SoMachine Modbus TCP IOScanner - User Guide - 09/2014

1y ago
10 Views
2 Downloads
3.07 MB
80 Pages
Last View : 8d ago
Last Download : 3m ago
Upload by : Raelyn Goode
Transcription

SoMachine Modbus TCP IOScannerEIO0000001456 09/2014SoMachineModbus TCP IOScannerUser .com

The information provided in this documentation contains general descriptions and/or technicalcharacteristics of the performance of the products contained herein. This documentation is notintended as a substitute for and is not to be used for determining suitability or reliability of theseproducts for specific user applications. It is the duty of any such user or integrator to perform theappropriate and complete risk analysis, evaluation and testing of the products with respect to therelevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates orsubsidiaries shall be responsible or liable for misuse of the information contained herein. If youhave any suggestions for improvements or amendments or have found errors in this publication,please notify us.No part of this document may be reproduced in any form or by any means, electronic ormechanical, including photocopying, without express written permission of Schneider Electric.All pertinent state, regional, and local safety regulations must be observed when installing andusing this product. For reasons of safety and to help ensure compliance with documented systemdata, only the manufacturer should perform repairs to components.When devices are used for applications with technical safety requirements, the relevantinstructions must be followed.Failure to use Schneider Electric software or approved software with our hardware products mayresult in injury, harm, or improper operating results.Failure to observe this information can result in injury or equipment damage. 2014 Schneider Electric. All rights reserved.2EIO0000001949 09/2014

Table of ContentsSafety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Chapter 1 Modbus TCP IOScanner Presentation . . . . . . . . . . . . .Modbus TCP IOScanner Overview . . . . . . . . . . . . . . . . . . . . . . . . . . .Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Chapter 2 Network Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .Network Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IP Address Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Network Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Chapter 3 Modbus TCP IOScanner Configuration . . . . . . . . . . . .Adding a Slave on the Modbus TCP IOScanner . . . . . . . . . . . . . . . . .Configuring a Modbus TCP IOScanner . . . . . . . . . . . . . . . . . . . . . . . .Configuring an Advantys OTB Distributed I/O Module on the ModbusTCP IOScanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Configuring a Pre-Defined Slave on the Modbus TCP IOScanner . . .Configuring a Generic Device on the Modbus TCP IOScanner . . . . .Chapter 4 Modbus TCP IOScanner Operation. . . . . . . . . . . . . . . .Modbus TCP IOScanner Resource Verification . . . . . . . . . . . . . . . . .Modbus TCP IOScanner Operating Modes . . . . . . . . . . . . . . . . . . . . .Application Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Chapter 5 Modbus TCP IOScanner Maintenance . . . . . . . . . . . . .Diagnostics: SoMachine Online Mode. . . . . . . . . . . . . . . . . . . . . . . . .Diagnostics: Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendices.Appendix A Modbus TCP IOScanner Functions . . . . . . . . . . . . . . .IOS GETSTATE: Read the State of the Modbus TCP IOScanner . . .IOS START: Launch the Modbus TCP IOScanner. . . . . . . . . . . . . . .IOS GETHEALTH: Read the Health Bit Value . . . . . . . . . . . . . . . . . .IOS STOP: Stop the Modbus TCP IOScanner . . . . . . . . . . . . . . . . . .CONFIGURE OTB: Send the Software Configuration of the AdvantysOTB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EIO0000001949 51535556575859603

Appendix B Modbus TCP IOScanner Data Types . . . . . . . . . . . . . .IosStateCodes: Modbus TCP IOScanner Status Values . . . . . . . . . . .CommunicationErrorCodes: Error Detected Codes . . . . . . . . . . . . . . .configurationOTBErrorCodes: Error Detected Codes in the OTBConfiguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix C Function and Function Block Representation . . . . . .Differences Between a Function and a Function Block . . . . . . . . . . . .How to Use a Function or a Function Block in IL Language . . . . . . . .How to Use a Function or a Function Block in ST Language. . . . . . . .Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .463646566676869727579EIO0000001949 09/2014

Safety InformationImportant InformationNOTICERead these instructions carefully, and look at the equipment to become familiar with the devicebefore trying to install, operate, or maintain it. The following special messages may appearthroughout this documentation or on the equipment to warn of potential hazards or to call attentionto information that clarifies or simplifies a procedure.EIO0000001949 09/20145

PLEASE NOTEElectrical equipment should be installed, operated, serviced, and maintained only by qualifiedpersonnel. No responsibility is assumed by Schneider Electric for any consequences arising out ofthe use of this material.A qualified person is one who has skills and knowledge related to the construction and operationof electrical equipment and its installation, and has received safety training to recognize and avoidthe hazards involved.6EIO0000001949 09/2014

About the BookAt a GlanceDocument ScopeUse this document to:Plan your Modbus TCP IOScanner network. Install and configure your Modbus TCP IOScanner network. Operate and maintain your Modbus TCP IOScanner network. NOTE: Read and understand this document and all related documents before installing, operating,or maintaining your controller.Validity NoteThis document has been updated with the release of SoMachine V4.1 Modbus TCP IOScanneradd-on.The technical characteristics of the devices described in this manual also appear online.The characteristics that are presented in this manual should be the same as those characteristicsthat appear online. In line with our policy of constant improvement, we may revise content over timeto improve clarity and accuracy. If you see a difference between the manual and online information,use the online information as your reference.Related DocumentsTitle of DocumentationReference NumberModicon M251 Logic Controller - Programming GuideEIO0000001462 (ENG),EIO0000001463 (FRE),EIO0000001464 (GER),EIO0000001465 (SPA),EIO0000001466 (ITA),EIO0000001467 (CHS)SoMachine - Programming GuideEIO0000000067 (ENG);EIO0000000069 (FRE);EIO0000000068 (GER);EIO0000000071 (SPA);EIO0000000070 (ITA);EIO0000000072 (CHS)Essential Guide: Networks, connectivity and Web serversDIA6ED2130205EN (ENG)EIO0000001949 09/20147

You can download these technical publications and other technical information from our websiteat www.schneider-electric.com.Product Related InformationWARNINGLOSS OF CONTROL The designer of any control scheme must consider the potential failure modes of control pathsand, for certain critical control functions, provide a means to achieve a safe state during andafter a path failure. Examples of critical control functions are emergency stop and overtravelstop, power outage and restart.Separate or redundant control paths must be provided for critical control functions.System control paths may include communication links. Consideration must be given to theimplications of unanticipated transmission delays or failures of the link.Observe all accident prevention regulations and local safety guidelines.1Each implementation of this equipment must be individually and thoroughly tested for properoperation before being placed into service.Failure to follow these instructions can result in death, serious injury, or equipmentdamage.1For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for theApplication, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latestedition), "Safety Standards for Construction and Guide for Selection, Installation and Operation ofAdjustable-Speed Drive Systems" or their equivalent governing your particular location.WARNINGUNINTENDED EQUIPMENT OPERATION Only use software approved by Schneider Electric for use with this equipment.Update your application program every time you change the physical hardware configuration.Failure to follow these instructions can result in death, serious injury, or equipmentdamage.8EIO0000001949 09/2014

SoMachine Modbus TCP IOScannerPresentationEIO0000001456 09/2014Chapter 1Modbus TCP IOScanner PresentationModbus TCP IOScanner PresentationWhat Is in This Chapter?This chapter contains the following topics:TopicPageModbus TCP IOScanner Overview10Architecture12Principles14EIO0000001949 09/20149

PresentationModbus TCP IOScanner OverviewPresentationThe Modbus TCP IOScanner is a service based on Ethernet that polls slave devices continuouslyto exchange data, status, and diagnostic information. This process monitors inputs and controlsoutputs of slave devices.The Modbus TCP IOScanner relies on the Modbus TCP standard. The core of this standard is amaster/slave network model. The unique master is the controller.The communication with the slaves is accomplished using Modbus TCP channels (see page 14).Principle12345610ControllerI/O imagesApplication interface (see page 43)ApplicationModbus channels (see page 14)Slave devices (see page 14)EIO0000001949 09/2014

PresentationSystem ArchitectureThe Modbus TCP IOScanner relies on:Ethernet network including the controller, the slaves and the infrastructure equipment(see page 12), Software configuration (see page 13). Controller CompatibilityThe Modbus TCP IOScanner service is available on the TM251MESE controller.EIO0000001949 09/201411

PresentationArchitectureEthernet NetworkThis figure presents a typical Modbus TCP IOScanner architecture.1234512Controller / Modbus masterTM4ES4 used as a standalone Ethernet switchDaisy chained slavesModbus slaveI/O islandEIO0000001949 09/2014

PresentationThe controller is connected to the upper level network as well as to the device level network.The device level network is controlled by the Modbus TCP IOScanner.The controller can be used as a gateway (see page 20) between the two networks.Software ConfigurationThe network area of slaves and each I/O is configured by software: The communication configuration defines the addressing and communication periods. The device configuration defines the device behavior.Slave configuration enables variable attribution in order to optimize the monitoring.I/O configuration adjusts the monitoring quality according to the network bandwidth.You can set several parameters (see page 15) to optimize the performance.Optional ServicesThe Modbus TCP IOScanner can be associated to several optional services: DHCP: Dynamic Host Configuration Protocol server assigns an IP address to a slave devicewhen it requests one. FDR: Fast Device Replacement server configures a replaced remote device controlled by theModbus TCP IOScanner without stopping the application. Web server (see page 49).EIO0000001949 09/201413

PresentationPrinciplesOverviewThe Modbus TCP IOScanner reads inputs and writes outputs of the slave devices.The communication between Modbus TCP IOScanner and the slave devices is accomplishedusing Modbus channels.The communication in the Modbus TCP IOScanner is configured with the SoMachine software.Slaves TypesThere are three different types of Modbus TCP IOScanner slaves in the SoMachine software:Advantys OTB slave devices are used for remote digital and analog I/Os.Use SoMachine software for the specific configuration of the device and of the associated I/Omodules. Predefined slave devices are common Modbus devices coming with predefined set ofcommunication parameters.Use a dedicated software and/or a local HMI to configure the devices. With the FDT/DTMtechnology, predefined slave devices with advanced settings can be configured in SoMachine,refer to the Device Type Manager User Guide. Generic slave devices are used for all other Modbus slave devices.The entire device configuration is done with a third-party software and/or a local HMI. With theFDT/DTM technology, some devices can be configured in SoMachine, refer to the Device TypeManager User Guide. Modbus ChannelA Modbus channel carries a Modbus request between the master and a slave.Advantys OTB and predefined slave devices use one channel per device. This channel isconfigured using SoMachine software.For a generic slave device, you can use multiple channels. To send several different requests to adevice, create several channels.14EIO0000001949 09/2014

PresentationCommunication Configuration ParametersConfigure each slave in the Modbus TCP IOScanner network using SoMachine software.This table presents the communication configuration parameters:ParameterDescriptionIP addressThe IP address of the slave in the Ethernet network.Health timeoutTime value expressed in ms.If the Modbus TCP IOScanner does not detect a reply from the slave after thisdelay, an error state occurs.Repetition rateTime value expressed in ms.This represents the delay between two sendings of a request. This value mustbe lower than the Health timeout.Channel IDUnique identifier for a channel.This value is automatically created by the SoMachine software when a newchannel is added. You can read this value in the Modbus TCP ChannelConfiguration tab or, for the Advantys OTB slave, in the Modbus TCP SlaveConfiguration tab.EIO0000001949 09/201415

Presentation16EIO0000001949 09/2014

SoMachine Modbus TCP IOScannerNetwork InstallationEIO0000001456 09/2014Chapter 2Network InstallationNetwork InstallationWhat Is in This Chapter?This chapter contains the following topics:TopicPageNetwork Planning18IP Address Configuration20Network Tests23EIO0000001949 09/201417

Network InstallationNetwork PlanningPurposeA planned network increases the installation efficiency as well as decreases the installation timeand costs. The interfacing of materials (switches, cables, ports) must be preliminarily designed inorder to plan the network.Network DesignTo design and plan the Modbus TCP IOScanner network, refer to the correspondingdocumentation, such as the Media Planning and Installation Manual, by ODVA. You can downloadthis manual from the ODVA website.Switch TypesDepending on the specific needs on your network, use the appropriate switch type:If you needThen plan to useNetwork diagnostics and operation informationManageable switchesCommunication availability in case of a physical connection lossRedundant switchesLong range network (fiber optic)Switch with duplex SC connectorNOTE: Do not use a hub to set up a Modbus TCP IOScanner network.For more information about switches, refer to theEssential Guide: Networks, connectivity and Web servers.18EIO0000001949 09/2014

Network InstallationCable TypesThese tables present cable references that can be used in the network.For more information about cables, refer to theEssential Guide: Networks, connectivity and Web servers.In standard installation, you can use these cables:ReferenceDescriptionDetailsLength490NTW000 Ethernet shieldedcable for DTEconnectionsStandard cable, equipped with RJ45connectors at each end for DTE.CE compliant2, 5,12, 40, or 80 m(6.56,16.4, 39.37, 131.23,or 262.47 ft)490NTW000 UStandard cable, equipped with RJ45connectors at each end for DTE.UL compliant2, 5, 12, 40, or 80 m(6.56,16.4, 39.37, 131.23,or 262.47 ft)TCSECE3M3M S4Cable for harsh environment, equipped withRJ45 connectors at each end.CE compliant1, 2, 3, 5, or 10 m(3.28, 6.56, 9.84, 16.4,32.81 ft)TCSECU3M3M S4Cable for harsh environment, equipped withRJ45 connectors at each end.UL compliant1, 2, 3, 5, or 10 m(3.28, 6.56, 9.84, 16.4,32.81 ft)In case of fiber optic network, you can use these 5Glass fiber opticcable for DTEconnections1 SC connector1 MT-RJ connector5m(16.4 ft)1 ST connector (BFOC)1 MT-RJ connector5m(16.4 ft)490NOR000032 MT-RJ connectors3m(9.8 ft)490NOR000052 MT-RJ connectors5m(16.4 ft)490NOT00005EIO0000001949 09/201419

Network InstallationIP Address ConfigurationPrerequisitesEach device in the Modbus TCP IOScanner network obtains its own IP address. All IP addressesmust be unique.NOTE: Assign Class C IP addresses for Modbus TCP IOScanner network.Configure the IP addresses in two stages:Stage1DescriptionUsing the SoMachine software, configure the controller port supporting theModbus TCP IOScanner: IP address, Subnet mask, Default gateway.NOTE: Only use fixed addresses.NOTE: Do not use the post configuration file to address the controller ports.2Configure each slave device of the Modbus TCP IOScanner network: IP address, Subnet mask, Default gateway.Slave Address AssignmentIn the Modbus TCP IOScanner network, assign the IP address of the slaves using the followingmethod (depending on the device type): By DHCP server, to manage all the IP addresses of the Modbus TCP IOScanner network fromthe SoMachine software, or if you need the FDR service, By third-party software, or local HMI, By an advanced settings configuration on Modbus serial line, through the FDT/DTM technology,refer to the Device Type Manager User Guide.FDR ServiceSome slaves support the FDR (Fast Device Replacement) service.The FDR service stores network and operating parameters of devices on the network. If a deviceis replaced, the service automatically configures the replacement device with parameters identicalto those of the removed device.In order to configure this service in the slave, refer to the slave device documentation.20EIO0000001949 09/2014

Network InstallationSlave Master IP Address ParameterSome slaves have a Master IP address parameter so that only one, declared Master controllerhas access to the slave device.If the device.Then .Is configured to use the Modbus TCP IOScannerConfigure the Master IP address parameter insidethe device, see below.Is not configured to use the Modbus TCP IOScanner Use 0.0.0.0 for the Master IP address parameterin the device.The Master IP address parameter of the slave has to be set to the IP address of the controllersupporting the Modbus TCP IOScanner (Ethernet 2 port).To configure this parameter in the slave, refer to the slave documentation.Slave Gateway ParameterThe gateway parameter of the slaves has to be set to the IP address of the Ethernet port of thecontroller supporting the Modbus TCP IOScanner (Ethernet 2).A configuration tool has to reach the slaves in order to set their parameters.If the configuration tool.Then.Is connected on the upper level networkUpdate the slave gateway parameter, see below.Is connected on the device level networkThe gateway parameter is not used.Uses a protocol other than TCP/IPThe gateway parameter is not used.To configure this parameter in the slave, refer to the slave documentation.NOTE: If the DHCP service is used to address the slaves, the gateway parameter is set in thecontroller DHCP table.PC RoutingThe PC supporting the configuration tool must be configured in order to communicate with theslaves.If the slave is configured.Then.As a pre-defined slave through advanced settings(FDT/DTM)No specific computer parameterization is needed.Through another toolUpdate the PC routing table, see below.NOTE: The computer configuration is not altered.To update the routing table of the PC, stop every connection from the PC to the controller and/orother devices. Then, in a Windows command prompt, execute the route ADD DestinationMASK Subnet Mask Gateway command.EIO0000001949 09/201421

Network InstallationThis table represents the parameters to update in this command syntax:ParameterValueDestinationIP address of the Modbus TCP IOScanner network.Subnet MaskSubnet mask of the Modbus TCP IOScanner network.GatewayAddress of the controller port connected to the upper level network.To verify these parameters in a Windows command prompt, execute the route PRINT command.To remove this route from the PC, in a Windows command prompt, execute the route DELETEDestination command where Destination is the IP address of the Modbus TCP IOScannernetwork entered beforehand.22EIO0000001949 09/2014

Network InstallationNetwork TestsPurposeBefore operating the Modbus TCP IOScanner, test the network.Verify the following:The address configuration of each device conforms to the planning. Each device is correctly wired. Some usual testing methods are presented below.Status LEDDepending on your devices, verify that the status LEDs display a correct wiring.Verification Using a ComputerWith a computer, verify that each slave device is connected and addressed:StepAction1Connect the computer in the Modbus TCP IOScanner network.2Access the command prompt.3Use a ping xxx.xxx.xxx.xxx command to reach each slave.xxx.xxx.xxx.xxx IP address of the slave to test.NOTE: The command ping -h displays the help for the ping command.Verification Using a Web ServerWith the controller Web server, verify that the controller can communicate with each slave device:StepAction1Access the controller Web server.2Open the Ethernet Diagnostic page.3Use the Remote ping function (see page 49) on each slave device.EIO0000001949 09/201423

Network Installation24EIO0000001949 09/2014

SoMachine Modbus TCP IOScannerConfigurationEIO0000001456 09/2014Chapter 3Modbus TCP IOScanner ConfigurationModbus TCP IOScanner ConfigurationWhat Is in This Chapter?This chapter contains the following topics:TopicPageAdding a Slave on the Modbus TCP IOScanner26Configuring a Modbus TCP IOScanner27Configuring an Advantys OTB Distributed I/O Module on the Modbus TCP IOScanner29Configuring a Pre-Defined Slave on the Modbus TCP IOScanner32Configuring a Generic Device on the Modbus TCP IOScanner34EIO0000001949 09/201425

ConfigurationAdding a Slave on the Modbus TCP IOScannerOverviewThis section describes how to add a slave on the Modbus TCP IOScanner.These slaves are divided in 3 categories: Pre-defined devices for Schneider Electric Modbus devices (ATV, LXM, and ZBRN), Advantys OTB for Modbus TCP module with configurable I/Os, Generic devices for all other Modbus TCP slaves.For each generic device, you must define the Modbus requests to send to this device by addingchannels. A channel corresponds to a Modbus request and can have its own repetition rate.Add a Slave on the Modbus TCP IOScannerTo add a slave on the Modbus TCP IOScanner, select the chosen device in the HardwareCatalog, drag it to the Devices tree, and drop it on the Ethernet 2 node of the Devices tree.For more information on adding a slave to your project, refer to:Using the Drag-and-Drop Method (see SoMachine, Programming Guide) Using the Contextual Menu or Plus Button (see SoMachine, Programming Guide) 26EIO0000001949 09/2014

ConfigurationConfiguring a Modbus TCP IOScannerPrerequisitesBefore configuring the Modbus TCP IOScanner:Set the IP address of the Ethernet 2 to fixed mode. It must be different from 0.0.0.0. The connected devices must be in the same subnet as the Ethernet 2 port For more information on IP address, refer to Ethernet Configuration (see Modicon M251 LogicController, Programming Guide).Add a Modbus TCP IOScannerThe Modbus TCP IOScanner node is automatically added when a slave is added on the Ethernet2 node (see page 26).Configure a Modbus TCP IOScannerTo configure a Modbus TCP IOScanner, proceed as follows:StepAction1In the Devices tree, double-click Modbus TCP IOScanner.Result: The configuration window is displayed.2Select the IOScanner I/O Mapping tab.EIO0000001949 09/201427

ConfigurationStep3ActionSelect the Bus cycle task in the list: Use parent bus cycle setting (by default), MAST, or An existing task of the project.NOTE: The Bus cycle task parameter inside the I/O mapping editor of the device that containsthe Modbus TCP IOScanner defines the task responsible for the refresh of the I/O images(%QW, %IW). These I/O images correspond to the Modbus request sent to the Modbus slavesand the health bits.NOTE: When the Modbus TCP IOScanner is configured, the post configuration file for the Ethernet2 network is ignored.28EIO0000001949 09/2014

ConfigurationConfiguring an Advantys OTB Distributed I/O Module on the Modbus TCPIOScannerConfigure an OTB SlaveTo configure the OTB slave added on the Modbus TCP IOScanner, proceed as follows:Step1ActionIn the Devices tree, double-click the Advantys OTB device node.Result: The configuration window is displayed.2In the Slave IP Address field, enter the IP address assigned to the Advantys OTB.3Enter a Health Timeout (ms) value (by default 1000).This represents the delay (in ms) between a request of the Modbus TCP IOScanner and aresponse from the slave. When the health timeout expires, the associated health bit valueschange to 0. Health bit values can be visualized in the IOScanner I/O Mapping tab (see page 27)or through the Web server. The health timeout applies to all the channels of the slave.4Enter a Repetition Rate (ms) value (by default 20). The Health Timeout (ms) value must begreater than the Repetition Rate (ms) value.5Configure the I/Os of the Advantys OTB device in the OTB I/O Configuration tab.6Add and configure TM2 expansion modules attached to the OTB.7Call a CONFIGURE OTB function block (see page 60) to update the Advantys OTB configurationwith the data created on the previous steps.NOTE: The expert functions of the Advantys OTB such as counters, fast counters, and pulsegenerators, cannot be directly used in the Modbus TCP IOScanner.TM3 Modules CompatibilityTM3 modules are not compatible with the Advantys OTB.EIO0000001949 09/201429

ConfigurationTM2 Modules CompatibilityThis table lists the TM2 modules compatible with the Advantys OTB:30ReferenceTypeTM2AMI2HT2 analog inputsTM2AMI2LT2 analog inputsTM2AMI4LT4 analog inputsTM2AMI8HT8 analog inputsTM2ARI8HT8 analog inputsTM2ARI8LRJ8 analog inputsTM2ARI8LT8 analog inputsTM2AMO1HT1 analog outputTM2AVO2HT2 analog outputsTM2AMM3HT2 analog inputs1 analog outputTM2AMM6HT4 analog inputs2 analog outputsTM2ALM3LT2 analog inputs1 analog outputTM2DAI8DT8 digital inputsSignal type: AC typeTM2DDI8DT8 digital inputsSignal type: Sink/SourceTM2DDI16DT16 digital inputsSignal type: Sink/SourceTM2DDI16DK16 digital inputsSignal type: Sink/SourceTM2DDI32DK32 digital inputsSignal type: Sink/SourceTM2DRA8RT8 contacts in 1 common lineOutput type: relay (NO contacts)TM2DRA16RT16 contacts in 2 common linesOutput type: relay (NO contacts)TM2DDO8UT8 transistor outputs in 1 common lineSignal type: SinkTM2DDO8TT8 transistor outputs in 1 common lineSignal type: SourceTM2DDO16UK16 transistor outputs in 1 common lineSignal type: SinkEIO0000001949 09/2014

ConfigurationReferenceTypeTM2DDO16TK16 transistor outputs in 1 common lineSignal type: SourceTM2DDO32UK32 transistor outputs in 2 common linesSignal type: SinkTM2DDO32TK32 transistor outputs in 2 common linesSignal type: SourceTM2DMM8DRT4 digital inputsSignal type: Sink/Source1 common line with 4 contactsOutput type: relay (NO contacts)TM2DMM24DRF16 digital inputsSignal type: Sink/Source2 common lines with 8 contacts eachOutput type: relay (NO contacts)EIO0000001949 09/201431

ConfigurationConfiguring a Pre-Defined Slave on the Modbus TCP IOScannerConfigure a Pre-Defined Slave Added on the Modbus TCP IOScannerTo configure the pre-defined slave added on the Modbus TCP IOScanner, proceed as follows:Step32Action1In the Devices tree, double-click the added slave node.Result: The configuration window is displayed.2In the Slave IP Address, enter the IP address of the Modbus slave.3Enter a Health Timeout (ms) value (by default 1000).This represents the delay (in ms) between a request of the Modbus TCP IOScanner and aresponse from the slave. When the health timeout expires, the associated health bit valueschange to 0. Health bit values can be visualized in the IOScanner I/O Mapping tab (see page 27)or through the Web server. The health timeout applies to all the channels of the slave.4For devices with advanced settings, some additional settings can be required. Refer to theDevice Type Manager User Guide.EIO0000001949 09/2014

ConfigurationEdit the Modbus TCP ChannelTo edit Modbus channel parameters for a pre-defined slave, proceed as follows:StepAction1In the Devices tree, double-click the added slave node.2Select the Modbus TCP Channel Configuration tab and click the Edit. button.Result: The Modbus Channel window is displayed.3Enter the Repetition Rate for the channel.The repetition rate is the polling interval of the Modbus requests.4You can enter a Comment for the channel.5Click OK.EIO0000001949 09/201433

ConfigurationConfiguring a Generic Device on the Modbus TCP IOScannerOverviewTo configure a generic device added on the Modbus TCP IOScanner, complete the parameters inthese two tabs: Modbus TCP Slave Configuration IO Scanner Channel ConfigurationModbus TCP Slave Configuration TabTo configure the parameters in the Modbus TCP Slav

EIO0000001949 09/2014 7 About the Book At a Glance Document Scope Use this document to: Plan your Modbus TCP IOScanner network. Install and configure your Modbus TCP IOScanner network. Operate and maintain your Modbus TCP IOScanner network. NOTE: Read and understand this document and all relate d documents before inst alling, operating, or maintaining your controller.

Related Documents:

NP ModBus TCP N System Configuration Example 8 Add a ModBus Master Port and Node Expand the "MB NP Modbus TCP" branch on the I/O Configuration Form by clicking on the . Expand the Modbus TCP by clicking on the . Expand the "ModBus Port NP ModBus TCP Master Port" branch on the I/O Configuration Form by clicking on the . Expand the Nodes branch on the I/O Configuration Toolbox by .

Modbus TCP Ethernet EN . Version 0.14 . MODBUS TCP ETHERNET EN - V0.14 Modbus TCP Ethernet EN RapidoScan, Modbus TCP and Ethernet, EN.docx Preface . But because of the master - slave principle of Modbus a controlled polling by a master unit is necessary. Therefore, to transmit a measurement result via Modbus an additional query .

3. System description 5 3.1 Modbus 5 3.2 CIM 200 Modbus RTU 5 3.3 CIM 260 3G/4G cellular Modbus 5 3.4 CIM 500 Modbus TCP 5 4. Specifications 6 4.1 CIM module 6 4.2 CIM 200 Modbus RTU 6 4.3 CIM 260 3G/4G cellular 7 4.4 CIM 500 Modbus TCP 7 5. CIM 200 Modbus RTU setup 8 5.1 Setting the Modbus transmission speed 8 5.2 Setting the stop bits and the .

The complete Modbus TCP/IP Application Data Unit is embedded into the data field of a standard TCP frame and sent via TCP to well-known system port 502, which is specifically reserved for Modbus applications. Modbus TCP/IP clients and servers listen and receive Modbus data via port 502. We can see that the operation of Modbus over Ethernet is .

Any device that supports the Modbus TCP/IP protocol : Network media type . Ethernet : Quantity of devices you can physically connect to i-Vu Link's Ethernet port . Up to 30 Modbus TCP/IP connections. Connections could be to a Modbus TCP/IP server device or to a Modbus TCP/IP server device that is acting as a Gateway to other Modbus serial devices.

Modbus/TCP Modbus Master/Slave A Modbus master/slave network provides a protocol for data transfer and programming with a single RTU master and up to 247 slave . The Modbus/TCP KEPServer driver supports Modbus and Mailbox device models. Modbus Device Model. Publication 2711P-UM002B-EN-P - March 2007 Modbus Applications PanelView Plus

User Manual Modbus Slave / Modbus TCP Master Document code: MN67510_ENG Revision 1.012 Page 1 of 26 INDEX: Page UPDATED DOCUMENTATION 2 REVISION LIST 2 WARNING 2 TRADEMARKS 2 INDEX 3 WARRANTIES AND TECHNICAL SUPPORT 4 User Manual Revision 1.012 English Modbus Slave / Modbus TCP Master - Converter

Peninsula School District School Improvement Worksheet. version 1.0 . ELA SMART Goal Worksheet 2015-16 School: DISCOVERY ELEMENTARY Team: ELA Leaders: ALL The primary focus of our work is for all students to meet or exceed rigorous standards.