SURELIGHT Corp. 0222 L7 IGNITION SYSTEM Service

2y ago
7 Views
2 Downloads
698.23 KB
44 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Dani Mulvey
Transcription

Service LiteratureCorp. 0222 L7Revised 11 2006SURELIGHT IGNITION SYSTEMTWO STAGE IGNITION SYSTEM& TWO STAGE VARIABLE SPEED IGNITION SYSTEMI GENERALThe two stage SureLight (figure 1 )and two stage variablespeed SureLight (figure 2 ) ignition systems, consists of aLennox control board and hot surface ignitor. Both typecontrol boards are similar except the two stage variablespeed board controls an ICM2 indoor blower motor.Boards and ignitor work in combination to ensure furnaceignition and ignitor durability. Boards control all major furnace operations. Tables 1 through 4 show jack plugterminal designations.Two stage boards 18M3401 and 46M9901 featuretwoLED lights, DS1 and DS2 for troubleshooting (see table 5for diagnostic codes). The boards also have two accessory terminals rated at (1) one amp each. Terminal EACenergizes an electronic air cleaner with the indoor blower.Terminal HUM energizes the humidifier when CAI is energized on a call for heat. The SureLight board has a built inheating isolation relay. See wiring diagram for heat anticipator settings.Two stage board 100869 features a red LED light, for furnace status and troubleshooting. The LED flashes in X" Y" codes. For example using table 7 under PRESSURESWITCH CODES", if the red LED flashes 2 times, then offfor 2 seconds then flashes 3 times, the low pressureswitch is failed open. The board also has two 120 volt accessory terminals rated at (1) one amp each. In additionthere is a 24 volt humidifier terminal located on TB1.Two stage variable speed boards 18M9901 and49M5901 features two LED lights, DS1 and DS2 for troubleshooting (see table 5 for diagnostic codes) and fourLED lights (DS3, DS6, DS7 and DS8) to show furnace status (see table 6 for status codes). The boards also havetwo accessory terminals rated at (1) one amp each. Terminal EAC energizes an electronic air cleaner with theindoor blower. Terminal HUM energizes the humidifierwhen CAI is energized on a call for heat. The SureLightboard has a built in heating isolation relay. See wiring diagram for heat anticipator settings.Page 1Two stage variable speed board 100870 features a redLED light, for furnace status and troubleshooting. TheLED flashes in X" Y" codes. For example using table 7under PRESSURE SWITCH CODES", if the red LEDflashes 2 times, then off for 2 seconds then flashes 3times, the low pressure switch is failed open. Two greenLEDs show indoor blower status and CFM. See for moredetail. The board also has two 120 volt accessory terminals rated at (1) one amp each. In addition there is a 24 volthumidifier terminal located on TB1.IMPORTANTIgnition control will not operate unless unit isproperly grounded. 120V supply must beinstalled with correct polarity.ELECTROSTATIC DISCHARGE (ESD)Precautions and ProceduresCAUTIONElectrostatic discharge can affect electroniccomponents. Take precautions during furnaceinstallation and service to protect the furnace’selectronic controls. Precautions will help toavoid control exposure to electrostatic discharge by putting the furnace, the control andthe technician at the same electrostatic potential. Neutralize electrostatic charge by touchinghand and all tools on an unpainted unit surface,such as the gas valve or blower deck, before performing any service procedure.Table of ContentsI General Information . . . . . . . . . . . . . .Board Terminal Designations . . . . . . . .Board Diagnostic Codes . . . . . . . . . . . .II Operation . . . . . . . . . . . . . . . . . . . . . . .III Additional Components . . . . . . . . . .IV Diagrams . . . . . . . . . . . . . . . . . . . . . .V Troubleshooting Flowcharts . . . . . . .Page 1Page 4Page 5Page 7Page 13Page 14Page 22 2002 Lennox Industries Inc.

TWO STAGE INTEGRATED CONTROL BOARD18M3401 & 46M99011/4" QUICK CONNECT TERMINALSNEUTRALLINE 120 VACXFMR TransformewrEAC Electronic Air CleanerCIRC Indoor BlowerHUM HumidifierHOTHUM HumidifierXFMR TransformerLINE 120 VACPARK Unused LeadsCOOL Cooling SpeedEAC Electronic Air CleanerHI HEAT High Heat SpeedLO HEAT Low Heat, Low Cool, Cont. Blower SpeedLEDsDIPSWITCHES1 4E20JUMPERFLAMESENSE(120V)THERMOSTAT CONNECTIONS (TB1)JUMPER W915DIP SWITCH(ES)FUNCTION1 and 2Blower Off Delay (Heating Mode)3Second Stage ON Delay (Single stage t’stat)4Blower Off Delay (Cooling Mode)TWO STAGE INTEGRATED CONTROL BOARD100869FLAME51/4" QUICK CONNECT TERMINALSSENSE(120V)1SENSE 120 VAC OUTPUT TO FLAME SENSERNEUTRALS 120 VAC NEUTRALPARK DEAD TERMINAL FOR UNUSED BLOWER LEADHEAT LOW 120 VAC OUTPUT TO CIRC BLWR LOW HT SPEEDHEAT HIGH/ COOL LOW 120 VAC OUTPUT TO CIRC BLWR HIGH HEAT AND LOW COOL SPEEDCOOL HIGH 120 VAC OUTPUT TO CIRC BLWR HIGH COOL SPEEDDIAGNOSTICLEDsTHERMOSTAT CONNECTIONS (TB1)15DIPSWITCHESON BOARDJUMPERSFUTURE USE1 4 7 101 ERROR CODE RECALLH 24V HUMIDIFIER OUTPUT DURING HEAT DEMANDL LENNOX SYSTEM OPERATION MONITORDIP SWITCH FUNCTIONSW915W951DIP SWITCH(ES)1 2 Stage T’stat2 2nd Stage Delay3 & 4 Heat Off Delay5 Cool Off DelayFIGURE 1Page 2FUNCTIONSelects t/stat type (single or two stage)Second stage ON delay (single stage t’stat)Heating fan OFF delayCooling fan OFF delay

TWO STAGE VARIABLE SPEED INTEGRATED CONTROL BOARD18M9901 & 49M59011/4" QUICK CONNECT TERMINALSDIAGNOSTICLEDsNEUTRALLINE 120 VACXFMR TransformewrEAC Electronic Air CleanerCIRC Indoor BlowerHUM HumidifierHOTHUM HumidifierXFMR TransformerLINE 120 VACCIRC Indoor BlowerEAC Electronic Air CleanerDIPSWITCHES1 3E20JUMPERFLAME SENSOR(120V)THERMOSTAT CONNECTIONS (TB1)DS8DIPSWITCHES5 12LEDsON BOARDJUMPERW915DS7DS3LEDDS6ON BOARDJUMPER W914(cut when CCB1 orHarmony II are used)16 PIN BLOWERCONTROL TERMINALSDIP SWITCH FUNCTIONSON BOARDJUMPER W951(cut when heat pump isused with FM21)DIP SWITCH(ES)FUNCTION1 and 2Blower Off Delay3Second Stage ON Delay (Single stage t’stat)4Not used5 and 6Cooling Mode Blower Speed7 and 8Blower Speed Adjustment9 and 10Cooling Mode Blower Ramping Profile11 and 12Heating Mode Blower SpeedTWO STAGE VARIABLE SPEED INTEGRATED CONTROL BOARD1008701/4" QUICK CONNECT TERMINALSFLAMESENSE(120V)NEUTRALS 120 VAC NEUTRALTHERMOSTAT CONNECTIONS (TB1)ON 1912DIAGNOSTICLEDs5168ON1 4INDOORBLOWER DIPSWITCHESHEATINGDIPSWITCHESFUTURE USE14 7 10W915W951W914H 24V HUMIDIFIER OUTPUT DURING HEAT DEMANDL LENNOX SYSTEM OPERATION MONITOR1 ERROR RECALLON BOARDJUMPERSDIP SWITCH FUNCTIONSHTG DIP SWITCH(ES)123 and 4INDOOR BLOWERDIP SWITCH(ES)5 and 67 and 89 and 1011 and 12FIGURE 2Page 3FUNCTIONT’stat Heat Stages (single or two stage)Second Stage ON Delay (single stage t’stat)Heating Fan OFF DelayFUNCTIONCooling Mode Blower SpeedBlower Speed AdjustmentCooling Mode Blower Ramping ProfileHeating Mode Blower Speed

TABLE 1SureLight 18M3401, 46M9901, 18M9901, 49M5901TABLE 3SureLight 100869, 100870Two Stage & Two Stage Variable Speed Control12Pin Terminal DesignationTwo Stage & Two Stage Variable Speed Control12Pin Terminal DesignationPIN #FunctionPIN #Function1Gas Valve 2nd. Stage (High Fire)1Gas Valve 2nd. Stage (High Fire)2Second Stage Pressure Switch2Second Stage Pressure Switch3Not Used3Rollout In4Ground4Ground524V Hot524V Hot6Primary Limit In6Primary Limit In7Gas Valve 1st. Stage (Low Fire)7Gas Valve 1st. Stage (Low Fire)8Gas Valve Common8Gas Valve Common924V Neutral924V Neutral10Ground10Ground11Primary Limit Out11Rollout Out / Limit Out121st Stage Pressure Switch121st Stage Pressure SwitchTABLE 2All SureLight Ignition Control BoardsTABLE 4SureLight 18M9901, 49M5901, 100870Two Stage & Two Stage Variable Speed Contol5 Pin Terminal DesignationTwo Stage Variable Speed Control Board16 Pin Blower Control TerminalsPIN #Function1Ignitor2Combustion Air Inducer High SpeedPIN #Function1Ground2Low Heat Speed3Combustion Air Inducer Low Speed4Combustion Air Inducer Neutral3Ground5Ignitor Neutral4 DELAY" Dip Switch Selection5 COOL" Dip Switch SelectionPage 46 Y1" Signal7 ADJUST" Dip Switch Selection8Ground9 O" From Thermostat10 DS" Output Signal11 HEAT" Dip Switch Selection1224 VAC13HIGH HEAT Speed14 Y2" Signal15 G"16CFM LED

TABLE 5SureLight Boards 18M3401, 46M9901, 18M9901, 49M5901DIAGNOSTIC CODESDiagnostic LEDs are labeled DS1 and DS2. See figure 1for location of diagnostic LEDs.DS1DS2SIMULTANEOUSSLOW FLASHSIMULTANEOUSSLOW FLASHPower on Normal operation.Also signaled during cooling and continuous fan.SIMULTANEOUSFAST FLASHSIMULTANEOUSFAST FLASHNormal operation signaled when heating demand initiated at thermostat.SLOW FLASHONOFFSLOW FLASHLow pressure switch open;OR: Blocked inlet/exhaust vent;OR: Low pressure switch closed prior to activation of combustion air inducer.OFFFAST FLASHHigh pressure switch open;OR: Blocked inlet/exhaust vent;OR: High pressure switch closed prior to activation of combustion air inducer.ALTERNATINGSLOW FLASHALTERNATINGSLOW FLASHWatchguard burners failed to ignite; OR limit open more than 3 minutes;OR lost flame sense 5 times in one heating cycle;OR pressure switch opened 5 times in one heating cycle.SLOW FLASHOFFFlame sensed without gas valve energized.ONONOFFONOFFONCircuit board failure or control wired incorrectly. Check 24 and 115 volts to board.FAST FLASHSLOW FLASHMain power polarity reversed. Switch line and neutral.SLOW FLASHFAST FLASHLow flame signal. Measures below 0.2 microAmps. Replace flame sense rod.ALTERNATINGFAST FLASHThe following conditions are sensed during the ignitor warm up period only:1) Improper main ground;2) Broken ignitor; OR: Open ignitor circuit;3) Line voltage below 75 volts.(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting oncall from thermostat, and will not respond.ALTERNATINGFAST FLASHDESCRIPTIONPrimary, secondary or rollout limit switch open. Limits must close within 3 minutesor unit goes into 1 hour Watchguard.NOTE Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).Minimum flame sense current 0.15 0.17 microAmps.TABLE 6SureLight Boards 18M9901, 49M5901STATUS CODESSTATUS LEDCOLORFUNCTIONDS3 ON / OFF ’GREENDS3 ON indicates that the motor has a demand to operate. (This LED must be on in allmodes).DS6 CFM"GREENDS6 blinking indicates the airflow (CFM) demand in the motor. The air flow is determined bycounting blinks between two (2) second pauses. One blink equals roughly 100 CFM.DS7 HI / LO"YELLOWDS7 ON indicates the DS to R" jumper has not been cut. When the jumper is cut the systemwill be operating with LENNOX HARMONY IIt (See Harmony Installation Instructions) orwith a humidity control.Humidity control: When ON, a 24 VAC is being applied and when OFF, it has been removed.This on/off operation varies the indoor blower’s performance so dehumidification can beenhanced.DS8 HEAT"YELLOWDS8 ON indicates the system is in HEAT mode.Page 5

TABLE 7100869, 100870SureLight BoardsFLASH CODE(X Y)STATUS / ERROR DESCRIPTIONFLASH CODE DESCRIPTIONSPulseA 1/4 second flash followed by four seconds of off time.HeartbeatConstant 1/2 second bright and 1/2 second dim cycles.X YLED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for fourseconds, then repeats.PulsePower on Standby.HeartbeatNormal operation signaled when heating demand initiated at thermostat.FLAME CODES1 2Low flame current run mode.1 3Flame sensed out of sequence flame still present.2 3Low pressure switch failed open.2 4Low pressure switch failed closed.2 5High pressure switch failed open.2 6High pressure switch failed closed.2 7Low pressure switch opened during ignition trial or heating demand.3 1Limit switch open.4 1Watchguard Exceeded maximum number of retries.4 2Watchguard Exceeded maximum number of retries or last retry was due to pressure switch opening.4 3Watchguard Exceeded maximum number of retries or last retry was due to flame failure.4 5Watchguard Limit remained open longer than three minutes.4 6Watchguard Flame sensed out of sequence; flame signal gone.4 7Ignitor circuit fault Failed ignitor or triggering circuitry.4 8Low line voltage.5 1Hard lockout Rollout circuit open or previously opened.5 2Control failed self check, internal error (control will restart if error recovers).5 3No Earth ground (control will restart if error recovers).5 4Reversed line voltage polarity (control will restart if the error recovers).5 6Low secondary (24VAC) voltage.PRESSURE SWITCH CODESLIMIT CODEWATCHGUARD CODESHARD LOCKOUT CODESError Code StorageThe ignition control stores the last ten error codes inmemory. The codes are retained in case of power loss.Error Code Review1 Short R (2) to (1). Within 1/2 second, the STATUS LEDwill stay lit continuously to indicate that the short wassensed.2 Continue to hold the short between R (2) to (1). After 5seconds, STATUS LED will go from being continuouslylit to off. This indicates that error code review is pending.3 Remove R (2) to (1) short within ten seconds of STATUS LED turning off. This activates error code review.5 After final error code is indicated, STATUS LED willflash to indicate normal operation.Clearing Error Codes1 Short R (2) to (1). Within 1/2 second, the STATUS LEDwill stay lit continuously to indicate that the short wassensed.2 Continue to hold the short between R (2) to (1). After 5seconds, STATUS LED will go from being continuouslylit to off.3 Continue to hold the short between R (2) to (1) beyondten seconds after STATUS LED has turned off. STATUS LED will turn on, indicating that error codes havebeen cleared.4 Last ten error codes will be flashed on the STATUS4 Remove R (2) to (1) short. STATUS LED will flash to inLED.dicate normal operation.Page 6

II Operation (all control boards)A Two Stage Operation / ThermostatSelectionElectronic IgnitionAt the beginning of each heating cycle, the SureLight control monitors the first stage and second stage combustionair inducer prove switch. The control will not begin the heating cycle if the first stage prove switch is closed(by passed). Likewise the control will not begin the secondstage heating cycle if the second stage prove switch isclosed, and will allow first stage heat only. However if thesecond stage prove switch closes during the first stage pre purge, the control WILL respond to second stage heat call.Once the first stage prove switch is determined to be open,the combustion air inducer is energized on low (first stage)heat speed. When the differential in the prove switch isgreat enough, the prove switch closes and a 15 secondpre purge begins. If the switch is not proven within 2 1/2minutes, the control goes into Watchguard PressureSwitch mode for a 5 minute re set period.After the 15 second pre purge period, the SureLight ignitorwarms up for 20 seconds after which the gas valve opensfor a 4 second trial for ignition. The ignitor energizes duringthe trial until flame is sensed. If ignition is not proved duringthe 4 second period, the control will try four more times withan inter purge and warm up time between trials of 35 seconds. After a total of five trials for ignition (including theinitial trial), the control goes into Watchguard Flame Failure mode. After a 60 minute reset period, the control willbegin the ignition sequence again.The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition,boards 18M3401, 46M9901, 18M9901 and 49M5901 utilizes less power to energize the ignitor on successive callsfor heat. The boards continue to ramp down the voltage tothe ignitor until it finds the lowest amount of power that willprovide a successful ignition. This amount of power is usedfor 255 cycles. On the 256th call for heat, the boards againramp down until the lowest power is determined and thecycle begins again. SureLight boards 100869 and 100870regulate 95 volts to the ignitor for consistent ignition andlong ignitor life.SureLight Boards 18M3401, 46M9901, 18M9901 &49M5901Page 7The control can be utilized in two modes: SINGLE STAGEthermostat or TWO STAGE thermostat. The thermostatselection jumper E20 must be positioned for the particularapplication. The jumper is factory set on TWO" for usewith a two stage thermostat with two stage heat. Re position jumper to SINGLE" for use with a single stagethermostat with two stage heat.While in the single stage thermostat mode (single jumpersetting), the burners will always fire on first stage heat. Thecombustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a fieldselectable 10 or 15 minute delay (dip switch 3), the unit willswitch to second stage heat. While in the two stage thermostat mode (two jumper setting) the burners will fire onfirst stage heat. The combustion air inducer will operate onlow speed and indoor blower will operate on low heatspeed. The unit will switch to second stage heat on callfrom the indoor thermostat. If there is a simultaneous callfor W1 and W2 (first and second stage heat) the unit will fireon first stage heat and switch to second stage heat after 30seconds of operation. See Sequence of Operation flowcharts in the back of this manual for more detail.SureLight Boards 100869 & 100870The control can be utilized in two modes: SINGLE STAGEthermostat or TWO STAGE thermostat. The thermostatselection is made using a dip switch (figure 2 ) and must bepositioned for the particular application. The dip switch isfactory set on TWO" for use with a two stage thermostatwith two stage heat. Re position dip switch to SINGLE" foruse with a single stage thermostat with two stage heat.While in the single stage thermostat mode (single dipswitch setting), the burners will always fire on first stageheat. The combustion air inducer will operate on low speedand indoor blower will operate on low heat speed. After a10 minute recognition period, the unit will switch to secondstage heat. While in the two stage thermostat mode (twodip switch setting) the burners will fire on first stage heat.The combustion air inducer will operate on low speed andindoor blower will operate on low heat speed. The unit willswitch to second stage heat on call from the indoor thermostat. If there is a simultaneous call for first and second stageheat, the unit will fire an first stage heat and switch to second stage heat after 30 seconds of operation. SeeSequence of Operation flow charts in the back of thismanual for more detail.

Diagnostic LED’s (DS1 and DS2)Two diagnostic LED’S are located on the two stage integrated control board. See figure 1 . These light flashescorrespond with the codes detailed in table 5.B Dip Switch SettingsSureLight Boards 18M3401 & 46M9901Dip Switches 1 and 2 Heating Fan off Delay The fan ontime of 45 seconds is not adjustable. Fan off time (time thatthe blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches 1 and 2located on the SureLight integrated control. The unit isshipped with a factory fan off setting of 90 seconds. Fan offtime will affect comfort and is adjustable to satisfy individualapplications. For customized comfort, monitor the supplyair temperature once the heat demand is satisfied. Note thesupply air temperature at the instant the blower is de energized. Adjust the fan off delay to achieve a supply airtemperature between 90 110 at the instant the blower isde energized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher airtemperature). See table 8 for dip switch settings.TABLE 8Heating Fan Off DelayDelay (Seconds)Switch 1Switch 26090120180OffOffOnOnOffOnOffOnSwitch 3 Second Stage Delay (Used with Single StageThermostat Only) This switch is used to determine thesecond stage on delay when a single stage thermostat isbeing used. The switch is factory set in the ON position,which provides a 10 minute delay before second stageheat is initiated. If the switch is toggled to the OFF position,it will provide a 15 minute delay before second stage heatis initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE stagethermostat use.Switch 4 Cooling Fan off Delay The fan on delay timeof 2 seconds is not adjustable. Fan off time (time that theblower operates after the cool demand has been satisfied)can be adjusted by flipping dip switch 4. The unit is shippedwith a factory fan off setting of 45 seconds. Fan off time willaffect comfort and is adjustable to satisfy individual applications. See table 9 for cool fan off time settings.TABLE 9Cooling Fan Off DelayDelay (Seconds)Switch 42Off45OnPage 8On Board Jumper W915A factory installed jumper from Y1 to Y2 terminals on theintegrated control board terminal strip must be removed fortwo stage cooling. On board 18M3401 remove the jumper,on board 46M9901 clip the jumper.SureLight Board 100869Switch 1 Thermostat Selection This unit may be usedwith either a single stage or two stage thermostat. Thethermostat selection is made using a DIP switch whichmust be properly positioned for the particular application.TheDIP switch is factory positioned for use with a two stage thermostat. If a single stage thermostat is to be used,the DIP switch must be repositioned.a Select OFF" for two stage heating operation controlled by a two stage heating thermostat (factorysetting);b Select ON" for two stage heating operation controlled by a single stage heating thermostat. Thissetting provides a timed delay before second stageheat is initiated.Switch 2 Second Stage Delay (Used with Single Stage Thermostat Only) This switch is used todetermine the second stage on delay when a single stagethermostat is being used. The switch is factory set in theOFF position, which provides a 10 minute delay beforesecond stage heat is initiated. If the switch is toggled to theON position, it will provide a 15 minute delay before second stage heat is initiated. This switch is only activatedwhen the thermostat selector jumper is positioned forSINGLE stage thermostat use.Switches 3 and 4 Heating Blower Off Delay Theheating blower on delay of 45 seconds is not adjustable.The heating blower off delay (time that the blower operatesafter the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated controlboard. The unit is shipped from the factory with a heatingblower off delay of 90 seconds. The heating blower offdelay affects comfort and is adjustable to satisfy individualapplications. Adjust the blower off delay to achieve a supply air temperature between 90 and 110 F at the exactmoment that the blower is de energized. Longer off delaysettings provide lower supply air temperatures; shorter settings provide higher supply air temperatures.Table 10provides the blower off timings that will result from differentswitch settings.

TABLE 11Heating Blower Off Delay Switch SettingsBlower Off DelaySwitch 3Switch 4(Seconds)60OffOn90OffOff120OnOff180OnOnSwitch 5 Cooling Blower Off Delay The coolingblower off delay (time that the blower operates after thecooling demand has been satisfied) can be adjusted bymoving switch 5 on the integrated control board. Theswitch is factory set in the OFF position, which provides acooling blower off delay of 45 seconds. If the switch istoggled to the ON position, it will provide a 2 second cooling blower off delayOn Board Jumper W951On board jumper W951, which connects terminals R and Oon the integrated control board, must be cut when the furnace is installed in applications which include a heat pumpunit and a thermostat which features dual fuel use. If thejumper is left intact, terminal O" will remain energized eliminating the HEAT MODE in the heat pump.On Board Jumper W915On board jumper W915, which connects terminals Y1 andY2 on the integrated control board, must be cut if two stagecooling will be used. If the jumper is not cut the outdoor unitwill operate in second stage cooling only.Variable Speed SureLight Board 18M9901 &49M5901Dip Switch SettingsSwitches 1 and 2 Blower Off Delay The blower on delayof 45 seconds is not adjustable. The blower off delay (timethat the blower operates after the heating demand hasbeen satisfied) can be adjusted by moving switches 1 and 2on the integrated control board. The unit is shipped fromthe factory with a blower off delay of 90 seconds. Theblower off delay affects comfort and is adjustable to satisfyindividual applications. Adjust the blower off delay toachieve a supply air temperature between 90 and 110 F atthe exact moment that the blower is de energized. Longeroff delay settings provide lower supply air temperatures;shorter settings provide higher supply air temperatures.The table below provides the blower off timings that will result from different switch settings.TABLE 12Blower Off Delay Switch SettingsBlower Off DelaySwitch 1Switch 2(Seconds)60OffOff90OffOn120OnOff180OnOnPage 9Switch 3 Second Stage Delay (Used with Single StageThermostat Only) This switch is used to determine thesecond stage on delay when a single stage thermostat isbeing used. The switch is factory set in the ON position,which provides a 10 minute delay before second stageheat is initiated. If the switch is toggled to the OFF position,it will provide a 15 minute delay before second stage heatis initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE stagethermostat use.Switch 4 Not usedSwitches 5 and 6 Cooling Mode Blower SpeedSwitches 5 and 6 are used to select cooling blower motorspeed. The unit is shipped from the factory with the dipswitches positioned for high speed (4) indoor blower motoroperation during the cooling mode. Table 13 provides thecooling mode blower speeds that will result from differentswitch settings.TABLE 13Cooling Mode Blower SpeedsSpeed1 Low2 Medium Low3 Medium High4 High (Factory)Switch 5OnOffOnOffSwitch 6OnOnOffOffSwitches 7 and 8 Blower Speed Adjustment Switches7 and 8 are used to select blower speed adjustment settings. The unit is shipped from the factory with the dipswitches positioned for NORMAL (no) adjustment. The dipswitches may be positioned to adjust the blower speed by 10% or 10% to better suit the application. Table 14 provides blower speed adjustments that will result fromdifferent switch settings.TABLE 14Blower Speed AdjustmentAdjustment 10% (approx.)NORMAL (Factory) 10% (approx.)Switch 7OnOffOffSwitch 8OffOffOnSwitches 9 and 10 Cooling Mode Blower Speed Ramping Switches 9 and 10 are used to select cooling modeblower speed ramping options. Blower speed ramping maybe used to enhance dehumidification performance. Theswitches are factory set at option A which has the greatesteffect on blower motor performance. Table 15 provides thecooling mode blower speed ramping options that will resultfrom different switch settings. The cooling mode blowerspeed ramping options are detailed on Page 12.

TABLE 15Cooling Mode Blower Speed RampingRamping OptionSwitch 9Switch 10A (Factory)OffOffBOnOffCOffOnD*OnOn*Only option for DehumidificaionSwitches 11 and 12 Heating Mode Blower SpeedSwitches 11 and 12 are used to select heating mode blowermotor speed. The unit is shipped from the factory with thedip switches positioned for medium low (2) speed indoorblower motor operation during the heating mode. Table 16provides the heating mode blower speeds that will resultfrom different switch settings.TABLE 16Heating Mode Blower SpeedsSpeedSwitch 11Switch 121 LowOnOn2 Medium LowOffOn(Factory)3 Medium HighOnOff4 HighOffOffPage 10On Board Jumper W914On board jumper W914, which connects terminals DS andR on the integrated control board, must be cut when the furnace is installed with either the Harmony II zone controlboard or a humidity control. Refer to furnace Installation Instructions for more detail.On Board Jumper W915A factory installed jumper from Y1 to Y2 terminals on theintegrated control board terminal strip must be removed fortwo stage cooling. On board 18M9901 remove the jumper,on board 49M5901 clip the jumper.On Board Jumper W951On board jumper W951, which connects terminals R and Oon the integrated control board, must be cut when the furnace is installed in applications which include a heat pumpunit and the FM21 FuelMaster control board.Diagnostic LEDs (DS1 and DS2)Two diagnostic LEDs are located on the two stage, variable speed integrated control just to the left of the first bankof dip switches. These lights’ flashes correspond with diagnostic codes detailed in table 5.

Status LEDs (HEAT, HI/LO, ON/OFF and CFM)The integrated control includes four LEDs which indicateoperating status. The green ON/OFF LED is lit any time theblower is operating. The green CFM LED indicates theblower motor speed. Count the number of blinks betweenthe two second pauses to determine the CFM. Each blinkrepresents approximately 100 CFM. The yellow HI/LO LEDis lit when the W914 (DS to R) jumper has not been clippedfor CCB1 or Harmony operation. The yellow HEAT LED islit when the indoor blower is operating at the HEATINGspeed.Variable Speed SureLight Board 100870Heating Operation DIP Switch SettingsSwitch 1 Thermostat Selection This unit may be usedwith either a single stage or two stage thermostat. Thethermostat selection is made using a DIP switch whichmust be properly positioned for the particular application.TheDIP switch is factory positioned for use with a two stage thermostat. If a single stage thermostat is to be used,the DIP switch must be repositioned.a Select OFF" for two stage heating operation controlled by a two stage heating thermostat (factorysetting);b Select ON" for two stage heating operation controlled by a single stage heating thermostat. Thissetting provides a timed delay before second stageheat is initiated.Switch 2 Second Stage Delay (Used with Single Stage Thermostat Only) This switch is used todetermine the second stage on delay when a single stagethermostat is being used. The switch is factory set in theOFF position, whic

Lennox control board and hot surface ignitor. Both type control boards are similar except the two stage variable speed board controls an ICM2 indoor blower motor. Boards and ignitor work in combination to ensure furnace ignition and ignitor durability. Boards control all major fur-nace operations. Tables 1 through 4 show jack plug terminal .

Related Documents:

ohio casualty corp lam research corp unitrin inc w r grace & co new oge energy corp kerr mcgee corp lsi logic corp southwest airlines co jds uniphase corp tech data corp jabil circuit inc public service co of new mexico international multifoods corp liz claiborne inc radioshack corp kellwood co pentair inc hughes supply inc teco energy inc hub .

Spark-ignition engines with turbocharger or direct fuel injection require higher spark energies. The high voltage connection between ignition coil and spark plug must be functional and safe. This is where BERU comes in with high-quality ignition cables with suitable contacts or high-voltage ignition coil connectors. 5 OPERATION OF IGNITION

WIRING INFORMATION: 2003 Mitsubishi Montero Sport WIRE WIRE COLOR WIRE LOCATION 12V CONSTANT WIRE WHITE Ignition Harness STARTER WIRE BLACK/YELLOW or BLACK/BLUE Ignition Harness IGNITION WIRE BLACK/WHITE Ignition Harness ACCESSORY WIRE BLUE/RED Ignition Harness SECOND ACCESSORY WIRE BLUE Ignition Harness

control circuit as well as the ignition 1 and ignition 2 relays. 3 GREEN Wire: Ignition 2 Output Connect this wire to the ignition 2 wire from the ignition switch. This wire will show 12 volts when the ignition key is turned to the "ON" or "RUN" p

Ignition Using the Ignition as a template, mark the location of the mount-ing holes on the mounting . plate. Remove the ignition and drill a 1/4” hole at each marked location. Mount the ignition using 10-32 x 3/4” or 5mm x 16mm stainless steel bolts (not supplied). Ignition Coil - Not On Plate

6-Volt Ignition System with Manual Adjustment of Ignition Timing 1 - Spark Plug (candle) 2 - Distributor Rotor 3 - Breaker 4 - Secondary Winding of Ignition Coil 5 - Primary Winding of Ignition Coil 6 - Breaker Hammer 7 - Camshaft Breaker Contact 8 - Breaker Anvil 9 - Condenser (Capaci

of Ignition circuit Æ RPM/ dwell angle of Ignition circuit Æ Timing of Ignition circuit Æ Timing of Ignition circuit Æ Oscilloscope primary/secondary Æ and voltage at terminal 15/1 of Ignition coil Oscilloscope primary/secondary Æ and voltage at terminal 15/1 of Ignition coil T1/1 T1

Take-off Tests Answer key 2 Answer key 1 Fill in the gaps 1 open 6 switch 2 turn 7 clean 3 pull 8 remove 4 start 9 rotate 5 press 10 hold 2 Complete the sentences 1 must 2 must not 3 must 4 cannot/must 5 must not 6 must not 7 must not 8 can 9 must 3 Make full sentences 1 Electric tools are heavier than air tools. 2 Air tools are easier to handle than electric tools. 3 Air tools are cheaper .