form QTC2-EG1 (515)Model QTC2Air-Cooled Scroll Chillers15 – 46 TON53-162 kW60 HzR-410ALD18973a

FORM QTC2-eg1 (515)NomenclatureQTC2015TEE46XEBDESIGN SERIESX ACROSSTHE LINEREFRIGERANT R-410ADEVELOPMENTLEVELVOLTAGE CODE:17 200-3-6028 230-3-6040 380-3-6046 460-3-6058 575-3-60QUANTECH CHILLER MODEL NUMBERApprovals ASME Boiler and Pressure Vessel Code – Section Vlll Division 1. AHRI Standard 550/590. UL 1995 – Heating and Cooling Equipment ASHRAE 15 – Safety Code for Mechanical Refrigeration ASHRAE Guideline 3 – Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-ConditioningEquipment and Systems N.E.C. – National Electrical Code OSHA – Occupational Safety and Health ActProducts are produced at afacility whose qualitymanagement systems areISO9001 certified.2QUANTECH

FORM QTC2-eg1 (515)Table Of ContentsIntroduction. 5MicroComputer Control Center. 7Accessories and Options. 10Design Parameters. 13Water Pressure Drop. 14Physical Data and Nominal Ratings. 16Part Load Ratings . 18Unit Dimensions - English . 20Unit Dimensions - Metric. 34Isolator Details. 48Electrical Data - 60Hz. 52Electrical Notes. 54Circuit Breaker Calculations. 56Power Wiring. 57Control Wiring. 60Application Data. 61Guide Specifications. 64Performance data provided in this document was created in accordance with Quantech software: YW version 13.02.QUANTECH3

FORM QTC2-eg1 (515)This Page Intentionally Left Blank.4QUANTECH

FORM QTC2-eg1 (515)IntroductionQuantech is proud to present the Model QTC2 Air-Cooled Scroll Chiller.The QTC2 Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications using central station air handling or terminal units. They are completely self-contained and are designed for outdoor (roof or ground level) installation. Each unit includeshermetic scroll compressors, a liquid cooler, air-cooled condenser, a charge of refrigerantR-410A, and a weather resistant microprocessor control center, all mounted on a rugged,formed-steel base.GENERALThe 15 - 46 Ton (53 - 162 kW) QTC2 models are shipped complete from the factory readyfor installation and use.The unit is pressure-tested, evacuated, and fully charged with Refrigerant-410A and includes an initial oil charge. After assembly, a complete operational test is performed withwater flowing through the cooler to assure that the refrigeration circuit operates correctly.The unit structure is heavy-gauge, galvanized steel. The steel is coated with baked-onpowder paint, which, when subjected to ASTM B117 1000 hour, salt spray testing, yieldsa minimum ASTM 1654 rating of “6”. Corrosion resistant wire mesh panels are added toprotect the condenser coil from incidental damage and restrict unauthorized access tointernal components. Unit also includes service isolation valves as standard. Units aredesigned in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safetycode for mechanical refrigeration, ASME, listed and labeled with Intertek Testing Services(ETL) and rated in accordance with the latest version of AHRI Standard 550/590.COMPRESSORSThe chiller has suction-gas cooled, hermetic, scroll compressors. The compressors incorporate a scroll design that is compliant in both the axial and radial direction. All rotatingparts are statically and dynamically balanced. A large internal volume and oil reservoirprovides greater liquid tolerance. Compressor crankcase heaters are also included forextra protection against liquid migration.COOLERBrazed plate heat exchangers are UL (Underwriters Laboratories) listed. Installing contractor must include accommodations in the chilled water piping to allow proper drainageand venting of the heat exchanger. Water inlet and outlet connections are grooved forcompatibility with factory supplied ANSI/AWWA C-606 connections.The cooler is equipped with a heater controlled by a separate thermostat. The heaterprovides freeze protection for the cooler down to -20 F (-29 C) ambient. The cooler iscovered with 3/4” (19mm) flexible, closed-cell, foam insulation (K 0.25).QUANTECH5

FORM QTC2-eg1 (515)Introduction (Cont'd)A 40 mesh strainer (0.5 and 1.5 mm) is recommended upstream of the heat exchanger toprevent clogging.CONDENSERCoils – Fin and tube condenser coils of seamless, internally-enhanced, high-condensingcoefficient, corrosion resistant copper tubes are arranged in staggered rows, mechanically expanded into aluminum fins. Integral subcooling is included. The design workingpressure of the coil is 650 PSIG (45 barg).Low Sound Fans – The condenser fans are composed of corrosion resistant aluminumhub and composite blades molded into a low noise airfoil section. They are designed formaximum efficiency and are statically and dynamically balanced for vibration-free operation. They are directly driven, and positioned for vertical air discharge. The fan guards areconstructed of heavy-gauge, rust-resistant, PVC (polyvinyl chloride)-coated steel wire.Motors – The fan motors are Totally Enclosed Air-Over, squirrel-cage type, current protected. They feature ball bearings that are double-sealed and permanently lubricated.6QUANTECH

FORM QTC2-eg1 (515)MicroComputer Control CenterAll controls are contained in a NEMA 3R powder painted steel cabinet with a gasketeddoor and include:Liquid Crystal Display (LCD) with Light Emitting Diode (LED) backlighting for outdoorviewing: Two display lines. Twenty characters per line.Color coded 12-button non-tactile keypad with sections for: DISPLAY/PRINT of typical information: Chilled liquid temperatures Ambient temperature System pressures (each circuit) Operating hours and starts (each compressor) Print calls up to the LCD Operating data for the systems History of fault shutdown data for up to the last six fault shutdown conditionsAn RS-232 port, in conjunction with this press-to-print button, is provided to permit thecapability of hard copy print-outs via a separate printer (by others). ENTRY section to enter setpoints or modify system values. SETPOINTS updating. Chilled liquid temperature setpoint and range. Remote reset temperature range. Set daily schedule/holiday for start/stop. Manual override for servicing. Low and high ambient cutouts. Number of compressors. Low liquid temperature cutout. Low suction pressure cutout. High discharge pressure cutout.QUANTECH7

FORM QTC2-eg1 (515)MicroComputer Control Center (Cont'd) Anti-recycle timer (compressor start cycle time) Anti-coincident timer (delay compressor starts). UNIT section to: Set time. Set unit options. UNIT ON/OFF switch.The microprocessor control center is capable of displaying the following: Return and leaving liquid temperature. Low leaving liquid temperature cutout setting. Low ambient temperature cutout setting. Outdoor air temperature. English or Metric data. Suction pressure cutout setting. Each system suction pressure. Discharge pressure (optional). Liquid Temperature Reset via a Quantech ISN DDC or building automation system(by others) via: A pulse width modulated (PWM) input as standard. A 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S.interface option. Anti-recycle timer status for each system. Anti-coincident system start timer condition. Compressor run status. No cooling load condition. Day, date and time. Daily start/stop times. Holiday status. Automatic or manual system lead/lag control. Lead system definition. Compressor starts and operating hours (each compressor).8QUANTECH

FORM QTC2-eg1 (515)MicroComputer Control Center (Cont'd) Status of hot gas valves, evaporator heater and fan operation. Run permissive status. Number of compressors running. Liquid solenoid valve status. Load & unload timer status. Water pump status.QUANTECH9

FORM QTC2-eg1 (515)Accessories and OptionsAll options are factory installed unless otherwise noted.ELECTRICAL OPTIONSSingle-Point Non-Fused Disconnect Switch – Unit-mounted disconnect switch with external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied toisolate the unit power voltage for servicing. Separate external fusing must be supplied,by others in the power wiring, which must comply with the National Electrical Code and/or local codes.Single-Point Circuit Breaker – A unit mounted circuit breaker with external, lockablehandle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the powerfor servicing. (This option includes the Single-Point Power connection.)Control Transformer – Converts unit power voltage to 115-1-60 or 115-1-50 if 50Hz isselected (0.5 or 1.0 KVA capacity). Factory mounting includes primary and secondary wiring between the transformer and the control panel.CONTROL OPTIONSAmbient Kit (Low) – Standard units will operate to 25 F (-4 C). This accessory includesall necessary components to permit chiller operation to 0 F (-18 C). (This option includesthe Discharge Pressure Transducer/Readout Capability option.) For proper head pressure control in applications below 25 F (-4 C), where wind gusts may exceed five mph, itis recommended that Optional Condenser Louvered Enclosure Panels also be included.Ambient Kit (High) – Required if units are to operate when the ambient temperature isabove 110 F (43 C). Includes discharge pressure transducers. (This option includes theDischarge Pressure Transducer/ReadoutCapability option.) (Field-Mounted.)Language LCD And Keypad Display – Spanish, French, and German unit LCD controlsand keypad display available. Standard language is English.Discharge Pressure Transducers And Readout Capability – The addition of pressuretransducers allows models to sense and display discharge pressure. This is recommended for glycol chilling applications. (This option is included with either the low or high ambient kits.)Suction Pressure Transducers – Permits unit to sense and display suction pressure.This capability is standard.Motor Current Module – Capable of monitoring compressor motor current. Providesextra protection against compressor reverse rotation, phase-loss and phase imbalance.Option consists of one module per electrical system.COMPRESSOR, PIPING, EVAPORATOR OPTIONSLow Temperature Glycol – Required for glycol chilling below 30 F (-1 C) leaving glycoltemperature. Option includes resized thermal expansion valve.Chicago Code Relief Valves – Unit will be provided with relief valves to meet Chicagocode requirements.10QUANTECH

FORM QTC2-eg1 (515)Accessories and Options (Cont'd)Service Isolation Valve – Service isolation valves are standard to unit. This includes asystem high pressure relief valve or internal compressor relief mechanism in compliancewith ASHRAE 15.Hot Gas By-Pass – Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unitand operating conditions) by introducing an artificial load on the cooler. Hot gas by-passis installed on only refrigerant system #1 on two-circuit units.Flanges (ANSI/AWWA C-606 coupling) – Consists of two (2) flange adapters for groovedend pipe (standard 150 psi [10.5 barg] cooler).Flow Switch – The flow switch or its equivalent must be furnished with each unit. 150 PSIG (10.5 barg) DWP – For standard units. a vaporproof SPDT, NEMA 4Xswitch (150 PSIG [10.5 barg] DWP), -20 F to 250 F (-29 C to 121 C), with 1” NPTconnection for upright mounting in horizontal pipe will be installed. (Field-mounted.)Differential Pressure Switch – Alternative to the above mentioned flow switches. A 300psig (21 barg) maximum working pressure, SPDT 5 amp 125/250VAC switch will be installed. The range will be 3-45 PSIG (0.2-3 barg), deadband 0.5 - 0.8 psi (0.003 - 0.005barg), with 1/4” NPTE Pressure Connections.CONDENSER AND CABINET OPTIONSCondenser coil protection against corrosive environments is available by choosing anyof the following options. For additional application recommendations, contact your localQuantech office.Pre-Coated Fin Condenser Coils – The unit's coils are constructed with epoxy coatedaluminum fins. This can provide corrosion resistance comparable to copper-fin coils intypical seashore locations. Either these or the post-coated coils (below), are recommended for units being installed at the seashore or where salt spray may hit the unit.Post-Coated Dipped Condenser Coils – The unit's coils are constructed with dippedcured condenser coils. This is the choice for corrosive applications (with the exception ofstrong alkalies, oxidizers and wet bromine, chlorine and fluorine in concentrations greaterthan 100 ppm).Enclosure Panels (Unit) – Tamperproof enclosure panels prevent unauthorized accessto units. Enclosure panels can provide an aesthetically pleasing alternative to expensivefencing.Louvered Panels (Full Unit) – Louvered panels surround the front, back, and sides of theunit. They prevent unauthorized access and visually screen unit components. Unrestrictedair flow is permitted through generously sized louvered openings. This option is applicablefor any outdoor design ambient temperature up to 115 F (46 C). Recommended for usewith the Low Ambient kit where wind gusts may exceed five mph (eight kph).Ultra Quiet Fans – The chiller is equipped with specially designed fans and motors to provide lower sound levels yet retain appropriate airflow. The result is reduced fan generatedsound with minimal effect on the chiller capacity or efficiency at standard AHRI conditions.The fans are three-bladed for 60Hz and five-bladed for 50Hz.Vibration Isolators – Level adjusting, spring type 1” (25.4mm) or 2" deflection or neoprene pad isolators for mounting under unit base rails. (Field-mounted.)QUANTECH11

FORM QTC2-eg1 (515)This Page Intentionally Left Blank.12QUANTECH

FORM QTC2-eg1 (515)Design 5T020T025T030T035T040T045TLEAVING WATERTEMPERATURE ( F)MINMAX4055405540554055405540554055QTC2 ENGLISHCOOLERFLOW (GPM)MINMAX10150101501015010150402004020060300AIR ONCONDENSER ( F)MINMAX0125012501250125012501250125LEAVING WATERTEMPERATURE ( 4.412.8QTC2 SI UNITSCOOLERFLOW .818.9AIR ONCONDENSER ( 1.7-17.751.7-17.751.7NOTES:1. For leaving brine temperature below 40 F (4.4 C), contact your nearest Quantech Sales Office for application requirements.2. For leaving water temperature higher than 55 F (12.8 C), contact the nearest Quantech Sales Office forapplication guidelines.3. The evaporator is protected against freezing to -20 F (-28.8 C) with an electric heater as standard.4. For operation at temperatures below 25 F (-3.9 C), the optional Low Ambient Kit will need to be installedon the system (for QTC2040T-045T models only).5. For operation at temperatures above 115 F (46.1 C), the optional High Ambient Kit will need to be installed on the system.QUANTECH13

FORM QTC2-eg1 (515)Water Pressure Dropqtc2 english evaporator pressure drop curvewater pressure drop (psi)100A101050CB100150D200250water flow rate (gpm)LD18667Evaporator CurveABBBCDC14Chiller 40TQTC2045TQUANTECH

FORM QTC2-eg1 (515)Water Pressure Drop (Cont'd)QTC2 si evaporator pressure drop curve100Cwater pressure drop (kPa)ADB1010246810WATER FLOW RATE (l/s)Evaporator CurveABBBCDCQUANTECH121416LD18668Chiller 40TQTC2045T15

FORM QTC2-eg1 (515)Physical Data and Nominal RatingsenglishQTC2LENGTHWIDTHHEIGHTNOMINAL TONSEER (AT AHRI)IPLVNumber of Refrigerant CircuitsRefrigerant Charge, Opt, R-410A (lbs) Circuit 1/Circuit 2Oil Charge, gallons ckt1/ckt2Shipping WeightAluminum Fin Coils, lbsOperating WeightAluminum Fin Coils, lbsNoMinal COMPressor CAPACITYCompressor 1Compressor 2Compressor 3Compressor 4Compressor 5Compressor 6CONDENSERTotal Face Area ft 2Circuit 1Number of Rows DeepCircuit 2Fins per InchCondenser Fans, Low SoundCircuit 1Number of FansCircuit 2Fan Power hp/fanFan RPMTotal Chiller CFMEvaporatorWater Volume GallonsMaximum Water Side Pressure PSIGMaximum Refrig Side Pressure PSIGMinimum Chiller Water Flow GPMMaximum Chiller Water Flow GPMWater Connection Size 4504020033.53004504020033.5300450603003QUANTECH

FORM QTC2-eg1 (515)Physical Data and Nominal Ratings 0.9NoMinal KW51EER (AT AHRI)10.6IPLV15.5Number of Refrigerant Circuits1Refrigerant Charge, Opt, R-410A (kg) Circuit 1/Circuit 211.3Oil Charge, gallons Circuit 1/Circuit 26.8Shipping WeightAluminum Fin Coils, kg.659.5Operating Weight Aluminum Fin Coils, kg671.8NoMinal Compressor CapacityCompressor 128.1Compressor 228.1Compressor 3–Compressor 4–Compressor 5–Compressor 6–CondenserTotal Face Area m23.2Circuit 12Number of Rows DeepCircuit 2–Fins per Inch17Condenser Fans, Low SoundCircuit 12Number of FansCircuit 2–Fan Power kW/fan0.2Fan RPM920Total Chiller l/s5112.6EvaporatorWater Volume Liters5.5Maximum Water Side Pressure Barg20.7Maximum Refrig Side Pressure Barg31Minimum Chiller Water Flow l/s0.6Maximum Chiller Water Flow l/s9.5Water Connections Size 20.46.5816829.6030T035T040T045T3012.4 3677.9 3677.9 3779.51135.4 2301.2 2301.2 2301.212701214.1 6.716.816.2122222.7 15.9/15.9 18.1/15.9 20.4/20.48.36.8/6.8 6.8/6.8 6.4/6.4922.61334.5 1346.3 1449.7942.11345.8 1361.2 8641.7 18641.7 7313.818.9317

FORM QTC2-eg1 (515)Part Load RatingsenglishQTC2015T% DISPL.TONS1005015.49.1KW17.66.3IPLV 14.6QTC2020T% DISPL.TONS1005018.711.5KW21.57.2IPLV 15.5QTC2025T% DISPL.TONS1005025.615.7KW27.511.7IPLV 13.4QTC2030T% DISPL.TONS1005028.616.718KW29.611.2IPLV 14.5AMBENT( F)95.070.2UNITEER10.016.0AMBIENT( F)95.072.1UNITEER10.016.9AMBIENT( F)95.071.9AMBIENT( F)95.070.0UNITEER10.114.3UNITEER10.515.7QTC2035T% .6IPLV 14.4QTC2040T% .5IPLV 14.7QTC2045T% .8IPLV 15.0AMBIENT( F)95.083.369.055.0UNITEER10.112.014.917.3AMBIENT( F)95.082.969.155.0UNITEER10.212.315.217.5AMBIENT( F)95.083.469.555.0UNITEER10.212.015.219.1QUANTECH

FORM QTC2-eg1 (515)Part Load Ratings (Cont'd)siQTC2015T% DISPL.TONS1005013.07.6KW14.25.1IPLV 15.5QTC2020T% DISPL.TONS1005015.69.7KW17.65.6IPLV 17.1QTC2025T% DISPL.TONS1005021.413.1KW22.09.1IPLV 14.7QTC2030T% DISPL.TONS1005024.013.8QUANTECHKW24.08.7IPLV 15.9AMBIENT( F)95.070.2UNITEER10.617.0AMBIENT( F)95.072.0UNITEER10.318.8AMBIENT( F)95.071.6UNITEER10.815.8AMBIENT( F)95.069.6UNITEER11.117.3QTC2035T% 6IPLV 16.7QTC2040T% 6IPLV 16.8QTC2045T% .3IPLV 16.2AMBIENT( F)95.083.368.855.0UNITEER10.713.217.121.5AMBIENT( F)95.082.868.955.0UNITEER10.813.517.021.7AMBIENT( F)95.083.068.755.0UNITEER11.113.316.719.919

FORM QTC2-eg1 (515)Unit Dimensions - EnglishQTC2015T3 1/4"6 3/4"7/8" TYP.3 15/16"VIEW B-BBOTTOM OF PANELIN46 1/16"45 1/4"2 1/4"BOUT2" DIA(2) 3.0 X 1.50RIGGING HOLESBOTH ENDSB11 5/8"TO ACCESS PANEL 16 1/4"11"12 13/16"12 13/16"8 5/16"18 3/4"8 5/16"2" ANSI/AWWA C-606CONN (typ)44 5/16"BASE WIDTHLD18669LEFT ENDPOWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCKNOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictableairflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is nohigher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.20QUANTECH

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2015T9/16" DIA MOUNTING HOLES(typ)1 1/16"CONTROLCOMPRENDPANEL44 3/8"ENDEND CAPWIDTH32 1/8"6 1/8"1 1/16"YORIGIN2 1/4"TOP VIEW17"CG5"X1"9 1/16"CONTROLPANEL38 3/16"13 3/4"3 3/8"2 1/4"(2) 7.0 X 2.25FORKLIFT HOLESBOTH SIDES15 5/8"44 1/2"(2) 3.0 X 1.50RIGGING HOLESBOTH SIDES74 1/2"97 1/8"109 3/16"ZFRONT VIEWCGQUANTECHLD18670X21

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2020T3 1/4"6 3/4"7/8" TYP.3 15/16"VIEW B-BBOTTOM OF PANELIN46 1/16"45 1/4"2 1/4"BOUT2" DIA(2) 3.0 X 1.50RIGGING HOLESBOTH ENDSB11 5/8"TO ACCESS PANEL 16 1/4"11"12 13/16"12 13/16"8 5/16"18 3/4"8 5/16"2" ANSI/AWWA C-606CONN (typ)44 5/16"BASE WIDTHLEFT ENDPOWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCKLD18671NOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictableairflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is nohigher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.22QUANTECH

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2020T9/16" DIA MOUNTING HOLES(typ)1 1/16"CONTROLCOMPRENDPANEL44 3/8"ENDEND CAPWIDTH32 1/8"6 1/8"1 1/16"YORIGIN2 1/4"TOP VIEW17"CG5"X1"9 1/16"CONTROLPANEL38 3/16"13 3/4"3 3/8"2 1/4"(2) 7.0 X 2.25FORKLIFT HOLESBOTH SIDES15 5/8"44 1/2"(2) 3.0 X 1.50RIGGING HOLESBOTH SIDES74 1/2"97 1/8"109 3/16"ZFRONT VIEWCGQUANTECHLD18672X23

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2025TLD18673NOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictableairflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is nohigher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.24QUANTECH

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2025TLD18674QUANTECH25

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2030T3 1/4"6 3/4"7/8" TYP.3 15/16"VIEW B-BBOTTOM OF PANELIN2" DIA50 1/16"B(2) 3.0 X 1.50RIGGING HOLESBOTH ENDS8 1/2"BOUT49 1/4"2 1/4"15 1/2"10 3/4"TO ACCESS PANEL 13 3/8"12 13/16"12 13/16"8 5/16"2" ANSI/AWWA C-606CONN (typ)19"8 5/16"44 5/16"BASE WIDTHLD18675LEFT ENDPOWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCKNOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictableairflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is nohigher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.26QUANTECH

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2030T9/16" DIA MOUNTING HOLES(typ)1 1/16"CONTROLPANELENDCOMPREND44 3/8"END CAPWIDTH32 1/8"6 1/8"1 1/16"1 7/8"ORIGINYCG5"17"TOP VIEWX1"9"CONTROLPANEL42 1/8"17 3/4"2 1/4"3 3/8"(2) 7.0 X 2.25FORKLIFT HOLESBOTH SIDES15 5/8"50 1/2"(2) 3.0 X 1.50RIGGING HOLESBOTH SIDES80 1/2"Z105 1/16"118 5/16"CGQUANTECHXFRONT VIEWLD1867627

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2035T6 3/4"3 1/4"3 15/16"7/8" TYP.VIEW B-BBOTTOM OF PANELLIQUID INELECTRICAL ACCESSPANEL47 3/4"46 15/16"9 7/8"LIQUID OUT3" ANSI/AWWAC-606 (typ)25 1/4"15 3/4"12 5/8"45 1/8"90 1/4" BASE WIDTHLD18677LEFT ENDNOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictableairflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is nohigher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.28QUANTECH

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2035T9/16" DIA MOUNTING HOLES(typ)1 1/16"COILENDCOOLEREND90 9/16"END CAPWIDTH45 1/8"1 1/16"9 13/16"ORIGINY9 13/16"TOP VIEW16 3/4"XCG5 5/16"38"CONTROL PANEL25 3/8"BB13 5/8"ZCGQUANTECH15 1/16"TWO LIFTING HOLESBOTH SIDES13 15/16"144 13/16"XFRONT VIEWLD1867829

FORM QTC2-eg1 (515)Unit Dimensions - English (Cont'd)QTC2040T6 3/4"3 1/4"3 15/16"7/8" TYP.VIEW B-BBOTTOM OF PANELLIQUID INELECTRICAL ACCESSPANEL47 3/4"46 15/16"9 7/8"LIQUID OUT3" ANSI/AWWAC-606 (typ)45 1/8"25 1/4"15 3/4"12 5/8"LD1867990 1/4" BASE WIDTHLEFT ENDNOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting

May 20, 2015 · Quantech is proud to present the model QTC2 Air-Cooled Scroll Chiller. The QTC2 Air-Cooled Scroll Chillers provide chilled water for all air conditioning applica-tions using central station air handling or terminal units. They are completely self-con-tained and are designed for outdoo

Related Documents:

Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 80 F chilled water. MAXIMUM SERIES † Air & Water-Cooled † 1/4 to 40 Tons † 20 F to 80 F † Using Non-Ozone Depleting Refrigerants 10 ton air-cooled model 10 ton water-cooled model 2 ton water-cooled model 1 ton air-cooled model

YORK Air-Cooled Scroll Condensing Units are the perfect refrigeration components for all air conditioning applications that use DX central station air handling. They are designed for outdoor (roof or ground level) installation. Each unit includes hermetic scroll compressors, an air cooled condenser, and a weather

Air Cooled Chiller Air Air 2 Air Air 6 AIR COOLED CHILLERS Air-cooled chillers are refrigeration machines that remove heat from cooling loads using chilled water and reject this heat into the atmosphere using refrigerant. THEY ALL HAVE fans, condenser coils, and compressors. Air-cooled chillers are used to provide cooling for human comfort and electronic equipment as well as industrial process .

2.0 ton com10023 2ton rotolock scroll com11165 zr25k5e-pfv-800 2ton sweat scroll 2.5 ton com10025 2.5 ton rotolock scroll com11166 zr32k5e-pfv-800 2.5 ton sweat scroll 3.0 ton com10026 3.0 ton rotolock scroll com11167 zr38k5e-pfv-800 3.0 ton sweat scroll 3.5 ton com08153 3.5 ton sweat scroll com11

YORK AMICHI SERIES AIR-COOLED DC INVERTER SCROLL CHILLERS AND HEAT PUMPS 45-60k W Exceeding Efficiency Standards The YORK Amichi Series Air-cooled DC Inverter Scroll Chiller and Heat Pump have been designed to meet tomorrow’s efficiency standards today. Delivering performance beyond typical chiller and heat pump eff

YORK AMICHI SERIES AIR-COOLED DC INVERTER SCROLL CHILLERS AND HEAT PUMPS 44-254kW Exceeding Efficiency Standards The YORK Amichi Series Air-cooled DC Inverter Scroll Chiller and Heat Pump have been designed to meet tomorrow's efficiency standards today. Delivering performance beyond typical chiller and heat pump efficiency levels, the YORK Amichi Series

ACH Air-Cooled, Horizontal Air Flow ACV Air-Cooled, Vertical Air Flow ACR Air-Cooled Remote Condenser WCC Water-Cooled Condenser Digit 6 — Chilled Water System P Recirculating System, Tank and Pump M Single Pass Chiller Unit (no tank and pump) Digit 7 — Cabinet Type H Horizontal Low Profile V Vertical Upright

Amrit Hindi Pathmala Series Jagriti Sulekhmala Series Jagriti Hindi Vyakaran Series Semester Series General Knowledge Series Value Education Series Toddler Trot Series Story Books AUP Worksheets General Books Effective from 1st Nov 2018 School Books Price List About Happy Hour Books There is nothing more precious in this world than our children, and nothing more enjoyable than happy children .