DeltaV Distributed Control SystemProduct Data SheetMarch 2020CTO DCS CHARM Field Enclosures(CE; ATEX; IECEx, Ordinary and Zone 2 Locations)Configure to Order (CTO) CHARM Field Enclosures. Delivers Electronic Marshalling enabled byCHARacterization Modules (CHARM) technology Reduce system footprint Eliminate I/O home run cables Significantly reduce cabinet design engineering Fully documented packageIntroductionThe DeltaV CTO CHARM Field Enclosures provide an offthe-shelf solution for faster project execution and reducedinstallation costs. Field Enclosures are factory tested productsand ready for installation in the field. Electronic Marshallingeliminates traditional I/O design tasks and allows field wiringto start long before control strategies are finalized.The field enclosures are designed for hazardous areas and harshenvironments, from extreme temperatures to corrosive gases.

CTO CHARM Field EnclosureBenefitsDelivers Electronic Marshalling enabled by CHARMstechnology: The CHARM Field Enclosures offer the full benefitsof Electronic Marshalling. The individual channels can bedefined for any combination of field signal type, as requiredby the process equipment. This allows for 100 % utilizationof channels, regardless of the I/O signal mix. Late changesare easily accommodated with minimal re-engineering andno rewiring.Reduce system footprint: Equipment room footprint is greatlyreduced by replacing traditional marshalling cabinets with fieldmounted I/O cards.Eliminate I/O home run cables: Field instrumentation wiringis reduced to the signal pair that connects the field device tothe Field Enclosure. Save on home run multi-core cables, cabletrays, associated engineering, and documentations.Significantly reduce cabinet design engineering: TheCHARM Field Enclosures are pre-engineered and factory tested.The I/O flexibility allows the same design to serve a wide varietyof I/O signals, conditioned individually by the CHARM. Fieldwiring design is complete at the terminal block.Fully documented package: Each Field Enclosure is suppliedwith full documentation and engineering drawings showinginternal lay-out, bill of materials, and internal wiring. Theyare designed to meet local building code and industry bestpractices in order to deliver proven functionality withminimal costs.DescriptionThe CTO CHARM Field Enclosures offering comprises a rangeof pre-engineered solutions based on industry standard, wallmounting enclosures that are available in AC-powered and DCpowered version with space for 48 or 96 CHARM I/O dependingon the model chosen.The designs have considered specific requirements relatedto outdoor installation in the field, including environmentalprotection, heat dissipation, power and groundingrequirements, and installation in hazardous areas.All components are prewired and tested at the factory. Simplyselect the required DeltaV Electronic Marshalling equipmentand the enclosure is ready to install, connect the field wiring,power and network cables. Install needed CHARMs tocommission your loops and autosense the hardware intoyour DeltaV system.www.emerson.com/deltavMarch 2020Before delivery, each field enclosure undergoes a full in-houseinspection and test, to assure that it is fully operational beforeleaving the factory. Electronic Marshalling eliminates the needfor custom designs. These enclosures can be ordered, togetherwith the DeltaV Electronic Marshalling equipment and CHARMI/O and delivered directly to site to begin field wiring (FactoryAcceptance Test (FAT) with client may be optional).The CTO CHARM Field Enclosures are ordered by selecting abase enclosure model and required options to meet specificproject needs.A range of base enclosure models are available: For different I/O quantities: 48 or 96 I/O’s. Distributed CHARM IOs (combination of Max. 12 / 24CHARMs inside FE and external 12 CHARM IO junction boxes- total IO count 96). For different power distribution needs: DC-Powered orAC- Powered. For different environmental requirements:Safe Area or Hazardous Area. European electrical codes/regulations.Each base model is further explained in the coming sections.Configurable options include the type of CHARMS (I.S. ornon I.S.), network (Fiberoptic or Copper), enclosure Material(SS304/SS316), cable entry, nameplate engraving, injectedpower, heater, etc.System planningElectronic Marshalling changes the game with respect tocontrol system I/O planning. The field I/O wiring can bedesigned independently from the control strategy design,allowing E&I engineers to determine the number and type ofI/O based on the process design. Count the I/O requirements and determine the number ofCHARM Field Enclosures you need. Determine whether the enclosure is for a safe area orhazardous area. Plan the power distribution and install the enclosures. Wire the field devices and commission them. When control strategies and associated controller hardwareis finalized, simply assign the I/O signals to the controllers asneeded, no wiring changes. You can change controller I/Oassignments with the click of a mouse, without touching awired connection.2

CTO CHARM Field EnclosureCHARM Field EnclosuresMarch 2020 Enclosure Material: Stainless Steel SS304 or SS316L.Stainless steel provides protection for corrosive environments(category NEMA 4X). SS316L provides superior corrosiveprotection and is typically applied in off-shore applications(salt resistant). Pre-drilled bottom entry with Nickel Plated Brass wireglands for I/O, power, communications and grounding cables.With standard drill pattern (with stop plugs). Orcable transit system with flexible cable gland blocks thatare installed in a cable entry frame. Name plate engraved with custom supplied cabinetidentification information. 24V DC power distribution for injected power or 4-wiretransmitter power: 6 or 12 fused circuits, prewired to all baseplates. (This option includes a redundancy diode to bringprimary and secondary power feeds to a common injectedpower distribution). Heaters, for extreme low temperature installations. Blue marking for wire ducts. Breather: Brass Ni plated / SS316L. Ethernet: Fiberoptic / Copper. Warning label languages other than standard English,French, Spanish, and German.All CHARM Field Enclosures come with the followingequipment installed: Power distribution and isolation components for primaryand secondary 24V DC Power to CHARM I/O Cards.AC power feeds with redundant AC/DC 24V DC bulkpower supplies.- or 24V DC power distribution from remote. Halogen-Free wire ducts. Grounding bars for CG (Chassis Ground) and DCReference Ground. Reference. Name Plate. Removable Gland Plate (3mm thick).Enclosures are designed for bottom entry for all cables(power, network, and I/O signals)The CTO CHARM Field Enclosures support all available lowvoltage CHARM I/O types with 24V DC bussed field power.CHARM I/O Cards (CIOC), Non-standard CHARM terminal blocks,and CHARMs are not included and are to be ordered separately.CTO OptionsFor a particular base enclosure model, a numberof pre-engineered CTO options can be specified.These options include: All CTO options are implemented, tested and shipped to site asone package, significantly reducing the required upfront designand certification effort.The following sections provide a more detailed specification forthe CTO CHARM Field Enclosures and available options.Type of CHARMs:48 IO Enclosure: 48IO (Non-IS)/ 48IO (IS)/ 48IO with24 (IS) 24(Non-IS)96IO Enclosure: 96IO (Non-IS)/ 96IO (IS)/ 96IO with60(IS) 36 (Non-IS)Dist. CHARM IO Enclosure: All 8 nos. external 12 CHARM IOjunction boxes / 12 CHARMs (IS /NIS) inside FE and 7 nos.ext. 12 CHARM IO Junction Boxes / 24 CHARMs (IS /NIS)inside FE and 6 nos. ext. 12 CHARM IO Junction Boxes –total IO count 96.Actual CHARMs to be ordered separately.www.emerson.com/deltav3

CTO CHARM Field EnclosureMarch 2020Overview of CHARM Field Enclosures – Base Models:No.CHARMIOPowerRequirements(Prim and Sec)DC Powered Field Enclosure for 48 CHARMI/O; CE; Safe Area Locations.4824V DCSafe Area CE(Europe)EU-FE-48-DC-CIOC-HADC Powered Field Enclosure for 48 CHARMI/O; CE; ATEX; IECEx, Zone 2 Locations.4824V DCHazardous AreaATEX/IECEx Zone 2EU-FE-48-AC-CIOC-SAAC Powered Field Enclosure for 48 CHARMI/O; CE; Safe Area Locations.48230V ACSafe Area CE(Europe)EU-FE-48-AC-CIOC-HAAC Powered Field Enclosure for 48 CHARMI/O; CE; ATEX; IECEx, Zone 2 Locations.48230V ACHazardous AreaATEX/IECEx Zone 2EU-FE-96-AC-CIOC-SAAC Powered Field Enclosure for 96 CHARMI/O; CE; Safe Area Locations.96230V ACSafe Area CE(Europe)EU-FE-96-AC-CIOC-HAAC Powered Field Enclosure for 96 CHARMI/O; CE; ATEX; IECEx, Zone 2 Locations.96230V ACHazardous AreaATEX/IECEx Zone 2EU-FE-96-AC-VLV-SAAC Powered Indoor Field Enclosure with60 CHARM I/O and ASCO Valve Island;CE; Safe Area Locations60230V ACSafe Area CE(Europe)EU-FE-96-DC-VLV-SADC Powered Indoor Field Enclosure with60 CHARM I/O and ASCO Valve Island;CE; Safe Area Locations6024V DCSafe Area CE(Europe)EU-FE-D96-AC-CIOC-SAAC Powered Field Enclosure for Distributed96 CHARM I/O; CE; Safe Area Locations.96230V ACSafe Area CE(Europe)Base Model No.DescriptionEU-FE-48-DC-CIOC-SAPermitted Location /World AreaOverview of CHARM Field Enclosures.The CTO base model reference for field enclosures uses the following naming convention:“EU-FE-XX-YY-CIOC-ZZ”, Distributed CHARM: EU-FE-DXX-YY-CIOC-ZZ, where EU Europe Design Standards and RegulationsFE Field EnclosureXX maximum I/O’s count in this CTO model.D Distributed CHARMYY Incoming Power, DC: 24V DC or AC: 230V AC.CIOC short description of content and purpose.ZZ SA: for use in Safe Area, HA: for use in Hazardous Area (ATEX/IECEx, Zone 2)www.emerson.com/deltav4

CTO CHARM Field EnclosureMarch V-SAOverview of CHARM Field Enclosures base models and options for EUROPE World Area#CHARM I/O48IO48IO48IO48IO96IO96IO96IO96IOPower Input (230V AC / 24V DC)DCDCACACACACDCACLocation (Safe Area -SA, Hazardous Area - HA)SAHASAHASAHASASACertification as per World AreaCEATEXCEATEXCEATEXCECELEGENDS:Base Model : Default option settingo : Configure to option setting.(Different from Default)NA Option setting not possible for BaseEnclosure Model: Intentionally left blank to fill in yourconfiguration choicesEnclosure OptionsEnclosure MaterialCable EntryEnclosure OptionsABC1Type of CHARMsC2C324V DC Injected power **(Applicable only for NISCHARM Baseplates)Ethernet - Safety NetworkHeater **Warning Label LanguagesD1D2EFG1Stainless Steel SS304 with single gland plate 2Stainless Steel SS316L with single gland plate 3Hygienic Design enclosure1Undrilled Gland Plate 2Gland Plate with Standard Drill Pattern 3Gland Plate with Roxtec Glands 148IO - NONIS 248IO - IS 324IO (IS) 24IO (NONIS) 196IO - NONIS 296IO - IS 360IO (IS) 36IO (NONIS) 160IO - NONIS260IO - IS1No (5A Power Supply)* 2Yes (8 Circuit - 10Amp Power Supply Diode) 1No (10A Power Supply)*2Yes (12 Circuits - 20Amp Power Supply Diode)1Multimode Fibre Optic w / Adapter 2Multimode Fibre Optic w / Splice Cassettes 3Single-mode Fibre Optic w / Adapter 4Single-mode Fibre Optic w / Splice Cassettes 5Copper 6Fiber Optic (Singe Mode IOP)1No2Single Heater3Two HeatersHNANA NANANANA NA NANANA NA NANA4Three Heaters 1English French German Spanish 2English French German User Specific Language 3Type of Valve IslandOptions SelectionEnglish French Spanish UserSpecific LanguageNA112 Coil Standard Configuration Valve Island 212 Coil Custom Configuration Valve Island 324 Coil Standard Configuration Valve Island 424 Coil Custom Configuration Valve Island 532 Coil Custom Configuration Valve Island 632 Coil Standard Configuration Valve Island NA** With 24V DC Injected power option selected “Yes”, Enclosure will be rated for maximum. 50Deg. C ambient temperature.* Maximum Power supply rating allowed for 55Deg. C Ambient installation is 10Amp for 96IO FE & 5Amp for 48IO FE.For 55Deg. C ambient installation, enclosure total internal heat dissipation cannot be exceeded beyond 90W for 96IO FE& 60W for 48IO FE.www.emerson.com/deltav5

CTO CHARM Field EnclosureMarch 2020LEGENDS:Base ModelEU-FE-D96-AC-CIOC-SAOverview of Distributed CHARM Field Enclosures base models and options : Default option settingo : Configure to option setting. (Differentfrom Default): Intentionally left blank to fill in userconfiguration choices#CHARM I/O96IOPower Input (230V AC)ACLocation (Safe Area -SA, Hazardous Area - HA)SACertification as per World AreaCEEnclosure OptionsOptions SelectionEnclosure OptionsEnclosure MaterialCable EntryHeatersNo. of Baseplates(Inj. Power will be connected by defaultto NIS CHARM Baseplates inside FE)Type of CHARMSExternal 12 CHARM IO Junction BOX24VDC SupplyCIOC NetworkCHARM Gateway NetworkSurge Protection DeviceEnclosure LightWarning Labels Languageswww.emerson.com/deltavABCDEFGHIJK 1Stainless Steel SS304 with single gland plate2Stainless Steel SS316L with single gland plate 1Undrilled Gland Plate 2Pre-drilled Gland Plate with Installed Cable Glands 3Pre-filled Roxtec Frame 1No 2Single Heater 10 21 (12 CHARMs) 32 (24 CHARMs) 1All NIS 2All IS 1Simplex 2Redundant 1MM Fiber Optic with Media Converter 2Copper Ethernet 3MM Fiber Optic with Fiber IOP 4SM Fiber Optic with Media Converter 1Ring 2Star 1No 2Yes 1No 2Yes 1STANDARD LABEL (ENG FRN GER SPN) 2ENG FRN GER USER SPECIFIC LANGUAGE 3ENG FRN SPN USER SPECIFIC LANGUAGE 6

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-48-DC-CIOC-SA.(*) Specifications given for the base model with default option settings. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosuresbase models and options table.EU-FE-48-DC-CIOC-SAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915mm (W) x 1070mm (H) x 325mm (D)AccessSingle door, left hand hingedProtection Category (*)IP 66 –Type 4X (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name Plate (*)Outside Door: Laser engraved plasticWeight 125 kgCertificationsCE, installation in Safe Area LocationsPower Requirements – Internal Power Distribution.Primary and secondary 24 VDC power to be supplied fromoutside the Field Enclosure.Includes full redundant (primary and secondary) 24 VDCdistribution through power terminals and circuit breakers.24VDC for injected power or 4-wire transmittersApplicable for Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode portwith LC Connector.Fiber Optic control network Includes: FO to Copper Converter(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode50/125-micron core/cladding diameters (OM2) or Single mode9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 48 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copperEthernet connectors. 4 x CHARM Base Plates and address plugs. 48 x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels.Design exclusions for Enclosure installation in55 Deg. C Ambient:1. No Injected power (Max. 5Amp PS allowed,No redundancy module)2. No HeaterNo DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, Halogen-Free wire ducts, external wallmounting brackets, door clamps, ground bars, externalgrounding bolt, drip edge, breather-drain.7

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-48-DC-CIOC-HA.(*) Specifications given for the base model with default option settings. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosures base modelsand options table.EU-FE-48-DC-CIOC-HAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915mm (W) x 1070mm (H) x 325mm (D)AccessSingle door, left hand hingedProtection Category (*)IP 66 –Type 4X (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name Plate (*)Outside Door: laser engraved plasticWeight 135 kgCertificationsATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gcfor NON-IS CHARMSATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gcfor IS CHARMSPower Requirements – Internal Power DistributionPrimary and secondary 24 VDC power to be supplied fromoutside the Field Enclosure.Includes full redundant (primary and secondary) 24 VDCdistribution through power terminals and circuit breakers.24VDC for injected power or 4-wire transmittersFor Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode port withLC Connector.Fiber Optic control network Includes: FO to Copper Converter(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode50/125-micron core/cladding diameters (OM2) or Single mode9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 48 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copperEthernet connectors. 4 x CHARM Base Plates and address plugs. 48 x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels.Design exclusions for Enclosure installation in55 Deg. C Ambient:1. No Injected power (Max. 5Amp PS allowed,No redundancy module)2. No HeaterNo DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, Halogen-Free wire ducts, external wallmounting brackets, door clamps, ground bars, externalgrounding bolt, drip edge, breather-drain.8

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-48-AC-CIOC-SA(*) Specifications given for the base model with default options. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosures base modelsand options table.EU-FE-48-AC-CIOC-SAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915mm (W) x 1070mm (H) x 325mm (D)AccessSingle door, left hand hingedProtection CategoryIP 66 –Type 4X (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name PlateOutside Door: Laser engraved plasticWeight 125 kgCertificationsCE, installation in Safe Area LocationsPower Requirements – Internal Power DistributionPrimary and secondary 230 VAC power supply supplied fromoutside the Field Enclosure.Redundant 230 VAC distribution through power terminals, andcircuit breakers. 24 VDC bulk power supplies: 2 x 5A and fullredundant (primary and secondary) 24 VDC distribution.24VDC for injected power or 4-wire transmittersFor Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode port withLC Connector.Fiber Optic control network Includes: FO to CopperConverter (MM or SM), SC adaptors, SC-LC FO patch cables,Multimode 50/125-micron core/cladding diameters (OM2) orSingle mode 9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 48 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copperEthernet connectors. 4 x CHARM Base Plates and address plugs. 48 x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels.Design exclusions for Enclosure installation in55 Deg. C Ambient:1. No Injected power (Max. 5Amp PS allowed,No redundancy module)2. No HeaterNo DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, Halogen-Free wire ducts, external wallmounting brackets, door clamps, ground bars, externalgrounding bolt, drip edge, breather-drain.9

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-48-AC-CIOC-HA.(*) Specifications given for the base model with default options. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosures base modelsand options table.EU-FE-48-AC-CIOC-HAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915mm (W) x 1070mm (H) x 325mm (D)AccessSingle door, left hand hingedProtection Category (*)IP 66 –Type 4X (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name Plate (*)Outside Door: Laser engraved plasticWeight 135 kgCertificationsFor NON-IS CHARMSATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 GcFor IS CHARMSATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 GcPower Requirements – Internal Power DistributionPrimary and secondary 230 VAC power supply supplied fromoutside the Field Enclosure.Redundant 230 VAC distribution through power terminals, andcircuit breakers. 24 VDC bulk power supplies: 2 x 5A and fullredundant (primary and secondary) 24 VDC distribution.24VDC for injected power or 4-wire transmittersApplicable for Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode port withLC Connector.Fiber Optic control network Includes: FO to Copper Converter(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode50/125-micron core/cladding diameters (OM2) or Single mode9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 48 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copperEthernet connectors. 4 x CHARM Base Plates and address plugs. 48 x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels.Design exclusions for Enclosure installation in55 Deg. C Ambient:1. No Injected power (Max. 5Amp PS allowed,No redundancy module)2. No HeaterNo DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, Halogen-Free wire ducts, external wallmounting brackets, door clamps, ground bars, externalgrounding bolt, drip edge, breather-drain.10

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-96-AC-CIOC-SA.(*) Specifications given for the base model with default options. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosures base modelsand options table.EU-FE-96-AC-CIOC-SAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915 mm (W) x 1220mm (H) x 475 mm (D)AccessSingle door, left hand hinged with door stopProtection Category (*)IP 66 – Type 4X (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name Plate (*)Outside Door: Laser engraved plasticWeight 165 kgCertificationscCSAus for Ordinary LocationsPower Requirements – Internal Power DistributionPrimary and secondary 120 VAC power supply supplied fromoutside the Field Enclosure.Redundant 120 VAC distribution through power terminals andcircuit breakers. 24 VDC bulk power supplies: 2 x 10A and fullredundant (primary and secondary) 24 VDC distribution.24VDC for injected power or 4-wire transmittersFor Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode port withLC Connector.Fiber Optic control network Includes: FO to CopperConverter (MM or SM), SC adaptors, SC-LC FO patch cables,Multimode 50/125-micron core/cladding diameters (OM2) orSingle mode 9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 96 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copper Ethernet connectors. 8 x CHARM Base Plates and address plugs. 96 x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels.Design exclusions for Enclosure installation in55 Deg. C Ambient:1. No Injected power (Max. 10Amp PS allowed,No redundancy module)2. No HeaterNo DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, wire ducts, external wall mounting brackets,door clamps, ground bars, external grounding bolt, drip edge,breather-drain.11

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-96-AC-CIOC-HA.(*) Specifications given for the base model with default options. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosures base modelsand options table.EU-FE-96-AC-CIOC-HAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915 mm (W) x 1220mm (H) x 475 mm (D)AccessSingle door, left hand hinged with door stopProtection Category (*)IP 66 – Type 4X (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name Plate (*)Outside Door: laser engraved plasticWeight 165 kgCertificationscCSAus for Ordinary LocationsPower Requirements – Internal Power Distribution (*)Primary and secondary 230 VAC power supply supplied fromoutside the Field Enclosure.Redundant 230 VAC distribution through power terminals andcircuit breakers. 24 VDC bulk power supplies: 2 x 10A and fullredundant (primary and secondary) 24 VDC distribution.24VDC for injected power or 4-wire transmittersFor Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter: One 100BASE-FX, Single Mode or Multi-mode port with LC Connector.Fiber Optic control network Includes: FO to Copper Converter(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode50/125-micron core/cladding diameters (OM2) or Single mode9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 96 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copper Ethernet connectors. 8 x CHARM Base Plates and address plugs. 96 x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels. 1 x WIOC (Optional) with 72 CHARM IODesign exclusions for Enclosure installation in55 Deg. C Ambient:1. No Injected power (Max. 10Amp PS allowed,No redundancy module)2. No HeaterNo DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, Halogen-Free wire ducts, external wallmounting brackets, door clamps, ground bars, externalgrounding bolt, drip edge, breather-drain.12

CTO CHARM Field EnclosureMarch 2020Specifications for Should be EU-FE-96-DC-VLV-SA.(*) Specifications given for the base model with default options. For other available configurations refer to Overview of CTO DCS CHARM Field Enclosures base modelsand options table.EU-FE-96-DC-VLV-SAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915 mm (W) x 1070mm (H) x 325 mm (D)AccessSingle door, left hand hingedProtection Category (*)IP 65 (Corrosive Environment)Cable Entry (*)Bottom, Single gland plate (Thickness 3mm)Name Plate (*)Outside Door: Laser engraved plasticWeight 125 kgCertificationsCE, installation in Safe Area LocationsPower Requirements – Internal Power Distribution (*)Primary and secondary 24 VDC power supply supplied fromoutside the Field Enclosure.Redundant 24 VDC distribution through power terminals; fullredundant (primary and secondary) 24 VDC distribution.24VDC for injected power or 4-wire transmittersFor Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode port withLC Connector.Fiber Optic control network Includes: FO to Copper Converter(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode50/125-micron core/cladding diameters (OM2) or Single mode9/125-micron cable.Example Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 60 CHARM I/Ochannels, including: 1 x CHARM I/O Carrier with redundant copperEthernet connectors. 5 x CHARM Base Plates and address plugs. 60x CHARM standard terminal blocks - Screw type. Base Plate and Channel Identifier Labels. 1 x ASCO valve (12 Channel Valve by default)No DeltaV equipment is included in the base model. All DeltaVequipment is to be specified separately through the Emersonquoting tools.Otherwww.emerson.com/deltavMounting plate, Halogen-Free wire ducts, external wallmounting brackets, door clamps, ground bars, externalgrounding bolt, drip edge, breather-drain.13

CTO CHARM Field EnclosureMarch 2020Specifications for EU-FE-96-AC-VLV-SA.(*) Specifications given for the base model with default options. WIOC is optional. For other available configurations: see Overview of CTO Options.EU-FE-96-AC-VLV-SAMaterial (*)Stainless Steel SS304, Enclosure Thickness 2mmDimensions915 mm (W) x 1070mm (H) x 325 mm (D)AccessSingle door, left hand hingedProtection Category (*)IP 65 (Corrosive Environment)Cable Entry (*)Bottom, single gland plate (Thickness 3mm)Name Plate (*)Outside Door: laser engraved plasticWeight 125 kgCertificationsCE, installation in Safe Area LocationsPower Requirements – Internal Power Distribution (*)Primary and secondary 230 VAC power supply supplied fromoutside the Field Enclosure.Redundant 230 VAC distribution through power terminalsand circuit breakers. 24VDC Power Supplies: 2x10A and fullredundant (primary and secondary) 24 VDC distribution.24VDC for injected power or 4-wire transmittersFor Non-IS Baseplates onlyControl Network (*)Redundant Single Mode or Multi-Mode FO Converter:One 100 BASE-FX, Single Mode or Multi-mode port withLC Connector.Fiber Optic control network Includes: FO to Copper Converter(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode50/125-micron core/cladding diameters (OM2) or Single mode9/125-micron cableExample Layout and Installed DeltaV CHARM Equipment (*)This field enclosure has space for 60 CHARM I/Ochannels, including: 1 x

your DeltaV system. Before delivery, each field enclosure undergoes a full in-house inspection and test, to assure that it is fully operational before leaving the factory. Electronic Marshalling eliminates the need for custom designs. These enclosures can be ordered, together with the D

Related Documents:

HP G62x-400 CTO, HP G72, HP Pavilion dv5t-2100 CTO, HP Pavilion dv6t-4000 CTO, HP Pavilion dv6t-6000 CTO, HP Pavilion dv7-1400, HP Pavilion dv7t-5000CTO, HP Pavilion dv7t-6000 CTO, HP Pavilion g4, HP Pavilion g4t-1000 CTO, HP Pavilion g4t-1100 CTO, HP Pavilion g6-1a00, HP Pavilion g7, HP Pavilion g7t-1000 CTO

00005 / colori 05 / colours pag. 04 charm brown pag. 10 charm white pag. 16 charm walnut pag. 22 charm taupe pag. 28 charm honey il fascino discreto e accogliente del legno È l'ispirazione stilistica di charm, la nuova collezione

Universal LPG BGB36-BQar-l DCs aa BGB48-BQr-l DCs aa BGB48-BQar-l DCs aa Natural gas BGB36-BQar-N DCs aa BGB48-BQr-N DCs aa Finish 304 grade stainless

– Pain, fatigue, Skin and lymphatic bends DCS Type II – Neurologic or spinal cord Pulmonary DCS “chokes” Vestibular DCS DCS Type III DCS - Time to onset of symptoms PERCENT CASES 50 85 95 1 TIME TO ONSET 30 minutes of surfacing 1 hour of surfacing 3 hours of surfacing delayed 6 hours DCS - Sport Divers SYMPTOMS FREQUENCY joint .

I/O configuration. CTO Cabinets are designed to meet local building code and industry best practices to deliver proven functionality with minimal costs. Product Description The CTO DCS Traditional IO Cabinets offering comprises a range of pre- engineered solutions based on industry standard, preinstalled with controller and 8-wide carriers.

– Emerson DeltaV DCS and SIS systems were used – The DeltaV - SPI Interface was proposed for the Project – Primary I/O was . CHAR. acterization . M. odule (CHARM) I/O – Project Configuration of CHARM I/O employed: Standardized Remote CHARM Field Encl

The Department for Correctional Services (DCS) - Offering career opportunities that are challenging, demanding and rewarding ABOUT DCS DCS employs more than 1900 people and is a part of the South Australian Government’s Justice System. DCS contributes to the administration of justice and community protection through management of prisoners in the

runout inspection according to DIN 3960/62 or AGMA 2000 (or other standards), the exact measurement and determination of the APEX point of herringbone gears, with a comprehensive evaluation software package, en-sures a final quality certification. KAPP NILES Callenberger Str. 52 96450 Coburg, Germany Phone: 49 9561 866-0 Fax: 49 9561 866-1003 E-Mail: info@kapp-niles.com Internet: www.kapp .