Motor Protection Circuit Breaker And Motor Circuit Protector - DDS

8m ago
6 Views
1 Downloads
2.60 MB
44 Pages
Last View : 11d ago
Last Download : 3m ago
Upload by : Josiah Pursley
Transcription

Technical Data Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Bulletin Number 140M, 140-CMN Topic Bulletin 140M Motor Protection Circuit Breakers Page 3 Overview 3 Catalog Number Explanation 5 Application Diagrams 7 Bulletin 140M Motor Circuit Protectors 11 Overview 11 Catalog Number Explanation 13 Application Diagrams 15 Specifications 17 Approximate Dimensions 35 Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Motor Protection Circuit Breaker and Motor Circuit Protector Specifications 2 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Bulletin 140M Motor Protection Circuit Breakers Overview Motor Protection Circuit Breakers may provide the following protective and control functions. Disconnect for Motor Branch Circuit Branch-Circuit, Short-Circuit Protection (Magnetic Protection) Overload Protection (Thermal Protection) Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D and F Frames: The 140M-C, D and F frame Motor Protection Circuit Breakers may have two cULus Listings - as Manual, Self-Protected Combination Motor Controllers and as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). When UL/CSA listed as Manual, Self-Protected Combination Motor Controllers, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. At some higher voltages and currents (particularly at 600V), a few of the 140M-C, D and F frame devices are only UL/CSA Listed as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). 140-CMN Frame: The 140-CMN frame Motor Protection Circuit Breakers are UL Listed/CSA Certified as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on UL/CSA Listed Application Ratings - Motor Protection Circuit Breaker (MPCB) Only for the specific ratings of each Motor Protection Circuit Breaker. Standards Compliance and Certifications Standards Compliance IEC/EN60947-1,-2,-4-1,-5-1 IEC/EN60204-1 CSA,C22.2 No.14 UL508 Certifications CE Marked CCC CSACertified cULus Listed (File No. E54612, NLRV(7); E205542, NKJH(7); E197878, DIVQ(7);) ATEX Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 3

Bulletin 140M Motor Protection Circuit Breakers Max.Current Ie Current Rating Short Circuit Protection Standard Magnetic T rip High Magnetic Trip Magnetic Only Trip (MCP) Overload Protection Trip Class Standards Compliance: CSA22.2, No.14 UL508 (Group Installation) UL508 Manual, Self Protected (Type E) UL508 (Overload Protection) IEC60947-1,-2 IEC60947-4-1 CE ATEX (IEC60079-14) CCC Accessories External Rotary Operator Auxiliary Contacts Trip Indication Contacts 4 C-Frame 32 A 0.1 32 A D-Frame 32 A 1.6 32 A F-Frame 45 A 6.3 45 A CMN-Frame 90 A 16 90 A 10 10 10 10 (see ratings) (see ratings) (up to 25 A) (up to 25 A) (see ratings) (see ratings) (up to 25 A) (up to 25 A) (see ratings) (see ratings) (see ratings) — — — Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 — — —

Bulletin 140M Motor Protection Circuit Breakers Catalog Number Explanation Examples given in this section are not intended to be used for product selection. 140M a Code 140M Code A B – C b 2 c E d a Bulletin Number Description Motor Protection Circuit Breaker e Current Range Description Example A16 0.16 A .10 B16 1.6 B 1.0 – A63 e – KN f b Frame/Rating Code Description C 32 A Code KN KRY C C 10 C16 16 TE D E D 100 E 1000 D16 160 E16 1600 MT D 32A F 45A f Miscellaneous Description Black Lockable Knob Red/Yellow Lockable Knob Spacing Adapter for SelfProtected Starters (TypeE) STD BusBar Mount, Top – CC g – GJ h c Interrupting Rating/Breaking Capacity Code Description 2 Normal Break 8 Frame Size C,D,F,CMN C,D,F,CMN High Break Code E T d Protection Type Description Adj Thermal/ Fixed Mag(13 x In) Adj Thermal/Fixed Mag (Fixed at 16.20 x In) g Auxiliary Trip Contacts C, D, F Frames 1st Code Description 2nd Code Description Bottom Front Right Side C,D,F X Placeholder X Placeholder C,D,F,CMN A B C 1 N.C. 1 N.O. 1 N.O. 1 N.C. C D E D 2N.O. K E 2N.C. L 1 N.O. 1 N.C. 2 N.O. 2 N.C. 1 N.C. (SC OL) 1 N.C. (SC) 1 N.O. (SC OL) 1 N.O. (SC) 1 N.C. (SC OL) 1 N.O. (SC) 1 N.O. (SC OL) 1 N.C. (SC) 1 N.O. (SC) 1 N.C.(SC) R S 1 N.C. 1 N.O. (SC OL) 1 N.O. 1 N.O.(SC OL) M N Q g (continued) Auxiliary Trip Contacts CMN Frames Description 1st Code Description 2nd Code Bottom Front Top Front(1) X Placeholder X Placeholder K 1 N.C. (OL) 1 N.C.(SC) C 1 N.O. 1 N.C. D 2 N.O. L 1 N.O. (OL) 1 N.O. (SC) E 2 N.C. M 1 N.C. (OL) 1 N.O. (SC) N 1 N.O. (OL) 1 N.C. (SC) (1) Cannot be combined with option “h”. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 5

Bulletin 140M Motor Protection Circuit Breakers 1st Code G P 1stCode G P 6 Description Left Side Undervoltage Trip Shunt Trip Description Top Front§ Undervoltage Trip Shunt Trip h UV and Shunt Trips C, D, F Frame 2nd Code Description Voltage J K D C H F A T N B VC M ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE CMN Frame 2nd Code KJ D A 24V AC, 60 Hz 24V AC, 50 Hz 120V AC, 60 Hz 110V AC, 50 Hz 208V AC, 60 Hz 220 230V AC, 50 Hz 240V AC, 60Hz 277V AC, 60 Hz 380 400V AC, 50 Hz 480V AC, 60Hz and415V AC, 50 Hz 600V AC, 60Hz 575V AC, 60Hz and500V AC, 50 Hz 9V DC 12V DC 24V DC 36V DC 48V DC 60V DC 64V DC 72V DC 80V DC Description Voltage 24V AC, 60 Hz and 24V AC, 50 Hz 120V AC, 60 Hz and 110V AC, 50 Hz 240V AC, 60 Hz and 220 230V AC, 50 Hz Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Bulletin 140M Motor Protection Circuit Breakers Application Diagrams Group Installation with MPCBs There is only one Branch Circuit Protective Device (BCPD) for the “Group” Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and other loads to be connected to the same branch-circuit ”. The most restrictive part of the conditions specified for Group Installation is the requirement for the protection of the conductors for each motor circuit. In the U.S. NEC for 2002, a new rule for the conductor sizing was added for devices that are listed and marked “Suitable for use as Tap Conductor Protection”. Below is an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”. Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Group Installation Conductors from the BCPD to each motor must be a minimum of 1/3 the ampacity of the Branch Circuit conductors. Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Tap conductor Protection in Group Installations Conductors from the BCPD to manual motor controller listed as “ Tap Conductor Protection ” must be minimum of 1/10 the rating or setting of the BCPD. Conductors from the controller to the motor must be 125% of the motor FLA. BCPD Branch Circuit Protective Device Group Installation: Single Motor Taps Must be 1/3 the ampacity of the Branch-Circuit conductors Fuses or Circuit Breaker Branch Circuit conductors Tap Conductor Protection in Group Installation: Conductors from BCPD to manual motor controller listed as “ Tap Conductor Protection ” must be minimum of 1/10 the rating or setting of the BCPD Tap Conductor Protection in Group Installation: Conductors to each motor sized normally at 125% of motor FLA Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 7

Bulletin 140M Motor Protection Circuit Breakers Multiple Motor Installation with MPCBs Each Motor has an Individual Branch Circuit Protective Device Bulletin 140M Motor Protection Circuit Breakers (MPCBs) UL/CSA Listed as Type E Manual Self-Protected Combination Motor Controllers or UL/CSA Listed as Circuit Breakers These UL/CSA Listings allow the Bulletin 140M MPCBs to provide the branch-circuit, short-circuit protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream protective device. Below is an example that illustrates installations involving multiple motors, each with its own branch-circuit protection (BCPD). Bulletin 140M-J L (Inverse Time Circuit Breakers) may provide the branch-circuit protection for each individual motor circuit Feeder Circuit Conductors Bulletin 140M-C F (Type E Self-Protected Combination Motor Controllers) may provide the branch-circuit protection for each individual motor circuit Conductors to each motor sized normally at 125% FLA 8 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Bulletin 140M Motor Protection Circuit Breakers Type E and Type F Combination Motor Controllers Most of the 140M-C F motor protection circuit breakers are UL listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass, is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit. By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a Bulletin 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits. A combination of a Bulletin 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, both the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require over sizing of the Bulletin 140M MPCB or the 100-C contactor to achieve weld free performance and meet the additional life requirements. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 9

Bulletin 140M Motor Protection Circuit Breakers Notes: 10 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Bulletin 140M Motor Circuit Protectors Overview Motor Circuit Protectors may provide the following protective and control functions. Disconnect for Motor Branch Circuit Branch-Circuit, Short-Circuit Protection (Magnetic Protection) Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D, and F Frames: The 140M-C, D and F frame Motor Circuit Protectors have one UL/CSA Listing - as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. Standards Compliance and Certifications Standards Compliance IEC/EN60947-1,-2,-4-1,-5-1 IEC/EN60204-1 CSA,C22.2 No.14 UL508 Certifications CE Marked CCC cULus Listed (File No. E54612, Guide No. NLRV, NLRV7) Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 11

Bulletin 140M Motor Circuit Protectors Max.Current Ie Current Rating Short Circuit Protection Standards Compliance: CSA22.2, No.14 UL508 (Group Installation) IEC60947-2 CE CCC Accessories External Rotary Operator Auxiliary Contacts Trip Indication Contacts 12 C-Frame 25 A 0.16 2.5 A D-Frame 32A 2.5 32 A F-Frame 45 A 25 45 A (up to 25 A) Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Bulletin 140M Motor Circuit Protectors Catalog Number Explanation Examples given in this section are not intended to be used for product selection. 140M a Code 140M Code A B – C b 2 c N d a Bulletin Number Description Motor Circuit Protector e Current Range Description Example A16 0.16 A .10 B 1.0 B16 1.6 – A63 e – KN f b Frame/Rating Code Description C 25 A D 32A F 45A Code KN KRY C C 10 C16 16 TE D E D 100 E 1000 D16 160 E16 1600 MT f Miscellaneous Description Black Lockable Knob Red/Yellow Lockable Knob Spacing Adapter for SelfProtected Starters (TypeE) STD BusBar Mount, Top – CC g – GJ h c Interrupting Rating/Breaking Capacity Code Description 2 Normal Break 8 High Break Frame Size C,D,F,CMN C,D,F,CMN d Protection Type Description Fixed Mag only (13 x In) Adj Mag only ( 13 x In) Adj Mag only ( 13 x In) Code N P R g Auxiliary Trip Contacts C, D, F Frames 1st Code Description 2nd Code Description Bottom Front Right Side C,D,F X Placeholder X Placeholder C,D,F,CMN A B C 1 N.C. 1 N.O. 1 N.O. 1 N.C. C D E D 2N.O. K E 2N.C. L 1 N.O. 1 N.C. 2 N.O. 2 N.C. 1 N.C. (SC OL) 1 N.C. (SC) 1 N.O. (SC OL) 1 N.O. (SC) 1 N.C. (SC OL) 1 N.O. (SC) 1 N.O. (SC OL) 1 N.C. (SC) 1 N.O. (SC) 1 N.C.(SC) R S 1 N.C. 1 N.O. (SC OL) 1 N.O. 1 N.O.(SC OL) M N Q g (continued) Auxiliary Trip Contacts CMN Frames Description 1st Code Description 2nd Code Top Front(1) Bottom Front X Placeholder X Placeholder K 1 N.C. (OL) 1 N.C.(SC) C 1 N.O. 1 N.C. D 2 N.O. L 1 N.O. (OL) 1 N.O. (SC) E 2 N.C. M 1 N.C. (OL) 1 N.O. (SC) N 1 N.O. (OL) 1 N.C. (SC) (1) Cannot be combined with option “h”. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 13

Bulletin 140M Motor Circuit Protectors 1st Code G P 1stCode G P 14 Description Left Side Undervoltage Trip Shunt Trip Description Top Front§ Undervoltage Trip Shunt Trip h UV and Shunt Trips C, D, F Frame 2nd Code Description Voltage J K D C H F A T N B VC M ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE CMN Frame 2nd Code KJ D A 24V AC, 60 Hz 24V AC, 50 Hz 120V AC, 60 Hz 110V AC, 50 Hz 208V AC, 60 Hz 220 230V AC, 50 Hz 240V AC, 60Hz 277V AC, 60 Hz 380 400V AC, 50 Hz 480V AC, 60Hz and415V AC, 50 Hz 600V AC, 60Hz 575V AC, 60Hz and500V AC, 50 Hz 9V DC 12V DC 24V DC 36V DC 48V DC 60V DC 64V DC 72V DC 80V DC Description Voltage 24V AC, 60 Hz and 24V AC, 50 Hz 120V AC, 60 Hz and 110V AC, 50 Hz 240V AC, 60 Hz and 220 230V AC, 50 Hz Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Bulletin 140M Motor Circuit Protectors Application Diagrams Group Installation with MCPs There is only one Branch Circuit Protective Device (BCPD) for the “Group” Group installation has been successfully used for many years in the U.S. and Canada. It allows “two or motors or one or more motors and other loads to be connected to the same branch-circuit ”. The most restrictive part of the conditions specified for Group Installation is the requirement for the protection of the conductors for each motor circuit. Below is an example that illustrates installations involving multiple motors with a single BCPD protecting the entire “Group”. Bulletin 140M Motor Circuit Protectors UL/CSA Listed for Group Installation Conductors from the BCPD to each motor must be a minimum of 1/3 the ampacity of the Branch Circuit conductors. Motor Circuit Protectors do not provide thermal protection, so a separate overload relay must be used. Therefore, MCPs cannot be UL/CSA Listed for Tap Conductor Protection in Group Installations. BCPD Branch Circuit Protective Device Bulletin 140M-C F Group Installation: Single Motor Taps Must be 1/3 the ampacity of the Branch-Circuit conductors Fuses or Circuit Breaker Branch Circuit conductors Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 15

Bulletin 140M Motor Circuit Protectors 16 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Specifications IEC Performance Data Cat.No.140M-C2EA63 B10 B16 B25 B40 B63 0.25 0.4 0.63 1 1.6 2.5 4 6.3 3.3 5.2 8.2 13 21 33 52 82 Switching of Standard Three-Phase Motors, AC-3 — 0.06 0.09 0.18 0.25 0.37 0.75 1.5 0.04 0.09 0.18 0.25 0.55 0.75 1.5 2.2 0.09 0.12 0.18 0.37 0.75 1.1 2.2 3.0 0.09 0.18 0.25 0.55 1.1 1.8 3.0 4.0 Back-Up Fuses gG, gL, only if Icc3 Icu A25 A40 C10 10 130 C16 16 208 C20 20 260 C25 25 325 C29 29 406 C32 32 448 2.2 4.0 6.3 7.5 4.0 7.5 10 13 5.5 10 11 17 5.5 11 15 22 7.5 13 18.5 25 7.5 15 20 25 50 63 80 50 80 80 80 63 100 100 80 80 63 100 100 80 80 63 125 125 100 100 80 125 125 100 100 80 100 100 100 100 4 100 100 50 50 4 100 65 10 10 3 65 50 6 6 3 65 15 6 6 3 50 15 6 6 3 50 15 6 6 3 100 100 100 100 4 100 100 50 50 4 100 50 6 6 3 50 15 6 6 3 50 15 6 6 3 25 15 6 6 3 25 15 6 6 3 Rated Operational Current, Ie Magnetic Release Current [A] [A] A16 0.16 2.1 230/240V 400/415V 500V 690V [kW] [kW] [kW] [kW] — 0.02 0.06 0.06 230/240V 400/415V 440/460V 500V 690V [A] [A] [A] [A] [A] 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] 100 100 100 100 100 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] 100 100 100 100 100 16 20 35 Ultimate Short Circuit Breaking Capacity, Icu 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 8 8 8 Rated Service Short Circuit Breaking Capacity, Ics 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 8 8 8 No back-up fuse required. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 17

Specifications Rated Operational Current, Ie Magnetic Release Current [A] [A] 230/240V 400/415V 500V 690V [kW] [kW] [kW] [kW] 230/240V 400/415V 440/460V 500V 690V [A] [A] [A] [A] [A] 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] 230/240V 400/415V 440/460V 500V 690V [kA] [kA] [kA] [kA] [kA] Cat.No.140M-D8EC10 C16 C20 C25 C29 4.0 6.3 10 16 20 25 29 52 82 130 208 260 325 406 Switching of Standard Three-Phase Motors, AC-3 0.37 0.75 1.5 2.2 4.0 5.5 5.5 7.5 0.75 1.5 2.2 4.0 7.5 10 11 13 1.1 2.2 3.0 6.3 10 11 15 18.5 1.8 3.0 4.0 7.5 13 17 22 25 Back-Up Fuses gG, gL, only if Icc3 Icu B25 2.5 33 B40 B63 100 100 125 80 100 100 125 80 80 80 100 20 35 50 50 63 63 63 80 Ultimate Short Circuit Breaking Capacity, Icu 100 100 100 100 100 100 100 65 100 100 100 100 100 100 65 50 100 100 100 100 50 50 50 25 100 100 100 100 50 50 50 25 10 10 10 6 6 6 6 6 Rated Service Short Circuit Breaking Capacity, Ics 100 100 100 100 100 100 100 50 100 100 100 100 50 25 25 25 100 100 100 100 50 25 25 20 100 100 100 100 50 25 25 20 10 10 10 6 4 4 4 4 C10 10 130 C16 16 208 7.5 15 20 25 2.2 4.0 6.3 7.5 4.0 7.5 10 13 5.5 10 11 17 6.3 11 15 22 7.5 15 20 30 13 22 30 40 125 125 100 80 80 80 80 63 100 100 100 80 100 100 100 80 100 100 100 80 125 125 125 100 125 125 125 100 65 50 25 25 6 100 100 65 50 10 100 100 65 50 10 100 100 65 50 10 100 100 65 50 10 100 65 65 50 10 100 65 50 50 10 50 25 20 20 4 100 50 50 50 10 100 50 50 50 10 100 50 50 50 10 100 50 50 50 10 100 50 50 50 6 100 50 50 50 6 No back-up fuse required. 18 Cat.No.140M-F8EC20 C25 C32 20 25 32 260 325 416 C32 32 448 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 C45 45 585

Specifications Cat.No. 140-CMN -4000 -6300 [A] 25 40 63 Rated Operational Current, Ie [A] 350 560 890 Magnetic Release Current Switching of Standard Three-Phase Motors, AC-3 230/240V ‡ [kW] 5.5/7.5 10/11 13/20 400/415V ‡ [kW] 7.5/13 15/22 25/32 500V ‡ [kW] 11/15 18.5/25 30/40 690V ‡ [kW] 15/22 25/30 37/55 Back-Up Fuses gG, gL, only if Icc3 Icu 230/240V [A] 400/415V [A] 160 160 160 500V [A] 160 160 160 690V [A] 160 160 160 Ultimate Short Circuit Breaking Capacity, Icu 230/240V [kA] 100 100 50 400/415V [kA] 50 30 20 500V [kA] 30 20 10 690V [kA] 15 8 4 Rated Service Short Circuit Breaking Capacity, Ics 230/240V [kA] 100 100 50 400/415V [kA] 50 30 8 500V [kA] 30 15 6 690V [kA] 15 8 4 -2500 -9000 90 1260 22/25 37/45 45/55 63/75 160 160 160 50 20 10 4 50 8 6 4 No back-up fuse required. ‡ Power ratings: Preferred values according to IEC 60072-1. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 19

Specifications Cat.No.140M-C2NA16 A25 A40 A63 B10 [A] 0.16 0.25 0.4 0.63 1 Rated Operational Current, Ie [A] 2.1 3.3 5.2 8.2 13 Magnetic Release Current Switching of Standard Three-Phase Motors, AC-3 230/240V [kW] — — 0.06 0.09 0.18 400/415V [kW] 0.02 0.04 0.09 0.18 0.25 500V [kW] 0.06 0.09 0.12 0.18 0.37 690V [kW] 0.06 0.09 0.18 0.25 0.55 Back-Up Fuses gG, gL, only if Icc3 Icu 230/240V [A] 400/415V [A] 440/460V [A] 500V [A] 690V [A] Ultimate Short Circuit Breaking Capacity, Icu 230/240V [kA] 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 500V [kA] 100 100 100 100 100 690V [kA] 100 100 100 100 100 Rated Service Short Circuit Breaking Capacity, Ics 230/240V [kA] 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 500V [kA] 100 100 100 100 100 690V [kA] 100 100 100 100 100 B16 1.6 21 B25 2.5 32 0.25 0.55 0.75 1.1 0.37 0.75 1.1 1.8 16 20 100 100 100 100 10 100 100 100 100 8 100 100 100 100 8 100 100 100 100 8 No back-up fuse required. 20 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Specifications Rated Operational Current, Ie Magnetic Release Current 230/240V 400/415V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V Cat.No.140M-D8NB25 B63 B40 C10 C16 C25 [A] 2.5 4.0 6.3 10 16 25 [A] 32 52 82 130 208 325 Switching of Standard Three-Phase Motors, AC-3 [kW] 0.37 0.75 1.5 2.2 4.0 5.5 [kW] 0.75 1.5 2.2 4.0 7.5 11 [kW] 1.1 2.2 3.0 6.3 10 15 [kW] 1.8 3.0 4.0 7.5 13 22 Back-Up Fuses gG, gL, only if Icc3 Icu [A] 100 [A] [A] 80 100 80 80 [A] [A] 20 35 50 50 63 63 Ultimate Short Circuit Breaking Capacity, Icu [kA] 100 100 100 100 100 100 [kA] 100 100 100 100 100 65 [kA] 100 100 100 100 50 50 [kA] 100 100 100 100 50 25 [kA] 10 10 10 6 6 6 Rated Service Short Circuit Breaking Capacity, Ics [kA] 100 100 100 100 100 100 [kA] 100 100 100 100 50 25 [kA] 100 100 100 100 50 25 [kA] 100 100 100 100 50 25 [kA] 10 10 10 6 4 4 C32 32 448 Cat.No.140M-F8NC25 C32 C45 25 32 45 325 416 585 7.5 15 20 25 6.3 11 15 22 7.5 15 20 30 13 22 30 40 125 125 100 80 100 100 100 100 80 125 125 125 125 100 125 125 125 125 100 65 50 25 25 6 100 100 65 50 10 100 65 65 50 10 100 65 50 50 10 50 25 20 20 4 100 50 50 50 10 100 50 50 50 6 100 50 50 50 6 No back-up fuse required. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 21

Specifications Rated Operational Current, Ie Magnetic Release Current 230/240V 400/415V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V 230/240V 400/415V 440/460V 500V 690V Cat.No.140M-C2TA16 A25 A40 A63 B10 B16 B25 [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 [A] 3.2 5.2 8.2 13 21 32 52 Switching of Standard Three-Phase Motors, AC-3 [kW] — — 0.06 0.09 0.18 0.25 0.37 [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75 [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1 [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8 Back-Up Fuses gG, gL, only if Icc3 Icu [A] [A] [A] [A] 16 20 [A] Ultimate Short Circuit Breaking Capacity, Icu [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 8 8 Rated Service Short Circuit Breaking Capacity, Ics [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 100 100 [kA] 100 100 100 100 100 8 8 B40 4.0 82 B63 6.3 130 C10 10 208 C16 16 260 0.75 1.5 2.2 3.0 1.5 2.2 3.0 4.0 2.2 4.0 6.3 7.5 4.0 7.5 10 13 80 80 80 63 35 50 63 80 50 100 100 100 100 8 100 100 100 100 4 100 100 50 50 4 100 50 10 10 3 100 100 100 100 8 100 100 100 100 4 100 100 50 50 4 100 15 6 6 3 No back-up fuse required. 22 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Specifications Cat.No.140M-D8TC16 C20 [A] 16 20 Rated Operational Current, Ie [A] 260 325 Magnetic Release Current Switching of Standard Three-Phase Motors, AC-3 230/240V‡ [kW] 4.0 5.5 400/415V‡ [kW] 7.5 10 [kW] 10 11 500V‡ [kW] 13 17 690V‡ Back-Up Fuses gG, gL, only if Icc3 Icu 230/240V [A] 400/415V [A] 80 100 440/460V [A] 80 100 500V [A] 80 80 690V [A] 63 63 Ultimate Short Circuit Breaking Capacity, Icu 230/240V [kA] 100 100 400/415V [kA] 100 65 440/460V [kA] 50 25 500V [kA] 50 25 690V [kA] 6 6 Rated Service Short Circuit Breaking Capacity, Ics 230/240V [kA] 100 100 400/415V [kA] 25 25 440/460V [kA] 25 25 500V [kA] 25 25 690V [kA] 4 4 Cat.No.140M-F8TC25 C32 25 32 416 585 6.3 11 15 22 7.5 15 20 30 100 100 100 80 125 125 125 100 100 65 65 50 10 100 65 65 50 10 100 50 50 50 6 100 50 50 50 6 No back-up fuse required. ‡ Consult your local Rockwell Automation sales office or Allen-Bradley distributor. General Data Cat.No. 140M-C Rated Insulation Voltage Ui IEC,SEV,VDE0660 [V] UL,CSA [V] Rated Impulse Withstand Voltage Uimp Pollution degree Main circuits Uimp/Overvoltage Category Auxiliary circuits Uimp/Overvoltage Category Rated Frequency [Hz] Utilization Category IEC60947-2 (Circuit breaker) IEC60947-4-1 (Motor starter) Lifespan Mechanical [operations] Electrical (Ie max.) [operations] Switching Frequency [operations/h] 140M-D 140M-F 140-CMN 690 600 690 600 3 6kV/III 6kV/III 50/60 3 6kV/III 6kV/III 40 60 A AC-3 A AC-3 (except 90 A) 100000 100000 30000 30000 max.25 Rockwell Automation Publication 140M-TD002B-EN-P - January 2015 30000 5000 max.20 23

Specifications Cat.No. 140M-C Ambient Temperature Storage [ C] Operation [ C] Climatic resistance Moisture change climate (600068-2-30) Dry heat (60086-2-2) Moisture heat (60068-2-3) Site Altitude [m] Protection Class Resistance to Shock, Transport (60068-2-27) Resistance to Vibration, Operation (60068-2-6) Rated Thermal Current Ith up to 40 C ambient temperature [A] up to 60 C ambient temperature [A] Rated Supply Current Ie [A] Dependence on Temperature 40 C [A] 50 C [A] 60 C [A] 70 C [A] Overload Protection Characteristics Ambient Temperature [ C] Compensation Phase-loss Protection Trip class Magnetic Release Release current( /-20%) Total Power loss Pv Circuit Breaker at rated load [W] operating temperature Main Disconnect Switch Application Application Conditions 24 140M-D 140M-F -40 80 140-CMN -25 80 -25 60 23 C/83% relative humidity and 40 C/92% relative humidity, 56 cycles 100 C, relative humidity 50%, 7 days 40 C, relative humidity 93%, 56 days to 2000 N.N. IP2X, when wired 30 g,11ms,all axes 5g 0.1 32 0.1 32 0.1 32 1.6 32 1.6 32 1.6 32 6.3 45 6.3 45 6.3 45 30g,11 ms 16 90 16 90 16 90 no reduction no reduction no reduction 15% current reduction of the upper rated current Ie IEC 60947-4-1Motor protection (except Cat.Nos.140M-C2N,140M-D8N,140M-F8N) IEC60947 -20 60 Differential release 10 (except Cat.Nos.140M-C2N,140M-D8N,140M-F8N) fixed setting fixed setting 13 14 x Ie max. (for F8N) 16 21 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T) Ie max. maximum values of setting ranges 6 11.5 6 11.6 9 16 10 fixed setting 14 x Ie max. 33 Yes, with accessories For utilization outside North America, assemblies (of products) shall comply to the IEC61439-1 requirements 140M manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments. Rockwell Automation Publication 140M-TD002B-EN-P - January 2015

Specifications Cat.No. 140M-C Conformity to Standards Approvals 140M- 140M-F IEC60947-1;-2;-4-1; EN60947-1;-2;-4-1; UL508; CSA22.2, No.14 CE,UL,CSA 140-CMN IEC60947-1;-2; EN60947-1;-2; UL508; CSA22.2, No.14 CE,UL,CSA Terminal Parts Type of terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor Tightening torque PozidrivNo.2/BladeNo.3 1 6/No.16 10 1 4/No.16 10 1 6/No.16 10 1 6/No.16 10 1.5 6/No.16 8 1.5 6/No.16 8 1 6/No.16 10 1 6/No.16 10 2 2.5/18 22 [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[AWG] [mm2]/[

Motor Circuit Protectors may provide the following protective and control functions. Disconnect for Motor Branch Circuit Branch-Circuit, Short-Circuit Protection (Magnetic Protection)

Related Documents:

Circuit-breaker with RHE RHD Circuit-breaker with HTC Circuit-breaker with LTC Circuit-breaker with FLD A IP 40 IP 20 IP 40 IP 40 IP 40 IP 40 B IP 20 IP 20 IP 20 IP 40 IP 30 IP 20 (1) During installation of the electrical accessories Weights A1 [Kg] A2 [Kg] A3 [Kg] Circuit-breaker 1 pole 0.245 0.37 - Circuit-breaker 2 poles 0.47 0.73 - Circuit .

electronic trip circuit breaker A circuit breaker which uses current sensors and electronic circuitry to sense, measure and respond to current levels. fixed-mounted circuit breaker A circuit breaker so mounted that it cannot be removed without removing primary and sometimes secondary connections and/or mounting supports.

MPW12i Motor Protective Circuit Breaker - Magnetic - Short-Circuit Protection Only2) MPW12 Motor Protective Circuit Breaker - Thermomagnetic - Overload and Short-Circuit Protection Notes: 1) For 50/60 Hz three-phase, 4 poles WEG W22 standard motors. These values are only for reference and may change on the number of poles and motor design;

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489 Data Sheet The miniature circuit breaker SU200 M is ABB's solution for UL 489 branch circuit protection up to 480 Y/277 V AC and 96 V DC. This circuit breaker is an all-round device for AC and DC applications for universal use in North

Student Manual Circuit Breaker Cubicle USNRC 4-1 Rev 0 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker,

Content Products Trends in High Voltage Circuit Breaker Technology 4 Dead Tank Based Compact Switchgear 8 Bypass Circuit-Breaker for 800 kV DC 13 1200 kV AC substations:Full-scale products and integrated solutions 19 Circuit-Breaker Platform for 550 kV 27 Siemens High-Voltage Circuit-Breakers for Use at Low Temperatures 34 3AP4/5 High-Voltage Circuit-Breaker for 800 kV 41

5.1 Circuit breaker offered shall be sulphur hexaflouride (SF6) type only. 5.2 Any part of the breaker, especially the removable ones, shall be freely interchangeable without the necessity of any modification at site. 5.3 Circuit breaker shall comprise of three identical single pole units. If the circuit breaker

TOP SECRET//HCS/COMINT -GAMMA- /TK//FGI CAN GBR//RSEN/ORCON/REL TO USA, CAN, GBR//20290224/TK//FGI CAN GBR//RSEN/ORCON/REL TO USA, CAN, GBR//20290224 In the REL TO marking, always list USA first, followed by other countries in alphabetical trigraph order. Use ISO 3166 trigraph country codes; separate trigraphs with a comma and a space. The word “and” has been eliminated. DECLASSIFICATION .