Boiler Manual - BoilerData

1y ago
4 Views
1 Downloads
2.06 MB
40 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Axel Lin
Transcription

HVX2-031322-HVX2HVXGas-Fired Residental BoilersModels 70-175Boiler ManualInstallation andOperation InstructionsThis manual is intended only for use by a qualified heating installer/technician. Read and follow this manual, all supplements and relatedinstructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in theseinstructions. Failure to do so can result in severe personal injury, death or substantial property damage.Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination ofthe burner, resulting in possible severe personal injury, death or substantial property damage. The boiler can only be operated with a dustfree air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated by operationwith contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.Affix these instructions near to the boiler/water heater. Instruct the building owner to retain the instructions for future use by a qualifiedservice technician, and to follow all guidelines in the User’s Information Manual.

TABLE OF CONTENTSTABLE OF CONTENTSUSING THIS MANUAL3A. INSTALLATION SEQUENCE . . . . . . . . . . . . .3B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .31. PREINSTALLATION4A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .4B. CLEARANCE FROM COMBUSTIBLECONSTRUCTION . . . . . . . . . . . . . . . . . . . . . .4C. AIR FOR COMBUSTION ANDVENTILATION . . . . . . . . . . . . . . . . . . . . . . . . .5D. PLANNING THE LAYOUT . . . . . . . . . . . . . . . .8E. MASSACHUSETTS INSTALLATIONS . . . . . .82. BOILER SET-UP4. VENTING13A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .13B. CHIMNEY VENTING . . . . . . . . . . . . . . . . . . .13C. DIRECT EXHAUSTHORIZONTAL VENTING- . . . . . . . . . . . . . . .13D. DIRECT EXHAUSTVERTICAL VENTING . . . . . . . . . . . . . . . . . .16E. BOILER REMOVAL FROMCOMMON VENTING SYSTEM . . . . . . . . . .1727. START-UP PROCEDURES22A. COMPLETING THE INSTALLATION . . . . . . .22B. CONTROL DESCRIPTIONS . . . . . . . . . . . . .26C. ADJUSTMENT OF GAS PRESSUREREGULATOR . . . . . . . . . . . . . . . . . . . . . . . . .26D. CHECKING BURNER INPUT . . . . . . . . . . . . .26E. CHECK-OUT PROCEDURE . . . . . . . . . . . . . .2783. WATER PIPING AND CONTROLS9A. BOILER SUPPLY AND RETURN . . . . . . . . . . .9B. SAFETY RELIEF VALVE . . . . . . . . . . . . . . . .10C. PIPING FOR ZONED SYSTEMS . . . . . . . . . .11D. EXPANSION TANK . . . . . . . . . . . . . . . . . . . .12E. INDIRECT-FIRED WATER HEATER . . . . . . . .12F. FREEZE PROTECTION . . . . . . . . . . . . . . . . .125. GAS PIPING6. ELECTRICAL20A. WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20B. ZONED SYSTEM WIRING . . . . . . . . . . . . . .20C. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . .20D. BOILER SEQUENCE OF OPERATION . . . . .22188. TROUBLESHOOTING29A. SHUT-DOWN CAUSED BY PILOT OUTAGE,PRESSURE SWITCH OR FLAME ROLL-OUTSAFETY SHUT-OFF SWITCH . . . . . . . . . . . .29B. TROUBLESHOOTING GUIDES . . . . . . . . . .29C. MEASURING SUCTION PRESSURE . . . . . .299. MAINTENANCE32A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .33B. DAILY (WITH BOILER IN USE) . . . . . . . . . . .33C. WEEKLY (WITH BOILER IN USE) . . . . . . . . .33D. MONTHLY (WITH BOILER IN USE) . . . . . . .33E. ANNUALLY (BEFORE START OF HEATINGSEASON) . . . . . . . . . . . . . . . . . . . . . . . . . . .3410. BOILER DIMENSIONS & RATINGS3511. REPAIR PARTS36A. BLOCK/BASE/FLOOR PANJACKET/FLUE COLLECTOR . . . . . . . . . . . . .36B. BASE/BURNERS/MANIFOLD . . . . . . . . . . . .38

USING THIS MANUALUSING THIS MANUALA. INSTALLATION SEQUENCEFollow the installation instructions provided in thismanual in the order shown. The order of theseinstructions has been set in order to provide the installerwith a logical sequence of steps that will minimizepotential interferences and maximize safety duringboiler installation.DANGERIndicates a condition or hazard which will causesevere personal injury, death or major propertydamage.WARNINGB. SPECIAL ATTENTION BOXESThroughout this manual you will see special attentionboxes intended to supplement the instructions and makespecial notice of potential hazards.Indicates a condition or hazard which may causesevere personal injury, death or major propertydamage.CAUTIONIndicates a condition or hazard which will or cancause minor personal injury or property damage.NOTICEIndicates special attention is needed, but not directlyrelated to potential personal injury or propertydamage.3

PREINSTALLATION1. PREINSTALLATIONRead carefully, study these instructions before beginning work.This boiler must be installed by a qualified contractor.The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.NOTICEThe equipment must be installed in accordance with those installation requirements of the authority havingjurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSIZ223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code.Where required by the authority having jurisdiction, the installation must conform to American Society ofMechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers,ANSI/ASME CSD-1.IMPORTANTIn accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with afeature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature isequipped with an override which is provided primarily to permit the use of an external energy managementsystem that serves the same function.THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE: An external energy management system is installed that reduces the boiler water temperature as theheating load decreases. This boiler is not used for any space heating This boiler is part of a modular or multiple boiler system having a total input of 300,000BTU/hr or greater. This boiler is equipped with a tankless coil.A. ACCESSIBILITY CLEARANCESInstall boiler not less than 24″ (610 mm) between the leftside, top, and front of the boiler and adjacent wall orother appliance, when access is required for servicing.B. CLEARANCE FROM COMBUSTIBLECONSTRUCTIONDANGERDo not install this boiler on combustible flooringunless it is installed on a special combustible floorpan. Boiler installation on combustible flooringwithout the special pan is a fire hazard.To order combustible floor pan, use the 5-digit stockcodes listed in Section 11 of this manual.The design of this boiler is certified for closet installationwith the following clearances:1. 6″ (152 mm) between sides, rear and front andcombustible construction.2. 24″ (610 mm)between top of jacket andcombustible construction.3. 2″ (51 mm) between vent pipe and combustibleconstruction.4DANGERDo not install this boiler on carpeting. Boilerinstallation on carpeting is a fire hazard. Install thisboiler on non-combustible flooring or use acombustible floor pan to install this boiler on othernon-carpeted flooring.

PREINSTALLATIONC. AIR FOR COMBUSTION ANDVENTILATION1. Adequate combustion air and ventilation air must beprovided in accordance with section 5.3, Air forCombustion and Ventilation, of the National FuelGas Code, ANSI Z223.1/NFPA 54, or Sections 7.2,7.3 or 7.4 of CAN/CSA B149.1, Natural Gas andPropane Installation Code or applicable provisions ofthe local building code. Subsections 2 through 8 asfollows are based on the National Fuel Gas Coderequirements.2. Required Combustion Air Volume: The total requiredvolume of indoor air is to be the sum of the requiredvolumes for all appliances located within the space.Rooms communicating directly with the space inwhich the appliances are installed and throughcombustion air openings sized as indicated inSubsection 3 are considered part of the requiredvolume. The required volume of indoor air is to bedetermined by one of two methods.a. Standard Method: The minimum requiredvolume of indoor air (room volume) shall be 50cubic feet per 1000 BTU/Hr (4.8 m3/kW). Thismethod is to be used if the air infiltration rate isunknown or if the rate of air infiltration is knownto be greater than 0.6 air changes per hour. Asan option, this method may be used if the airinfiltration rate is known to be between 0.6 and0.4 air changes per hour. If the air infiltration rateis known to be below 0.4 then the Known AirInfiltration Rate Method must be used. If thebuilding in which this appliance is to be installedis unusually tight, we recommend that the airinfiltration rate be determined.b. Known Air Infiltration Rate Method: Wherethe air infiltration rate of a structure is known,the minimum required volume of indoor air forthe Boiler and other fan assisted appliances shallbe determined as follows:Required Volumefan 15 ft3ACH(I fan1000Btu/hrwhere:Ifan Input of the fan assisted appliances inBtu/hrACH air change per hour (percent of thevolume of the space exchanged perhour, expressed as a decimal))3. Indoor Air Opening Size and Location: Openingsconnecting indoor spaces shall be sized and locatedas follows:a. Combining spaces on the same floor:Provide two permanent openings communicatingwith additional spaces that have a minimum freearea of 1 in2 per 1000 Btu/hr (22 cm2 per 1000 W)of the total input rating of all gas fired equipmentbut not less than 100 in2 (645 cm2). Oneopening is to begin within 12 inches (305 mm)from the top of the space and the other is tobegin within 12 inches (305 mm) from the floor.The minimum dimension of either of theseopenings shall be 3 inches (76 mm). See Figure1.1 for an illustration of this arrangement.Figure 1.1: Air Openings – All Air from Indoorson the Same Floorb. Combining spaces on different floors:Provide one or more permanent openingscommunicating with additional spaces that havea total minimum free area of 2 in2 per 1000Btu/hr (44 cm2 per 1000 W) of total input ratingof all equipment. See Figure 1.2 for anillustration of this arrangement.For appliances other than fan assisted, calculatethe required volume of air using the followingequation:Required Volumeother 21 ft3ACH(I other1000Btu/hr)Iother Input of appliances other than fanassisted in Btu/hrNote: These calculations are not to be used forinfiltration rates greater than 0.60 ACH.Figure 1.2: Air Openings – All Air from Indoorson Different Floors5

PREINSTALLATION4. Outdoor Combustion Air: Outdoor combustion air isto be provided through one or two permanentopenings. The minimum dimension of these airopenings is 3 inches (76 mm).a. Two Permanent Opening Method: Providetwo permanent openings. One opening is tobegin within 12 inches (305 mm) of the top ofthe space and the other is to begin within 12inches (305 mm) of the floor. The openings areto communicate directly or by ducts with theoutdoors or with spaces that freely communicatewith the outdoors. The size of the openings shallbe determined as follows:i.ii. Where communicating with the outdoorsthrough horizontal ducts, each opening shallhave a minimum free area of 1 in2 per 2000Btu/hr (22 cm2 per 2000 W) of total ratedinput for all appliances in the space. SeeFigure 1.5.Where communicating directly or throughvertical ducts with the outdoors each openingshall have a minimum free area of 1 in2 per4000 Btu/hr (22 cm2 per 4000 W) of totalinput rating for all equipment in the space.See Figure 1.3 for openings directlycommunicating with the outdoors or Figure1.4 for openings connected by ducts to theoutdoors.Figure 1.5: Air Openings – All Air from Outdoorsthrough Horizontal DuctsFigure 1.3: Air Openings – All Air Directly fromOutdoorsFigure 1.4: Air Openings – All Air from Outdoorsthrough Vertical Ducts6b. One Permanent Opening Method: Provideone permanent opening beginning within 12inches (305 mm) of the top of the space. Theopening shall communicate directly with theoutdoors, communicate through a vertical orhorizontal duct, or communicate with a spacethat freely communicates with the outdoors. Theopenings shall have a minimum free area of 1 in2per 3000 Btu/hr of total rated input for allappliances in the space and not less than thesum of the cross-sectional areas of all ventconnectors in the space. The gas fired equipmentshall have clearances of at least 1 inch (25 mm)from the sides and back and 6 inches (150 mm)from the front of the appliance. See Figure 1.6for this arrangement.Figure 1.6: Air Openings – All Air from Outdoorsthrough One Opening

PREINSTALLATION5. Combination Indoor and Outdoor Combustion Air:If the required volume of indoor air exceeds theavailable indoor air volume, outdoor air openings orducts may be used to supplement the availableindoor air provided:a. The size and location of the indoor openingscomply with Subsection 3.b. The outdoor openings are to be located inaccordance with Subsection 4.c. The size of the outdoor openings are to be sizedas follows:Areq Afull x(Vavail1–Vreq)where:Areq minimum area of outdoor openings.Afull full size of outdoor openings calculatedin accordance with Subsection 4.Vavail available indoor air volumeVreq required indoor air volume6. Engineered Installations: Engineered combustion airinstallations shall provide an adequate supply ofcombustion, ventilation, and dilution air and shall beapproved by the authority having jurisdiction.7. Mechanical Combustion Air Supply:a. In installations where all combustion air isprovided by a mechanical air supply system, thecombustion air shall be supplied from theoutdoors at the minimum rate of 0.35 ft3/min per1000 Btu/hr (0.034 m3/min per 1000 W) of thetotal rated input of all appliances in the space.b. In installations where exhaust fans are installed,additional air shall be provided to replace theexhaust air.c. Each of the appliances served shall beinterlocked to the mechanical air supply toprevent main burner operation where themechanical air supply system is not in operation.d. In buildings where the combustion air is providedby the mechanical ventilation system, the systemshall provide the specified combustion air rate inaddition to the required ventilation air.8. Louvers & Grills:a. The required size of openings for combustion,ventilation, and dilution air shall be based on thenet free area of each opening.i.b. Motorized dampers shall be interlocked with theequipment so that they are proven in the fullopen position prior to ignition and duringoperation of the main burner.i.The interlock shall prevent the main burnerfrom igniting if the damper fails to openduring burner startup.ii. The interlock shall shut down the burner ifthe damper closes during burner operation.9. Combustion Air Ducts:a. Ducts shall be constructed of galvanized steel oran equivalent corrosion- resistant material.b. Ducts shall terminate in an unobstructed space,allowing free movement of combustion air to theappliances.c. Ducts shall serve a single space.d. Ducts shall not serve both upper and lowercombustion air openings where both suchopenings are used. The separation between ductsserving upper and lower combustion airopenings shall be maintained to the source ofcombustion air.e. Ducts shall not be screened where terminating inan attic space.f. Horizontal upper combustion air ducts shall notslope downward toward the source of thecombustion air.g. The remaining space surrounding a chimneyliner, gas vent, special gas vent, or plastic pipinginstalled within a masonry, metal, or factory builtchimney shall not be used to supply combustionair.h. Combustion air intake openings located on theexterior of buildings shall have the lowest side ofthe combustion air intake opening at least 12inches (305 mm) above grade.WARNINGLiquefied Petroleum (LP) is heavier than air and maycollect or “pool” in a low area in the event of a leakfrom defective equipment. This gas may then ignite,resulting in a fire or explosion.Where the free area through a louver or grilleis known, it shall be used in calculating theopening size required to provide the free areaspecified.ii. Where the free area through a louver or grilleis not known, it shall be assumed that woodenlouvers will have 25% free area and metallouvers and grilles will have 75% free area.iii. Nonmotorized dampers shall be fixed in theopen position.7

PREINSTALLATIOND. PLANNING THE LAYOUT Prepare sketches and notes of the layout to minimize thepossibility of interferences with new or existingequipment, piping, venting and wiring.E. MASSACHUSETTS INSTALLATIONSMassachusetts requires manufacturers of Side WallVented boilers to provide the following informationfrom the Massachusetts code: A hard wired carbon monoxide detector with analarm and battery back-up must be installed onthe floor level where the gas equipment is to beinstalled AND on each additional level of thedwelling, building or structure served by the sidewall horizontal vented gas fueled equipment.In the event that the side wall horizontally ventedgas fueled equipment is installed in a crawl spaceor an attic, the hard wired carbon monoxidedetector with alarm and battery back-up may beinstalled on the next adjacent floor level. Detector(s) must be installed by qualified licensedprofessionals. APPROVED CARBON MONOXIDEDETECTORS: Each carbon monoxide detectorshall comply with NFPA 720 and be ANSI/UL2034 listed and IAS certified.SIGNAGE: A metal or plastic identification plateshall be permanently mounted to the exterior ofthe building at a minimum height of eight (8) feetabove grade directly in line with the exhaust ventterminal for the horizontally vented gas fueledheating appliance or equipment. The sign shallread, in print size no less than one-half (1/2) inchin size, “GAS VENT DIRECTLY BELOW.KEEP CLEAR OF ALL OBSTRUCTIONS”. The above requirements do not apply if theexhaust vent termination is seven (7) feet ormore above finished grade in the area of theventing, including but not limited to decksand porches.The above requirements do not apply to aboiler installed in a room or structure separatefrom the dwelling, building or structure usedin whole or in part for residential purposes.See the latest edition of Massachusetts Code248 CMR for complete verbage and also foradditional (non-vent related) requirements(248 CMR is available online).If your installation is NOT in Massachusetts, pleasesee your authority of jurisdiction for requirementsthat may be in effect in your area. In the absence ofsuch requirements, follow the National Fuel GasCode, ANSI Z223.1/NFPA 54 and/or CAN/CSAB149.1, Natural Gas and Propane Installation Code.Venting System Installation Instructions – Seeboiler manual and instructions provided with theVenting System components. Additional copies maybe obtained from the Venting System Manufacturerby visiting the following web addresses:Heat-Fab – www.selkirkcorp.com/heatfabZ-Flex – www.NovaFlex.comPro-Tech – www.protechinfo.comMetal-Fab – www.mtlfab.comEXEMPTIONS to the requirements listed above:2. BOILER SET-UP1. Provide a sound, level foundation. Locate boiler asnear to the chimney or outside wall as possible andcentralized with respect to the heating system.4. Separate the wood shipping pallet from the boilerbase by removing two (2) hold-down bolts at eachend of the boiler base.2. Locate boiler in front of installation position beforeremoving crate.5. Move boiler into final position. If using combustiblefloor pan, install boiler on pan as outlined in theinstructions included with the pan.3. If using combustible floor pan, position pan onfoundation or flooring.8

WATER PIPING AND CONTROLS3. WATER PIPING AND CONTROLSA. BOILER SUPPLY AND RETURN1. Size the supply and return to suit the system. Atypical piping arrangement is shown in Figure 3.1.Refer also to the I B R Guide to ResidentialHydronic Heating Installation/Design for additionalguidance during water piping installation.2. Return Piping:a. Pipe the outlet connection of the circulator to atee, provided with a drain valve, at the 1-1/4NPT return tapping near the bottom of the leftsection. Pipe the return to the inlet connection ofthe circulator.3. Supply Piping:Pipe the supply to the 1-1/2 NPT supply tapping atthe top of the boiler.4. When system return water temperature will be below130 F (54 C), pipe the boiler with a bypassarrangement to blend the system return and hotsupply to obtain at least 130 F (54 C) entering theboiler.5. If desired, install the circulator in the alternatelocation shown in Figure 3.1.Figure 3.1: Supply and Return Piping9

WATER PIPING AND CONTROLS6. Install this boiler so that the gas ignition systemcomponents are protected from water (dripping,spraying, etc.) during appliance operation andservice (circulator replacement, condensate trap,control replacements, etc.).7. If this boiler and distribution system is used inconjunction with a refrigeration system, pipe thechilled medium in parallel with the boiler and installthe proper valve to prevent the chilled medium fromentering the boiler. A drawing illustrating this hookup is provided in Figure 3.2.8. When the boiler is connected to heating coils locatedin air handling units where they may be exposed torefrigerated air circulation, install flow control valvesor other automatic means to prevent gravitycirculation of the boiler water during the coolingcycle.9. If this boiler is installed above radiation level,provide a low water cutoff device, either as a part ofthe boiler or at the time of boiler installation.Figure 3.3: Safety Relief Valve Hook-UpInstallation with Air Elimination inSystem PipingB. SAFETY RELIEF VALVE1. Locate safety relief valve and fittings in bagassembly.2. If air elimination is not required at the safety reliefvalve tapping, install valve and piping as shown inFigure 3.3.3. For air elimination at the safety relief valve tapping,install valve and piping as shown in Figure 3.4.CAUTIONPipe the discharge of safety relief valve to preventinjury in the event of pressure relief. Pipe thedischarge to a drain. Provide piping that is the samesize as the safety relief valve outlet.Figure 3.4: Safety Relief Valve Hook-Up withAir EliminationFigure 3.2: Parallel Hook-up with Water Chiller10

WATER PIPING AND CONTROLSC. PIPING FOR ZONED SYSTEMS1. See Figures 3.5 and 3.6 for basic zoned systemlayouts.2. Run each zone pipe down then up to zone toprevent air accumulation in piping.3. If required, provide means to isolate and drain eachzone separately.Figure 3.5: Zone Piping with Zone ValvesFigure 3.6: Zone Piping with Circulators11

WATER PIPING AND CONTROLSD. EXPANSION TANKF.For new or existing systems that must be freezeprotected:1. Consult the tank manufacturer’s instructions forspecific information relating to tank installation. Sizethe expansion tank for the required system volumeand capacity. See Table 10.2 in Section 10 for boilerwater capacity.2. Expansion tanks are available with built-in fill valvesand check valves for reducing supply water pressureand maintaining minimum system pressure. Checkthe design features of the tank and provide valves asnecessary.FREEZE PROTECTIONWARNINGUse only inhibited propylene glycol solutions of up to50% by volume with water. Ethylene glycol is toxicand can attack gaskets and seals used in hydronicsystems.Refer back to Figure 3.1 for typical expansion tank piping.E. INDIRECT-FIRED WATER HEATERIf the boiler is to be used in conjunction with an indirectfired water heater, refer to Figure 3.7 for typical piping.Follow the instructions provided by the water heatermanufacturer. Pipe the water heater as a separate zone.1. Glycol in hydronic applications is speciallyformulated for this purpose. It includes inhibitorswhich prevent the glycol from attacking metallicsystem components. Make certain that the systemfluid is checked for the correct glycol concentrationand inhibitor level.2. The antifreeze solution should be tested at least oncea year and as recommended by the antifreezemanufacturer.3. Antifreeze solutions expand more than water. Forexample, a 50% by volume solution expands 4.8%in volume for a temperature increase from 32 F(0 C) to 180 F (82 C), while water expands 3% withthe same temperature rise. Allowance must be madefor this expansion in system design.Figure 3.7: Typical Piping with Indirect-Fired Water Heater12

VENTING4. VENTINGA. GENERAL1. Install vent system in accordance with the “Ventingof Equipment” Chapter of the National Fuel GasCode, ANSI Z223.1/NFPA 54, the “Venting Systemsand Air Supply for Appliances” Section of theCAN/CSA B149.1, Natural Gas and PropaneInstallation Code. or applicable provisions of thelocal building codes.2. Do not connect vent connectors serving appliancesvented by natural draft into any portion ofmechanical draft systems operating under positivepressure.3. Refer to the following venting options to determinewhich method is applicable.ON –WARNINGB. CHIMNEY VENTINGIf venting into a masonry chimney; chimney must belined with a fire clay tile liner or corrosion resistant metalliner. Type B vent may also be used as a lining system oras a stand alone chimney vent.1. The vent system, when installed per the followinginstructions, will operate with a negative pressure (draft).Table 4.1: Increaser & Chimney Size70105140165Increaser Size3" to 4"3" to 5"3" to 5"3" to 5"(7.6 to 10.2 cm)(7.6 to 12.7 cm)(7.6 to 12.7 cm)(7.6 to 12.7 cm)Vent m)4. Apply 1/4" (6 mm) bead of silicone around fanadapter and slip increaser over the fan adapter. Referto Table 4.1 for increaser and chimney sizes.Increaser to be provided by installer.5. Single wall vent pipe should be furnished betweenincreaser and chimney. If the vent connector shall belocated in or pass through a cold area, the ventconnector shall be type B material.C. DIRECT EXHAUST; HORIZONTALVENTINGNOTICEAll joints of positive pressure vent systems must besealed completely to prevent leakage of flue productsinto the living space.BoilerSize3. Locate fan adapter, silicone, hardware and fanadapter gasket in boiler miscellaneous parts boxand attach to blower outlet flange. Refer to Fig. 4.1for )m)m)m)2. Horizontal portions of the vent pipe shall slopeupward from the boiler towards the vertical vent notless than 1/4" per foot (21 mm per meter). Supporthorizontal portions of the venting system to preventsagging by use of metal strapping or equivalentmeans. Locate supports at no more than 4 foot (1.2meter) intervals.Parties horizontales de l'évent doit pente ascendantede la chaudière vers la cheminée verticale d'aumoins 1/4 "par pied (21 mm par mètre). Fournir unsupport à toute portion horizontale du systèmed’évacuation à l’aide de courroies de metal ou uneméthode équivalente afin de l’empêcher des’affaisser. Placer les supports à des intervalles nedépassant pas cent vingt deux (122) centimètres (4po), ou en suivant les recommandations d’installation du fabricant.Flue gases will condense as they exit the venttermination. This condensate can freeze on exteriorbuilding surfaces which may cause discoloration ofthese surfaces.1. This vent system will operate with a positive pressurein the vent pipe. Follow vent pipe manufacturersinstructions for proper assembly of vent pipe andfittings.2. Refer to Table 4.2 for minimum and maximum ventlength allowed.3. Maintain a minimum 2" (51 mm) clearance betweenvent pipe and combustible construction for an unenclosed vent. See vent manufacturer instructions forminimum clearance to an enclosed vent.4. When installing vent pipe through a combustiblewall, pipe must pass through a metal wall thimble;maintain a 2" (51 mm) clearance between vent pipeand thimble. Follow thimble manufacturer’sinstructions. Seal between thimble and exterior wallusing exterior-rated caulk or silicone to prevent waterdamage and also to prevent recirculation of flueproducts into the structure.5. Determine vent terminal location.a. Vent terminal shall be located at least 3 feet (1meter) above any forced air inlet located within10 feet (3 meters).b. Vent terminal shall be located at least 4 feet (1.2meters) below, 4 feet (1.2 meters) horizontallyfrom, or 1 foot (0.3 meters) above any door,window, or gravity air inlet into any building.c. Vent terminal shall be located at least 1 foot (0.3meters) above ground level or normal snow lines.See subsection 7 below if terminal needs to beextended above ground level or snow line.13

VENTINGFigure 4.1: Chimney Ventingd. Vent terminal shall not be located over publicwalkways where condensate could create anuisance or hazard.e. When adjacent to a public walkway, ventterminal shall be at least 7 feet (2.1 meters)above grade.f. Vent terminal shall be located at least 4 feet (1.2meters) horizontally from electric meters, gasmeters, regulators and relief equipment. InCanada, this dimension must be 6 feet (2 meters).g. Vent terminal should not be located directlyunder roof overhangs to prevent icicles fromforming.6. Vent Pipe Assembly:a. Horizontal portions of the vent pipe shall slopedownward from the boiler to the venttermination elbow, not less than 1/4" per foot(21 mm per meter). If any horizontal portions ofthe vent pipe instead slope toward boiler, providea horizontal drain tee as per instructions insection D. Direct Exhaust; Vertical Venting.Parties horizontales de l'évent doit s'incliner versle bas de la chaudière à la terminaison deventilation (coude), pas moins de 1/4 "par pied(21 mm par mètre).Si les parties horizontales de l'évent au lieu pentevers la chaudière, prévoir un tee drain horizontalen suivant les instructions de la section D.échappement direct, évacuation verticale.b. Support horizontal portions of the venting systemto prevent sagging by use of metal strapping orequivalent me

C. AIR FOR COMBUSTION AND VENTILATION 1. Adequate combustion air and ventilation air must be provided in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections 7.2, 7.3 or 7.4 of CAN/CSA B149.1, Natural Gas and Propane Installation Codeor applicable provisions of the local building code.

Related Documents:

the boiler and they have to enter the registration number of the boiler along with the following details a. Boiler Details : User need to provide following details of the boiler i. Types of Boiler/ Economizer ii. Total Heating Surface Area (Sq. mt) iii. Name of Manufacturer iv. Boiler/ Small Industrial Boiler/ Economizer Works Number v.

Raypak Hi-Delta Boiler Raypack Hi-Delta boiler with on/off state animations. Murray Boiler Murray boiler with flame animation. Multistack Boiler Multistack boiler with open/closed version but no animations. Superior Boiler Superior boiler with flame animation. F - salesqagraphicscom C 515-965-3403 O S P O S P O S P O S P O S P O S P D

A Lochinvar Crest series condensing boiler, model FBN2001 was installed to replace "Boiler 2" in January 2019. Boiler 2 was an AERCO Benchmark 2.0, serial number G-08-0799. New Boiler Information-SUN-224 Boiler Identification: Boiler 2 Location: Boiler Room Boiler Make/Model

Fire tube steam boilers may be either high or low pressure boilers. There are three types of fire tube steam boilers: (i) horizontal return tubular boiler, (ii) scotch marine boiler, and (iii) vertical fire tube boiler. The boiler studied in the present experiment is horizontal return tubular boiler. This boiler is a 3 pass fire tube boiler.

Inspect boiler jacket door gaskets on front of cabinet and reinstall boiler jacket door after start or servicing. The boiler jacket door must be securely fastened to the boiler to prevent boiler from drawing air from inside the boiler room. This is particularly important if the boiler is

EU-34.2 Nebraska Boiler - #2 fuel oil EU-34.3 Nebraska Boiler - soybean oil EU-34.4 Nebraska Boiler - animal fats EU-34.5 Nebraska Boiler - biodiesel heavies EU-34.6 Nebraska Boiler - biodiesel EP-34.2 EU-34.21 Nebraska Boiler (Heat Recover Stack) - natural gas 02-A-387-S1 EU-34.22 Nebraska Boiler (Heat Recover Stack) - #2 fuel oil

8 UNIVERSAL steam boiler U-ND/U-HD 12 UNIVERSAL steam boiler U-MB 16 UNIVERSAL steam boiler UL-S/UL-SX 20 UNIVERSAL steam boiler ZFR/ZFR-X 24 Self-fired waste heat boiler 26 UNIVERSAL heat recovery steam boiler HRSB 27 Series UL-S and UT-H as waste heat boilers 28 Boiler control BCO 29 Service 30 References middle of 2012 the systems were sold .

Lattner Boiler Company Scotch Marine Steam & Hot Water Boilers INSTRUCTION MANUAL December 2005 Lattner Boiler Company 1411 9th St. SW Cedar Rapids, IA 52404 T: (800) 345-1527 F: (319) 366-0770 E: info@lattner.com www.lattnerboiler.com