Distribution Shrink-fit Terminations Ranger2 Terminations B3 Copy .

1y ago
11 Views
2 Downloads
612.54 KB
7 Pages
Last View : 7d ago
Last Download : 3m ago
Upload by : Helen France
Transcription

A60E L A S T I M O L D/ F I S H E R P I E R C E C A B L E A C C E S S O R I E S—Distribution shrink-fit terminationsRanger2 terminations Silicone polymer housing provides superiormemory and weathering characteristics Shrink-fit housing uses common installationprocedures and cable preparation dimensions,and field-removable center core allows foreasy installation Three different shed designs for superiorweathering:- Four sheds for 15 kV outdoor model- Six sheds for 25/28 kV outdoor model- Eight sheds for 35 kV outdoor model Three sizes cover entire cable range from #2 AWGto 1250 kcmil Units accommodate popular XLP and EPR cabletypes and various shield constructions Integral Hi-K voltage stress-control tube providesuniform voltage grading over the length of thetermination and eliminates damaging voltagestress concentrations at the cable insulationshield edge Thick wall construction securely maintains criticalinterface pressure for consistent long-termreliability and performance Pull-down tabs for easy installation of built-injacket seal – Accommodate CN, JCN, tape,wire or LC shielded cable construction Lightweight, compact design installs in restrictedspaces and permits application where freehanging is desired Dark gray molded silicone insulator uses speciallyformulated silicone materials with improved UVstability, track, erosion and weather resistancefor enhanced performance under the worstenvironmental conditions Optional connectors with copper stem and onehole or two-hole spade Optional cable and support bracket with threesizes ranging from 0.80"–2.40" O.D.—Silicone polymer housingsThe R2T and R2IT terminations are manufacturedusing an optimized weather-resistant siliconeformulation. The housing offers superior cablesealing and voltage withstand characteristics.Elastimold terminations meet or exceed allrequirements of IEEE 48 for Class 1 outdoor orClass 2 indoor terminations. Unit tests includevoltage withstand wet and dry, before and afterload cycling on units installed on maximumconductor sized cable.Kit contentsEvery R2T and R2IT comes complete with housingand stress tube preassembled on the core, readyfor installation. Easy-to-read installationinstructions will take you from cable preparationthrough installation. All kits include a tube ofsilicone grease, two plastic gloves and two stripsof self-fusing silicone tape. Outdoor kits alsoinclude mastic for sealing. Metallic tape (M) kitsinclude a grounding adapter for tape shield, wireshield and unishield cables. LC shield (L) kitsinclude a high ampacity grounding adapter forlongitudinally corrugated shield, tape shield andwire over tape shield cables.

A61EL A STIMOLD UNDERGROUND C ABLE ACCESSORIES—Distribution shrink-fit terminationsRanger2 terminations—Stress relief—CertifiedThe R2T and R2IT terminations provide electricstress control for the cable by means of a flexibletube with a high permittivity dielectric constant.Elastimold Ranger2 terminations have beendesigned and tested per applicable portionsof ANSI, IEEE, AEIC, ICEA and other industrystandards.The stress-relief tube is preassembled on the coreunder the polymer housing. As the core is removed,the stress-relief tube and housing shrink onto thecable at the same time, in exactly the rightposition. No secondary operations are requiredduring installation. The electrical fields arerefracted through the high dielectric constanttube and housing as shown.IEEE 48Standard for indoor and outdoor cableterminations.ANSI C119.4Standard for cable connectors for aluminumand copper conductors.AEIC CS8-06 and ANSI/ICEA S-94-649-2004and S-97-682-2000Standards for XLP and EPR insulated cables.—InstallationStandard cable preparation techniques are usedfor all R2T Elastimold Ranger2 outdoorterminations and R2IT Elastimold Ranger2 indoorterminations. The Elastimold shrink-fitterminations are assembled on a removable core.After the termination is placed onto the preparedcable, the core is removed by pulling on the end.The housing then collapses onto the preparedcable. Memory of the material provides theinterface solid dielectric and sealing propertiesrequired to meet the electrical ratings and preventthe ingress of moisture.STRESS RELIEFSTRESS RELIEF—Voltage stressConductorConnectorSiliconetape sealTerminal housingTerminal stress reliefCable insulationConductorCable semiconductorCableinsulationGray moldedsiliconeinsulatorBuilt-in cableentrance sealCableshieldHi-k resCablejacket

A62E L A S T I M O L D/ F I S H E R P I E R C E C A B L E A C C E S S O R I E S—Distribution shrink-fit terminationsRanger2 terminations—RatingsSizes 5outdoor2, 41, 2, 41, 2, 42, 4Voltage rating (kV)151525/2835Max. design voltage to ground (kV)9.59.51622Corona extinction voltage (kV) ( 3 pC)(partial discharge)13132230110110150200–4560801 Minute dry (60 Hz) (kV)505065905 Hour dry (60 Hz) (kV)35355575DC withstand 15 min. dry R2T35outdoor1, 2, 41, 2, 42, 42, 4151525/28350468Minimum strike distance in. (mm)8.4 (213)11.6 (295)14.5 (368)16.8 (427)Creepage distance in. (mm)8.4 (213)15.0 (381)22.8 (579)30.0 (762)Insulation withstand voltage:Lightning impulse (BIL dry 110 withstand) (kV crest)10 Sec. wet (60 Hz) (kV)—Application informationIEEE 48 classificationOutdoor Class 1A, indoor Class 2Ambient temperature rangePower system frequencyAltitude rangeMounting-30 C to 65 C48 to 62 Hz3,300 feet max.Free hanging or optional bracket—DimensionsSizes available*Voltage rating (kV)Number of sheds* See page A63 for cable insulation diameter ranges.

A63EL A STIMOLD UNDERGROUND C ABLE ACCESSORIES—Distribution shrink-fit terminationsRanger2 terminationsThe R2T and R2IT termination design couplesshrink-fit technology and Elastimold’s pull-downjacket seal feature to provide a termination linethat covers the widest range of applications withthe fewest number of models. Three sizes cover0.64" (16 mm) to 2.10" (53 mm) insulation diametercables (#2 AWG through 1,250 kcmil).The R2T housings are designed for maximumperformance in all field conditions with superiorcreepage and strike distances for long-termservice. Insulating silicone sleeves are also availablewhen more creepage is required or when wildlifeprotection is needed to insulate the connectors.Contact your ABB sales representativefor further information.—Ranger2 terminations base catalog numbersCat. no.Cable range(insulation diameter)kV class151525/2835TypeConcentricneutral andjacketedconcentricneutral cableLC shield,Tape shield, wire over tapewire shield and shield and tapeunishield cableshield cableInchesmmIndoor 0.64 to 1.1216.3 to 28.4R2IT15J1R2IT15M1R2IT15L10.84 to 1.3821.3 to 35.1R2IT15J2R2IT15M2R2IT15L21.30 to 2.1033.0 to 53.3R2IT15J4R2IT15M4R2IT15L4Outdoor 0.64 to 1.1216.3 to 28.4R2T15J1R2T15M1R2T15L10.84 to 1.3821.3 to 35.1R2T15J2R2T15M2R2T15L21.30 to 2.1033.0 to 53.3R2T15J4R2T15M4R2T15L4Outdoor 0.84 to 1.3820.3 to 35.1R2T28J2R2T28M2R2T28L21.30 to 2.1033.0 to 53.3R2T28J4R2T28M4R2T28L4Outdoor 0.84 to 1.3820.03 to 35.1R2T35J2R2T35M2R2T35L21.30 to 2.1033.0 to 53.3R2T35J4R2T35M4R2T35L4

A64E L A S T I M O L D/ F I S H E R P I E R C E C A B L E A C C E S S O R I E S—Distribution shrink-fit terminationsRanger2 terminations—Ranger2 termination connector optionsTypeMaterialConductorConductor sizeConnector prefix*AluminumAluminum or copper#2–4/0(34–107)T0AluminumAluminum only#2–4/0(34–107)T1One-hole spade connectorTinned aluminumAluminum or copper#2–500(34–253)H0Two-hole spade connectorTinned aluminumAluminum or copper#2–1250(34–633)N0Tinned copperCopper#2–1250(34–633)N2Cable range (overall O.D.)Cat. no.Single clamp0.80"–1.25" (20–32 mm)JB-1B1Single clamp1.10"–1.50" (28–38 mm)JB-2B2Stem compression connector* See page A65 for conductor code.—Optional cable support bracketsStainless steelTypeSuffix numberDouble clamp1.45"–1.95" (37–50 mm)JB-3B3Double clamp1.80"–2.40" (45–61 mm)JB-4B4—Add-on grounding kitsConvert a jacketed concentric neutral “J” kit to an “M” or “L” shield kitCat. no.TypeSizeUse with seriesGMATape shield/wire shield/unishieldAR2IT15J1, R2IT15J2, R2T15J1, R2T15J2, R2T28J2, R2T35J2GMBTape shield/wire shield/unishieldBR2IT15J4, R2T15J4, R2T28J4, R2T35J4GLALC shield/wire over tape shieldAR2IT15J1, R2IT15J2, R2T15J1, R2T15J2, R2T28J2, R2T35J2GLBLC shield/wire over tape shieldBR2IT15J4, R2T15J4, R2T28J4, R2T35J4

A65EL A STIMOLD UNDERGROUND C ABLE ACCESSORIES—Distribution shrink-fit terminationsRanger2 terminations—Ordering information for Ranger2 terminationsI ndicates field that must be filled in tocomplete order. Note: Availability ofselected configuration will be verifiedat quotation time.Ranger2 terminations may be ordered incomponents or as complete kits by followingthe steps outlined and using the model below todevelop the catalog number for your application.Contact your local ABB sales representative forspecial requirements.The following diagram shows how to constructa catalog number for a Ranger2 termination.Step 1. Select the termination housing:Select outdoor or indoor(15 kV only) housing style ASelect applicable voltage class BSelect neutral/shield type CSelect the size based on the cableinsulation diameter* DConnector optionCable support bracket optionStep 2. Select the connector:Select desired connector ESelect connector code based onconductor size and conductor type FStep 3. Select the cable support bracket:Select cable support bracket basedon the overall O.D. of the cable GAdd a connectorHousing onlyTypeOutdoor R2TIndoor R2ITkV code15 kV 25/28 kV 35 kV 152835Cable typeConcentric neutral/jacketedconcentric neutral JTape shield/wire shield/unishield MLC shield tape shield/wire overtape shield LConnector typeUniversal aluminum barrelfor Al or Cu conductor withcopper wire lead #2–4/0 TOAluminum barrel for Alconductor only with copperwire lead #2–4/0 T1Aluminum 1-hole spade#2–500 kcmil HOAluminum 2-hole spade#2–1250 kcmil NOCopper 2-hole spade#2–1250 kcmil N2Insulation range0.64"–1.12"(16mm–28 mm)(15 kV only) 10.84"–1.38"(21mm–35 mm)(15 kV, 25 kV, 35 kV) 21.30"–2.10"(33mm–53 mm)(15 kV, 25 kV, 35 kV) 4* To help in selecting the proper terminator, ICEA and AEIC standarddimensions for XLP and EPR cables are on pages A50 to A52.** In 28 kV, the connector type "NO" is only for insulation range 2 and 4.Stranded orcompressed(AWG orkcmil)#2 220#1 2301/0 2402/0 2503/0 2604/0 270250 280300 290350 300400 310500 330650 360750 380900 4001000 4101250 440Connector onlyAdd a cable support bracketCompactor solid(AWG orkcmil)#2 #1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 750 900 1000 1250 ble mountingbracket materialSize PMS0.80"–1.25"(20–32 mm) B11.10"–1.50"(28–38mm) B21.45"–1.95"(37–50 mm) B31.80"–2.40"(45–61 mm) B4

A66E L A S T I M O L D/ F I S H E R P I E R C E C A B L E A C C E S S O R I E S—Distribution shrink-fit terminationsRanger2 terminations—01 Train the cable intoposition and cut tolength. Using standardpractices, cut back thecable jacket, metallicshield, semi-conductiveshield and cableinsulation, exposingthe conductor.—02 Finish preparingthe metallic shield. Forconcentric neutral orjacketed concentricneutral cables, bend backthe neutral wires and sealwith mastic strips andvinyl tape. For metallictape, drain wire, unishieldor LC shield cables: installthe ground braid usingthe constant force springand seal with masticstrips and vinyl tape.—03 Clean the exposedconductor, install andcrimp the connector.—04 Use mastic andvinyl tape to fill anygap or step betweenthe connector andthe cable insulation.Clean the cable.—05 Apply a liberal beadof silicone lubricant tothe semi-con shield step.—06 Pull the looseend of the core corduntil the core is evenwith the end of thetermination housing.—07 Position theterminator ontothe cable.—08 Shrink into placeby unwinding theremovable core.—09 Apply siliconelubricant to skirtand mastic area.—10 Fold down the skirtover the mastic to sealthe cable entrance.—11 Seal the top of theterminator at theconnector area withsilicone tape.—12 Attach the neutralwires or optionalground braid to thesystem ground perlocal code. Install theoptional cable supportbracket if required.Typical installation of Elastimold Ranger2 shrink-fit terminations (R2T – Outdoor and R2IT – Indoor)Warning: Refer to local code for required PPE.—01, 02, 03, 04—05—06—08—10—07—09—11—12

Distribution shrink-fit terminations Ranger2 terminations — Silicone polymer housings The R2T and R2IT terminations are manufactured using an optimized weather-resistant silicone formulation. The housing offers superior cable sealing and voltage withstand characteristics. Elastimold terminations meet or exceed all

Related Documents:

The project "Optimization of shrink fit in press tools" aim was to find an optimized shrink fit to obtain longer and more predictable service life of insert dies. Meanwhile the project was also aiming to evaluate the DOE module in DEFORM to see its capabilities to create and maintain press tools. The aim could be summarized as

this standard, methods are provided to enable an estimation of the range of vertical movement due to swelling and shrinkage. These estimates are based on the Shrink . 7.2.8 Correlation of Shrink Swell Index and CBR Swell .40 7.2.9 Correlation of Shrink Swell Index and Soil Suction.42 7.2.10 Correlation of Shrink Swell Index and .

The non-shrink grout pull-out tests were conducted at 24-hours and 96-hours. The results for the tests are shown in Tables 3 and 4. All of the grout samples de-bonded at strengths below the required 12,000 lbs. Table 3 - Non-shrink grout strengths at 24 hours. Non-Shrink Grout - 24 hr. pull

The Complete Guide to Shrink Film Shrink wrap film is available in a variety of types, thicknesses, clarities, strengths and shrink ratios, which can be employed alone or in conjunction with one another to create the precise type of layering and protection for your product. These options and constructions

HSPO - HEAT SHRINK TUBING Thin wall, flame retardant, 2:1 shrink ratio, flexible, crosslinked polyolefin heat shrinkable tubing. DESCRIPTION HSPO thin wall, heat shrinkable tubing is a general purpose heat shrink tubing made from a specially formulated, cross-linked polyolefin. It offers excellent electrical, chemical, and physical properties.

The United States Coast Guard (USCG) has issued Marine Safety Alert 04-21 relating to wire rope terminations. The Safety Alert addresses the importance of verifying the condition and manufacturing of wire rope terminations used in various systems that utilize wire rope in a load-handling capacity (e.g., lifesaving appliances, cranes, lifting .

R&G Unit 1, Shelley's Lane, East Worldham, Alton, Hampshire, GU34 3AQ Tel: 44 (0) 1420 89007 Fax: 44 (0) 420 87301 www.rg-racing.com Email: info@rg-racing.com Fit one length of heat-shrink (item 14) to the wires of each indicator so the heat-shrink fits over the stem of the nut/wire cover and gently heat until the heat-shrink contracts to the wiring

The themes of pilgrimage and welcome are central to The Canterbury Journey. A lasting part of its legacy will be the new free-to-enter Welcome Centre with dedicated community and exhibition spaces and viewing gallery. The journey to our new centre is underway, to open in 2019. A New Welcome In 2017, the face of the Cathedral has changed .