SITRANS P DS III With HART - Siemens

2y ago
24 Views
2 Downloads
5.22 MB
238 Pages
Last View : 1d ago
Last Download : 3m ago
Upload by : Gannon Casey
Transcription

SITRANS P DS III with HART1Introduction2Safety instructionsSITRANSPressure transmitterSITRANS P DS III with erationOperating InstructionsOperating functions through7HART8Functional safety9Commissioning10Service and maintenance11Technical data12Dimension drawings13Spare 92-09BList of abbreviations

Legal informationWarning notice systemThis manual contains notices you have to observe in order to ensure your personal safety, as well as to preventdamage to property. The notices referring to your personal safety are highlighted in the manual by a safety alertsymbol, notices referring only to property damage have no safety alert symbol. These notices shown below aregraded according to the degree of danger.DANGERindicates that death or severe personal injury will result if proper precautions are not taken.WARNINGindicates that death or severe personal injury may result if proper precautions are not taken.CAUTIONindicates that minor personal injury can result if proper precautions are not taken.NOTICEindicates that property damage can result if proper precautions are not taken.If more than one degree of danger is present, the warning notice representing the highest degree of danger willbe used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating toproperty damage.Qualified PersonnelThe product/system described in this documentation may be operated only by personnel qualified for the specifictask in accordance with the relevant documentation, in particular its warning notices and safety instructions.Qualified personnel are those who, based on their training and experience, are capable of identifying risks andavoiding potential hazards when working with these products/systems.Proper use of Siemens productsNote the following:WARNINGSiemens products may only be used for the applications described in the catalog and in the relevant technicaldocumentation. If products and components from other manufacturers are used, these must be recommendedor approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation andmaintenance are required to ensure that the products operate safely and without any problems. The permissibleambient conditions must be complied with. The information in the relevant documentation must be observed.TrademarksAll names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publicationmay be trademarks whose use by third parties for their own purposes could violate the rights of the owner.Disclaimer of LiabilityWe have reviewed the contents of this publication to ensure consistency with the hardware and softwaredescribed. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, theinformation in this publication is reviewed regularly and any necessary corrections are included in subsequenteditions.Siemens AGIndustry SectorPostfach 48 4890026 NÜRNBERGGERMANYOrder number: A5E00047092 08/2013 Technical data subject to changeCopyright Siemens AG 2013.All rights reserved

Table of contents1234Introduction . 111.1Purpose of this documentation .111.2Product information .111.3History .121.4Scope of the instructions .121.5Checking the consignment .131.6Transportation and storage .131.7Notes on warranty .14Safety instructions . 152.12.1.12.1.2Precondition for use .15Laws and directives .15Conformity with European directives .162.2Use in hazardous areas .17Description . 193.1System configuration .193.2Application range .203.3Structure .223.4Nameplate layout .233.5Measuring point label layout .6.3.53.6.3.63.6.3.7Functional principle .24Overview of mode of operation .24Operation of the electronics .25Measuring cell operation .26Measuring cell for gauge pressure.27Measuring cell for differential pressure and flow rate .28Measuring cell for level .29Measuring cell for absolute pressure from the differential pressure series .30Measuring cell for absolute pressure from the gauge pressure series .31Measuring cell for gauge pressure, front-flush membrane .32Measuring cell for absolute pressure, front-flush membrane .323.7Remote seal .333.8SIMATIC PDM.34Installing/mounting . 354.14.1.14.1.2Basic safety instructions .35Installation location requirements .39Proper mounting.39SITRANS P DS III with HARTOperating Instructions, 06/2013, A5E00047092-095

Table of contents564.2Disassembly . 404.34.3.14.3.24.3.3Installation (except level) . 41Instructions for installation (except level) . 41Installation (except level) . 42Fastening. 424.44.4.14.4.24.4.3"Level" installation . 44Instructions for level installation . 44Installation for level . 45Connection of the negative pressure line. 464.54.5.14.5.2"Remote seal" installation . 49Remote seal installation . 49Installation of the remote seal with the capillary line . 504.6Turing the measuring cell against housing . 564.7Rotating the display . 58Connecting . 595.1Basic safety instructions . 595.2Connecting the device. 625.3Connecting the Han plug. 645.4Connecting the M12 connector . 66Operation . 696.1Overview of operation . 696.2Basic safety instructions . 706.3Instructions for operation. 706.46.4.16.4.26.4.36.4.46.4.56.4.6Display. 71Display elements . 71Units display . 72Error display . 73Mode display . 74Status display . 74Overflow range . 56.5.5.16.5.5.26.5.5.36.5.5.46.5.5.5Local operation . 76Local control elements . 76Operation using buttons . 79Start of scale value/full scale value . 79Difference between setting and adjusting . 79Setting/adjusting the start of scale value . 83Setting/adjusting the full scale value . 84Setting/adjusting electrical damping . 86Blind start of scale value/full scale value . 87Difference between setting/adjusting and blind setting/adjusting . 87Blind setting of start of scale value . 89Blind setting of full scale value . 90Blind adjusting of the start of scale value. 90Blind adjustment of the full scale value . 91SITRANS P DS III with HART6Operating Instructions, 06/2013, A5E00047092-09

Table of 137Trimming the zero point .91Current transmitter .92Output current in case of fault .93Locking buttons and functions .94Releasing key lock or function lock .96Flow rate measurement (only differential pressure) .96Measured value display .99Unit .100Operating functions through HART . 1057.1Operating functions through HART communication .1057.2Process tag data .97.3.107.3.11Selecting the measuring modes.106Overview of measuring modes .106Measuring mode selector .107Variable mapper .107Measuring mode "Pressure" .108Customized characteristic curve .109Measuring mode "Level" .110Measuring mode "Flow rate" .112Measuring mode "User" .114Measured value status .116Analog output .120Scaling the display value .1217.4Setting zero point and limit point .1227.5Blind setting of zero point and limit point .1237.6Zero point calibration (position correction) .1237.7Electrical damping .1247.8Fast response mode .1247.9Current sensor .1247.10Fault current .1247.11Setting the current limits .1257.12Key lock and write protection .1267.13Measured value display .1277.14Selection of the physical unit .1287.15Bar graph .1297.167.16.17.16.2Sensor calibration .129Sensor trim .129Trimming the sensor .1307.17Current sensor trim .1307.18Factory calibration .1327.19Static configuration data .1327.20Flow rate measurement (only differential pressure) .134SITRANS P DS III with HARTOperating Instructions, 06/2013, A5E00047092-097

Table of nostic functions . 134Overview . 134Operating hours counter . 135Calibration timer and service timer . 135Min/max indicator . 137Limit modules . 1387.227.22.17.22.27.22.3Simulation. 140Overview of simulation . 140Simulation as fixed value . 141Simulation with a ramp function . 1417.23Limit monitor . 141Functional safety .1458.1Safety function . 1458.2Safety Integrity Level (SIL) . 1478.3Settings . 1498.4Safety characteristics . 1508.5Maintenance/Checking. 1518.68.6.18.6.2Add-on parts . 152Checking a device with add-on pneumatic block . 152Checking a device with add-on remote seal . 152Commissioning .1539.1Basic safety instructions . 1539.2Introduction to commissioning . 1549.39.3.19.3.2gauge pressure, absolute pressure from the differential pressure series and absolutepressure from the gauge pressure series . 155Commissioning for gases . 155Commissioning with steam or liquid . 1579.49.4.19.4.29.4.39.4.4Differential pressure and flow rate . 158Safety notes for commissioning with differential pressure and flow rate . 158Commissioning in gaseous environments . 159Commissioning for liquids . 160Commissioning with vapor . 162Service and maintenance .16510.1Basic safety instructions . 16510.210.2.110.2.210.2.310.2.4Maintenance and repair work . 168Defining the maintenance interval . 168Checking the gaskets . 169Display in case of a fault . 170Changing the measuring cell and application electronics . 17010.310.3.1Cleaning . 171Servicing the remote seal measuring system . 17210.4Return procedure . 173SITRANS P DS III with HART8Operating Instructions, 06/2013, A5E00047092-09

Table of contents10.5111213ABDisposal .174Technical data . 17511.1Overview of technical data .17511.2Input point .17611.3Output .18311.4Measuring accuracy .18411.5Operating conditions .19111.6Construction .19411.7Display, keyboard and auxiliary power .19911.8Certificates and approvals .20011.9HART communication .202Dimension drawings . 20312.1SITRANS P, DS III for gauge pressure and absolute pressure from the gauge pressureseries .20312.2SITRANS P DS III for differential pressure, flow rate and absolute pressure from thedifferential pressure series .20512.3SITRANS P DS III for level .20812.412.4.112.4.212.4.312.4.412.4.5SITRANS P DS III (flush-mounted) .209Note 3A and EHDG .210Connections as per EN and ASME .210F&B and pharma flange .211PMC Style .215Special connections .216Spare parts/accessories . 21913.1Order data .

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are

Related Documents:

SITRANS F flowmeters SITRANS F M MAGFLO MAG 5100 W Siemens FI 01 · 2007 4/57 4 Overview The SITRANS F M MAGFLO MAG 5100 W is an electromagnetic flow sensor designed to meet ground water, drinking water, waste water, sewage or sludge applications. Benefits DN 25 to DN 1200 (1” to

SITRANS F flowmeters SITRANS F Product overview 4/2 Siemens FI 01 · 2005 4 Overview Application Description Catalog page Software for parameterization SITRANS F M electromagnetic flowmeters Choose MAG 5000/6000 for more demanding applications where you need the benefits of highly func-tional, accura

SITRANS F M MAG 1100 DN 2- DN 100 SITRANS F M MAG 1100 DN 2- DN 3 1.3 Items supplied SITRANS F M MAG 1100/1100 F Calibration report DVD with documentation and cerificates . Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and .

SITRANS F flowmeters SITRANS F M MAGFLO MAG 1100 Food Siemens FI 01 · 2008 4/51 4 MAG 5000/6000 transmitters and sensors are packed in sepa-rate boxes, the final assembly takes place during installation at

ciated transmitter MAG 5000, 6000 and 6000 I. . FM Class 1 Div 2 CSA Class 1, Div 2 1) Larger sizes on request 2) Conditions are also dependent on liner characteristiques 3) Sealing O-ring in Viton. SITRANS F flowmeters SITRANS F M MAGFLO MAG 3100/3100 Ex Siemens FI 01 · 2007 4/67 4

sitrans f sitrans f m magflo mag 5100 w siemens fi 01 · 2007 3/59 3 mag 5100 w 1) dn 300 6 " 6 25 , 40 300

Instrumentos para medida de caudal SITRANS F SITRANS F M MAGFLO MAG 5100 W Siemens FI 01 · 2005 4/55 4 - no disponible Con transmisor MAG 5000 ó MAG 6000 montado, el peso aumenta unos 0,8 kg (1.8 lbs), co

Durchflussmessgeräte SITRANS F SITRANS F M MAG 5100 W 4/60 Siemens FI 01 · 2009 4 Messumformer und Messaufnehmer des Typs MAG 5000/6000 werden einzeln verpackt geliefert und vor Ort beim Kunden wäh-rend der Installation zusammengesetzt. Messumformer und Messaufnehmer des Typs MAG