLER MASTIC CFS-FIL APPLICATIONS ADVANTAGES For use with Hilti firestop plug CFS-PL Can be used with Hilti dispenser CFS-DISP Order designation Package content Firestop filler mastic CFS-FIL 310 ml Discount group Minimum order quantity 1 pc Item number 02052899 FIRESTOP PUTTY BANDAGE CFS-B PA APPLICATIONS ADVANTAGES For use with Hilti firestop plug CFS-PL For specific cable configurations, to achieve EI 120 Easy to cut Self-adhesive Order designation Package content Firestop putty bandage CFS-P BA 5m 02 Discount group Minimum order quantity 1 pc Item number 02062876

INSTALLATION INSTRUCTIONS Clean the opening. )LUHVWRS 3OXJ &)6 3/ Cables can be placed in any part of the opening. If cables are in place, cut the firestop plug CFS-PL as required. )LUH 5DWHG VVHPEO\ VVHPEODJH RPROXJXp 3URGXFW 3URGXW /RFDWLRQ (QGURLW 6\VWHP 6\VWqPH 7HO ,QVWDOOHG E\ 5HSHQHWUDWHG E\ ,QVWDOODWLRQ 'DWH 'DWH G·LQVWDOODWLRQ 'DWH Fill gaps between cables and plug with firestop filler mastic CFS-FIL to a depth of at least 20 mm on both sides of the penetration. Fire Rated Assembly / Assemblage Homolugué Product: Produt: System #: Système #: Installed by: Repenetrated by: Location: Endroit: Tel: Installation Date: Date d’installation: Date: Fasten an identification plate in place, if required. USE TWO PLUGS EACH FOR WALL AND FLOOR APPLICATION Note: From the firestop plugs that are offered, some smaller sizes of these plugs can be created by cutting out pieces of a larger plug. 03

USE OF THE CFS-P BA BANDAGE 2076306 10.02.2020 For some applications, firestop putty bandage CFS-P Firestop PuttyBA must be installed to upgrade the firestop classification to EI 120. Bandage CFS-P BA 2076306-02.2020 1 2 2076306 10.02.2020 Cut lengths of firestop putty bandage CFS-P BA, as required, to cover all cables. Firestop Putty Bandage CFS-P BA CFS-BL 3a 2 2076306-02.2020 1 2 3b 3a m 0m 10 CFS-PL CFS-BL 100 mm 3b m 0m 10 2076306-02.2020 Remove the paper from the CFS-P BA firestop putty bandage. m 2076306-02.2020 2 CFS-PL 0m 10 Firestop Putty Bandage CFS-P BA 100 mm 3b CFS-PL Cover all cables with a single layer of the firestop putty bandage CFS-P BA. The firestop putty bandage CFS-P BA must extend to at least 100 mm from the surface of the opening. There is 100 a flexible mesh on one side of the firestop putty bandage CFS-P BA, which must mm face the outside of the penetration. When installed correctly, the flexible mesh will be visible from all sides of the penetration. Cover the cables with a second layer of firestop putty bandage CFS-P BA. The firestop putty bandage CFS-P BA must extend to at least 100 mm from the surface of the opening. CFS-PL m 0m 10 3b Firestop Putty Bandage CFS-P BA There is a flexible mesh on one side of the firestop putty bandage CFS-P BA, which must face the outside of the penetration. When installed correctly, the flexible mesh will be visible from all sides of the penetration. 100 mm DISTANCE REQUIREMENTS w s1 A s2 Distances valid for installations of services in wall and floor penetrations. s2 s20 s2 s22 s1 Figure 1: Distance requirements 04 s21 Minimum distances in mm (see Figure 1: Distance requirements) s1 0 (distance between cables and seal edge) s2 0 (distance between cables) s20, 21, 22 0 (conduits Ø 16 mm) s20 0 (conduits Ø 16 mm; distance between conduits to each other) s21, 22 20 (conduits Ø 16 mm; distance between conduits and other services or seal edges)

APERTURE FRAMING/BEADING DETAILS FOR WALLS AND FLOORS The minimum penetration seal depth is 150 mm (figure 2a, t A) independent of the thickness of the wall or floor. In case of walls or floors with a thickness of less than 150 mm, a beading must be used (figure 2a, E1). Aperture framing: Fire test results demonstrated that the aperture framing is not required. Beading: Square plates made of gypsum or calcium silicate board with a size of 2 x WA (at least 100 mm wide) plus W (figure 2c, diameter of plug) are installed around the opening in the necessary number of layers. Two frames of the same height on both sides of the wall (figure 2a) have to be installed. a b W( ( c ( Z ( W( W ( Z ( Figure 2: Aperture framing / beading and position of the seal in walls / floors ABBREVIATIONS USED IN FIGURE 2 Abbreviation Description Abbreviation Description A Hilti firestop product tE Thickness of the building element E Building element (rigid or flexible wall construction, floor) w Width of the seal E1 Beading wA Width of the frame tA Thickness of the seal 05

WALL PENETRATIONS The walls must be classified in accordance with EN 13501-2 for the required fire resistance period or fulfill the requirements of the relevant Eurocode. This ETA does not cover use of the product as a penetration seal in sandwich panel structures. THE INTENDED USE OF HILTI FIRESTOP PLUG KIT IS TO PERMANENTLY OR TEMPORARILY REINSTATE THE FIRE RESISTANCE OF: Flexible wall, figure 3, top section (E) The wall must have a minimum thickness of 100 mm (tE) and comprise of timber or steel studs lined on both faces with minimum 2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and any stud and the cavity between stud and seal must be filled. A minimum of 100 mm Class A1 or A 2 insulation (in accordance with EN 13501-1) is necessary in the cavity between the stud and seal. Rigid wall, figure 3, bottom section (E) The wall must have a minimum thickness of 100 mm (tE) and comprise of concrete, aerated concrete or masonry with a minimum density of 600 kg/m3. Blank wall seal, no services, figure 3: Maximum opening size 202 mm, and 60 % of the seal area can be penetrated. Seal thickness 150 mm (t A). W( ( W( ( ( ( W & & & ( ( Figure 3: Blank wall seal, no services Figure 4: Details of filler (A1) and 2 x putty (A 2) ABBREVIATIONS USED IN FIGURES 3, AND 4 Abbreviation Description Abbreviation Description A, A1, A 2,. Firestop products A1 Hilti CFS-FIL firestop filler, to a depth of 20 mm E, E1, E 2, Building elements (wall, floor) A2 2 x Hilti CFS-P BA putty bandage tA Thickness of penetration seal tE Thickness of the building element C, C1, C2,. Penetrating services Note: Gaps between services and Hilti firestop plugs CFS-PL (A) are filled with Hilti firestop filler CFS-FIL (A1), depth 20 mm. 06

CABLE PENETRATIONS, FLEXIBLE / RIGID WALL, AT LEAST 100 MM THICK Description of services Classification E Integrity, I Insulation Blank opening, from 52 mm to 202 mm in diameter, without filler and without putty EI 120 Standard cable services Filler All sheathed cables up to 21 mm diameter Tied cable bundles up to 100 mm diameter, max. diameter of single cables 21 mm Filler 2 x putty EI 120 All sheathed cables from 21 mm diameter and up to 50 mm diameter El 90 All sheathed cables from 50 mm diameter and up to 80 mm diameter El 90 / E 120 Non-sheathed electrical cables up to 24 mm diameter EI 60 / E 120 Plastic conduits and tubes up to 16 mm with or without cables EI 120-U/U Steel conduits and tubes up to 16 mm with or without cables EI 120-C/U Small plastic conduits and tubes: PO: polyolefin (PE, PP, PPE, PPO, .) PVC: polyvinyl chloride Filler El 120 Flexible PO: 16 mm to 40 mm with or without cable Flexible PVC: 16 mm to 32 mm with or without cable Rigid PO: 16 mm to 40 mm, with or without cable Rigid PVC: 16 mm to 40 mm, with or without cable EI 120-U/U Conduit bundles up to 100 mm diameter, max. diameter of single conduits 20 mm Note: PVC, max. 5 mm wall thickness, 150 mm length, flush to wall surface 07

FLOOR PENETRATIONS The floors must be classified in accordance with EN 13501-2 for the required fire resistance period or fulfill the requirements of the relevant Eurocode. THE INTENDED USE OF HILTI FIRESTOP PLUG KIT IS TO PERMANENTLY OR TEMPORARILY REINSTATE THE FIRE RESISTANCE OF: Blank floor seal, no services, figure 5: Maximum opening size 202 mm, and 60 % of the seal area can be penetrated. Seal thickness 150 mm. Rigid floor, figure 6, (E) The floor must have a minimum thickness of 150 mm (tE) and comprise of aerated concrete or concrete with a minimum density of 600 kg/m3. Maximum distance of the first service support: 250 mm. Z ( W( & & & Figure 5: Blank floor seal, no services Figure 6: Details of filler (A1) and 2 x putty (A 2) ABBREVIATIONS USED IN FIGURES 5 AND 6 Abbreviation Description Abbreviation Description A, A1, A 2,. Firestop products tA Thickness of the building element C, C1, C2, Penetrating services A1 Hilti firestop filler CFS-FIL, at a depth of 20mm W Height of penetration seal A2 2 x Hilti putty bandage CFS-P BA E, E1, E 2,. Building elements (wall, floor) 08

CABLE PENETRATIONS, RIGID FLOOR, AT LEAST 150 MM THICK Description of services Classification E Integrity, I Insulation Blank opening, from 52 mm to 202 mm in diameter, without filler and without putty EI 120 Standard cable services Filler All sheathed cables up to 21 mm diameter Tied cable bundles up to 100 mm diameter, max. diameter of single cables 21 mm Filler 2 x putty Bandage EI 120 All sheathed cables from 21 mm diameter and up to 50 mm diameter El 120 All sheathed cables from 50 mm diameter and up to 80 mm diameter El 90 / E 120 Non-sheathed electrical cables up to 24 mm diameter EI 30 / E 120 Plastic conduits and tubes up to 16 mm with or without cables EI 120-U/U Steel conduits and tubes up to 16 mm with or without cables EI 120-C/U Small plastic conduits and tubes: PO: polyolefin (PE, PP, PPE, PPO, .) PVC: polyvinyl chloride Filler EL 30 / E 120 Flexible PO: 16 mm to 40 mm with or without cable Flexible PVC: 16 mm to 32 mm with or without cable Rigid PO: 16 mm to 40 mm, with or without cable Rigid PVC: 16 mm to 40 mm, with or without cable EI 120-U/U Conduit bundles up to 100 mm diameter, max. diameter of single conduits 20 mm Note: PVC, max. 2 mm wall thickness, 150 mm length, flush to floor surface 09

CHARACTERISTICS OF HILTI CFS-PL FIRESTOP PLUG Additional Attributes Bauchemie Piktos neu.ai 05.11.2007 Hilti firestop products are comprehensively tested and individually tailored to the technical requirements of a building’s mechanical and electrical installations. In addition to their superior behavior in passive fire protection, Hilti firestop products also meet the requirements in building technology that continue to gain significance and also help the designer and installer to meet these additional requirements. The assessment of fitness for use has been made in accordance with EAD 350454-00-1104. 45% 30 years Wasserbeständigkeit 30 Jahre Elektische Characteristics Assessment of Characteristics Norm, standard, test Health and the environment Dangerous substances Clean-Tec Below any respective occupational exposure limits as far as such limits exist (compared with the list of dangerous substances of the European Commission Hilti Clean-Tec criteria Material safety data sheet Air-seal/Luftdichtheit Protection against noise (air borne sound insulation) Double plug CFS-PL Rw (C; Ctr) 54 (-1; –7) dB EN ISO 140-3 Thermal properties Thermal conductivity λ 0.089 W/mK and thermal resistance R 0.563 m2K/W EN 12667 Electrical properties Electrical volume resistivity: 2.17E 9 ( 0.5) Ω cm Electrical surface resistivity: 49.6E 9 ( 10 ) Ω DIN IEC 60093 (VDE 0303 Part 30):1993-12 Durability and servicability Category Y1 (Products intended for use at temperatures between -5 C and 70 C with exposure to UV but without exposure to rain.) EAD 350454-00-1104 Reaction to Fire Class E EN 13501-1 Rauch- und Gasdichtigkeit Schallschutz Dampfdichtigkeit Wärmedämmend British Standard BS 476 FM FM APPROVED Factory Mutual C US SERVICE With more than 20 years of experience worldwide, Hilti is one of the leading suppliers of firestop systems. We actively help you manage your firestop projects better by providing: Quick engineering judgments Extensive technical literature On-site training and demonstration Sophisticated jobsite logistics Assurance of conformity with specific application requirements International network of Hilti firestop specialists Our network of experienced sales representatives, field engineers, firestop specialists and customer service representatives is just a phone call away (use the local toll-free Hilti number). 10

11

Hilti Corporation 9494 Schaan, Liechtenstein P 423-234 2965 Hilti registered trademark of Hilti Corp., Schaan W4302 0320 0-en 2 Printed in Liechtenstein 2020 www.facebook.com / hiltigroup www.hilti.group Right of technical and programme changes reserved S. E. & O.

Firestop plug CFS-PL 107 max. opening size Ø 107 mm 1 pc 02059530 Firestop plug CFS-PL 132 max. opening size Ø 132 mm 4 pc 02059531 Firestop plug CFS-PL 158 max. opening size Ø 158 mm 2 pc 02059532 Firestop plug CFS-PL 202 max. opening size Ø 202 mm 2 pc 02059533 Order designation Package content Discount group Minimum order quantity Item .

Related Documents:

HILTI FIRESTOP SOLUTIONS Hilti CP 606 Flexible Firestop Sealant Hilti CP 601S Elastomeric Silicone Sealant Hilti CP 636 Firestop Mortar Hilti CFS-SP WB Fire Stop Joint Spray O u r P r o d u c t s. HILTI MECHANICAL ANCHORS Hilti HST3 Mechanical Expansion Anchor Hilti Hus3-c 8/10 New Ultimate-Performance Screw Anchor

local Hilti contact or www.hilti.com Package Volume Color Order designation Sales Quantity Item Number Cartridge 310 ml white Firestop acrylic sealant CFS-S ACR 1 pc 435859 Cartridge 310 ml white Firestop acrylic sealant CFS-S ACR 1 pc 435860 Cartridge 310 ml grey Firestop acrylic sealant CFS-S ACR 1 pc 435862

Oct 20, 2017 · ATTENDEES* FIRST LAST COMPANY CITY, STATE EMAIL Francesca Del Rosso Hilti, Inc. Plano, TX delrfra@hilti.com Dave Gifford Hilti, Inc. Southbury, CT da Bud Griffin Hilti, Inc. Herndon, VA vincent.griffin@hilti.com Kris Kuehn Hilti, Inc. Plano, TX kris.kuehn@hilti.com Shana Stein Hilti, Inc. Sausalito, CA shana.stein@hilti.com John Wuebbeling Hilti, Inc. St louis, MO John.wuebbeling@hilti.com

Hilti Firestop Joint Spray CFS-SP WB has been tested in accordance with EN 1364-4 and has been classified in accordance with EN 13501-2. Hilti Firestop Joint Spray CFS-SP WB is a membrane-forming coating used to form a perimeter seal between rigid floor slabs and

Hilti Firestop Saving lives through innovation and education Product Information Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com en español 1-800-879-5000 Hilti Firestop Systems Guide Firestop Block

Trade name CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Product code BU Fire Protection 1.2. Relevant identified uses of the substance or mixture and uses advised against Use of the substance/mixture Firestop putty pad 1.3. Details of the supplier of the safety data sheet Hilti, Inc. Legacy Tower, Suite 1000 7250 Dallas Parkway

Solution Hilti / Hilti solution N ATE EI 240 EI 180 EI 120 EI 90 EI 60 Sans traversant Béton Dalle 150 Sans traversant CFS-CT 11/0429 Béton Dalle 150 CFS-IS 10/0406 Béton Dalle 150 CFS-PL 13/0125 Béton Dalle 150 CFS-BL 13/0099 Traversants électriques Béton Dalle 150 CFS-PL 13/0125 Béton Dalle 150 CFS-CT 11/0429

Princess Anne -Minchinhampton " S.LBC.414/ . Mr. Sutherland Haresfield SLBC L4 Granleon Ltd Wallbridge, Stroud U .Lek5/ Powell Mr D Cainscross" SaJBQ.238/B Littlestok E ineigNailsworth .4B 68 . LageScam,mell Cons truc tionjEbley'I 5.L .66 The Vicar and ChurchflWardens Strod S . LBC65 Mr _D.Weeks Newport " SLB.ko.M Hn MriAdrdpe c0. Mr. Ingham SouthWoodchester 5.7.02 S.LBC.177/A Zermi S.A .