Page 1/ 5 20/11/2008 STANDARD STANDARD FORFOR INSULATIONOF OFCHILLED INSULATION CHILLED WATER, WATER, HEATING, COLD HEATING, COLD WATER AND WATER AND DOMESTIC HOT WATER PIPES DOMESTIC HOT WATER PIPES CONTENTS 1. Insulation for chilled water and cold water pipes . 2 2. Photos of insulation for chilled water and domestic cold water pipes. 3 3. Insulation for domestic hot water and heating pipes . 4 4. Photos of insulation for domestic hot water and heating pipes . 5

Page 2/ 5 1. 20/11/2008 Insulation for chilled water and cold water pipes Type of insulation for chilled water and cold water pipes (see photos below): - Chilled water pipes must be insulated using preformed PIR sheaths. 30 mm thick sheaths must be used for - pipe diameters up to DN 40; above this diameter the sheaths must be 50 mm thick and Armaflex insulation may be used in service ducts with the consent of UNOG. The pipes and sheaths must be coated with tar or another product with the same characteristics. The preformed PIR sheaths must be assembled using galvanised wire and coated with the same product as described above. This assembly must be covered with a finishing sheet of hammered (stucco) aluminium. Connections must be made with rivets in a non-visible area (see Photos 1 and 2). Valve bodies, filters and check valves must be insulated. This insulation must allow the valves to be operated, and be removable and replaceable for maintenance purposes. The finishing sheets must be fixed in place using strapping bands or hooks riveted to the preformed sheaths, depending on the application (see Photos 4 and 5). - - Pipes supplying pressure switches, manometers, flow meters, vents and evacuation pipes must be insulated with Armaflex (see Photos 2 and 3). Pipes passing through service wells or ducts may be insulated with an Armaflex-type blanket of minimum thickness 19 mm or preformed PIR sheaths coated with tar or another product with the same characteristics. In this case, the insulation must not be covered with a hammered aluminium sheet or PVC sheet. These techniques may be used only with the consent of UNOG representatives. All insulated parts must be completely sealed to prevent any condensation or thermal bri dging. Domestic cold water pipes must be insulated using preformed PIR sheaths covered with a sheet of hard PVC. The thickness of the insulation must be identical to that used for chilled water pipes. A green sleeve must be glued to the end of each domestic cold water supply pipe (see Photo 6).

Page 3/ 5 2. 20/11/2008 Photos of insulation for chilled water and domestic cold water pipes Photo 1 Photo 2 Photo 3 Photo 4 Photo 5 Photo 6

Page 4/ 5 3. 20/11/2008 Insulation for domestic hot water and heating pipes Type of insulation for domestic hot water and heating pipes (see photos below): - Pipes for domestic hot water and heating must be insulated using preformed compressed mineral wool sheaths. 30 mm thick preformed sheaths must be used for pipe diameters of less than ¾”, 40 mm thick for pipe diameters of ¾” to 40 mm, 50 mm thick for pipe diameters of 50 mm to 90 mm, and 80 mm thick for pipe diameters over 90 mm. - The preformed sheaths must be assembled using galvanised wire (see Photos 7, 8 and 9). - This assembly must be covered with a sheet of hammered (stucco) aluminium for all heating pipes (photos 10 and 11) and a sheet of rigid PVC for domestic hot water pipes (Photo 12). Depending on the points of passage of the pipes, a sheet of hammered (stucco) aluminium may be installed, but only at the request of the head of the mechanics subunit. - Equipment welded to pipes (thermowells, vents, evacuation pipes, etc.) must be insulated. Valves must remain accessible and operated easily (see Photos 11 and 12). - A coloured PVC sleeve must be glued to the end of each supply pipe, red for domestic hot water supply pipes and orange for the hot water loop circuit (see Photo 12). All pipe insulation work must be performed according to industry standards. The thicknesses of the insulation materials used and their implementation must conform to the above description.

Page 5/ 5 4. 20/11/2008 Photos of insulation for domestic hot water and heating pipes Photo 7 Photo 8 Photo 9 Photo 10 Photo 11 Photo 12

PVC. The thickness of the insulation must be identical to that used for chilled water pipes. A green sleeve must be glued to the end of each domestic cold water supply pipe (see Photo 6). Page 3/ 5 20/11/2008 2. Photos of insulation for chilled water and domestic cold water pipes . 40 mm thick for pipe diameters of ¾" to 40 mm, 50 mm thick .

Related Documents:

Bruksanvisning för bilstereo . Bruksanvisning for bilstereo . Instrukcja obsługi samochodowego odtwarzacza stereo . Operating Instructions for Car Stereo . 610-104 . SV . Bruksanvisning i original

SITC of MS Class-C Chilled Water Piping with insulation including valves etc. to connect Existing AHUs from KBAC Plant. Tender No: IPR/TN/PUR/TPT/17-18/42 DATED 28/02/2018 Section-C 2 INDEX . Insulation of new and existing chilled water pipe lines where ever required. d) Supply and fabrication of MS support works for chilled water pipes with .

Hotell För hotell anges de tre klasserna A/B, C och D. Det betyder att den "normala" standarden C är acceptabel men att motiven för en högre standard är starka. Ljudklass C motsvarar de tidigare normkraven för hotell, ljudklass A/B motsvarar kraven för moderna hotell med hög standard och ljudklass D kan användas vid

Mechanical Insulation Pipe, Tank and Equipment Insulation Micro-Flex Large Diameter Pipe & Tank Insulation Micro-Lok HP Pipe Insulation Micro-Lok Pipe Insulation Spin-Glas 800 Series Duct & Equipment Insulation Spin-Glas 1000 Series High Temperature Equipment Insulation Insulation for Rectangular Steel Ducts Linacoustic RC Duct Liner

Chilled beams are typically are designed so the typical inlet static pressure is 0.5” w.c. or less. According to DADANCO, chilled beams, when designed in this manner, can achieve a background noise of less the 35dB. 12.9 CHILLED BEAM DISADVANTAGES First cost of chilled beams is typi

10 tips och tricks för att lyckas med ert sap-projekt 20 SAPSANYTT 2/2015 De flesta projektledare känner säkert till Cobb’s paradox. Martin Cobb verkade som CIO för sekretariatet för Treasury Board of Canada 1995 då han ställde frågan

service i Norge och Finland drivs inom ramen för ett enskilt företag (NRK. 1 och Yleisradio), fin ns det i Sverige tre: Ett för tv (Sveriges Television , SVT ), ett för radio (Sveriges Radio , SR ) och ett för utbildnings program (Sveriges Utbildningsradio, UR, vilket till följd av sin begränsade storlek inte återfinns bland de 25 största

The Highway Asset Management Policy and the Highway Asset Management Strategy have been developed to help us to take account of these challenges. The policy is designed to drive continuous improvement in the way we maintain our highway network to ensure that it continues to be safe serviceable and sustainable. It sets out the principles that will ensure we adopt and develop a strategic .