Section 6 Fire Detection And Alarm Systems - FPA A

1y ago
2 Views
1 Downloads
4.89 MB
65 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Amalia Wilborn
Transcription

Section 6 – Fire Detection andAlarm SystemsRussell PorteousChief Executive OfficerFirewize Services

Section 6 – Fire Detection and Alarm SystemsGeneral InformationSection 6 of AS1851-2012 covers: Fire Detection and Alarms Systems Electrical Detection and Control Systems for: Special Hazards Systems; and Smoke Hazard Management Systems Smoke and Heat Alarms Emergency Warning Systems Emergency Intercom Systems Occupant Warning Systems

Section 6 – Fire Detection and Alarm SystemsPrecautions Prevent adversely affecting the normal operation of anysystem, except for those systems to be serviced. Inform responsible person on-site that activities mayadversely affect the occupants or operations of thebuilding. Inform the responsible entity of the expected duration ofthe impairment so that alternative safety arrangementscan be implemented Notify the monitoring service provider where testing orservice may cause signals to be transmitted. This could include configuring the alarmsignalling equipment to test mode and confirmnormal operation at completion

Section 6 – Fire Detection and Alarm SystemsDefinitions Impedance Distinctly Audible

Section 6 – Fire Detection and Alarm SystemsBaseline DataBaseline DataIs the capturing of system design and performance requirements. For firedetection and alarm systems it should include: Systems interface diagram A statement detailing the design Standard of the system, including dateof publication and any approved exceptions Documentation required by the approved design such ascommissioning documentation as detailed in the relevant systemdesign, installation and commissioning Standard Date of initial system installation. Cause and effect statement for each system interface function.

Section 6 – Fire Detection and Alarm SystemsBaseline DataBaseline Data (cont.) System quiescent current. System full alarm current, including warning system load. Nominal battery capacity fitted. Required battery capacity. Battery manufacture date. Installation date of fitted battery. Load current of each ancillary circuit. Amplifier rated output; impedance (Ω) and power (W). Measured impedance (Ω) and power load (W) of each loud speakercircuit.

Section 6 – Fire Detection and Alarm SystemsRoutine Service – Frequency and Table ReferencesSystem / EquipmentMonthlyFire Detection and Alarm SystemsYearly5 Yearly6.4.1.26.4.1.46.4.1.5Occupant Warning Systems6.4.1.26.4.1.46.4.1.5Special Hazards Systems – CIE6.4.1.2Smoke Hazard Systems – CIE6.4.1.26.4.1.4Emergency Warning System6.4.3.16.4.3.2Emergency Intercom Systems6 Monthly6.4.1.36.4.1.46.4.4.16.4.3.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.2Monthly RoutineService ScheduleFire Detection andAlarm System, SpecialHazard Systems andSmoke HazardManagement Systems

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.36 Monthly RoutineService ScheduleFire Detection, Alarmsand Controls for SpecialHazard Systems

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4Yearly Routine ServiceScheduleFire Detection andAlarm System, SpecialHazard Systems andSmoke HazardManagement Systems

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.4

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.55 Yearly RoutineService ScheduleFire Detection andAlarm Systems

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.5

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.5

Section 6 – Fire Detection and Alarm SystemsTable 6.4.1.5

Section 6 – Fire Detection and Alarm SystemsTable 6.4.2.26 Monthly RoutineService ScheduleSmoke Alarms and HeatAlarms

Section 6 – Fire Detection and Alarm SystemsTable 6.4.2.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.2.3Yearly Routine ServiceScheduleSmoke Alarms and HeatAlarms

Section 6 – Fire Detection and Alarm SystemsTable 6.4.2.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.2.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.1Monthly Routine ServiceScheduleEmergency WarningSystem

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.1

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.1

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.2Yearly Routine ServiceScheduleEmergency WarningSystem

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.2

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.35 Yearly Routine ServiceScheduleEmergency WarningSystem

Section 6 – Fire Detection and Alarm SystemsTable 6.4.3.3

Section 6 – Fire Detection and Alarm SystemsTable 6.4.4.1Yearly Routine ServiceScheduleEmergency IntercomSystems

Section 6 – Fire Detection and Alarm SystemsTable 6.4.4.1

Section 6 – Fire Detection and Alarm SystemsTable 6.4.4.1

Section 6 – Fire Detection and Alarm SystemsTable 6.4.4.1

Section 6 – Fire Detection and Alarm SystemsTable 6.4.4.1

Appendix F – Battery Capacity TestingDetermining Required Battery CapacityThe battery capacity requirement shall be determined as follows:a) Determine the quiescent load current (IQ).b) Determine the alarm current (IA).c) Determine the capacity de-rating factor (FC) of the battery when dischargedat the alarm load rate.

Appendix F – Battery Capacity TestingDetermining Required Battery CapacityThe battery capacity requirement shall be determined as follows (cont.):d) The 20 h discharge battery capacity C20 at 15 C to 30 C shall be determinedas follows:C20 L[(IQ TQ) FC (IA TA)]whereC20IQTQFCIATAL battery capacity in Ah at 20 h discharge rate total quiescent current quiescent standby power source time capacity de-rating factor total current in alarm state alarm load standby power source time compensation factor for expected battery deterioration.L shall be 1.25 for new batteries and 1.1 for used batteries required toperform for at least 12 months

Appendix F – Battery Capacity TestingBattery Test ProcedureThe procedure shall be as follows:a) Prior to testing, ensure the battery is fully chargedwith the correct charging voltage.b) Set the battery testers to a discharge current of 0.8 C20/1 A (e.g. A 100 Ah battery is tested at 80 A),subtracting the system quiescent current if the test isto be carried out without disconnecting the batteryfrom the system.c) Record the total load current used.d) Where the battery is to be tested without beingdisconnected from the system, isolate the primary(mains) supply just before the commencement of thebattery condition test.

Appendix F – Battery Capacity TestingBattery Test ProcedureThe procedure shall be as follows (cont ):e) Apply the test load for 25 min or until battery terminal voltage falls to theminimum test voltage of 21 V (for a 24 V battery set).NOTE: The battery load tester carries a large current and must beconnected as close as practicable to the battery terminals.f) If the battery terminal voltage does not fall below 21 V during the 25 minperiod record the final test voltage and note as a pass.g) Restore the system to allow the battery to begin to be re-charged.

Appendix G – Fire Detector TestingTest MediaSmoke detectorsa source of particulate material that does not contaminate thesensing chamber or entry screen and which contains particlesin the size range appropriate to the detector.Heat detectorsa source of heated air is the preferred medium. Thetemperature of the air shall be controlled to produce apredictable rate of increase. The upper temperature shall belimited to a value appropriate to the detector being tested.

Appendix G – Fire Detector TestingTest MediaAspirating smoke detection systemsMedia that does not excessively contaminate, impact the testresult or be of a nature that adheres to the internal surfaces ofthe aspirating smoke detector pipe system.Carbon monoxide (CO) detectorsa source of gas that does not adversely affect the sensingelement, or entry screen, of the detector and which containsgas appropriate to the detector.

Appendix G – Fire Detector TestingDetector Testing – Heat DetectorsG2 POINT TYPE HEAT DETECTOR FUNCTIONAL TEST Test 20% of detectors per circuit Test last detector on a circuit (for collective circuits, the one nearest tothe end of line device) Sample should include detectors that are representative of: all detector models and types or grades all environmental conditions all detectors are to be tested over a five year periodFor non-resettable fixed temperature detectors, simulate an alarm on thecircuit at the end of line.G3 LINEAR HEAT DETECTOR FUNCTIONAL TEST For resettable linear type heat detectors, test the operation using asuitable heat source at a random location and different locationfrom previous tests. For non-resettable fixed temperature detectors simulate an alarm on thecircuit at the end of line.

Appendix G – Fire Detector TestingDetector Testing – Point Type Smoke DetectorsG4 POINT TYPE SMOKE DETECTOR FUNCTIONAL TEST Test 50% of all detectors per annum on each circuit Ensure all detectors are tested over a two year period exceptwhere this requirement is satisfied under G5G5 POINT TYPE SMOKE DETECTOR SENSITIVITY All smoke detectors shall be replaced with cleaned and calibratedor new detectors every 10 years followed by the functional test(G4); unless the sensitivity is tested or verified in accordance withG6 or G7

Appendix G – Fire Detector TestingDetector Testing – Point Type Smoke DetectorsG6 POINT SMOKE DETECTOR IN SITU SENSITIVITY TEST Test sensitivity of all detectors in situ using test equipment listedand calibrated in accordance with a national or internationalstandard Test to be conducted after 10 years from installation and thenevery 5 years Report all detectors that fail the testG7 SMOKE DETECTORS CAPABLE OF REPORTING ‘OUT OFSENSITIVITY RANGE’ Where the sensitivity or ‘out of sensitivity range’ can be indicatedor read at either the CIE or at the detectors, carry out the relevantprocedure in accordance with the manufacturer’s instructionsyearly. Report all detectors that indicate they are at the end of themanufacturer’s sensitivity range.

Appendix G – Fire Detector TestingDetector Testing – Beam Type Smoke DetectorsG8 BEAM TYPE SMOKE DETECTORSFUNCTIONAL TEST Test yearly the operation of each linear beam type smokedetector use neutral density light filters of the appropriateobscuration percentages for alarm and beam blockage forfault.NOTE: Where information is not available on theappropriate total obscuration then, for direct beamstypes, a 60% obscuration filter should be used and forreflected beam types a 30% obscuration filter. For faults,greater than 95% obscuration (opaque) should be used.

Appendix G – Fire Detector TestingDetector Testing – Aspirating Smoke Detection SystemsG9 ASPIRATING SMOKE DETECTOR (ASD) TRANSPORTTIME TEST Test yearly by introducing smoke at the last sampling point oneach pipe run or branch Record the transport time Verify transport time is within 10% or /- 5s of the requiredtime. If not: Inspect each sampling hole and clean as needed Inspect filters Verify sensitivity Inspect pipework and all sampling pointsG10 ASPIRATING SMOKE DETECTOR SENSITIVITY TEST Verify and record that the sensitivity calibration of the detectiondevice is within 5% of the original calibration value

Appendix G – Fire Detector TestingDetector Testing – FailuresG16 CONSEQUENCES OF FAILURE When a failure occurs - further sampling and testing of not less than 10 of theremaining detectors per circuit shall be conducted until the results can be claimed tobe truly representative. If there is further failure - the balance of the detectors on the circuit shall be tested. All detectors that fail the test shall be replaced.Note: Detectors, equipment or other items that have a defined service life shall bereplaced before the service life is exceeded

Fire Alarm Monitoring SystemsFire Alarm Monitoring Systems Maintenance requirements from Part 8 of AS1851-2005 have notbeen included in AS1851-2012.

Section 6 - Fire Detection and Alarm Systems Routine Service - Frequency and Table References System / Equipment Monthly 6 Monthly Yearly 5 Yearly Fire Detection and Alarm Systems 6.4.1.2 6.4.1.4 6.4.1.5 Occupant Warning Systems 6.4.1.2 6.4.1.4 6.4.1.5 Special Hazards Systems - CIE 6.4.1.2 6.4.1.3 6.4.1.4

Related Documents:

FIRE TOPPER Fire Bowl User Manual Home » FIRE TOPPER » FIRE TOPPER Fire Bowl User Manual Contents [ hide 1 FIRE TOPPER Fire Bowl 2 Setting Up Your Fire Topper Fire Bowl 2.1 Set-Up 3 Placement and Location 3.1 Liquid Propane Tank 4 Using your Fire Topper Fire Bowl - For your safety, read before lighting. 5 Cleaning, Maintenance, Storage 6 .

comply with particularly stringent fire detection demands. Smouldering fires Open flames/ exponential development Fully developed fire Very early fire detection (High sensitivity) EN 54-20, Class A Early fire detection (increased sensitivity) EN 54-20, Class B Normal fire detection (normal sensitivity) EN 54-20, Class C/ EN 54-7

fire detection protection systems scope limited to equipments and does not cover disaster management physical evacuation etc . fire detection and protection: intro fire detection system smoke detectors fire alarm panel hooters mcp fire protection system water storage pump house hydrant line hydrant valves hose reels

social or cultural context (livelihoods, festivals, traditional, conflict) and perhaps regulatory framework (permit fires, illegal fires). The terms include fires, wildfires, wildland fire, forest fire, grass fire, scrub fire, brush fire, bush fire, veldt fire, rural fire, vegetation fire and so on (IUFRO 2018). The European Forest Fire

Fire Detection and Alarm Systems A key aspect of fire protection is to identify a developing fire emergency in a timely manner, and to alert the building's occupants and fire emergency organizations. This is the role of fire detection and alarm systems. Depending on the anticipated fire scenario, building and use type, number

2.7 UL - 268 UL Standard for Safety Smoke Detectors for Fire Alarm Systems 2.8 EN 54/22 Fire detection and fire alarm systems. Resettable line‐type heat detectors 2.9 EN 54/20 Fire detection and fire alarm systems. Aspirating Smoke detectors 2.10 IS 15519:2004 Water Mist Fire Protection Systems-System Design, Installation

The POLON 4100 fire detection and alarm control panel is designed to: 1. signal a fire occurrence detected by an interoperating fire warning devices (automatic and manual), 2. indicate a fire endangered place, 3. actuate fire protection equipment, 4. transmit a fire signal to proper services, e.g. Fire Brigades.

Building fire detection system Physical fire detection system in place at the demonstration sites and test site Event Any message sent from a system to the monitoring system (T4.5 for WP4) Fire detection system Fire detection system to be developed in T4.2 Incident An alert that has been manually raised to an