WIRING CHARM I/O IN SMARTPLANT FLUOR

2y ago
20 Views
2 Downloads
1.71 MB
26 Pages
Last View : 4d ago
Last Download : 3m ago
Upload by : Bennett Almond
Transcription

WIRING CHARM I/O INSMARTPLANTINSTRUMENTATIONFLUORSmartPlant Implementation TeamBy: Emeka NwagbaraCopyright 2018 Fluor Corporation all rights reserved

Wiring CHARM I/O in SPI Introduction The User Experience on a Project with over 50,000 I/O While several wiring methods were used on the project, thispresentation will focus on the use of Electronic marshalling Reasons for using Electronic Marshalling on the Project:–––––Emerson was the MIC and the MAC on the ProjectEmerson DeltaV DCS and SIS systems were usedThe DeltaV - SPI Interface was proposed for the ProjectPrimary I/O was CHARacterization Module (CHARM) I/OProject Configuration of CHARM I/O employed: Standardized Remote CHARM Field Enclosures Redundant Fiber Optic Network to Control Centers Wiring and Loop Diagrams to be SPI Enhanced Reports

Benefits of using Electronic Marshalling Redundant Ethernet topology Elimination of homerun wiring Reduced overall System Costs Flexibility:–––––––Any type of I/O at any locationReconfigurable at any timeStandard Ethernet hardwareRemote I/O Eliminate WiringPlug and Play ConfigurationSingle Channel GranularityEach I/O Card can serve 4 controllers

DeltaV SPI Interface Workflow The diagram below provides an overview of the workflowthat is supported by the interface

Download I/O Definitions Into SPI The DeltaV I/O definitionsare maintained by Emersonbut downloaded using a linkfrom taV Definition Files This assures the definitionsare the latest and provideinformation to improve thedata transfer process The downloaded definitionsappear in the ReferenceExplorer as SPI Objects

Download I/O Definitions Into SPIWhat is Downloaded? DeltaV Conventional I/O Definitions DeltaV S Series I/O Definitions Types CHARM Card �––– AI 4-20 mA HART RTD Thermocouple / mV AI 0-10V DC Isolated AO 4-20 mA HART DI NAMUR DI 24V DC low-side sense DI 24V DC Isolated DO 24V DC High Side DO 100mA Energy Limited DO 24V DC Isolated 24V DC Power DI 120V AC Isolated DI 120V AC Isolated Plus DI 230V AC Isolated DO V AC Isolated

Reference I/O Definitions Reference I/O Definitions include:– Wiring Equipment NameDescriptionManufacturer– Terminal Strip NamePanel NameManufacturer– Terminals 2 or 4 Terminals for connections Note: We eliminated unused CHARMcards from Reference Explorer Reference I/O can be used to buildCHARM I/O Card (CIOC) Panels inthe Wiring Module

CHARM I/O Card (CIOC) Configuration Each Field Panel has a redundant CIOCCarrier ; I/O Cards with redundantEthernet Communications Module and24VDC Power Supply CHARM Base Plate; DIN rail-mounted withpower, bus connectors, and Supports 12CHARMs per Base Plate CHARM Terminal Block - removableterminal block providing connections tofield wiring and physical latch for CHARM CHARMs - Characterization Module foreach field signal - Provides basic analog todigital conversion and signal isolation tothe redundant communication bus DIN rail mount for all CIOC components

CHARM I/O Card (CIOC) FIE/RIE Wiring Shown below is the proposed DCSFIE/RIE Hierarchy per EmersonCHARM white paper– Panel Rack Slot (Branch)-CHARM-Terminal Strip-Channel-Terminals However this hierarchy resulted in theSPI Terminal Strip wiring report withadjacent connections having only onesignal per drawing

CHARM I/O Card (CIOC) FIE/RIE Wiring Actual Project DCS FIE Hierarchy– Panel Rack Slot-CHARM-Terminal Strip (Branch)-Channel-Terminals The Terminal Strip report nowshowed all 12 CHARM channels Con: The CHARM was above thebranch now and lost unique CHARMdata per channel

CHARM Field Enclosures Benefits of using Field Enclosures:– Allows for Electronic Marshallingand Remote I/O in one Cabinet– Optimizes use of CHARM I/OTechnology– Reduce Overall System Footprint– Eliminates I/O Home Run Cables– Reduce design engineeringworkhours– Safe for Hazardous Areas– Fully Vendor Tested andDocumented Enclosures

CHARM Field Enclosures Field Enclosures Equipped as Follows:– Power distribution and isolationcomponents for primary andsecondary 24V DC Power toCHARM I/O Cards.– AC power feeds with redundantAC/DC 24V DC bulk powersupplies.– Grounding bars for CG (ChassisGround) and DC Reference Ground– Wire Ducts and Name Plates– CIOC Carriers, Base Plates andTerminals.

CHARM Cards Analog Input 4-20 mA HARTCHARM Characteristics– 2 wire Loop Powered– Signal - 4-20 mA with or withoutHART– Impedance - 250 Ω 1%– Accuracy - 0.1% of span (0-60 C)– Repeatability - 0.05% of span– Resolution - 16 bit A/D converter– Calibration - None required– Loop Power - 15 V at 20 mA @24V DC

CHARM Cards Analog Input 4-20 mA HARTCHARM Characteristics– 2 wire Field Powered– Signal - 4-20 mA with or withoutHART– Impedance - 250 Ω 1%– Accuracy - 0.1% of span (0-60 C)– Repeatability - 0.05% of span– Resolution - 16 bit A/D converter– Calibration - None required– Field Powered

CHARM Cards Analog Input 4-20 mA HARTCHARM Characteristics– 3 wire CHARM Powered– 24V DC Power CHARM– Max Power 24V DC at 20mA– Signal - 4-20 mA with or withoutHART– Impedance - 250 Ω 1%– Accuracy - 0.1% of span (0-60 C)– Repeatability - 0.05% of span– Resolution - 16 bit A/D converter– Calibration - None required

CHARM Cards Analog Output 4-20 mA HARTCHARM– Signal Range: 4 to 20 mA– Full Signal Range: 0 to 24 mA– Accuracy - 0.25% of span (0 to60 C)– Accuracy - 0.5% of span (-40 to70 C)– Resolution 16-bit D/A converter– Calibration None required– Available Field Power 20 mA at15V DC supply into 750 Ω load

CHARM Cards RTD Input CHARM– 2 wire RTD– Operating Range - -200 to 850 C– Temperature drift - 0.02 C/ C– Accuracy - 0.25 C– Repeatability - 0.05% of span– Resolution - 24 bit A/D converter– Calibration - None required– Common Mode Rejection - 90dBtypical– Open Sensor Detection

CHARM Cards RTD Input CHARM– 3 wire RTD– Operating Range - -200 to 850 C– Temperature drift - 0.02 C/ C– Accuracy - 0.25 C– Repeatability - 0.05% of span– Resolution - 24 bit A/D converter– Calibration - None required– Common Mode Rejection - 90dBtypical– Includes Open Sensor Detection

CHARM Cards RTD Input CHARM– 4 wire RTD– Operating Range - -200 to 850 C– Temperature drift - 0.02 C/ C– Accuracy - 0.25 C– Repeatability - 0.05% of span– Resolution - 24 bit A/D converter– Calibration - None required– Common Mode Rejection - 90dBtypical– Includes Open Sensor Detection

CHARM Cards Discrete Input 24 V DC low-sidesense (dry contact) CHARM– Sensor Types 24V DC - DryContacts– On Detection Level - 2.25 mA– Off Detection Level - 1.75 mA– Channel Impedance - 4.8 KΩ– Wetting Voltage - 22.5Volts– Configurable Channel Types - Discrete Input or Pulse Count

CHARM Cards Discrete Output 24V DC High-SideCHARM– On State Rating - 100 mA @ 24V DC– Off State Leakage Current - 1 mALine Fault Detection Short circuit: 50 Ω load Good status: 240 Ω to 10 kΩ load Open circuit: 20 kΩ load– Configurable Output Behavior Momentary Output Continuous Pulse Output

CHARM Cards 24V DC Power CHARM– Device Type 24V DC Power output– Status for Power Good 10V DC– Status for Power Bad 5V DC– Isolation - Status read back circuitryis optically isolated and factorytested to 1000V DC.– Field Circuit Protection 2 Amp fuse– CHARM Power - 12 mA max– Available Power - 1.01 Amps max

CIOC Strip with Adjacent Terminals Report Enhanced CIOC StripReport with adjacentTerminals shows:– Field Wiring from theinstrument to the CIOC– Two Page report with 9 I/O onfirst and 3 on the second– Cable Names– Wire Colors– Panel Number– Strip Number– Channel Numbers– Terminal Numbers– CS Tag NumbersDisplays per set Preferences

CIOC Loop Diagram Example Due to lack of Marshalling Strip, Enhanced SPI LoopDiagram typically only shows the Device PanelsInstrument and COIC Terminations

Using Electronic Marshalling Conclusion CIOC is Configurable for:– Basic Process Control Systems (BPCS)– Safety Instrumented Systems (SIS)– Intrinsically Safe (IS) Systems CIOC Can be RIE or Field Mounted Instrument Wiring to CIOC can be Director by Junction Boxes and HomerunCables Eliminates Marshalling Cabinets Eliminates need for Loop Diagrams Potential to replace other wiring methods

Wiring CHARM I/O in SPI“I prefer intellect and CHARM” Angie Everhart26

– Emerson DeltaV DCS and SIS systems were used – The DeltaV - SPI Interface was proposed for the Project – Primary I/O was . CHAR. acterization . M. odule (CHARM) I/O – Project Configuration of CHARM I/O employed: Standardized Remote CHARM Field Encl

Related Documents:

00005 / colori 05 / colours pag. 04 charm brown pag. 10 charm white pag. 16 charm walnut pag. 22 charm taupe pag. 28 charm honey il fascino discreto e accogliente del legno È l'ispirazione stilistica di charm, la nuova collezione

TYPES OF ELECTRICAL WIRING There are following types of electrical wiring. 1. Cleat wiring or Temporary wiring 2. Wooden or Batten wiring 3. Casing and Capping 4. Conduit Wiring 5. Trunking Wiring 1 Cleat Wiring or Temporary Wiring AIR UNIVERSITY, PAF COMPLEX E-9, ISLAMABAD It is a temporary wiring used for function and construction work.

Texts of Wow Rosh Hashana II 5780 - Congregation Shearith Israel, Atlanta Georgia Wow ׳ג ׳א:׳א תישארב (א) ׃ץרֶָֽאָּהָּ תאֵֵ֥וְּ םִימִַׁ֖שַָּה תאֵֵ֥ םיקִִ֑לֹאֱ ארָָּ֣ Îָּ תישִִׁ֖ארֵ Îְּ(ב) חַורְָּ֣ו ם

Fig. 1. Overview of the O-RAN-based ChARM spectrum-sharing framework. For this reason, in this paper we propose the Channel-Aware Reacting Mechanism framework (in short, ChARM). Fig. 1 shows a high-level overview of ChARM and its main logical components, including the O-RAN interfaces used to collect and exchange data among the different .

Wiring Diagram (Code 9983) M17050 1 Wiring Diagram (Code 10021) M17053 1 Wiring Diagram (Code 10110, 10341) M17464 1 Wiring Diagram (Code 10373, 10526, 10535, 10541) M18331 1 Wiring Diagram (Code 10274, 10377, 10536) M18332 1 Wiring Diagram (Code 10375, 10537) M18333 1 Wiring Diagram (Code 10376, 10538) M18334 1 Wiring Diagram (Code 10886) M19988 1

4 Wiring Diagrams TP-6712 4/10 Wiring Diagrams Use the Wiring Diagram Cross-Reference chart to determine the wiring diagram version number for a given model number and spec number. Then find that version number, the controller type, and the alternator type on the Wiring Diagrams Reference chart to determine the wiring diagram numbers for your unit.

wiring your motor p.06 9.1 nema three-phase wiring diagrams p.07 9.1.1 nema brake motor wiring diagrams p.08 9.2 iec three-phase wiring diagrams p.09 9.2.1 iec brake motor wiring diagrams p.10 9.3 nema farm duty wiring diagrams p.11 9.4 nema single-phase wiring diagrams p.12 9.5 iec single-phase wir

Security activities in scrum control points 23 Executive summary 23 Scrum control points 23 Security requirements and controls 24 Security activities within control points 25 References 29 Risk Management 30 Executive summary 30 Introduction 30 Existing frameworks for risk and security management in agile software development 34 Challenges and limitations of agile security 37 a suggested model .