Tranquility Compact (TC) SeriesSubmittal DataModels TCH/V006 - 060 60Hz - HFC-410ALC405Rev.: Septmeber 27, 2021ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.

Table of ContentsTC Compact Packaged SeriesUnit FeaturesiGate Communicating ControlsConstant Volume ECM ControlSelection ProcedureTC Series NomenclaturePerformance Data – ASHRAE/AHRI/ISO 13256-1Performance Data – Selection NotesPerformance Data – TC H/V 006 (PSC Blower)Performance Data – TC H/V 006 (ECM Blower)Performance Data – TC H/V 009 (PSC Blower)Performance Data – TC H/V 009 (ECM Blower)Performance Data – TC H/V 012 (PSC Blower)Performance Data – TC H/V 012 (ECM Blower)Performance Data – TC H/V 015 (PSC Blower)Performance Data – TC H/V 015 (ECM Blower)Performance Data – TC H/V 018 (PSC Blower)Performance Data – TC H/V 018 (ECM Blower)Performance Data – TC H/V 024 (PSC Blower)Performance Data – TC H/V 024 (ECM Blower)Performance Data – TC H/V 030 (PSC Blower)Performance Data – TC H/V 030 (ECM Blower)Performance Data – TC H/V 036 (PSC Blower)Performance Data – TC H/V 036 (ECM Blower)Performance Data – TC H/V 041 (PSC Blower)Performance Data – TC H/V 042 (PSC Blower)Performance Data – TC H/V 042 (ECM Blower)Performance Data – TC H/V 048 (PSC Blower)Performance Data – TC H/V 048 (ECM Blower)Performance Data – TC H/V 060 (PSC Blower)Performance Data – TC H/V 060 (ECM Blower)Performance Correction Tables for UnitsAntifreeze Correction TableBlower Performance Data – TC006Blower Performance Data – TC009Blower Performance Data – TC012Blower Performance Data – TC015 23334353638394041Document page number is shown next to part number (e.g. LC405 - 3 page 3). Since not all pages are typically used inthe submittals process, the page number in the lower right corner can still be used (page of ).ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 2Page of

Table of ContentsTC Compact Packaged SeriesBlower Performance Data – TC018Blower Performance Data – TC024Blower Performance Data – TC030Blower Performance Data – TC036Blower Performance Data – TC041Blower Performance Data – TC042Blower Performance Data – TC048Blower Performance Data – TC060Waterside Economizer DataAirside PDWaterside Economizer Correction TablesPhysical DataTC - Horizontal – Dimensional DataTCH - with Waterside Economizer - Dimensional DataTC - Horizontal Service AccessTC - Vertical Upflow – Dimensional DataTCV - with Waterside Economizer - Dimensional DataTC - Vertical Service AccessCorner Weights for TCH Series UnitsElectrical Data – Standard UnitElectrical Data – High Static BlowerElectrical Data – Constant Torque ECMElectrical Data – Constant Volume ECMTC Series Wiring Diagram MatrixEngineering SpecificationsPerformance SheetRevision 97071728284ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 3Page of

Unit FeaturesTHE Tranquility 16 COMPACT(TC) SERIESUNIT FEATURESThe award winning Tranquility 16 Series raises thebar for water-source heat pump efficiencies, featuresand application flexibility. Not only does the Tranquility16 exceed ASHRAE 90.1 efficiencies, but it also usesEarthPure HFC-410A zero ozone depletion refrigerant,making it an extremely environmentally-friendly option.Tranquility 16 is eligible for LEED (Leadership in Energyand Environmental Design) points because of the “green”technology design. With one of the smallest cabinets in theindustry, the Tranquility 16 will easily fit into tight spaces.Designed to be backward compatible with thousands ofolder water-source heat pumps, the Tranquility 16 CompactSeries heat pump is packed full of the innovation you havecome to expect from the experts at ClimateMaster.Available in sizes from 1/2 ton (1.76 kW) through 5 tons(17.6 kW) with multiple cabinet options (vertical upflow andhorizontal) the Tranquility 16 offers a wide range of units formost any application.ClimateMaster’s exclusive double isolation compressormounting system makes the Tranquility 16 one of thequietest units on the market. Compressors are mountedon specially engineered sound-tested EPDM grommetsto a heavy gauge mounting plate, which is further isolatedfrom the cabinet base with rubber grommets for maximizedvibration/sound attenuation. The easy access control boxand large access panels make installing and maintaining theunit easier than other water-source heat pumps currently inproduction, proving that a small unit can be easy to service.Options such as tin-plated air coil, DDC controls, and highefficiency pleated MERV rated air filters allow customizeddesign solutions. Optional high static fan motor expands theoperating range and helps overcome some of the challengesassociated with ductwork for retrofit installations. ECMconstant CFM or constant torque motors available forall sizes. A cupro-nickel water-coil and sound absorbingUltraQuiet package are options that make a great unit evenbetter. Optional factory installed Waterside Economizer(WSE) uses cool loop water for “free” cooling. WSE optionmeets IECC section C403.3.1 and is a requirement in manystates. Sizes 006 (1/2 ton, 1.76 kW) through 060 (5 tons, 17.6kW) EarthPure HFC-410A refrigerant Exceeds ASHRAE 90.1 efficiencies Galvanized steel construction Sound absorbing glass fiber insulation Unique double isolation compressor mounting viavibration isolating rubber grommets for quiet operation Insulated divider and separate compressor/air handlercompartments Copeland scroll compressors (rotary for size 018 andbelow) TXV metering device Microprocessor controls standard Field convertible discharge air arrangement for horizontalunits PSC three-speed fan motor Unit Performance Sentinel performance monitoringsystem Eight Safeties Standard Extended range (20 to 120 F, -6.7 to 48.9 C) capable Polymer drain panAVAILABLE OPTIONS Advanced DXM2 controls High static blowers BACnet, Modbus and Johnson N2 compatibility optionsfor DDC controls Cupro-nickel water-coil Sound absorbing UltraQuiet package Constant CFM ECM variable speed communicating motor Constant torque ECM 4 or 5 speed TAP motor Waterside Economizer (WSE) Stainless steel condensate drain pan Electrical service disconnectThe Tranquility 16 (TC) Series Water-Source Heat Pumpsare designed to meet the challenges of today’s HVACdemands with one of the most innovative products availableon the market.ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 4Page of

iGate Communicating ControlsiGate - Information gateway to monitor,control, and diagnose your systemFanTranquility 30 Digital is equipped with industry-first, iGate – Information Gateway – 2-way communicating system.iGate allows users to interact with their geothermal system inplain English. It delivers improved reliability and efficiency byprecisely controlling smart variable speed components. iGatemakes Tranquility 30 Digital series the easiest geothermalproducts to install and service.Monitor/Configure – Installers can configure Tranquility cToolTwo-Way Communication30 Digital units from the iGate communicating thermostator configuration/ diagnostic tool. This includes: Air flow, loop,water-flow option configuration, unit configuration, accessoryconfiguration, and demand reduction (optional - to limit unitoperation during peak times). Users can look up the currentsystem status: temperature sensor readings and operationalstatus of the blower and pump.Precise Control – The new DXM2 board enables intelligent,2-way communication between the DXM2 board and smartcomponents like the communicating thermostat, fan motor,and water pump. The DXM2 board can also directly controlthe modulating valve and accepts various feedback/input(see figure). The Intelligent DXM2 board uses informationreceived from the smart components/sensors to preciselycontrol operation of the variable speed fan and variable speedwater pump (or modulating valve) to deliver higher efficiency,reliability and increased comfort.Diagnostics – iGate takes diagnosing geothermal unitsto the next level of simplicity, by providing a dashboard ofsystem and fault information, in plain English, on the iGatethermostat/ service tool.iGate Service Warning will alert the occupant of a fault anddisplay dealer information (if programmed), fault description,possible causes, and current system status (temperaturereadings, fan RPM, and water flow status) which may bereported to service personnel.In iGate Service Mode, the service personnel can accessfault description, possible causes, and most importantly, theconditions (temp, flow, i/o conditions, configuration) at thetime of the fault. Manual Operation mode allows the servicepersonnel to manually command operation for any of thethermostat outputs, blower speed, pump speed, or valveposition from the thermostat to help troubleshoot specificcomponents.With the iGate communicating system, users and contractorshave a gateway to system information thats never beenavailable before now.One-Way pAIRFLOW SELECTIONCFM6007508508505257004255503506030HEAT STAGE 1HEAT STAGE 2AUXILIARY HEATEMERGENCY HEATCOOL STAGE 1COOL STAGE 2COOL DEHUMID 1COOL DEHUMID 2CONTINUOUS FANHEAT OFF DELAYCOOL OFF DELAYPREVIOUSNEXTPOSSIBLE FAULT CAUSESLOW WATER COIL TEMPLOW WATER TEMP - HTGLOW WATER FLOW - HTGLOW REFRIG CHARGE - HTGINCORRECT LT1 SETTINGBAD LT1 THERMISTORPREVIOUSFAULT TEMPERATURE CONDITIONSLT1 LOW WATER TEMPHEAT 1 11:11 AM 11/14LT1 TEMPLT2 TEMPHOT WATER EWTCOMP DISCHARGELEAVING AIRLEAVING WATERENTERING WATERCONTROL limateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 5Page of

Constant Volume ECM ControlThe ECM Constant Volume (CV) blower motor (optional) iscontrolled directly by the DXM2 control board that convertsthermostat inputs and CFM settings to signals used by theECM-CV motor controller. The DXM2 control must be used tocontrol the CV ECM motor.To take full advantage of the ECM-CV motor features, acommunicating multi-stage thermostat should be used(ATC32U03C). The DXM2 control maintains a selectableoperating airflow [CFM] for each heat pump operating mode.For each operating mode there are maximum and minimumairflow limits. See the ECM-CV Blower Performance tablesfor the maximum, minimum, and default operating airflows.Airflow levels are selected using the configuration menus ofa communicating thermostat (ATC32U03C) or configuration/diagnostic tool (ACDU03C) and harness 11B0100N27).The configuration menus allow the installer to independentlyselect and adjust the operating airflow for each of theoperating modes. Airflow can be selected in 25 CFMincrements within the minimum and maximum limits shownin the ECM-CV Blower Performance Table. The bloweroperating modes include: CV ECMBlowerMotorATC CommunicatingThermostatDXM2DiagnosticToolFirst Stage Cooling (Y1 & O)Second Stage Cooling (Y1, Y2, & O)First Stage Heating (Y1)Second Stage Heating (Y1 & Y2)Fan (G with no Y1, Y2, or W)AIRFLOW SELECTIONHEAT STAGE 1HEAT STAGE 2AUXILIARY HEATEMERGENCY HEATCOOL STAGE 1COOL STAGE 2COOL DEHUMID 1COOL DEHUMID 2CONTINUOUS FANHEAT OFF DELAYCOOL OFF DELAYThe ECM-CV motor includes “soft start” and “ramp down”features. The soft start feature is a gentle increase of motorrpm at blower start up. This creates a much quieter blowerstart cycle.The ramp down feature allows the blower to slowly decreaserpm to a full stop at the end of each blower cycle. Thiscreates a much quieter end to each blower cycle and addsoverall unit efficiency. The ramp down feature is eliminatedduring an ESD (Emergency Shut Down) situation. When theDXM2 ESD input is activated, the blower and all other controloutputs are immediately 06030NEXTAirflow Configuration Screen on CommunicatingThermostat or (ACDU) Service Tool.The ramp down feature (also known as the heating or cooling“Off Delay”) is field selectable by the installer. The allowablerange is 0 to 255 seconds.1. Constant Dehumidification Mode: When thedehumidification mode is selected (via DIP switch or jumpersetting), the ECM motor will operate with a multiplierapplied to the cooling CFM settings (approx. 20-25% lowerairflow). Any time the unit is running in the cooling mode, itwill operate at the lower airflow to improve latent capacity.The “DEHUM” LED will be illuminated at all times. Heatingairflow is not affected. Note: Do not select dehumidificationmode if cooling setting is tap 1.2. Automatic (Humidistat-controlled): DehumidificationMode: When the dehumidification mode is selected (via DIPswitch) AND a humidistat is connected to terminal DH, thecooling airflow will only be reduced when the humidistatsenses that additional dehumidification is required. TheDH terminal is reverse logic. Therefore, a humidistat(not dehumidistat) is required. The “DEHUM” LED willbe illuminated only when the humidistat is calling fordehumidification mode. Heating airflow is not affected.ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 6Page of

Selection ProcedureReference CalculationsHeatingHELWT EWT GPM x ConstantLAT EAT HCCFM x1.08CoolingLWT EWT HRGPM x ConstantLAT (DB) EAT (DB) -LC TC - SCSCCFM x1.08S/T SCTCConstant 500 for water, 485 for antifreeze.Legend and Glossary of AbbreviationsBTUH BTU (British Thermal Unit) per hourMBTUH 1,000 BTU per hourTC total cooling capacity, BTUHSC sensible cooling capacity, BTUHS/T sensible to total cooling ratioLC latent cooling capacity, BTUHHC air heating capacity, BTUHCFM airflow, cubic feet/minuteESP external static pressure (inches w.g.)EAT entering air temperatureLAT leaving air temperature, FDB dry bulb temperature ( F)WB wet bulb temperature ( F)EWT entering water temperatureLWT leaving water temperature, FTD or delta T temperature TMWVWSEVFD water flow in U.S. gallons/minute waterside pressure drop (psi & ft. of hd.) total heat of extraction, BTUH total heat of rejection, BTUH total power unit input, kilowatts energy efficient ratio BTUH output/Watt input coefficient of performance BTUH output/BTUH input male pipe thread female pipe thread hot water generator (desuperheater) capacity, Mbtuh electronic commutated constant volume fan motor electronic commutated constant torque fan motor motorized water valve waterside economizer variable frequency driveConversion Table - to convert inch-pound (English) to S-I (Metric)Air FlowWater FlowEst Static PressureWater Pressure DropAirflow (L/s) CFM x 0.472Water Flow (L/s) gpm x 0.0631ESP (Pa) ESP (in of wg) x 249PD (kPa) PD (ft of hd) x 2.99ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 7Page of

Selection ProcedureStep 1 Determine the actual heating and cooling loads at thedesired dry bulb and wet bulb conditions.Step 1 Load Determination:Step 2 Obtain the following design parameters: Entering watertemperature, water flow rate in GPM, air flow in CFM,water flow pressure drop and design wet and dry bulbtemperatures. Air flow CFM should be between 300 and450 CFM per ton. Unit water pressure drop should bekept as close as possible to each other to make waterbalancing easier. Go to the appropriate tables and findthe proper indicated water flow and water temperature.Step 3 Select a unit based on total and sensible coolingconditions. Select a unit which is closest to, but no largerthan, the actual cooling load.Step 4 Enter tables at the design water flow and waterAssume we have determined that the appropriate cooling loadat the desired dry bulb 80 F and wet bulb 65 F conditions is asfollows:Total Cooling.23,700 BTUHSensible Cooling.16,500 BTUHEntering Air Temp.80 F Dry Bulb / 65 F Wet BulbStep 2 Design Conditions:Similarly, we have also obtained the following design parameters:Entering Water Temp.90 FWater Flow (Based upon 10 F rise in temp.).6.0 GPMtemperature. Read the total and sensible coolingcapacities (Note: interpolation is permissible,extrapolation is not).Air Flow.800 CFMSteps 3, 4 & 5 HP Selection:Step 5 Read the heating capacity. If it exceeds the designcriteria it is acceptable. It is quite normal for WaterSource Heat Pumps to be selected on cooling capacityonly since the heating output is usually greater than thecooling capacity.Step 6 Determine the correction factors associated with theAfter making our preliminary selection (TC024), we enter thetables at design water flow and water temperature and read TotalCooling, Sens. Cooling and Heat of Rej. capacities:Total Cooling.23,400 BTUHSensible Cooling.17,500 BTUHHeat of Rejection.30,200 BTUHvariable factors of dry bulb, wet bulb and air flow.Corrected Total Cooling tabulated total cooling x wetbulb correction x air flow correctionCorrected Sensible Cooling tabulated sensible coolingx dry bulb correction x air flow correction.Steps 6 & 7 Entering Air and Airflow Corrections:Next, we determine our correction factors.TableEnt AirAir FlowCorrectedCorrected Total Cooling 23,400 x 0.9681 x 1.0050 22,767Corrected Sens Cooling 17,500 x 1.1213 x 0.9820 19,270Step 7 Compare the corrected capacities to the loadrequirements. Normally if the capacities are within 10%of the loads, the equipment is acceptable. It is betterto undersize than oversize, as undersizing improveshumidity control, reduces sound levels and extends thelife of the equipment.Step 8 When completed, calculate water temperature riseExample Equipment Selection For Coolingand assess the selection. If the units selected are notwithin 10% of the load calculations, then review whateffect changing the GPM, water temperature and/or airflow and air temperature would have on the correctedcapacities. If the desired capacity cannot be achieved,select the next larger or smaller unit and repeat theprocedure. Remember, when in doubt, undersize slightlyfor best performance.Corrected Heat of Rej. 30,200 x 0.9747 x 1.0434 30,713Step 8 Water Temperature Rise Calculationand Assessment:Actual Temperature Rise.10.2 FWhen we compare the Corrected Total Cooling and CorrectedSensible Cooling figures with our load requirements stated in Step1, we discover that our selection is within /- 10% of our sensibleload requirement. Furthermore, we see that our Corrected TotalCooling figure is within 1,000 Btuh the actual indicated load.ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 8Page of

TC Series Nomenclature12TC3H4 5 60367A8G9C1011312013A14P15BSMODEL TYPESUPPLY AIR OPTIONSTC TRANQUILITY COMPACT R410AOptionTBSV1Y1Z1K2P2W2122232CONFIGURATIONH HORIZONTALV VERTICALS STANDARDUNIT SIZE006 - E,G009 - E,G012 - E,G015 - E,G018 - E,G024 - E,F,G,H030 - E,FG,H036 - E,FG,H041 - F,G,H,N (TCV ONLY)042 - F,G,H,N048 - F,G,H,N060 - F,G,H,N12Supply CTopTCVPSC Hi StaticPSC Hi StaticTCHBackPSC Hi HNot available for sizes 006, 009, 012, 041Not available for size 041RETURN AIR OPTIONSP LEFT RETURNC RIGHT RETURNS LEFT RETURN S.S. DRAIN PANT RIGHT RETURN S.S. DRAIN PANQ FRONT RETURN S.S. DRAIN PAN and VERTICAL 009-030 AND 041 ONLYREVISION LEVELA CURRENT REVISION FOR ALL SIZESHEAT EXCHANGER OPTIONSVOLTAGEOPTIONG 208/230/60/1E 265/60/1H 208/230/60/3F 460/60/3N 575/60/3ACJN1234CONTROLSw/DISCONNECT{C CXMD DXM2N CXM w/MPCP DXM2 w/MPCR CXM w/MPCS DXM2 w/MPCYESNONOYESYESNONOYESTIN PLATEDAIR COILYESNOYESNOYESE-COATEDECON COILN/AN/AN/AN/AYESNOYESNONOYESNOWATER SIDEECONOMIZERNOYESFUTURE USE0 NONECABINET INSULATIONOPTION RANGEA CXMB DXM2COPPERCUPRO-NICKELWATER COILWATER COIL1AJK2CLM3ENP4GRSULTRAQUIETNOYESNOYES1” FILTER 2” FILTER 1” FILTER 2” ONOYESNONOYESYESNONONote: Above model nomenclature is a general reference. Not all configurations are available on all models.Consult selection software for detailed information.ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merelyClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.LC405 - 9Page of

Performance Data – ASHRAE/AHRI/ISO 13256-1ASHRAE/AHRI/ISO 13256-1. English (I-P) 30TC-036TCV-041TC-042TC-048TC-060Fan ECMPSCPSCECMPSCECMPSCECMWater Loop Heat PumpCooling 86 FHeating 68 FGround Water Heat PumpCooling 59 FHeating 50 FGround Loop Heat PumpCooling 77 FHeating 32 Cooling capacities based upon 80.6 F DB, 66.2 F WB entering air temperatureHeating capacities based upon 68 F DB, 59 F WB entering air temperatureAll ratings based upon operation at lower voltage of dual voltage rated modelsASHRAE/AHRI/ISO 13256-1. Metric (S-I) 30TC-036TCV-041TC-042TC-048TC-060Fan ECMPSCPSCECMPSCECMPSCECMWater Loop Heat PumpCooling 30 CHeating 20 CGround Water Heat PumpCooling 15 CHeating 10 CGround Loop Heat PumpFull Cooling 25 CFull Heating 0 .33.4Cooling capacities based upon 27 C DB, 19 C WB entering air temperatureHeating capacities based upon 20 C DB, 15 C WB entering air temperatureAll ratings based upon operation at lower voltage of dual voltage rated modelsClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer ServiceDepartment at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warrant

Nov 14, 2017 · ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.

Related Documents:

ClimateMaster: Declare your personal energy independence. ClimateMaster Geothermal Heating Cooling ClimateMaster Production Innovative products demand innovative manufacturing processes. ClimateMaster’s integrated production process combines every aspect of the manufacturing of our equipment into an organized, balanced, and controlled whole.File Size: 1MBPage Count: 20

CLIMATEMASTER WATER-SOURCE HEAT PUMPS TSL Vertical Stack Rev.: 09/26/2018 4 ClimateMaster Water-Source Heat Pumps TSL Model Nomenclature - Cabinet Cabinet A X X X X OPTION S.S. DRAIN PAN ENO F YES OPTION ISO PADFile Size: 1MBPage Count: 68

CLIMATEMASTER WATER-SOURCE HEAT PUMPS Packaged Units Rev.: 03 January, 2011 6 ClimateMaster Water-Source Heat Pumps Unit Physical Data Tranquility 27 Two-Stage (TT) Series (60Hz Only) Model 026 038 049 064 072 Compressor (1 Each) Two-Stage Scroll

CLIMATEMASTER WATER-SOURCE HEAT PUMPS Tranquility 20 (TS) Series Rev.: June 5, 2020 6 CliateMaster Water-Soure Heat Pus Unit Physical Data Tranquility 20 Single-Stage (TS) Series

Dream Machine ClimateMaster has designed the Tranquility 22 Digital unit with the technician in mind. From industry-exclusive vFlow, with built-in water flow components that cut down on installation time and space, to easy access panels, to refrigerant pressure ports right in the front of

TES/TEP 4 Tranquility S TES/TEP/TAH/TAC S C iGate Information gateway to monitor, control and diagnose your system The Tranquility Digital Split Units are equipped with industry-first, iGate - Information Gateway - a 2-way communicating system that allows users to interact with their geothermal system in plain English AND delivers improved reliability and efficiency by precisely

climatemaster.com 3 Tranuility 30 Digital (TE) Series IOM 60Hz HFC410A Rev. October 5, 2021 Model Nomenclature: General Overview NOTE: Above model nomenclature is a general reference. Consult individual specification sections for detailed information.

Pipe Size ASTM Designation (in) (mm) (D2310) (D2996) 2 - 6 50 - 150 RTRP 11FX RTRP 11FX-5430 8 - 16 200 - 400 RTRP 11FX RTRP 11FX-3210 Fittings 2 to 6-inch Compression-molded fiberglass reinforced epoxy elbows and tees Filament-wound and/or mitered crosses, wyes, laterals and reducers 8 to 16-inch Filament-wound fiberglass reinforced epoxy elbows Filament-wound and/or mitered crosses, wyes .