ACF Series Counter Flow Induced Draft Cooling TowersEngineering Data.

American Cooling Tower, Inc.ACF Series FeaturesOverviewThe ACF series induced draft counter flow cooling tower is American Cooling Tower's factory assembled cooling towersystem which offers clients with a wide range of capacities and sizes to help accommodate their project needs.CapacityThe ACF series cooling tower line provides 86 unique models, all of which are CTI STD-201 certified. Nominal tonnageranges from 97 to 1043 tons of cooling capacity.Technology & PartnershipWhen American Cooling Tower began working on the ACF series cooling tower design, we wanted to ensure that everyaspect of the tower design included the best components available in our industry. To achieve this, every majorcomponent supplier was deeply involved in the development and testing of the ACF cooling tower line to ensure that onlythe very best materials and components were selected and utilized within the design. Through this ongoing process welook forward to the continual development of additional accessories and products to further enhance the ACF series line.Quality Control & WorkmanshipFor more than 25 years, American Cooling Tower has beeninvolved in the cooling tower industry by providing a widerange of services and products to customers throughout theUnited States. Over this time, American Cooling Tower hasdeveloped a stringent in house quality control program toclosely monitor production and quality of workmanship fromstart to finish. Through our Total Quality Management systemAmerican Cooling Tower monitors and records all aspects ofour production process from raw material acquisition thrupackaging of completed units for shipping.SustainabilityAs all manufacturers have continuedto strive to meet growing demands forutilizing sustainable and recycledmaterials, American Cooling Tower ispleased that the current ACF seriescooling tower is comprised of morethan 65% recycled materials.1.www.AmericanCoolingTower.com

American Cooling Tower, Inc.ComponentsMechanical System Premium Efficient Cooling Tower Duty Fan MotorsIP55 construction and in accordance withMGI part 31 inverter duty rating. Marine grade axial fan assemblies with stainless steel316 hardware and reliant mounting system whicheliminates almost all resonant frequencies. Heavy Duty L10 100,000 hour bearings Solid banded belt drive systems Adjustable motor bases External lube lines for ease of maintenance 5 year mechanical warrantyDistribution System PVC header and lateral system Removable and cleanable Low pressure non-clogging spray nozzleswill not rust or corrode Long service life and easy to maintain. Low pump head requirementsFill Media Flame Spread rating of 5 per ASTM E84-77a PVC mechanical assembly fill media Resistant to rot, decay, and biological attack High performance alternating tip design 140 F continuous operating condition Manufactured in accordance with CTI STD-136Drift Eliminators Cellular PVC design - Electronic make-up water assemblies Multi-pass configuration - Variable Frequency Drives 0.001% drift loss rates - Fully customizable control panels Low pressure drop for better fan performance - Springisolator rail mounting systems Flame spread rating of 5 per ASTM E84-77aAccessories & Options Stainless Steel 304 or 316 construction options SPDT & DPDT Vibration switches Gear driven mechanical systems Electronic make-up water assemblies Variable Frequency Drives Fully customizable control panels Spring isolator rail mounting systems Sand Filter and Vortex Separator systems Holding tanks for remote sump applications Sound attenuation for low noise applications Industrial liner option for maximum corrosion protection Service platform and ladder systemsAdditional accessories and options are available upon request.Contact your representative or call American Cooling Tower for more information.www.AmericanCoolingTower.com2

American Cooling Tower, Inc.ACF 18-6A-1 78-8D-1SINGLE CELL COUNTER FLOW DESIGN97 200 NOMINAL TONSThermal performance of the ACF series models listed above have been certifiedin accordance to cooling technology institute (CTI) Standand STD-201. Single cell models only.For multiple cell configurations, please contact American Cooling Tower Inc.For design conditions not shown, please contact American Cooling Tower Inc.Validation 10-38-013www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 18-6A-1 78-8D-1SINGLE CELL COUNTER FLOW DESIGN97 200 NOMINAL TONSH3”ACCESSDOOR6” INLET2” MAKE-UPLW3” OVERFLOW3” DRAIN6” OUTLETLWACCESS DOORMM - Denotes motor locationModel No.Fan Motor(HP)Air Flow(CFM)DimensionsWeightShippingOperatingLength (L)Width(W)Height (H)ACF-18-6A-1530000296050406'8' 6"10'ACF-28-6B-17.533000299050806'8' 6"10'ACF-38-6B-17.531200320052906'8' 6"11'ACF-48-6C-11034000323053206'8' 6"11'ACF-58-6D-11535600353056106'8' 6"12'ACF-18-8A-1537000335058208'8' 6"10'ACF-28-8B-17.540000339058608'8' 6"10'ACF-38-8C-11043000340058908'8' 6"10'ACF-48-8B-17.537500362060908'8' 6"11'ACF-58-8C-11039000393064008'8' 6"12'ACF-68-8D-11544500372061808'8' 6"11'ACF-78-8D-11543100399064608'8' 6"12'Above drawings are for reference only.Inlet & Outlet connections are grooved for mechanical coupling.Dimensions and weights are subject to change without notification.Units are shipped factory assembled in two sections. Final assembly required by installer.www.AmericanCoolingTower.com4

American Cooling Tower, Inc.ACF 18-6A-1 78-8D-1SINGLE CELL COUNTER FLOW DESIGNRECOMMENDED TOWER SUPPORT LAYOUTACDECBFUNIT OUTLINEMOUNTING HOLESSIX (6) TOTALCL TOWER LOADGUNIT OUTLINEMOUNTING HOLESSIX (6) TOTALModel No.DimensionsShippingOperating Anchor Bolt QtyWeight (lbs) Weight (lbs)& DiameterLoad PerAnchor (lbs)CDEFGACF-18-6A-129605040(6) 5/8"8' -6" 6' -0"6"39"51"71 1/4"3/8"840ACF-28-6B-129905080(6) 5/8"8' -6" 6' -0"6"39"51"71 1/4"3/8"847ACF-38-6B-132005290(6) 5/8"8' -6" 6' -0"6"39"51"71 1/4"3/8"882ACF-48-6C-132305320(6) 5/8"8' -6" 6' -0"6"39"51"71 1/4"3/8"887ACF-58-6D-135305610(6) 5/8"8' -6" 6' -0"6"39"51"71 1/4"3/8"935ACF-18-8A-133505820(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"ACF-28-8B-133905860(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"3/8"3/8"970977ACF-38-8C-134005890(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"3/8"982ACF-48-8B-136206090(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"3/8"1015ACF-58-8C-139306400(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"3/8"1067ACF-68-8D-137206180(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"3/8"1030ACF-78-8D-139906460(6) 5/8"8' -6" 8' -0"6"39"51"95 1/4"3/8"1077ABSupport steel selection and anchors by others.All steel supports must have a level installation surface.Applicable building codes may require alternate support designs.For alternate support designs please consult the factory.Weights are subject to change and do not include any options or accessories.5www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 18-9C-1 48-12G-1SINGLE CELL COUNTER FLOW DESIGN193 344 NOMINAL TONSThermal performance of the ACF series models listed above have been certifiedin accordance to cooling technology institute (CTI) Standand STD-201. Single cell models only.For multiple cell configurations, please contact American Cooling Tower Inc.For design conditions not shown, please contact American Cooling Tower Inc.Validation 10-38-01www.AmericanCoolingTower.com6

American Cooling Tower, Inc.ACF 18-9C-1 48-12G-1SINGLE CELL COUNTER FLOW DESIGN193 344 NOMINAL TONSH3”8” INLET2” MAKE-UPWL3” OVERFLOW8” OUTLET3” DRAINWLACCESS DOORMM - Denotes motor locationDimensionsWeightModel No.Fan Motor(HP)Air Flow(CFM)ShippingOperatingLength (L)ACF-18-9C-11045100421071109'8' 6"12'ACF-28-9D-11552400429071809'8' 6"12'Width(W)Height (H)ACF-38-9D-11550400460075009'8' 6"12' 9"ACF-48-9E-12055200465075509'8' 6"12' 9"ACF-18-10B-17.5505004450782010' 6"8' 6"10' 10"ACF-28-10C-110500004810817010' 6"8' 6"11' 10"ACF-38-10D-115562005240860010' 6"8' 6"12' 10"ACF-48-10E-120645004930829010' 6"8' 6"11' 10"ACF-58-10E-120621005290865010' 6"8' 6"12' 10"ACF-18-12E-120740005460939512'8' 6"12' 3"ACF-28-12E-120710005860979012'8' 6"13' 3"ACF-38-12G-130790005480942012'8' 6"12' 3"ACF-48-12G-130777005880984012'8' 6"13' 3"Above drawings are for reference only.Inlet & Outlet connections are grooved for mechanical coupling.Dimensions and weights are subject to change without notification.Units are shipped factory assembled in two sections. Final assembly required by installer.7www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 18-9C-1 48-12G-1SINGLE CELL COUNTER FLOW DESIGNRECOMMENDED TOWER SUPPORT LAYOUTACDECBFUNIT OUTLINEMOUNTING HOLESSIX (6) TOTALCL TOWER LOADGUNIT OUTLINEMOUNTING HOLESSIX (6) TOTALModel No.DimensionsShippingOperating Anchor Bolt QtyWeight (lbs) Weight (lbs)& -12G-158809840(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"(6) 3/4"DE9' -0" 8' -6"6"41"55"100 3/8" 13/16"11859' -0" 8' -6"6"41"55"100 3/8" 13/16"1197100 3/8" 13/16"1250BFLoad PerAnchor (lbs)CAG9' -0" 8' -6"6"41"55"9' -0" 8' -6"6"41"55"100 3/8" 13/16"125810' -6" 8' -6"6"49"65"100 3/8" 13/16"130310' -6" 8' -6"6"49"65"100 3/8" 13/16"136210' -6" 8' -6"6"14336"65"65"100 3/8" 13/16"10' -6" 8' -6"49"49"100 3/8" 13/16"138210' -6" 8' -6"6"49"65"100 3/8" 13/16"144212' -0" 8' -6"6"56"76"100 3/8" 13/16"156612' -0" 8' -6"6"56"76"100 3/8" 13/16"163212' -0" 8' -6"6"56"76"100 3/8" 13/16"157012' -0" 8' -6"6"56"76"100 3/8" 13/16"1640Support steel selection and anchors by others.All steel supports must have a level installation surface.Applicable building codes may require alternate support designs.For alternate support designs please consult the factory.Weights are subject to change and do not include any options or accessories.www.AmericanCoolingTower.com8

American Cooling Tower, Inc.ACF 18-14D-1 912-12H-1SINGLE CELL COUNTER FLOW DESIGN286 477 NOMINAL TONSThermal performance of the ACF series models listed above have been certifiedin accordance to cooling technology institute (CTI) Standand STD-201. Single cell models only.For multiple cell configurations, please contact American Cooling Tower Inc.For design conditions not shown, please contact American Cooling Tower Inc.Validation 10-38-019www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 18-14D-1 912-12H-1SINGLE CELL COUNTER FLOW DESIGN286 477 NOMINAL TONSH3”ACCESSDOOR8” INLET2” MAKE-UPWL3” OVERFLOW8” OUTLET3” DRAINWLM - Denotes motor locationACCESS DOORMMotors are located internally on models 112-12D-1 to 912-12H-1WeightDimensionsModel No.Fan Motor(HP)Air Flow(CFM)ShippingOperatingLength (L)ACF-18-14D-1157330059201052014'8' 6"12' 3"ACF-28-14D-1157050063801097014'8' 6"13' 3"ACF-38-14E-1208070059601056014'8' 6"12' 3"ACF-48-14F-1258750059801058014'8' 6"12' 3"ACF-58-14G-1309250060001060014'8' 6"12' 3"ACF-68-14G-1308860064601106014'8' 6"13' 3"Width(W)Height (H)ACF-112-12D-1159150074401365012'12'13' 8"ACF-212-12E-1209950074901370012'12'13' 8"ACF-312-12F-12510650075401375012'12'13' 8"ACF-412-12E-1209360080301424012'12'14' 8"ACF-512-12E-1209020085201473012'12'15' 8"ACF-612-12F-12510060080801429012'12'14' 8"14' 3010300086701488012'12'15' 8"ACF-912-12H-14011010089201513012'12'15' 8"Above drawings are for reference only.Inlet & Outlet connections are grooved for mechanical coupling.Dimensions and weights are subject to change without notification.Units are shipped factory assembled in two sections. Final assembly required by installer.www.AmericanCoolingTower.com10

American Cooling Tower, Inc.ACF 18-14D-1 912-12H-1SINGLE CELL COUNTER FLOW DESIGNRECOMMENDED TOWER SUPPORT LAYOUTCDAEDCBFUNIT OUTLINEMOUNTING HOLESEIGHT (8) TOTALCL TOWER LOADGUNIT OUTLINEMOUNTING HOLESEIGHT (8) TOTALModel No.DimensionsShippingOperating Anchor Bolt QtyWeight (lbs) Weight (lbs)& DiameterABCDEFGLoad PerAnchor (lbs)ACF-18-14D-1592010520(8) 3/4"14' -0" 8' -6"5"72"14"100 3/8" 13/16"1315ACF-28-14D-1638010970(8) 3/4"14' -0" 8' -6"5"72"14"100 3/8" 13/16"1371ACF-38-14E-1596010560(8) 3/4"14' -0" 8' -6"5"72"14"100 3/8" 13/16"1320ACF-48-14F-1598010580(8) 3/4"14' -0" 8' -6"5"72"14"100 3/8" 13/16"1323ACF-58-14G-1600010600(8) 3/4"14' -0" 8' -6"5"72"14"100 3/8" 13/16"1325ACF-68-14G-1646011060(8) 3/4"14' -0" 8' -6"5"72"14"100 3/8" 13/16"1383ACF-112-12D-1744013650(8) 3/4"12' -0" 12' -0"5"59"16"16"142 3/8" 13/16"17065"59"142 3/8" 13/16"1713ACF-212-12E-1749013700(8) 3/4"12' -0" 12' -0"ACF-312-12F-1754013750(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1719ACF-412-12E-1803014240(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1780ACF-512-12E-1852014730(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1841ACF-612-12F-1808014290(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1786ACF-712-12G-1818014390(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1799ACF-812-12G-1867014880(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1860ACF-912-12H-1892015130(8) 3/4"12' -0" 12' -0"5"59"16"142 3/8" 13/16"1891Support steel selection and anchors by others.All steel supports must have a level installation surface.Applicable building codes may require alternate support designs.For alternate support designs please consult the factory.Weights are subject to change and do not include any options or accessories.11www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 112-14G-1 812-20K-1SINGLE CELL COUNTER FLOW DESIGN416 768 NOMINAL TONSThermal performance of the ACF series models listed above have been certifiedin accordance to cooling technology institute (CTI) Standand STD-201. Single cell models only.For multiple cell configurations, please contact American Cooling Tower Inc.For design conditions not shown, please contact American Cooling Tower Inc.Validation 10-38-01www.AmericanCoolingTower.com12

American Cooling Tower, Inc.ACF 112-14G-1 812-20K-1SINGLE CELL COUNTER FLOW DESIGN416 768 NOMINAL TONSH3”ACCESSDOOR10” INLET2” MAKE-UPWL3” OVERFLOW10” OUTLET3” DRAINWLMACCESS DOORM - Denotes motor locationWeightDimensionsModel No.Fan Motor(HP)Air Flow(CFM)ShippingOperatingLength -12510900088601619014'12'15' 2"ACF-312-14G-13011200094501678014'12'16' 2"ACF-412-14H-14012700091901652014'12'15' 2"Width(W)Height (H)14' 2"ACF-512-14H-14012250097101704014'12'16' 2"ACF-112-18G-130142000112602053018'12'15' 8"ACF-212-18G-130137000120002127018'12'16' 8"ACF-312-18H-140156000115202079018'12'15' 8"ACF-412-18H-140150200122602153018'12'16' 8"ACF-512-18J-150167000115802085018'12'15' 8"ACF-612-18K-160167300124302170018'12'15' 8"ACF-712-20J-150175000122302263020'12'15' 8"ACF-812-20K-160174300132402364020'12'16' 8"Above drawings are for reference only.Inlet & Outlet connections are grooved for mechanical coupling.Dimensions and weights are subject to change without notification.Units are shipped factory assembled in two sections. Final assembly required by installer.13www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 112-14G-1 812-20K-1SINGLE CELL COUNTER FLOW DESIGNRECOMMENDED TOWER SUPPORT LAYOUTADCDDDECBFUNIT OUTLINEMOUNTING HOLESTWELVE (12) TOTALCL TOWER LOADGUNIT OUTLINEMOUNTING HOLESTWELVE (12) TOTALModel No.DimensionsShippingOperating Anchor Bolt QtyWeight (lbs) Weight (lbs)& 40(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"DE14' -0" 12' -0"6"34 1/2"18"142 3/8" 13/16"130014' -0" 12' -0"6"34 1/2"18"142 3/8" 13/16"1349BFLoad PerAnchor (lbs)CAG14' -0" 12' -0"6"34 1/2"18"142 3/8" 13/16"139814' -0" 12' -0"6"34 1/2"18"142 3/8" 13/16"137714' -0" 12' -0"6"34 1/2"18"142 3/8" 13/16"142018' -0" 12' -0"8"20"142 3/8" 13/16"171118' -0" 12' -0"8"45"45"17738"45"20"20"142 3/8" 13/16"18' -0" 12' -0"142 3/8" 13/16"173318' -0" 12' -0"8"45"20"142 3/8" 13/16"179418' -0" 12' -0"8"45"20"142 3/8" 13/16"173818' -0" 12' -0"8"45"20"142 3/8" 13/16"180820' -0" 12' -0" 10"49"24"142 3/8" 13/16"188620' -0" 12' -0" 10"49"24"142 3/8" 13/16"1970Support steel selection and anchors by others.All steel supports must have a level installation surface.Applicable building codes may require alternate support designs.For alternate support designs please consult the factory.Weights are subject to change and do not include any options or accessories.www.AmericanCoolingTower.com14

American Cooling Tower, Inc.ACF 114-24G-1 1214-24LK-1SINGLE CELL COUNTER FLOW DESIGN669 1043 NOMINAL TONSThermal performance of the ACF series models listed above have been certifiedin accordance to cooling technology institute (CTI) Standand STD-201. Single cell models only.For multiple cell configurations, please contact American Cooling Tower Inc.For design conditions not shown, please contact American Cooling Tower Inc.Validation 10-38-0115www.AmericanCoolingTower.com

American Cooling Tower, Inc.ACF 114-24G-1 1214-24LK-1SINGLE CELL COUNTER FLOW DESIGN669 1043 NOMINAL TONS3”HACCESSDOOR14” INLET3” MAKE-UPW4” OVERFLOW14” OUTLET4” DRAINLWLMM - Denotes motor locationACCESS DOORWeightDimensionsModel No.Fan Motor(HP)Air Flow(CFM)ShippingOperatingLength (L)ACF-114-24G-130194100165103236024'14'17' 6"ACF-214-24H-140210000166603251024'14'17' 6"ACF-314-24F-125182000185703442024'14'19' 6"ACF-414-24J-150225000170103286024'14'17' 6"ACF-514-24G-130183000185903444024'14'19' 6"Width(W)Height (H)ACF-614-24H-140204400177003355024'14'18' 6"ACF-714-24H-140200800187403459024'14'19' 6"ACF-814-24J-150218000180503390024'14'18' 6"ACF-914-24J-150211500190903494024'14'19' 6"ACF-1014-24K-160230700182203407024'14'18' 6"ACF-1114-24K-160224000192603511024'14'19' 6"ACF-1214-24L-175235600195003535024'14'19' 6"Above drawings are for reference only.Inlet & Outlet connections are grooved for mechanical coupling.Dimensions and weights are subject to change without notification.Units are shipped factory assembled in two sections. Final assembly required by installer.www.AmericanCoolingTower.com16

American Cooling Tower, Inc.ACF 114-24G-1 1214-24LK-1SINGLE CELL COUNTER FLOW DESIGNRECOMMENDED TOWER SUPPORT LAYOUTADCDDEDCBFUNIT OUTLINEMOUNTING HOLESTWELVE (12) TOTALCL TOWER LOADGUNIT OUTLINEMOUNTING HOLESTWELVE (12) TOTALModel No.DimensionsShippingOperating Anchor Bolt QtyWeight (lbs) Weight (lbs)& K-11926035110ACF-1214-24L-11950035350(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"(12) 3/4"E24' -0" 14' -0" 12"60"24"166 3/8" 13/16"269724' -0" 14' -0" 12"60"24"166 3/8" 13/16"270924' -0" 14' -0" 12"60"24"166 3/8" 13/16"286824' -0" 14' -0" 12"60"24"166 3/8" 13/16"273824' -0" 14' -0" 12"60"24"166 3/8" 13/16"287024' -0" 14' -0" 12"60"24"166 3/8" 13/16"279624' -0" 14' -0" 12"60"24"166 3/8" 13/16"288324' -0" 14' -0" 12"60"24"166 3/8" 13/16"282524' -0" 14' -0" 12"60"24"166 3/8" 13/16"291224' -0" 14' -0" 12"60"24"166 3/8" 13/16"283924' -0" 14' -0" 12"60"24"166 3/8" 13/16"292624' -0" 14' -0" 12"60"24"166 3/8" 13/16"2946BCFLoad PerAnchor (lbs)DAGSupport steel selection and anchors by others.All steel supports must have a level installation surface.Applicable building codes may require alternate support designs.For alternate support designs please consult the factory.Weights are subject to change and do not include any options or accessories.17www.AmericanCoolingTower.com

American Cooling Tower, Inc.SpecificationsGENERAL1.0 SELECTIONFurnish American Cooling Tower ACF-cooling tower(s). The ACF series cooling tower is a factoryassembled, induced draft, axial fan, counter flow cooling towerwith vertical air discharge. The cooling tower’s overalldimensions shall not exceed FT in length X FT inwidth X FT in height. Each cooling tower shall consistof cell(s).1.1 PERFORMANCEThe ACF- model cooling tower is designed toprovide USGPM of total cooling capacity based on anentering hot water temperature of oF with an exiting coldwater temperature of oF and an entering ambient wetbulb temperature of oF. The ACF Series unit single cellthermal performance and capacity is certified under CTI STD201 validation number 10-38-01. On multiple cell coolingtower selections the thermal performance and capacities aresupplied with a manufacturer’s thermal performanceguarantee. For models that are not covered by CTI STD 201Certification the manufacturer shall provide performancecurves for 90%, 100%, and 110% of design water flow. Thedesign point for the project shall be clearly indicated forverification.MATERIALS OF CONSTRUCTION2.0 STRUCTUREThe cooling tower shall be constructed out of a heavy-gaugesteel design and engineered for maximum strength, durability,and service life. All cooling tower seams shall be sealed toprovide watertight joints.2.1 COLD WATER BASINThe cold water basin section shall be constructed of G-235galvanized steel to provide maximum durability and excellentresistance to rust and corrosion. The G-235 galvanized steelcold water basin section area shall include all componentsfrom the base of the unit up to the top of the air inlet louversupport which the louver attaches to and where the casingpanels start. The G-235 material means that an averagecoating thickness of 2.35 ounces of zinc per square foot shallbe applied to the steel surfaces. The cold water basin shall bedesigned with a tiered configuration allowing for reduced watervolume to be retained in the basin which shall lower operatingweight, and allow for easier maintenance. The cold waterbasin section shall include piping locations for the overflow,make-up, drain, and outlet connections. On multiple cell unitsan internal equalization system will be provided which allowsisolation of individual cells for maintenance. When a coldwater holding tank is utilized in the overall design, the outletconnection shall be designed as a bottom discharge type forgravity feed. The make-up, overflow, and drain connectionsshall be located on the remote tank instead of the cold waterbasin. ACT offers beveled for weld, grooved, and flanged inlet/outlet connections.2.1a (OPTION) STAINLESS STEEL COLDWATER BASINThe cold water basin section shall be constructed of stainlesssteel 304 (316) steel to provide superior service life, durabilityand excellent resistance to rust and corrosion. The stainlesssteel 304 (316) steel cold water basin section area shallinclude all components from the base of the unit up to the topof the air inlet louver support which the louver attaches to andwhere the casing panels start. The air inlet louver framesshall also be designed with stainless steel 304 (316)materials. The cold water basin shall be designed with atiered configuration allowing for reduced water volume to beretained in the basin which shall lower operating weight, andallow for easier maintenance. The cold water basin sectionshall include piping locations for the overflow, make-up,adrain, and outlet connections. On multiple cell units aninternal equalization system will be provided which allowsisolation of individual cells for maintenance. When a coldwater holding tank is utilized in the overall design, the outletconnection shall be designed as a bottom discharge type forgravity feed. The make-up, overflow, and drain connectionsshall be located on the remote tank instead of the cold waterbasin. ACT also offers welded cold water basin seams.2.2 INTERNAL SUPPORT MEMBERSThe cooling tower shall be constructed of heavy-gauge G-235galvanized steel for maximum strength and durability. Allweight bearing support pieces will be fabricated from heavygauge steel to ensure structural integrity of the unitthroughout its service life. All supports will be fastened withgalvanized hardware and fasteners.2.2a (OPTION) STAINLESS STEEL INTERNALSUPPORTSThe cooling tower shall be constructed of series 304 (316)stainless steel for maximum protection against corrosion andto ensure structural integrity of the unit throughout its superiorservice life. All weight bearing support pieces will befabricated from heavy gauge steel. All supports will befastened with stainless steel series 304 (316) hardware andfasteners. Self tapping fasteners shall not be accepted.2.3 CASING PANELSThe casing panels shall be constructed of G-235 galvanizedsteel to maximize the life of the cooling tower and minimizerust and corrosion. The casing panels shall be designed withheavy-gauge steel that incorporates flanged edges formaximum strength and durability. The panels shall befastened to the cooling tower structure with all seams sealedto provide watertight joints.*Options are indicated in italics or stated as (OPTION).www.AmericanCoolingTower.com18

American Cooling Tower, Inc.Specifications2.3a (OPTION) STAINLESS STEEL CASINGPANELSThe casing shall be constructed of series 304 (316) stainlesssteel to maximize the life of the cooling tower and providesuperior protection against rust and corrosion. The casingpanels shall be designed with heavy-gauge steel thatincorporates flanged edges for maximum strength anddurability. The panels shall be fastened to the cooling towerstructure utilizing stainless steel 304 (316) series stainlesssteel hardware with all seams sealed to provide watertightjoints. Self tapping fasteners shall not be accepted.3.0 MECHANICAL COMPONENTS3.1 FAN MOTORHP Premium Efficiency totally enclosed fan cooled(T.E.F.C.) ball bearing fan motor(s) with a minimum 1.25service factor shall be furnished and suitable for cooling towerservice on volts, hertz, phase. Themotor(s) shall be installed on an adjustable base which ismounted on the side of the unit for service. The fan motorshall be designed in accordance with MGI, part 31 suitable forinverter duty operation. The motor shall also be designedexclusively for use in cooling tower environments and shallhave both external and interior epoxy protective coating andshall be supplied with RS2 sealed bearings to maximize life.A protective cover shall shield externally mounted motors andmechanical drive system from the weather. For units wherethe motor is located internally, the motor shall be installed onan adjustable motor base but shall not include any protectiveweather coverings in order to provide complete accessibility tothe mechanical drive system for maintenance and inspection.3.2 FAN DRIVEThe fan drive system shall be belt driven consisting of a multigroove, solid back Banded V-belt with taper lock sheavesdesigned for 150% of the motor nameplate horsepower.Multiple single belt systems shall not be accepted. Drivensheaves shall be supplied in aluminum alloy.3.3 BEARINGSFan shaft bearings shall be heavy duty self-aligning ball typewith self locking collars and lube lines that extend to theoutside of the unit for servicing. Bearings shall be designed fora minimum L10 life of 100,000 hours minimum and shall beguaranteed for a period of five (5) years under the mechanicalwarranty.3.4 FANFan(s) shall be axial propeller, adjustable pitch type that aredynamically balanced. The fan(s) shall be supplied andinstalled by the manufacturer prior to shipping. The fan(s)shall be constructed of marine grade aluminum and stainlesssteel materials for maximum protection against rust andcorrosion. Fan tip clearance shall be no greater than ½” fromfan stack and shall be positioned within the stack at anappropriate elevation to maximize airflow and efficiency. Fanshall be designed with a resilient mount system to eliminateresonant frequencies. The fan(s) must be designed with lownoise velocity tips on each fan blade. Fans that do notinclude velocity tips that offer noise reduction shall not beacceptable. The fan shall be located within a fan stack thatshall be designed out of G235 galvanized steel (stainlesssteel type 304 (316)) and shall include a hot dippedgalvanized steel (stainless steel 304) OSHA compliant fanguard that is securely fastened to the fan stack by fastenersduring operation and can be removed for inspection orservicing.3.5 MECHANICAL WARRANTYCooling tower fan drive components shall be covered by afive year complete mechanical warranty. Drive componentsprotected by this warranty shall include the fans, bearings, fanshafts, fan sheaves, drive sheaves and fan motors.4.0 WATER DISTRIBUTION4.1 WATER DISTRIBUTION SYSTEMThe unit shall be provided with a non-corrosive waterdistribution system that utilizes a single inlet connection foreach fan cell. The spray header and branches shall beconstructed of Schedule 40 polyvinyl chloride (PVC) pipe toprevent corrosion and shall have an external steel connectionthat is beveled for welding or grooved for a mechanicalcoupling to attach inlet piping. Spray laterals shall beremovable and designed with clean out end caps for servicingand maintenance. The water shall be distributed over the fillby low clog polypropylene spray nozzles to minimize clogging.The nozzles shall be threaded into the water distributionpiping to assure correct positioning and allow for easyreplacement or cleaning. Nozzles which are attached to thesystem by way of grommets shall not be acceptable. Nozzleswhich include moving parts or steel components prone to rustor breaking shall not be accepted. ACT offers Two Speed, TEAO,and Explosion proof motors as well.*Options are indicated in italics or stated as (OPTION).19www.AmericanCoolingTower.com

Amer

The ACF series induced draft counter flow cooling tower is American Cooling Tower's factory assembled cooling tower system which offers clients with a wide range of capacities and sizes to help accommodate their project needs. For more than 25 years, American Cooling Tower has been involved in the cooling tower industry by providing a wide

Related Documents:

Cooling Tower Marley MD Cooling Tower Marley NC alpha SPLASH-FILL COOLING TOWER Marley MD 5000 COUNTERFLOW COOLING TOWER Marley AV Cooling Tower Marley AV CROSSFLOW COOLING TOWER ADDITIONAL NC COOLING TOWER PuBLICATIONS For further information about the NC Cooling Tower – including eng

With the roll-out of CARS Release 1.0, the following CCDF forms are in: CARS ACF-700: ACF-800: ACF-118a (document repository) legacy OCCIS: ACF-801 ACF-118: ACF-218: To access CARS, OCC recommends using Chrome, Firefox, or Edge. 4. User Roles. Reminder: In the Legacy system, user accounts were approved via email.

Types of RCC Cooling Tower Cross Flow Cooling Tower Counter Flow Cooling Tower Capacity of RCC Cooling Tower Capacity Available : 500 m3/hr to 4,500 m3/hr per cell and upto any capacity in multi cell. RCC Cooling Tower Capacity 200CuM/hr. to 3500 CuM/hr. per cell JC Equipments has a enormous variety of models to go well with different requirements.

Marley aquatower Cooling tower Marley AV CROSSFLOW COOLING TOWER Marley Aquatower CROSSFLOW COOLING TOWER aNDDitiO aL NC COOLiNG tOWEr PUbLiCatiONS For further information about the NC cooling tower – includ

Rohn 25G Guyed Tower 44 Rohn 45G Guyed Tower 46 Rohn 55G Guyed Tower 48 Rohn SSV Towers 49 Sabre 1200 TLWD Guyed Tower 50 Sabre 1800 TLWD Guyed Tower 52 Sabre 1800 SRWD Guyed Tower 54 Sabre Series UL Self-Supporting Tower 55 Sabre Series VL Self-Supporting Tower 55 Lightweight Towe

May 20, 2016 · Units called evaporative coolers and fluid coolers are also considered cooling towers. . more than one “cell” (sometimes called a “basin”). For example, an “eight-cell tower” is one cooling tower with eight cooling tower “cells.” As long as the different cells inside a cooling tower and

Cooling Tower Restoration After 40 years of use, cooling tower #91 was showing its age and required lots of attention. If the entire cooling tower was demolished and rebuilt, including the interior concrete structure, it would be very costly and require a long downtime. Even though the cooling tower was showing signs of advanced deterioration .

Superior Court of California County of Imperial “NOTICE OF UNCLAIMED MONIES” I, Maria Rhinehart, Court Executive Officer, Superior Court of California, County of